Amendment_3_Specification_260519_Low-Voltage_Electrical_Power_Conductors_and_Cables_0003.pdf

PDF 73 KB Posted

Attached to
GAOA - Replace Multipurpose Building, Maintenance Federal contract opportunity
Solicitation number
140FGA24R0003
Issued by
Department of the Interior Fish and Wildlife Service

About this file

This document is a specification for low-voltage electrical power conductors and cables required for the GAOA - Replace Multipurpose Building, Maintenance Shop, Cold Storage Building, and Maintenance Yard at Luster Heights NWR project. The specification details the required products, including Romex, copper building wire rated 600V or less, metal-clad cable rated 600V or less, and connectors and splices rated 600V and less. It provides manufacturers, standards, and installation and testing requirements. The related federal contract opportunity is solicitation number 140FGA24R0003 from the Department of the Interior Fish and Wildlife Service to replace several buildings and improve the maintenance yard at the Luster Heights National Wildlife Refuge.

View the file

Other files for this federal contract opportunity

Other files attached to GAOA - Replace Multipurpose Building, Maintenance, newest first.
File Type Posted
Amendment_3_Additional_Project_Information_0003.pdf PDF
Amendment_3_Drawing_Sheet_A17_Multipurpose_Building_Window_Details_0003.pdf PDF
Amendment_3_Drawing_Sheet_A18_Multipurpose_Building_Window_and_Door_Details_0003.pdf PDF
Sol_140FGA24R0003_Amd_0003.pdf PDF
Amendment_3_UMR1145A0_Bid_Item_6_Cold_Storage_Building_Floor_Plan_0003.pdf PDF
Amendment_3_Specification_085200_Wood_Windows_0003.pdf PDF
Amendment_3_Drawing_Sheet_A38_Maintenance_Shop_Door_and_Window_Schedules_and_Details_0003.pdf PDF
Amendment_3_Specification_083613_0003.pdf PDF
Amendment_3_Specification_281300_Access_Control_Software_and_Database_Management_0003.pdf PDF
Amendment_3_UMR1148E0_Bid_Item_6_Cold_Storage_Building_Electrical_Plan_0003.pdf PDF
Amendment_3_Drawing_Sheet_A16_Multipurpose_Building_Door_Schedules_and_Details_0003.pdf PDF
Amendment_3_Specification_095113_Acoustical_Panel_Ceilings_0003.pdf PDF
Amendment_3_Questions_and_Answers_0003.pdf PDF
Amendment_3_Drawing_Sheet_A12_Multipurpose_Building_Wall_Sections_and_Details_0003.pdf PDF
Amendment_3_Drawing_Sheet_A39_Maintenance_Shop_Enlarged_Plans_and_Elevations_0003.pdf PDF
Amendment_3_Drawing_Sheet_L8_Site_Details_0003.pdf PDF
Amendment_3_Drawing_Sheet_A13_Multipurpose_Building_Finish_Plan_0003.pdf PDF
Questions_and_Answers_Amendment_2_0002.pdf PDF
Sol_140FGA24R0003_Amd_0002.pdf PDF
Luster_Heights_Pre-bid_Site_Visit_0002.pdf PDF
Additional_Project_Information_Amendment_2_0002.pdf PDF
Revised_Notice_to_Offerors_0001.pdf PDF
Sol_140FGA24R0003_Amd_0001.pdf PDF
Drawings_Luster_Heights.pdf PDF
Price_Schedule.pdf PDF
Wage_Determination.pdf PDF
Drawings_Cold_Storage.pdf PDF
Sol_140FGA24R0003.pdf PDF
Notice_to_Offerors.pdf PDF
SOW_Luster_Heights_Multiple_Bldgs.pdf PDF
Past_Performance_Questionnaire_(PPQ).pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UPPER MISSISSIPPI RIVER NATIONAL FISH AND WILDLIFE REFUGE USFWSR3 UMRLH

- MCGREGOR DISTRICT

MULTIPURPOSE BUILDING AND MAINTENANCE SHOP

100% CONSTRUCTION DOCUMENT SUBMISSION

LUSTER HEIGHTS, IOWA

3.15.2023

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 1

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Romex.

2. Copper building wire rated 600 V or less.

3. Metal-clad cable, Type MC, rated 600 V or less.

4. Connectors, splices, and terminations rated 600 V and less.

1.3 DEFINITIONS

A. PV: Photovoltaic.

B. RoHS: Restriction of Hazardous Substances.

C. VFC: Variable-frequency controller.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Product Schedule: Indicate type, use, location, and termination locations.

1.5 INFORMATIONAL SUBMITTALS

A. Qualification Data: For testing agency.

B. Field quality-control reports.

MULTIPURPOSE BUILDING AND MAINTENANCE SHOP

100% CONSTRUCTION DOCUMENT SUBMISSION

LUSTER HEIGHTS, IOWA

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2

1.6 QUALITY ASSURANCE

A. Testing Agency Qualifications: Member company of NETA.

1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.

PART 2 - PRODUCTS

2.1 COPPER BUILDING WIRE

A. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less.

B. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Alpha Wire Company.

