This document is an amendment providing additional project information for solicitation number 140FGA24R0003 to replace the multipurpose building, maintenance shop, cold storage building, and maintenance yard at Luster Heights National Wildlife Refuge.

The amendment includes numerous revisions to drawings and specifications. On the drawings, it changes details and notes for concrete thickness, rebar size, and dampproofing. It also removes security cameras from the cold storage building electrical plan. In specifications, it removes control options for sectional doors, adds exterior and interior finish requirements, changes the modular size for acoustical ceiling panels, and modifies low-voltage cable and access control software specifications.

The related federal contract opportunity is for the Department of Interior Fish and Wildlife Service to replace the above-mentioned facilities at Luster Heights National Wildlife Refuge, as identified by solicitation number 140FGA24R0003. The amendment provides bidders with additional project information and revisions to consider for this opportunity.

View the file

Other files for this federal contract opportunity

Other files attached to GAOA - Replace Multipurpose Building, Maintenance, newest first.
File Type Posted
Sol_140FGA24R0003_Amd_0003.pdf PDF
Amendment_3_UMR1145A0_Bid_Item_6_Cold_Storage_Building_Floor_Plan_0003.pdf PDF
Amendment_3_Specification_085200_Wood_Windows_0003.pdf PDF
Amendment_3_Drawing_Sheet_A38_Maintenance_Shop_Door_and_Window_Schedules_and_Details_0003.pdf PDF
Amendment_3_Specification_083613_0003.pdf PDF
Amendment_3_Specification_095113_Acoustical_Panel_Ceilings_0003.pdf PDF
Amendment_3_Questions_and_Answers_0003.pdf PDF
Amendment_3_Drawing_Sheet_A12_Multipurpose_Building_Wall_Sections_and_Details_0003.pdf PDF
Amendment_3_Drawing_Sheet_A39_Maintenance_Shop_Enlarged_Plans_and_Elevations_0003.pdf PDF
Amendment_3_Drawing_Sheet_L8_Site_Details_0003.pdf PDF
Amendment_3_Drawing_Sheet_A13_Multipurpose_Building_Finish_Plan_0003.pdf PDF
Amendment_3_Specification_281300_Access_Control_Software_and_Database_Management_0003.pdf PDF
Amendment_3_UMR1148E0_Bid_Item_6_Cold_Storage_Building_Electrical_Plan_0003.pdf PDF
Amendment_3_Drawing_Sheet_A16_Multipurpose_Building_Door_Schedules_and_Details_0003.pdf PDF
Amendment_3_Specification_260519_Low-Voltage_Electrical_Power_Conductors_and_Cables_0003.pdf PDF
Amendment_3_Drawing_Sheet_A17_Multipurpose_Building_Window_Details_0003.pdf PDF
Amendment_3_Drawing_Sheet_A18_Multipurpose_Building_Window_and_Door_Details_0003.pdf PDF
Questions_and_Answers_Amendment_2_0002.pdf PDF
Additional_Project_Information_Amendment_2_0002.pdf PDF
Sol_140FGA24R0003_Amd_0002.pdf PDF
Luster_Heights_Pre-bid_Site_Visit_0002.pdf PDF
Sol_140FGA24R0003_Amd_0001.pdf PDF
Revised_Notice_to_Offerors_0001.pdf PDF
Price_Schedule.pdf PDF
Wage_Determination.pdf PDF
Sol_140FGA24R0003.pdf PDF
Notice_to_Offerors.pdf PDF
SOW_Luster_Heights_Multiple_Bldgs.pdf PDF
Past_Performance_Questionnaire_(PPQ).pdf PDF
Drawings_Cold_Storage.pdf PDF
Drawings_Luster_Heights.pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment 3; Attachment 2

Luster Heights Multipurpose Building, Maintenance Shop, Cold Storage Building, and Maintenance Yard at National Wildlife Refuge

Solicitation # 140FGA24R0003 Additional Project Information

This additional information has stemmed from the additional contractor questions received.

Documents/Drawings have also been updated to reflect the below changes.

- Details 4/A39, 11/A39, 13/A39 and 14/A39 leader text shall be changed from "TB1" to

"RB2.”

