This document provides details for a design-build construction project solicitation for the renovation of Building 1 Wings 4 and 5 and partial spine at the National Institute of Standards and Technology campus in Boulder, Colorado. The solicitation will include a base contract line item for Wing 5 renovation and seven option contract line items, including furnishings, Wing 4 renovation, furnishings, partial spine renovation, furnishings, and remobilization. The period of performance for Wing 5 is 616 days, while Wings 4 and partial spine will be 420 and 308 days respectively if those options are exercised. A LEED Gold certification is required. The project magnitude is over $10 million. The solicitation will utilize full and open competition and result in a single award. The pre-proposal conference will be in June 2019 and proposals are due as specified in the solicitation.
Attachment 9 - HVAC Design Data and Sizing Summary for Wing 5 from PPR Appendix A
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
60560981 - B1R Design Development Design Summary Description Baseline Remarks
Wing 5
Square Footage (AHU-5-1) 47,007 SQFT
Square Footage (AHU-5-2) 26,141 SQFT
Total 73,148 SQFT
HVAC Cooling Load 258 TONS sum of peaks - connected loads
Process Cooling Load 73 Tons (Included in above figure) 12 W/SF of Lab Area (21 336 SF) = 256.0kW = 874
MBH = 72.9 tons
Future Cooling load (0%) - Applied to accommodate future building tenant demand
Design Margin (0%) TONS Applied to make the current value upper bounding for space allocation at conceptual design
Total Chilled Water Flow Demand 519 GPM Qty. (2) pumps @ 100% each
Total Cooling Tower Capacity 260 TONS Qty. (2) towers @ 50% each
Condenser Water Flow Demand 780 GPM Qty. (2) pumps @ 100% each
Process Cooling Flow Demand 175 GPM Qty. (2) pumps @ 100% each
Engineering Checks 391 SQFT/TON Process Load, Conceptual Design Factor removed from calc
HVAC Heating Load 3,063 MBH sum of peaks - connected load
Future Heating load (0%) - Applied to accommodate future building tenant demand
Conceptual Design Factor (10%) 307 MBH Applied to make the current value upper bounding for space allocation at conceptual design
Total Heating Plant Capacity 3,063 MBH Capacity is Site Output.
Total Heating Water Flow Demand 247 GPM 25 deg F delta T
Engineering Checks 65 BTUH/SQFT Domestic Load and Conceptual Design Factor removed from calc.
1,382 MBH OA heating Load
19 BTUH/SQFT
Domestic Heating Load 41 MBH Estimate is based on engineering judgement and previous building designs.
Future Heating load (0%) - Applied to accommodate future building tenant demand
Conceptual Design Factor (0%) MBH Applied to make the current value upper bounding for space allocation at conceptual design
Total Dom. Heating Capacity 41 MBH Capacity is Site Output.
Sea Level Input 100 MBH Required Sea Level Input. Assume 84% (0.84) efficiency and 4%/1000 ft. elev. (0.784) derate
Hot Water Generator installation
Hot Water Generator redundancy
FCU and DOAS System (AHU-5-1)
DOAS Airflow 20,825 CFM
Future Airflow Expansion (0%) -
Conceptual Design Factor (10%) 2,100 CFM
23,000 CFM Demand
AHU Installation
Engineering Checks 0.44 CFM/sqft (OA) Conceptual Design Factor removed from calc.
