IAC Silencers Submittal Sheets 9017-DR.pdf

PDF 358 KB Posted

Attached to
NOAA Ship Okeanos Explorer FY 2024 Drydock Repairs
Solicitation number
1305M223QNMAN0142
Issued by

About this file

This document contains submittal sheets for silencer products for a NOAA vessel. The submittal sheets provide specifications for six silencers of various sizes for applications including stern thruster exhaust, tween deck exhaust, winch room supply, and ROV exhaust and supply. Dimensions, weights, construction details, pressure and combustion ratings are specified for each silencer. Testing was conducted in accordance with ASTM E477 standards. Approval of the submittal sheets is requested by September 29, 2022 for incorporation into a project for NOAA vessel repairs and refit.

The related federal contract opportunity is solicitation number 1305M223QNMAN0142 for drydock repairs to the NOAA ship Okeanos Explorer in fiscal year 2024. The solicitation was issued by the Department of Commerce National Oceanic and Atmospheric Administration for repair work on the NOAA research vessel.

View the file

Other files

File Type Posted
Amendment 0008 Continuation Page.pdf PDF
HJ241 Product Manual.pdf PDF
Amendment 0008.pdf PDF
A314OSTG OKEANOS EXPLORER UPGRADE.PDF PDF
B119454-A.pdf PDF
B119261 DIAGRAM.pdf PDF
Airborne Survey Results.pdf PDF
KNC_Project_230202RH_Schedule.pdf PDF
Amendment 0007 Continuation Page.pdf PDF
Amendment 0007.pdf PDF
22-55552 NOAA Vessel.pdf PDF
KNC_Project_230202RH_Quote.pdf PDF
OE-123-101.pdf PDF
Amendment 0006 Continuation Page.pdf PDF
OE-422-103 LED Navigation Lights Installation.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0005 Continuation Page.pdf PDF
Model HH 219_Separator_Manual.pdf PDF
Boss 107 Separator System.pdf PDF
OE-570-001.pdf PDF
Amendment 0004 Continuation Page.pdf PDF
Amendment 0004.pdf PDF
RFQ_1305M223QNMAN0142 REV 2.pdf PDF
Continuation Page.pdf PDF
RFQ_1305M223QNMAN0142 REV 1.pdf PDF
Amendment 0003.pdf PDF
508 Standards Checklist.pdf PDF
Amendment 0002.pdf PDF
Amendment 0002 Continuation Page.pdf PDF
243-6233870.pdf PDF
524-6233814.pdf PDF
OE-555-001_Fire Control Plan_Rev D (3).pdf PDF
T9568-AC-MMO-010_0_0.PDF PDF
OE_583_06_REV0_MAN.pdf PDF
SSPC-SP-1-Solvent-Wipe.pdf PDF
0606- Standards for Lifting Appliances on NOAA Ships.doc DOC document
Explorer GSSP Hydrostatics.pdf PDF
OE_575_04_MAN - Traction Winch.pdf PDF
NOAA Pre-Drydock Worksheet.pdf PDF
528-6233824.pdf PDF
562-6233911.pdf PDF
436-6233675.pdf PDF
OE_583_03_MAN.pdf PDF
Manual-HP46-18KE-6600-06262.pdf PDF
OE-601-101.pdf PDF
OE-165-101.pdf PDF
320-6233663.pdf PDF
OE-436-001.pdf PDF
528-6233903.pdf PDF
Show 40 more

Latest 50 of 140 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Noise Control | HVAC Silencers | Acoustical Louvers | Plenums

401 Airport Road North Aurora, IL 60542 United States

Tel: (630) 270-1790 Fax: (630) 966-9710 www.iacacoustics.com

File No.: 5 Date: 29 Sep 2022

Supersedes: 4 Date: 29 Sep 2022

Transmittal

Company

AAP

Project Name NOAA Vessel

Quote #

9017-DR

Address

Your P.O. #

IAC Order #

IAC Project Manager Desiree Mills

Phone #

(603) 674-0850

Attention Desiree Mills

Date Sent 2022-09-29T12:41:24.

