This specification document outlines requirements for acoustical panel ceilings for the replacement of the Multipurpose Building, Maintenance Shop, Cold Storage Building, and Maintenance Yard at the Luster Heights National Wildlife Refuge. The project involves installing acoustical panel ceilings using Type III, Form 1, pattern E panels made of 3/4 inch thick, 24 by 24 inch modular fiberglass with a white painted finish, a noise reduction coefficient of not less than 0.70, and a ceiling attenuation class of not less than 35. Suspension systems must be intermediate-duty, double-web steel with a G30 galvanized coating. The specification also provides requirements for edge moldings, suspension accessories, seismic restraints, and installation.
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPPER MISSISSIPPI RIVER NATIONAL FISH AND WILDLIFE REFUGE USFWSR3_UMRLH
- MCGREGOR DISTRICT
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
3.15.2023
ACOUSTICAL PANEL CEILINGS 095113 - 1
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for interior ceilings.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Delegated-Design Submittal: For seismic restraints for ceiling systems.
1. Include design calculations for seismic restraints including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 2
1.6 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weathertight, wet-work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain each type of acoustical ceiling panel and its supporting suspension system from single source from single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design seismic restraints for ceiling systems.
B. Seismic Performance: Suspended ceilings shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.
C. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Class A according to ASTM E 1264.
2. Smoke-Developed Index: 50 or less.
2.3 ACOUSTICAL PANELS ACP1
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
1. Basis-of-Design Product: Armstrong Cirrus 15/16" Angled Tegular.
a. American Gypsum.
b. Armstrong World Industries, Inc.
c. CertainTeed Corporation.
d. Tectum Inc.
e. United States Gypsum Company.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 3
B. Acoustical Panel Standard: Provide manufacturer's standard panels according to
ASTM E 1264 and designated by type, form, pattern, acoustical rating, and light reflectance unless otherwise indicated.
C. Recycled Content: 15% Post-Consumer recylced content plus 71% Pre-Consumer recycled content.
D. Classification: Provide panels as follows:
1. Type and Form: Type III; Form 1, Pattern E
E. Color: White.
F. Light Reflectance (LR): Not less than 0.85.
G. Ceiling Attenuation Class (CAC): Not less than 35.
H. Noise Reduction Coefficient (NRC): Not less than 0.70.
I. Edge/Joint Detail: Angled Tegular Square.
J. Thickness: 3/4 inch.
K. Modular Size: 24 by 24 inches.
2.4 METAL SUSPENSION SYSTEM
offering products that may be incorporated into the Work include, but are not limited to, the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corporation.
3. Chicago Metallic Corporation.
4. United States Gypsum Company.
B. Metal Suspension-System Standard: Provide manufacturer's standard, direct-hung, metal suspension system and accessories according to ASTM C 635/C 635M and designated by type, structural classification, and finish indicated.
C. Recycled Content: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.
D. Wide-Face, Capped, Double-Web,Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized, G30 coating designation; with prefinished 15/16-inch- wide metal caps on flanges.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 4
1. Structural Classification: Intermediate -duty system.
2. End Condition of Cross Runners: Override (stepped) type.
3. Face Design: Flat, flush.
4. Cap Material: Cold-rolled steel
5. Cap Finish: Painted white.
E. Wide-Face, Capped, Double-Web, Stainless-Steel Suspension System: Main and cross runners roll formed from Type 304 or 316 stainless-steel sheet, with prefinished 15/16-inch- wide, stainless-steel caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. Face Design: Flat, flush.
2.5 ACCESSORIES
A. Attachment Devices: Size for five times the design load indicated in ASTM C 635/C 635M, Table 1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements.
B. Wire Hangers, Braces, and Ties: Provide wires as follows:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Wire diameter sufficient for its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but not less than 0.106-inch-diameter wire.
C. Seismic Clips: Manufacturer's standard seismic clips designed to secure acoustical panels in place during a seismic event.