Recirc VAV System (AHU-5-2)
Total Airflow (DOAS)
Cooling Demand
Heating Plant
Air Handling Units
Domestic Water Heating
Chilled Water System Sizing
Project: NIST B1R
System: Chilled Water Glycol: 0%
MBH kW GPM L/s F C
1337 391.6 222.9 14.06 12.06 6.70
AHU-5-2 675 197.7 112.5 7.10 12.06 6.70
PFHX-5-1 874 256.0 145.7 9.19 12.06 6.70
FCU-5-201 5.2 1.5 0.9 0.06 11.62 6.45
FCU-5-202 1.1 0.3 0.2 0.01 11.06 6.14
FCU-5-203 6.4 1.9 1.1 0.07 11.70 6.50
FCU-5-204 2.8 0.8 0.5 0.03 11.26 6.26
FCU-5-205 2.3 0.7 0.4 0.03 11.56 6.42
FCU-5-206 2.3 0.7 0.4 0.03 11.56 6.42
FCU-5-207 2.3 0.7 0.4 0.03 11.56 6.42
FCU-5-208 1.1 0.3 0.2 0.01 11.06 6.14
FCU-5-209 3.6 1.1 0.6 0.04 12.06 6.70
FCU-5-301 4.7 1.4 0.8 0.05 11.81 6.56
FCU-5-302 2.2 0.6 0.4 0.03 11.06 6.14
FCU-5-303 4.4 1.3 0.8 0.05 11.06 6.14
FCU-5-304 6.4 1.9 1.1 0.07 11.70 6.50
FCU-5-305 1.1 0.3 0.2 0.01 11.06 6.14
FCU-5-306 1.5 0.4 0.3 0.02 10.05 5.58
FCU-5-307 2.3 0.7 0.4 0.03 11.56 6.42
FCU-5-308 6.4 1.9 1.1 0.07 11.70 6.50
FCU-5-309 1.5 0.4 0.3 0.02 10.05 5.58
FCU-5-310 1.5 0.4 0.3 0.02
FCU-5-311 1.5 0.4 0.3 0.02 10.05 5.58
FCU-5-312 1.5 0.4 0.3 0.02 10.05 5.58
FCU-5-313 1.7 0.5 0.3 0.02 11.39 6.33
FCU-5-314 1.7 0.5 0.3 0.02 11.39 6.33
FCU-5-315 1.7 0.5 0.3 0.02 11.39 6.33
FCU-5-316 1.7 0.5 0.3 0.02 11.39 6.33
FCU-5-317 4.7 1.4 0.8 0.05 11.81 6.56
FCU-5-318 6.4 1.9 1.1 0.07 11.70 6.50
FCU-5-319 4.4 1.3 0.8 0.05 11.06 6.14
FCU-5-320A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-320B 5.6 1.6 1 0.06 11.26 6.26
FCU-5-320A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-320B 5.6 1.6 1 0.06 11.26 6.26
FCU-5-321A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-321B 5.6 1.6 1 0.06 11.26 6.26
FCU-5-322A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-322B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-323A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-323B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-324A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-324B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-325A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-325B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-326A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-326B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-327 7 2.1 1.2 0.08 11.73 6.52
Temp. Differential
AHU-5-1
System Tot. Cooling Cap. Water Flow
30CD Equipment Sizing-WING 5 - Chilled Water 7/24/2018 - 11:04 AM
FCU-5-328A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-328B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-329A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-329B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-330A 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-330B 3.1 0.9 0.6 0.04 10.39 5.77
FCU-5-331 7 2.1 1.2 0.08 11.73 6.52
FCU-5-401 2.7 0.8 0.5 0.03 10.86 6.03
FCU-5-402 4.4 1.3 0.8 0.05 11.06 6.14
FCU-5-403 2 0.6 0.4 0.03 10.05 5.58
FCU-5-404 1.8 0.5 0.3 0.02 12.06 6.70
FCU-5-405 4.4 1.3 0.8 0.05 11.06 6.14
FCU-5-406 4.4 1.3 0.8 0.05 11.06 6.14
FCU-5-407 1.6 0.5 0.3 0.02 10.72 5.96
FCU-5-408 2.9 0.8 0.5 0.03 11.66 6.48
FCU-5-409 4.4 1.3 0.8 0.05 11.06 6.14
FCU-5-410 0.6 0.2 0.1 0.01 12.06 6.70
FCU-5-411 2.5 0.7 0.5 0.03 10.05 5.58
0.0 0.00 0.00 0.00
0.0 0.00 0.00 0.00
Sub-Total 3092 906 519 32.7
0.0 0 0 0.0
Total 3091.8 906 519 32.7 12.0 6.7 or 257.7 Tons
Growth Factor (0%)
30CD Equipment Sizing-WING 5 - Chilled Water 7/24/2018 - 11:04 AM
Heating Water System Sizing
Project: NIST B1R
System: Heating Water Glycol: 0%
MBH kW GPM L/s F C
663 194.2 53.1 3.35 25.10 13.95
AHU-5-2 (HC-5-2) 442 129.5 35.4 2.23 25.10 13.95
15.6 4.6 1.3 0.08 24.13 13.40
CUH-5-301 15.6 4.6 1.3 0.08 24.13 13.40
CUH-5-302 15.6 4.6 1.3 0.08 24.13 13.40
CUH-5-303 15.6 4.6 1.3 0.08 24.13 13.40
CUH-5-401 16.6 4.9 1.4 0.09 23.84 13.24
CUH-5-402 17.6 5.2 1.5 0.09 23.59 13.11
CUH-5-403 18.6 5.4 1.5 0.09 24.93 13.85
CUH-5-404 18.6 5.4 1.5 0.09 24.93 13.85
UH-5-201 20.1 5.9 1.7 0.11 23.77 13.21
UH-5-301 20.1 5.9 1.7 0.11 23.77 13.21
UH-5-302 20.1 5.9 1.7 0.11 23.77 13.21
R-5-5 (184LF@815 BTUh/LF)) 150 43.9 12 0.76 25.13 13.96
R-5-1:4 (340LF@815 BTUh/LF) 375 109.8 30 1.89 25.13 13.96