- Sheet A13 Mud Room 122 Finish Key base material shall be changed from "TB1" to

"IC1.”

- The following changes shall be made to detail 12/L8:

o 8” concrete thickness shall be changed to “10” concrete thickness.”

o “#4 bars at 12" on center each way" shall be changed to #6 bars at 12" on center each way.”

- Drawing Sheet L8 Site Details:

o Detail 12/L8: 8" concrete thickness changed to 10" concrete thickness, #4 bars changed to #6 bars.

- Drawing Sheet A12 Multipurpose Building Wall Sections and Details:

o Details 3/A12, 4/A12, 5/A12, 6/A12, 7/A12, 9/A12, and 10/A12: replaced self-adhered waterproofing membrane for full depth of stem wall, typical at all stem walls with bituminous dampproofing for full depth of stem wall, typical at all stem walls.

- Drawing Sheet A13 Multipurpose Building Finish Plan:

o Changed Mud Room 122 Finish Key base material from "TB1" to "IC1".

- Drawing Sheet A16 Multipurpose Building Door Schedules and Details:

o Added bird friendly film to openings 100-02 and 122.02.

o Added detail callouts 11/A17 and 12/A17 to Hollow Metal Frame Types 2 and 3.

o Replaced detail callouts 2/A17 and 6/A17 with 7/A18 and 8/18 to Hollow Metal

Frame Type 4.

- Drawing Sheet A17 Multipurpose Building Window Elevations:

o Added details 11/A17 and 12/A17.

- Drawing Sheet A18 Multipurpose Building Window and Door Details:

o Added note (HM SIM) to details 7/A18 and 8/A18.

- Drawing Sheet A38 Maintenance Shop Door and Window Schedules and Details:

o Added Prefinished Metal Cover Trim to details 6/A38 and 8/A38.

o Changed Overhead Doors Thickness from 1-1/2" to 2".

- Drawing Sheet A39 Maintenance Shop Enlarged Plans and Elevations:

o Details 4/A39, 11/A39, 13/A39 and 14/A39: replaced "TB1" with "RB2".

- Drawing Sheet UMR1145A0 Bid Item #6: Cold Storage Building Floor Plan:

o Changed Overhead Doors Thickness from 1-1/2" to 2".

- Drawing Sheet UMR1148E0 Bid Item #6: Cold Storage Building Electrical Plan:

o Deleted CCTV 13 and CCTV 20 security cameras.

- Specification 083613 Sectional Doors:

o Deleted 2.3.L.9.c.1) Vehicle detection operation.

o Deleted 2.3.L.9.c.3) Card-reader control.

o Deleted 2.3.L.9.c.5) Door-timer operation.

o Deleted 2.3.L.9.c.6) Explosion-and dust-ignition-proof control wiring.

o Deleted 2.3.L.9.c.7) Audible and visual signals that comply with regulatory requirements for accessibility.

o Added 2.3.M.2: Exterior Finish: Factory finished with acrylic baked enamel, color as selected by Government from manufacturer's standard colors.

o Added 2.3.M.3: Interior Finish: Factory finished with acrylic baked enamel, manufacturer's standard white color.

- Specification 085200 Wood Windows:

o Added Bird Friendly Film.

- Specification 095113 Acoustical Panel Ceilings:

o Changed 2.3.K Modular Size from 24 by 48 inches to 24 by 24 inches.

- Specification 260519 Low-Voltage Electrical Power Conductors and Cables:

o Changed paragraph 3.2.D to: “Branch Circuits Concealed in Ceilings, Walls, and

Partitions: For receptacles Type THHN/THWN-2, single conductors in raceway or Metal-clad cable, Type MC. Lighting circuits shall be similar with the exception of using MC cable between fixtures with homeruns to the panel as Type THHN/THWN-2, single conductors in raceway or Metal-clad cable, Type MC.

- Specification 281300 Access Control Software and Database Management:

o Deleted Existing system in Multipurpose Building from paragraph 2.1.A.

Please use the following link to access the .DWG file that requires AutoCAD drafting software to open: https://fws-fileshare.box.com/s/ldt474ev5ox7dpkvjfn875rxmthnfpnr