Drawing Type: x For Approval Records Installation If "For Approval" box is checked, return one copy of drawings marked "Approved" when releasing product.

Tag Product Description

Stern Thruster Exhaust Fan 22”

3CL Conic Flow®

Stern Thruster Supply 22”

3CL Conic Flow®

Tween Deck Exhaust 13”

3CS Conic Flow®

Winch Room supply 15”

3CL Conic Flow®

ROV Exhaust 3MS Quiet-Duct® Commercial Series

ROV Supply 3MS Quiet-Duct® Commercial Series

* Lead times begin when final submittals are returned approved with no changes.

Notes

Tel: (630) 270-1790 Web: www.IACsilencers.com

Fax: (630) 966-9710 Eml: HVACinfo@industrialacoustics.com

CONIC FLOW® SILENCER 3CL

File No.: 5 Date: 29 Sep 2022

Supersedes: 4 Date: 29 Sep 2022

TAG:

Stern Thruster Exhaust Fan 22” QTY:

Submitted for : Approval Dwg #: 1

Project NOAA Vessel

Customer

AAP

Customer P.O. No.

IAC Project No.

80954

IAC Project Mananger Desiree Mills

Consultant

Quote #

9017-DR

Performance for Model 3CL Airflow Velocity Pressure Drop Dynamic Insertion Loss (dB)

CFM FPM in.w.g. 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz

8010 3034.31 0.14 0 7 10 15 31 28 25 20 17 Self-Noise Power Levels

0 60 56 54 54 53 52 50 40

Silencer performance data has been obtained from tests conducted in a laboratory facility NVLAP accredited for the ASTM E477 test standard.

* Duct configuration must be known for at least 5 duct diameters upstream and downstream of the silencer to determine pressure drop with system effects.

Dimensions and Weights

Silencer Size (in/mm) Total Wt Shipping Sections (same as silencer size if blank)

ID OD L (lb/kg) QTY D E C

22.00 30.00 44.00 150

Construction Casing Standard (22 Ga) Perforated liner Standard (22 Ga) Media Fill Fiberglass Media Protection None

End connections 1 1/2 x 1 1/2 x 1/8

1 1/2 x 1 1/2 x 1/8

Ratings Pressure rating 8 in.W.G

Combustion rating (ASTM E84 or

CAN/ULC S102)

Flamespread classification <20 Smoke development rating <20

Notes

IAC's recommendations as based off of limited information at this point. Customer is to confirm all dimensions.

Lead time is approx. (3-4) weeks for build / production ARO.

Please confirm lead time when ordering. Lead time doesn't include transportation time.

Pricing is good for 30 days from the date stated above.

Delivery within 120 days of order based on current steel prices.

Engineering and design is allocated as needed. Silencer construction and published acoustic and aerodynamic performance meets all needed requirements of SMACNA, ASHRAE and in strict accordance with ASTM E477, in an NVLAP Accredited laboratory.

Standard Freight: FRT Included.

Shipping Includes: Palletizing & shrink-wrapping and skidding.

Tolerances: a) Width: +1/8, -1/8 Inch; b) Height: +1/8, -1/8 Inch. Gauge of material is based on SMACNA standards unless noted otherwise.

Should changes be made to any of the following quoted silencers, whether it be in QTY and or in any dimensions (W or H or L), IAC reserves the right to re-price as needed and accordingly upon any changes.

Fax: (630) 966-9710 Eml: HVACinfo@industrialacoustics.com

CONIC FLOW® SILENCER 3CL

File No.: 5 Date: 29 Sep 2022

Stern Thruster Supply 22” QTY:

Submitted for : Approval Dwg #: 2

Project NOAA Vessel

Customer

AAP

Customer P.O. No.

IAC Project No.