D. Seismic Struts: Manufacturer's standard compression struts designed to accommodate seismic forces.
2.6 METAL EDGE MOLDINGS AND TRIM
offering products that may be incorporated into the Work include, but are not limited to, the following:
B. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corporation.
3. Chicago Metallic Corporation.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 5
4. Fry Reglet Corporation.
5. Gordon, Inc.
6. United States Gypsum Company.
C. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.
B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders unless otherwise indicated, and comply with layout shown on reflected ceiling plans.
B. Layout openings for penetrations centered on the penetrating items.
3.3 INSTALLATION
A. Install acoustical panel ceilings according to ASTM C 636/C 636M, seismic design requirements, and manufacturer's written instructions.
B. Suspend ceiling hangers from building's structural members and as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 6
2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.
3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.
4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly to structure or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.
5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.
6. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.
C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs.
Fasten bracing wires into concrete with cast-in-place or postinstalled anchors.
D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.
1. Apply acoustical sealant in a continuous ribbon concealed on back of vertical legs of moldings before they are installed.
2. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends. Miter corners accurately and connect securely.
3. Do not use exposed fasteners, including pop rivets, on moldings and trim.
E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.
F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide precise fit.
1. Arrange directionally patterned acoustical panels as follows:
a. As indicated on reflected ceiling plans.
b. Install panels with pattern running in one direction parallel to long axis of space.
c. Install panels in a basket-weave pattern.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 7
2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.
3. For reveal-edged panels on suspension-system runners, install panels with bottom of reveal in firm contact with top surface of runner flanges.
4. For reveal-edged panels on suspension-system members with box-shaped flanges, install panels with reveal surfaces in firm contact with suspension-system surfaces and panel faces flush with bottom face of runners.
5. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.
6. Install clips in areas indicated; space according to panel manufacturer's written instructions unless otherwise indicated.
7. Install clean-room gasket system in areas indicated, sealing each panel and fixture as recommended by panel manufacturer's written instructions.
8. Protect lighting fixtures and air ducts according to requirements indicated for fire-resistance-rated assembly.
3.4 ERECTION TOLERANCES
A. Suspended Ceilings: Install main and cross runners level to a tolerance of 1/8 inch in 12 feet, non-cumulative.
B. Moldings and Trim: Install moldings and trim to substrate and level with ceiling suspension system to a tolerance of 1/8 inch in 12 feet, non-cumulative.
3.5 FIELD QUALITY CONTROL
A. Special Inspections: Engage a qualified special inspector to perform the following special inspections:
1. Periodic inspection during the installation of suspended ceiling grids according to
ASCE/SEI 7.
B. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
C. Perform the following tests and inspections of completed installations of acoustical panel ceiling hangers and anchors and fasteners in successive stages and when installation of ceiling suspension systems on each floor has reached 20 percent completion, but no panels have been installed. Do not proceed with installations of acoustical panel ceiling hangers for the next area until test results for previously completed installations of acoustical panel ceiling hangers show compliance with requirements.
MULTIPURPOSE BUILDING AND MAINTENANCE SHOP
100% CONSTRUCTION DOCUMENT SUBMISSION
LUSTER HEIGHTS, IOWA
ACOUSTICAL PANEL CEILINGS 095113 - 8
1. Within each test area, testing agency will select one of every 10 power-actuated fasteners and postinstalled anchors used to attach hangers to concrete and will test them for 200 lbf of tension; it will also select one of every two postinstalled anchors used to attach bracing wires to concrete and will test them for 440 lbf of tension.
2. When testing discovers fasteners and anchors that do not comply with requirements, testing agency will test those anchors not previously tested until 20 pass consecutively and then will resume initial testing frequency.
D. Acoustical panel ceiling hangers, anchors, and fasteners will be considered defective if they do not pass tests and inspections.
E. Prepare test and inspection reports.
3.6 CLEANING
A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage.
B. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.
END OF SECTION 095113