FCU-5-201 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-202 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-203 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-204 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-205 31.3 9.2 2.6 0.16 24.20 13.45
FCU-5-206 31.3 9.2 2.6 0.16 24.20 13.45
FCU-5-207 31.3 9.2 2.6 0.16 24.20 13.45
FCU-5-208 15.1 4.4 1.3 0.08 23.35 12.97
FCU-5-209 16.3 4.8 1.4 0.09 23.41 13.00
FCU-5-301 21.2 6.2 1.7 0.11 25.07 13.93
FCU-5-302 10.6 3.1 0.9 0.06 23.68 13.16
FCU-5-303 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-304 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-305 4.8 1.4 0.4 0.03 24.13 13.40
FCU-5-306 6.9 2.0 0.6 0.04 23.12 12.85
FCU-5-307 10.3 3.0 0.9 0.06 23.01 12.78
FCU-5-308 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-309 6.9 2.0 0.6 0.04 23.12 12.85
FCU-5-310 6.9 2.0 0.6 0.04 23.12 12.85
FCU-5-311 6.9 2.0 0.6 0.04 23.12 12.85
FCU-5-312 6.9 2.0 0.6 0.04 23.12 12.85
FCU-5-313 7.4 2.2 0.6 0.04 24.80 13.78
FCU-5-314 7.4 2.2 0.6 0.04 24.80 13.78
FCU-5-315 7.4 2.2 0.6 0.04 24.80 13.78
FCU-5-316 7.4 2.2 0.6 0.04 24.80 13.78
FCU-5-317 21.2 6.2 1.7 0.11 25.07 13.93
FCU-5-318 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-319 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-320A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-320B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-320A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-320B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-321A 41 12.0 3.3 0.21 24.98 13.88
System Tot. Heating Cap. Water Flow Temp. Differential
AHU-5-1 (HC-4-1)
CUH-5-201
30CD Equipment Sizing-WING 5 - Heating Water 7/24/2018 - 11:04 AM
FCU-5-321B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-322A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-322B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-323A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-323B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-324A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-324B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-325A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-325B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-326A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-326B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-327 33.6 9.8 2.7 0.17 25.02 13.90
FCU-5-328A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-328B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-329A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-329B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-330A 41 12.0 3.3 0.21 24.98 13.88
FCU-5-330B 41 12.0 3.3 0.21 24.98 13.88
FCU-5-331 33.6 9.8 2.7 0.17 25.02 13.90
FCU-5-401 12.2 3.6 1 0.06 24.53 13.63
FCU-5-402 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-403 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-404 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-405 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-406 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-407 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-408 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-409 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-410 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-5-411 0 0.0 0 0.00 #DIV/0! #DIV/0!
0.0 0.00 0.00 0.00
0.0 0.00 0.00 0.00
Sub-Total 3063 897 247 15.6
0.0 0 0 0.0
Total 3063.0 897 247 15.6 24.9 13.8
Growth Factor (0%)
30CD Equipment Sizing-WING 5 - Heating Water 7/24/2018 - 11:04 AM
DOAS AHU Sizing
System: AHU-5-1 Project: NIST
CFM L/s Min Max Min Max in.w.g. Pa
- 0 0 164 410 77.408 193.52 0.5 124.535
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
580 273.76 0 0 0
580 273.76 0 0 0
580 273.76 0 0 0
275 129.8 0 0 0
500 236 0 0 0
350 165.2 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
110 51.92 0 0 0
55 25.96 0 0 0
85 40.12 0 0 0
0 0 0 0 0
55 25.96 0 0 0
55 25.96 0 0 0
55 25.96 0 0 0
55 25.96 0 0 0
125 59 0 0 0
55 25.96 0 0 0
55 25.96 0 0 0
55 25.96 0 0 0
350 165.2 0 0 0
0 0 0 0 0
0 0 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
0 0 0 0 0
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0FCU-5-329A
FCU-5-326A
FCU-5-326B
FCU-5-327
FCU-5-328A
FCU-5-328B
FCU-5-323B
FCU-5-324A
FCU-5-324B
FCU-5-325A
FCU-5-325B
Primary Flow (L/s) Req'd Inlet Press.