80954

IAC Project Mananger Desiree Mills

Consultant

Quote #

9017-DR

Performance for Model 3CL Airflow Velocity Pressure Drop Dynamic Insertion Loss (dB)

CFM FPM in.w.g. 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz

8010 -3034.31 0.14 0 9 12 18 32 30 19 16 11 Self-Noise Power Levels

0 56 56 55 56 55 55 50 45

Silencer performance data has been obtained from tests conducted in a laboratory facility NVLAP accredited for the ASTM E477 test standard.

* Duct configuration must be known for at least 5 duct diameters upstream and downstream of the silencer to determine pressure drop with system effects.

Dimensions and Weights

Silencer Size (in/mm) Total Wt Shipping Sections (same as silencer size if blank)

22.00 30.00 44.00 150

Perforated liner Standard (22 Ga) Media Fill Fiberglass Media Protection None

End connections 1 1/2 x 1 1/2 x 1/8

1 1/2 x 1 1/2 x 1/8

Ratings Pressure rating 8 in.W.G

Combustion rating (ASTM E84 or

CAN/ULC S102)

Flamespread classification <20 Smoke development rating <20

Notes

IAC's recommendations as based off of limited information at this point. Customer is to confirm all dimensions.

Lead time is approx. (3-4) weeks for build / production ARO.

Please confirm lead time when ordering. Lead time doesn't include transportation time.

Pricing is good for 30 days from the date stated above.

Delivery within 120 days of order based on current steel prices.

Engineering and design is allocated as needed. Silencer construction and published acoustic and aerodynamic performance meets all needed requirements of SMACNA, ASHRAE and in strict accordance with ASTM E477, in an NVLAP Accredited laboratory.

Standard Freight: FRT Included.

Shipping Includes: Palletizing & shrink-wrapping and skidding.

Tolerances: a) Width: +1/8, -1/8 Inch; b) Height: +1/8, -1/8 Inch. Gauge of material is based on SMACNA standards unless noted otherwise.

Should changes be made to any of the following quoted silencers, whether it be in QTY and or in any dimensions (W

Fax: (630) 966-9710 Eml: HVACinfo@industrialacoustics.com

CONIC FLOW® SILENCER 3CS

File No.: 5 Date: 29 Sep 2022

Tween Deck Exhaust 13” QTY:

Submitted for : Approval Dwg #: 3

Project NOAA Vessel

Customer

AAP

Customer P.O. No.

IAC Project No.

80954

IAC Project Mananger Desiree Mills

Consultant

Quote #

9017-DR

Performance for Model 3CS Airflow Velocity Pressure Drop Dynamic Insertion Loss (dB)

CFM FPM in.w.g. 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz

470 509.9 0.02 0 10 15 20 35 37 30 22 16 Self-Noise Power Levels

0 43 41 37 37 36 36 21 20

Silencer performance data has been obtained from tests conducted in a laboratory facility NVLAP accredited for the ASTM E477 test standard.

* Duct configuration must be known for at least 5 duct diameters upstream and downstream of the silencer to determine pressure drop with system effects.

Dimensions and Weights

Silencer Size (in/mm) Total Wt Shipping Sections (same as silencer size if blank)

13.00 21.00 36.00 111

Perforated liner Standard (22 Ga) Media Fill Fiberglass Media Protection None

End connections 1 1/2 x 1 1/2 x 1/8

1 1/2 x 1 1/2 x 1/8

Ratings Pressure rating 8 in.W.G

Combustion rating (ASTM E84 or

CAN/ULC S102)

Flamespread classification <20 Smoke development rating <20

Notes

IAC's recommendations as based off of limited information at this point. Customer is to confirm all dimensions.

Lead time is approx. (3-4) weeks for build / production ARO.

Please confirm lead time when ordering. Lead time doesn't include transportation time.

Pricing is good for 30 days from the date stated above.

Delivery within 120 days of order based on current steel prices.

Engineering and design is allocated as needed. Silencer construction and published acoustic and aerodynamic performance meets all needed requirements of SMACNA, ASHRAE and in strict accordance with ASTM E477, in an NVLAP Accredited laboratory.

