This document package includes a design development design summary and related federal contract opportunity notice. The design summary provides technical specifications for HVAC, chilled water, heating water, and DOAS AHU systems for the proposed NIST Boulder Campus Renovation of Building 1 Wing 5, Wing 4 and Partial Spine project. Key details include square footage, cooling and heating loads, pump capacities, airflow requirements, and equipment sizing calculations.
The federal contract opportunity is a solicitation notice for design-build construction services for the above-mentioned NIST renovation project. Services include base renovation of Wing 5 with options for furnishings, Wing 4 renovation and furnishings, Spine renovation and furnishings, and remobilization. The period of performance for Wing 5 is 616 days with options and 308 days for the Spine. The project value is over $10M requiring LEED Gold certification. The solicitation will be posted on June 3, 2019 on FBO, with a pre-proposal conference scheduled. The NAICS code is 236220 and small business size standard is $36.5M. The award will result in a single design-build contract.
Attachment 7 - HVAC Design Data and Sizing Summary for Spine from PPR Appendix A
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
60560981 - B1R Design Development Design Summary Description Baseline Remarks
Spine
Square Footage 23,644 SQFT
HVAC Cooling Load 55 TONS sum of peaks - connected loads
Process Cooling Load 14 Tons (Included in above figure) 12 W/SF of Lab Area (3908 SF) = 46.9kW = 2160.1
MBH = 13.3 tons
Future Cooling load (0%) - Applied to accommodate future building tenant demand
Design Margin (0%) TONS Applied to make the current value upper bounding for space allocation at conceptual design
Total Chilled Water Flow Demand 111 GPM Qty. (2) pumps @ 100% each
Total Cooling Tower Capacity 55 TONS Qty. (2) towers @ 50% each
Condenser Water Flow Demand 165 GPM Qty. (2) pumps @ 100% each
Process Cooling Flow Demand 32 GPM Qty. (2) pumps @ 100% each
Engineering Checks 577 SQFT/TON Process Load, Conceptual Design Factor removed from calc
HVAC Heating Load 587 MBH sum of peaks - connected load
Future Heating load (0%) - Applied to accommodate future building tenant demand
Conceptual Design Factor (10%) 59 MBH Applied to make the current value upper bounding for space allocation at conceptual design
Total Heating Plant Capacity 587 MBH Capacity is Site Output.
Total Heating Water Flow Demand 48 GPM 25 deg F delta T
Engineering Checks 25 BTUH/SQFT Domestic Load and Conceptual Design Factor removed from calc.
282 MBH OA heating Load
12 BTUH/SQFT
Domestic Heating Load 41 MBH Estimate is based on engineering judgement and previous building designs.
Future Heating load (0%) - Applied to accommodate future building tenant demand
Conceptual Design Factor (0%) MBH Applied to make the current value upper bounding for space allocation at conceptual design
Total Dom. Heating Capacity 41 MBH Capacity is Site Output.
Sea Level Input 100 MBH Required Sea Level Input. Assume 84% (0.84) efficiency and 4%/1000 ft. elev. (0.784) derate
Hot Water Generator installation
Hot Water Generator redundancy
FCU and DOAS System
DOAS Airflow 4,255 CFM
Future Airflow Expansion (0%) 0 CFM
Conceptual Design Factor (10%) 500 CFM
4,800 CFM Demand
AHU Installation
Engineering Checks 0.18 CFM/sqft (OA) Conceptual Design Factor removed from calc.