FCU-5-203
FCU-5-204
FCU-5-205
FCU-5-201
FCU-5-202
FCU Box
Mark Type
Zone OA Req'd Primary Flow (CFM)
FCU-5-303
FCU-5-304
FCU-5-305
FCU-5-306
FCU-5-311
FCU-5-308
FCU-5-309
FCU-5-310
FCU-5-207
FCU-5-208
FCU-5-209
FCU-5-301
FCU-5-302
FCU-5-206
FCU-5-312
FCU-5-313
FCU-5-320B
FCU-5-314
FCU-5-315
FCU-5-316
FCU-5-317
FCU-5-318
FCU-5-319
FCU-5-320A
FCU-5-320A
FCU-5-307
FCU-5-320B
FCU-5-321A
FCU-5-321B
FCU-5-322A
FCU-5-322B
FCU-5-323A
30CD Equipment Sizing-WING 5 - AHU-5-1 7/24/2018 - 11:04 AM
750 354 0 0 0
750 354 0 0 0
750 354 0 0 0
0 0 0 0 0
350 165.2 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0
0 0 0 0
Sub-Total 20825 9829.4 164 410 77.408 193.52 0.5 124.535
0 0 0 0
Total 20825 9829.4 410 193.52
FCU-5-401
FCU-5-402
placeholder
FCU-5-329B
FCU-5-330A
FCU-5-330B
FCU-5-331
placeholder placeholder
Growth Factor (0%) placeholder placeholder placeholder placeholder placeholder placeholder
30CD Equipment Sizing-WING 5 - AHU-5-1 7/24/2018 - 11:04 AM
Heat Exchanger Sizing
Printed On: 7/24/2018
Project Name: NIST B1R
Project #: 60560981
Heat Exchanger: STHX-SP-1
Service Steam (15 PSI) to Heating Water
System Properties
Hot Side Steam Cold Side Heating Water
Flow 3930 PPH Flow 247 GPM
EWT 0 deg F EWT 135 deg F
LWT 0 deg F LWT 165 deg F
Delta T 0 deg F Delta T 30 deg F
Fluid Steam Fluid Water
Percent Glycol 0 % Percent Glycol 0 %
Derate Factor 500 Derate Factor 500
Heat Transfer 3708 MBH
Code Requirements:
TBD
Notes:
M:\DCS\Projects\BDL\60560981_NIST_Bould\400-Technical\437-Mechanical\Calculations\30CD_Equipment Sizing\30CD Equipment
Sizing-WING 5
Project Name: NIST B1R
Project #: 60560981
Heat Exchanger: STHX-SP-1
Service Steam (15 PSI) to Heating Water
System Properties
Hot Side Process Water Cold Side Chilled Water
Flow 146 GPM Flow 121 GPM
EWT 65 deg F EWT 44 deg F
LWT 55 deg F LWT 56 deg F
Delta T 10 deg F Delta T 12 deg F
Fluid Water Fluid Water
Percent Glycol 0 % Percent Glycol 0 %
Derate Factor 500 Derate Factor 500
Heat Transfer 729 MBH Heat Transfer 729 MBH
Code Requirements:
TBD
Notes:
M:\DCS\Projects\BDL\60560981_NIST_Bould\400-Technical\437-Mechanical\Calculations\30CD_Equipment Sizing\30CD Equipment
Project Name: NIST B1R
Project #: 60560981
Heat Exchanger: STHX-SP-1
Service Steam (15 PSI) to Heating Water
System Properties
Hot Side Heating Water Cold Side Snowmelt
Flow 65 GPM Flow 65 GPM
EWT 160 deg F EWT 132 deg F
LWT 135 deg F LWT 157 deg F
Delta T 25 deg F Delta T 25 deg F
Fluid Water Fluid Water
Percent Glycol 0 % Percent Glycol 0 %
Derate Factor 500 Derate Factor 500
Heat Transfer 813 MBH Heat Transfer 813 MBH
Code Requirements:
TBD
Notes:
M:\DCS\Projects\BDL\60560981_NIST_Bould\400-Technical\437-Mechanical\Calculations\30CD_Equipment Sizing\30CD Equipment
File details come from the government source that posted it. Updated .