This is an architectural amendment drawing for Level One Open Office 129, dated July 16, 2026, prepared for the Emergency Fire Center in Boise, Idaho.
The amendment specifies interior renovation and modification requirements including: demo and replacement of acoustic ceiling grid and tiles in secure storage with new components matching project specifications; centering new lights in the room with grid adjustment; installation of two A5 lights in secure storage; addition of a new 6-inch diameter ceiling register duct (CFM = 100) to existing systems; modification of existing 8-inch diameter duct lines to 10-inch diameter to service two ceiling registers (each CFM = 175); relocation of a light occupancy sensor switch from salvaged materials; repositioning of the thermostat to avoid placement behind modular furniture; flipping door swing orientation for a Type F solid door with no glazing and Group 4 hardware; installation of retention film (meeting specified tensile strength and elongation requirements) on all glazing marked GF1; painting interior partition walls (PT6) extended to deck underside; flooring finish (RF1) in secure storage; television mount blocking at 72 inches above finished floor with associated power and data provisions; addition of standard power and data outlets; card reader, switch, and data port locations (2-port and 4-port configurations); and wall powerwhip installation. All modifications must comply with the marked specifications and dimensional requirements shown on the drawing.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(1) WORKSTATION
(1) WORKSTATION
(1) HOTEL STATION (1) HOTEL STATION
INTERIOR PARTITION TYPE
(E) EXTENDED TO
UNDERSIDE OF DECK
3o / 7o DOOR MATCHING
SPECIFICATIONS, TYPE 'F'
SOLID, NO GLAZING, GROUP
4 DOOR HARDWARE
RELOCATED LIGHT OC
SENSOR SWITCH FROM
SALVAGED SWITCH
WALL PAINTED PT6
FLOORING
FINISH RF1
SECURE STORAGE
BLOCKING FOR TELEVISION
MOUNT,
POWER AND DATA AT 72" AFF
ADDITIONAL
POWER AND DATA
STANDARD AFF
WALL POWERWHIP
KEY SHOP
DEMO ACT/GRID IN SECURE
STORAGE, NEW GRID AND ACT TO
MATCH SPECIFICATION OF PROJECT
NEW LIGHTS TO BE CENTERED IN
ROOM, GRID TO ADJUST AND MATCH
(2) A5 LIGHTS IN SECURE STORAGE
NEW CEILING REGISTER WITH
6" DIAMETER DUCT BACK TO
EXISTING - CFM = 100
CEILING REGISTER
CFM = 175
CEILING
REGISTER CFM
= 175
CHANGE TO 10" DIAMETER
DUCT LINE TO REGISTERS
FROM MAIN TRUNK
(DRAWINGS SHOW 8")
CR
$T
CARD READER LOCATION
SWITCH LOCATION
T STAT LOCATION (T STAT SHOWN IN
NOW STORAGE ROOM ON DRAWINGS
MOVED TO HERE)
DOOR SWING FLIPPED
FROM DRAWINGS, TYPE 'F'
SOLID, NO GLAZING
T STAT LOCATION TO NOT BE
BEHIND MODULAR FURNITURE
2 PORT DATA
4 PORT DATA
2 PORT DATA 2 PORT DATA
RETENTION FILM TO BE INSTALLED ON ALL GLAZING WITH MARK GF1.
ACCEPTABLE FRAGMENT RETENTION FILM SHALL MEET OR EXCEED THE
LISTING BELOW. FILM COMPOSITE STRENGTH AND ELONGATION RATE
MEASURED AT A STRAIN RATE NOT EXCEEDING THE FOLLOWING:
• YIELD STRENGTH: 12,000 PSI
• ELONGATION AT YIELD: 3%
• LONGITUDINAL TENSILE STRENGTH: 22,000 PSI
• TRAVERSE TENSILE STRENGTH: 25,000 PSI
• LONGITUDINAL ELONGATION AT BREAK: 90%
• TRAVERSE ELONGATION AT BREAK: 75%
GF1 GF1 GF1 GF1 GF1
G F
GF1
N
ARETNI
L A N
OI
T A
G
R
ENCY FIRE
C E N
TE
B esio , oIdah
LEVEL ONE OPEN OFFICE 129 AMENDMENT
07.16.2026 Drawn By:MMCANULTY
| Sheets |
| SD102 - LEVEL ONE OPEN OFFICE 129 AMENDMENT |