Total Airflow (DOAS)
Cooling Demand
Heating Plant
Air Handling Units
Domestic Water Heating
Chilled Water System Sizing
Project: NIST B1R
System: Chilled Water Glycol: 0%
MBH kW GPM L/s F C
215 63.0 35.9 2.26 12.04 6.69
159.6 46.7 26.6 1.68 12.06 6.70
FCU-SP-301 13.3 3.9 2.3 0.15 11.63 6.46
FCU-SP-302 7.8 2.3 1.3 0.08 12.06 6.70
FCU-SP-303 6 1.8 1 0.06 12.06 6.70
FCU-SP-304 8.8 2.6 1.5 0.09 11.80 6.55
FCU-SP-305 6.4 1.9 1.1 0.07 11.70 6.50
FCU-SP-306 13.3 3.9 2.3 0.15 11.63 6.46
FCU-SP-307 8.9 2.6 1.5 0.09 11.93 6.63
FCU-SP-308 12.4 3.6 2.1 0.13 11.87 6.60
FCU-SP-309 9.3 2.7 1.6 0.10 11.69 6.49
FCU-SP-310 10.7 3.1 1.8 0.11 11.95 6.64
FCU-SP-311 13.2 3.9 2.2 0.14 12.06 6.70
FCU-SP-312 11.5 3.4 2 0.13 11.56 6.42
FCU-SP-313 11.1 3.3 1.9 0.12 11.75 6.53
FCU-SP-314 13.3 3.9 2.3 0.15 11.63 6.46
FCU-SP-315 8.8 2.6 1.5 0.09 11.80 6.55
FCU-SP-401 4 1.2 0.7 0.04 11.49 6.38
FCU-SP-402 7.2 2.1 1.2 0.08 12.06 6.70
FCU-SP-403 10.8 3.2 1.8 0.11 12.06 6.70
FCU-SP-404 6.2 1.8 1.1 0.07 11.33 6.30
FCU-SP-405 7.7 2.3 1.3 0.08 11.91 6.62
FCU-SP-406 9.3 2.7 1.6 0.10 11.69 6.49
FCU-SP-407 6.2 1.8 1.1 0.07 11.33 6.30
FCU-SP-408 9.3 2.7 1.6 0.10 11.69 6.49
FCU-SP-409 9 2.6 1.5 0.09 12.06 6.70
FCU-SP-410 12 3.5 2 0.13 12.06 6.70
FCU-SP-411 6.2 1.8 1.1 0.07 11.33 6.30
FCU-SP-412 6.2 1.8 1.1 0.07 11.33 6.30
FCU-SP-413 6.2 1.8 1.1 0.07 11.33 6.30
FCU-SP-414 10.4 3.0 1.8 0.11 11.62 6.45
FCU-SP-415 10.4 3.0 1.8 0.11 11.62 6.45
FCU-SP-416 7.3 2.1 1.3 0.08 11.29 6.27
0.0 0 0.00 #DIV/0! #DIV/0!
0.0 0.00 0.00 0.00
Sub-Total 658 193 111 7.0
0.0 0 0 0.0
Total 657.8 193 111 7.0 11.9 6.6 or 54.8 Tons
Temp. Differential
AHU-SP-1
PFHX-SP-1
System Tot. Cooling Cap. Water Flow
Growth Factor (0%)
30CD Equipment Sizing-SPINE - Chilled Water 7/24/2018 - 11:06 AM
Heating Water System Sizing
Project: NIST B1R
System: Heating Water Glycol: 0%
MBH kW GPM L/s F C
139 40.7 11.2 0.71 24.95 13.86
20 5.9 1.6 0.10 25.13 13.96
CUH-SP-2 20 5.9 1.6 0.10 25.13 13.96
R-SP-1 (236LF@815 BTUh/LF)) 193 56.5 15.5 0.98 25.03 13.91
FCU-SP-301 10.6 3.1 0.9 0.06 23.68 13.16
FCU-SP-302 5.8 1.7 0.5 0.03 23.32 12.96
FCU-SP-303 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-304 14.6 4.3 1.2 0.08 24.46 13.59
FCU-SP-305 10.6 3.1 0.9 0.06 23.68 13.16
FCU-SP-306 22.1 6.5 1.8 0.11 24.69 13.71
FCU-SP-307 14.8 4.3 1.2 0.08 24.80 13.78
FCU-SP-308 9.3 2.7 0.8 0.05 23.37 12.98
FCU-SP-309 7 2.1 0.6 0.04 23.46 13.03
FCU-SP-310 17.8 5.2 1.5 0.09 23.86 13.25
FCU-SP-311 9.9 2.9 0.8 0.05 24.88 13.82
FCU-SP-312 19.1 5.6 1.6 0.10 24.00 13.33
FCU-SP-313 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-314 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-315 6.6 1.9 0.6 0.04 22.12 12.29
FCU-SP-401 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-402 5.4 1.6 0.5 0.03 21.71 12.06
FCU-SP-403 8.1 2.4 0.7 0.04 23.27 12.93
FCU-SP-404 4.6 1.3 0.4 0.03 23.12 12.85
FCU-SP-405 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-406 7 2.1 0.6 0.04 23.46 13.03
FCU-SP-407 4.6 1.3 0.4 0.03 23.12 12.85
FCU-SP-408 7 2.1 0.6 0.04 23.46 13.03
FCU-SP-409 6.8 2.0 0.6 0.04 22.79 12.66
FCU-SP-410 9 2.6 0.8 0.05 22.62 12.57
FCU-SP-411 4.6 1.3 0.4 0.03 23.12 12.85
FCU-SP-412 4.6 1.3 0.4 0.03 23.12 12.85
FCU-SP-413 4.6 1.3 0.4 0.03 23.12 12.85
FCU-SP-414 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-415 0 0.0 0 0.00 #DIV/0! #DIV/0!