Standard Freight: FRT Included.

Shipping Includes: Palletizing & shrink-wrapping and skidding.

Tolerances: a) Width: +1/8, -1/8 Inch; b) Height: +1/8, -1/8 Inch. Gauge of material is based on SMACNA standards unless noted otherwise.

Should changes be made to any of the following quoted silencers, whether it be in QTY and or in any dimensions (W

Fax: (630) 966-9710 Eml: HVACinfo@industrialacoustics.com

CONIC FLOW® SILENCER 3CL

File No.: 5 Date: 29 Sep 2022

Winch Room supply 15” QTY:

Submitted for : Approval Dwg #: 4

Project NOAA Vessel

Customer

AAP

Customer P.O. No.

IAC Project No.

80954

IAC Project Mananger Desiree Mills

Consultant

Quote #

9017-DR

Performance for Model 3CL Airflow Velocity Pressure Drop Dynamic Insertion Loss (dB)

CFM FPM in.w.g. 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz

2510 2045.33 0.06 0 7 11 16 31 29 25 20 17 Self-Noise Power Levels

0 52 48 46 46 45 42 40 26

Silencer performance data has been obtained from tests conducted in a laboratory facility NVLAP accredited for the ASTM E477 test standard.

* Duct configuration must be known for at least 5 duct diameters upstream and downstream of the silencer to determine pressure drop with system effects.

Dimensions and Weights

Silencer Size (in/mm) Total Wt Shipping Sections (same as silencer size if blank)

15.00 23.00 36.00 111

Perforated liner Standard (22 Ga) Media Fill Fiberglass Media Protection None

End connections 1 1/2 x 1 1/2 x 1/8

1 1/2 x 1 1/2 x 1/8

Ratings Pressure rating 8 in.W.G

Combustion rating (ASTM E84 or

CAN/ULC S102)

Flamespread classification <20 Smoke development rating <20

Notes

IAC's recommendations as based off of limited information at this point. Customer is to confirm all dimensions.

Lead time is approx. (3-4) weeks for build / production ARO.

Please confirm lead time when ordering. Lead time doesn't include transportation time.

Pricing is good for 30 days from the date stated above.

Delivery within 120 days of order based on current steel prices.

Engineering and design is allocated as needed. Silencer construction and published acoustic and aerodynamic performance meets all needed requirements of SMACNA, ASHRAE and in strict accordance with ASTM E477, in an NVLAP Accredited laboratory.

Standard Freight: FRT Included.

Shipping Includes: Palletizing & shrink-wrapping and skidding.

Tolerances: a) Width: +1/8, -1/8 Inch; b) Height: +1/8, -1/8 Inch. Gauge of material is based on SMACNA standards unless noted otherwise.

Should changes be made to any of the following quoted silencers, whether it be in QTY and or in any dimensions (W

Fax: (630) 966-9710 Eml: HVACinfo@industrialacoustics.com

QUIET-DUCT® COMMERCIAL

SERIES SILENCER 3MS

File No.: 5 Date: 29 Sep 2022

ROV Exhaust QTY:

Submitted for : Approval Dwg #: 5

Project NOAA Vessel

Customer

AAP

Customer P.O. No.

IAC Project No.

80954

IAC Project Mananger Desiree Mills

Consultant

Quote #

9017-DR

Performance for Model 3MS Airflow Velocity Pressure Drop Dynamic Insertion Loss (dB)

CFM FPM in.w.g. 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz

500 480 0.02 0 5 7 13 23 25 20 15 10 Self-Noise Power Levels

0 45 35 38 36 36 37 33 22

Silencer performance data has been obtained from tests conducted in a laboratory facility NVLAP accredited for the ASTM E477 test standard.

* Duct configuration must be known for at least 5 duct diameters upstream and downstream of the silencer to determine pressure drop with system effects.