2. American Bare Conductor.

3. Belden Inc.

4. Cerro Wire LLC.

5. Encore Wire Corporation.

6. General Cable Technologies Corporation.

7. Okonite Company (The).

8. Service Wire Co.

9. Southwire Company.

10. WESCO.

C. Standards:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

2. RoHS compliant.

3. Conductor and Cable Marking: Comply with wire and cable marking according to

UL's "Wire and Cable Marking and Application Guide."

D. Conductors: Copper, complying with ASTM B 3 for bare annealed copper and with ASTM B 8 for stranded conductors.

E. Conductor Insulation:

1. Type THHN and Type THWN-2: Comply with UL 83.

2. Type XHHW-2: Comply with UL 44.

MULTIPURPOSE BUILDING AND MAINTENANCE SHOP

100% CONSTRUCTION DOCUMENT SUBMISSION

LUSTER HEIGHTS, IOWA

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 3

2.2 METAL-CLAD CABLE, TYPE MC

A. Description: A factory assembly of one or more current-carrying insulated conductors in an overall metallic sheath.

B. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Alpha Wire Company.

2. American Bare Conductor.

3. Belden Inc.

4. Encore Wire Corporation.

5. General Cable Technologies Corporation.

6. Okonite Company (The).

7. Service Wire Co.

8. Southwire Company.

9. WESCO.

C. Standards:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

2. Comply with UL 1569.

3. RoHS compliant.

4. Conductor and Cable Marking: Comply with wire and cable marking according to

UL's "Wire and Cable Marking and Application Guide."

D. Circuits:

1. Single circuit and multi-circuit with color-coded conductors.

E. Conductors: Copper, complying with ASTM B 3 for bare annealed copper and with ASTM B 8 for stranded conductors.

F. Ground Conductor: Insulated.

G. Conductor Insulation:

1. Type THHN/THWN-2: Comply with UL 83.

H. Armor: Steel, interlocked.

2.3 CONNECTORS AND SPLICES

A. Description: Factory-fabricated connectors, splices, and lugs of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as

MULTIPURPOSE BUILDING AND MAINTENANCE SHOP

100% CONSTRUCTION DOCUMENT SUBMISSION

LUSTER HEIGHTS, IOWA

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 4

defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

B. Jacketed Cable Connectors: For steel and aluminum jacketed cables, zinc die-cast with set screws, designed to connect conductors specified in this Section.

C. Lugs: One piece, seamless, designed to terminate conductors specified in this Section.

1. Material: Copper.

2. Type: One or Two hole with standard or long barrels.

3. Termination: Compression.

PART 3 - EXECUTION

3.1 CONDUCTOR MATERIAL APPLICATIONS

A. Feeders: Copper for feeders smaller than No. 4 AWG; copper or aluminum for feeders No. 4 AWG and larger. Conductors shall be solid for No. 10 AWG and smaller;

stranded for No. 8 AWG and larger.

B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND

WIRING METHODS

A. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces:

Type THHN/THWN-2, single conductors in raceway.

B. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground:

Type THHN/THWN-2, single conductors in raceway or Type XHHW-2, single conductors in raceway.

C. Exposed Branch Circuits, Including in Crawlspaces: Type THHN/THWN-2, single conductors in raceway.

D. Branch Circuits Concealed in Ceilings, Walls, and Partitions: For receptacles shall be Type THHN/THWN-2, single conductors in raceway or Metal-clad cable, Type MC.

Lighting circuits shall be similar with the exception of using MC cable between fixtures with homeruns to the panel as Type THHN/THWN-2, single conductors in raceway or Metal-clad cable, Type MC.

E. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground:

Type THHN/THWN-2, single conductors in raceway.

MULTIPURPOSE BUILDING AND MAINTENANCE SHOP

100% CONSTRUCTION DOCUMENT SUBMISSION

LUSTER HEIGHTS, IOWA

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 5

3.3 INSTALLATION OF CONDUCTORS AND CABLES

A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.

B. Complete raceway installation between conductor and cable termination points according to Section 260533 "Raceways and Boxes for Electrical Systems" prior to pulling conductors and cables.

C. Use manufacturer-approved pulling compound or lubricant where necessary;

compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

F. Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."

3.4 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.

B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

1. Use oxide inhibitor in each splice, termination, and tap for aluminum conductors.

C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches (150 mm) of slack.

3.5 IDENTIFICATION

A. Identify and color-code conductors and cables according to Section 260553 "Identification for Electrical Systems."

B. Identify each spare conductor at each end with identity number and location of other end of conductor and identify as spare conductor.

MULTIPURPOSE BUILDING AND MAINTENANCE SHOP

100% CONSTRUCTION DOCUMENT SUBMISSION

LUSTER HEIGHTS, IOWA

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 6

3.6 FIRESTOPPING

A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly.

3.7 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Cables will be considered defective if they do not pass tests and inspections.

C. Prepare test and inspection reports to record the following:

1. Procedures used.

2. Results that comply with requirements.

3. Results that do not comply with requirements, and corrective action taken to achieve compliance with requirements.

END OF SECTION 260519