FCU-SP-416 0 0.0 0 0.00 0.00 0.00
0.0 0.00 0.00 0.00
Sub-Total 587 172 48 3.0
0.0 0 0 0.0
Total 586.5 172 48 3.0 24.5 13.6
Growth Factor (0%)
System Tot. Heating Cap. Water Flow Temp. Differential
AHU-SP-1 (HC-SP-1)
CUH-SP-1
30CD Equipment Sizing-SPINE - Heating Water 7/24/2018 - 11:06 AM
DOAS AHU Sizing
System: AHU-SP-1 Project: NIST
CFM L/s Min Max Min Max in.w.g. Pa
- 0 0 164 410 77.408 193.52 0.5 124.535
70 33.04 0 0 0
0 0 0 0 0
470 221.84 0 0 0
320 151.04 0 0 0
635 299.72 0 0 0
475 224.2 0 0 0
105 49.56 0 0 0
90 42.48 0 0 0
475 224.2 0 0 0
115 54.28 0 0 0
475 224.2 0 0 0
0 0 0 0 0
0 0 0 0 0
120 56.64 0 0 0
0 0 0 0 0
90 42.48 0 0 0
110 51.92 0 0 0
60 28.32 0 0 0
0 0 0 0 0
90 42.48 0 0 0
60 28.32 0 0 0
90 42.48 0 0 0
80 37.76 0 0 0
105 49.56 0 0 0
60 28.32 0 0 0
60 28.32 0 0 0
60 28.32 0 0 0
0 0 0 0 0
0 0 0 0 0
40 18.88 0 0 0
0 0 0 0
Sub-Total 4255 2008.4 164 410 77.408 193.52 0.5 124.535
212.75 100.42 20.5 9.676
Total 4467.8 2108.8 430.5 203.196
FCU-SP-306
FCU-SP-307
Primary Flow (L/s) Req'd Inlet Press.
FCU-SP-303
FCU-SP-304
FCU-SP-305
FCU-SP-301
FCU-SP-302
FCU Box
Mark Type
Zone OA Req'd Primary Flow (CFM)
FCU-SP-406
FCU-SP-407
FCU-SP-415
FCU-SP-408
FCU-SP-409
FCU-SP-410
FCU-SP-411
FCU-SP-412
FCU-SP-413
FCU-SP-414
Growth Factor (5%)
FCU-SP-416
FCU-SP-308
FCU-SP-309
FCU-SP-310
FCU-SP-311
FCU-SP-312
FCU-SP-313
FCU-SP-314
FCU-SP-315
FCU-SP-405
FCU-SP-402
FCU-SP-403
FCU-SP-404
FCU-SP-401
30CD Equipment Sizing-SPINE - AHU-SP-1 7/24/2018 - 11:06 AM
Heat Exchanger Sizing
Printed On: 7/24/2018
Project Name: NIST B1R
Project #: 60560981
Heat Exchanger: PFHX-SP-1
Service Process Chilled Water
System Properties
Hot Side Process Water Cold Side Chilled Water
Flow 32 GPM Flow 27 GPM
EWT 65 deg F EWT 44 deg F
LWT 55 deg F LWT 56 deg F
Delta T 10 deg F Delta T 12 deg F
Fluid Water Fluid Water
Percent Glycol 0 % Percent Glycol 0 %
Derate Factor 500 Derate Factor 500
Heat Transfer 160 MBH Heat Transfer 160 MBH
Code Requirements:
TBD
Notes:
M:\DCS\Projects\BDL\60560981_NIST_Bould\400-Technical\437-Mechanical\Calculations\30CD_Equipment Sizing\30CD Equipment
Sizing-SPINE