Dimensions and Weights

Silencer Size (in/mm) Total Wt Shipping Sections (same as silencer size if blank)

A B C (lb/kg) QTY D E C

15.00 10.00 36.00 33

Perforated liner Standard (26 Ga) Media Fill Fiberglass Media Protection None

End connections 1 1/2 x 1 1/2 x 1/8

1 1/2 x 1 1/2 x 1/8

Ratings Pressure rating 8 in.W.G

Combustion rating (ASTM E84 or

CAN/ULC S102)

Flamespread classification <20 Smoke development rating <20

Notes

IAC's recommendations as based off of limited information at this point. Customer is to confirm all dimensions.

Lead time is approx. (3-4) weeks for build / production ARO.

Please confirm lead time when ordering. Lead time doesn't include transportation time.

Pricing is good for 30 days from the date stated above.

Delivery within 120 days of order based on current steel prices.

Engineering and design is allocated as needed. Silencer construction and published acoustic and aerodynamic performance meets all needed requirements of SMACNA, ASHRAE and in strict accordance with ASTM E477, in an NVLAP Accredited laboratory.

Standard Freight: FRT Included.

Shipping Includes: Palletizing & shrink-wrapping and skidding.

Tolerances: a) Width: +1/8, -1/8 Inch; b) Height: +1/8, -1/8 Inch. Gauge of material is based on SMACNA standards unless noted otherwise.

Should changes be made to any of the following quoted silencers, whether it be in QTY and or in any dimensions (W

Fax: (630) 966-9710 Eml: HVACinfo@industrialacoustics.com

QUIET-DUCT® COMMERCIAL

SERIES SILENCER 3MS

File No.: 5 Date: 29 Sep 2022

ROV Supply QTY:

Submitted for : Approval Dwg #: 6

Project NOAA Vessel

Customer

AAP

Customer P.O. No.

IAC Project No.

80954

IAC Project Mananger Desiree Mills

Consultant

Quote #

9017-DR

Performance for Model 3MS Airflow Velocity Pressure Drop Dynamic Insertion Loss (dB)

CFM FPM in.w.g. 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz

500 -480 0.02 0 5 7 13 23 25 20 15 10 Self-Noise Power Levels

0 45 42 43 39 45 46 39 22

Silencer performance data has been obtained from tests conducted in a laboratory facility NVLAP accredited for the ASTM E477 test standard.

* Duct configuration must be known for at least 5 duct diameters upstream and downstream of the silencer to determine pressure drop with system effects.

Dimensions and Weights

Silencer Size (in/mm) Total Wt Shipping Sections (same as silencer size if blank)

A B C (lb/kg) QTY D E C

15.00 10.00 36.00 33

Perforated liner Standard (26 Ga) Media Fill Fiberglass Media Protection None

End connections 1 1/2 x 1 1/2 x 1/8

1 1/2 x 1 1/2 x 1/8

Ratings Pressure rating 8 in.W.G

Combustion rating (ASTM E84 or

CAN/ULC S102)

Flamespread classification <20 Smoke development rating <20

Notes

IAC's recommendations as based off of limited information at this point. Customer is to confirm all dimensions.

Lead time is approx. (3-4) weeks for build / production ARO.

Please confirm lead time when ordering. Lead time doesn't include transportation time.

Pricing is good for 30 days from the date stated above.

Delivery within 120 days of order based on current steel prices.

Engineering and design is allocated as needed. Silencer construction and published acoustic and aerodynamic performance meets all needed requirements of SMACNA, ASHRAE and in strict accordance with ASTM E477, in an NVLAP Accredited laboratory.

Standard Freight: FRT Included.

Shipping Includes: Palletizing & shrink-wrapping and skidding.

Tolerances: a) Width: +1/8, -1/8 Inch; b) Height: +1/8, -1/8 Inch. Gauge of material is based on SMACNA standards unless noted otherwise.

Should changes be made to any of the following quoted silencers, whether it be in QTY and or in any dimensions (W