This document is a solicitation for the construction of a new office building less than 5,000 square feet, associated septic system, and utility connections for the Green Base Work Center (Pittman Valley Helibase) in Williams, Arizona. The project is a 100% Small Business Set-Aside with an estimated value between $1,000,000 and $5,000,000. The contract will be Firm Fixed-Price, awarded based on a Best Value-Tradeoffs evaluation, considering technical factors and price. A site visit is scheduled for July 9, 2024, and the deadline for offer submission is August 1, 2024 at 1:00 pm PT. The solicitation package will be available through SAM.gov, and all amendments will be posted there. Davis-Bacon wages apply, and payment and performance bonds are required. The contracting agency is the USDA Forest Service, Southwestern Region.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF SHEETS
FOREST LOCATION
PROJECT LOCATION MAP
TRAVEL DIRECTIONS:
SHEET OF
United States Department of Agriculture
Forest Service
RECOMMENDED BY:
APPROVED:
FOREST ENGINEER
DISTRICT RANGER DATE
DATE
DATE
DIRECTOR OF ENGINEERING DATE
ARIZONA
COCONINO COUNTY
(R03) SOUTHWESTERN REGION
KAIBAB NATIONAL FOREST
FROM THE COCONINO NATIONAL FOREST SUPERVISOR’S OFFICE, HEAD NORTH ON S
THOMPSON ST FOR 0.1 MILES. TURN LEFT ONTO I-40 BL W/HISTORIC RTE 66 FOR 3.4 MILES.
MERGE ONTO 1-40 W FOR 19.1 MILES. TAKE EXIT 171 TOWARD PITTMAN VALLEY RD/DEER
FARM ROAD FOR 0.3 MILES. TURN RIGHT ONTO COOL PINES RD FOR 0.1 MILES. TURN LEFT
ONTO N BUGGY WHEEL RANCH RD FOR 1.0 MILE. TURN LEFT ONTO FOREST SERVICE ROAD
74G FOR 226 FEET. MAKE SLIGHT RIGHT ONTO FOREST SERVICE ROAD 74 FOR 0.2 MILES.
TURN RIGHT TO STAY ON FOREST ROAD 74. PITTMAN VALLEY WORK CENTER WILL BE ON THE
LEFT IN 95 FEET.
Map data © 2024 Google
TECHNICAL ASPECTS REVIEWED:
FOREST SUPERVISOR
/2
/2
:5
:3
A
M C
U s e rs
\M a rk
R \D o c u m e n ts
\G re e n B a s e W o rk
C e n te r_ r2 m ro y la n c e
.r v t
GREEN BASE WORK CENTER
(PITTMAN VALLEY HELIBASE)
OFFICE REPLACEMENT
THESE DRAWINGS WERE PREPARED BY MOSAIC ARCHITECTURE, P.C. FOR CONSTRUCTION OF THE PROJECT DESCRIBED HEREIN. AS SUCH, THE DOCUMENTS ARE THE PROPERTY OF MOSAIC ARCHITECTURE, P.C. & MAY NOT BE REPRODUCED, COPIED OR USED IN ANY WAY WITHOUT PRIOR APPROVAL FROM MOSAIC ARCHITECTURE, P.C.
N
FS RD 74
TO FLAGSTAFF
1782 Co Road 74, Williams, AZ
ARCHITECTURAL DRAWINGS
A000 COVER
A001 CODE SUMMARY & PROJECT ABBREVIATIONS
A002 GENERAL INFORMATION & ASSEMBLY TYPES
A101 SITE PLAN
A102 FLOOR PLAN
A103 REFLECTED CEILING PLAN
A104 ROOF PLAN
A201 EXTERIOR ELEVATIONS
A202 GLAZING ELEVATIONS
A301 BUILDING SECTIONS
A401 WALL SECTIONS
A402 WALL SECTIONS
A501 DOOR TYPES, SCHEDULE & DETAILS
A502 DOOR & WINDOW DETAILS
A503 EXTERIOR DETAILS
A504 EXTERIOR DETAILS
A701 FINISH PLAN & SCHEDULE
A801 INTERIOR ELEVATIONS
A802 CASEWORK DETAILS
A901 CEILING DETAILS
STRUCTURAL DRAWINGS
S000 GENERAL STRUCTURAL NOTES
S001 GENERAL STRUCTURAL NOTES
S002 ANNOTATIONS, SYMBOLS, AND ABBREVIATIONS
S003 STATEMENT OF SPECIAL INSPECTIONS AND
UNBALANCED SNOW LOAD PLAN
S100 FOUNDATION/MAIN FLOOR STRUCTURAL PLAN
S101 ROOF STRUCTURAL PLAN
S501 STRUCTURAL DETAILS
S701 TYPICAL CONCRETE DETAILS
S702 TYPICAL WOOD DETAILS
ELECTRICAL DRAWINGS
E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E0.2 ELECTRICAL DETAILS
E0.3 ELECTRICAL DETAILS
E0.4 ELECTRICAL SCHEDULES
E0.5 ELECTRICAL SCHEDULES
E1.1 ELECTRICAL SITE PLAN
E2.1 ELECTRICAL POWER PLAN
E2.2 ELECTRICAL LIGHTING PLAN
MECHANICAL DRAWINGS
M0.1 MECHANICAL LEGEND & NOTES
M0.2 MECHANICAL SCHEDULES
M0.3 MECHANICAL SCHEDULES
M0.4 MECHANICAL DETAILS
M0.5 MECHANICAL DETAILS
M1.1 MECHANICAL PLAN
M1.2 MECHANICAL PIPING PLAN
M1.3 MECHANICAL ROOF PLAN
PLUMBING DRAWINGS
P0.1 PLUMBING LEGEND & NOTES
P0.2 PLUMBING SCHEDULES
P0.3 PLUMBING DETAILS
P0.4 PLUMBING DETAILS
P1.0 UNDERSLAB PLUMBING PLAN
P1.1 PLUMBING PLAN
P1.2 PLUMBING ROOF PLAN
CIVIL DRAWINGS
C100 OVERALL SITE PLAN
C101 ENLARGED GRADING PLAN
C102 UTILITIES PLAN
C103 WASTEWATER SYSTEM PLAN
C104 WASTEWATER TREATMENT DETAILS
C105 WASTEWATER TREATMENT DETAILS
C106 SITE DETAILS
C107 DETAILS
ICT DRAWINGS
T0.1 ICT SYMBOLS AND ABBREVIATIONS
T0.2 ICT DETAILS
T0.3 ICT DETAILS
T1.0 ICT SITE PLAN
T1.1 STRUCTURED CABLING PLAN
T1.2 SECURITY PLAN
T1.3 PAGING PLAN
T2.1 ICT ENLARGED VIEWS
MOSAIC ARCHITECTURE, P.C.
317 CRUSE AVE., SUITE 201
HELENA, MT 59601
(406) 449-2013 CONTACT: JEFF DOWNHOUR, AIA jeff@mosaicarch.com
MARK ROYLANCE, AIA markr@mosaicarch.com
ARCHITECT:
PROJECT DIRECTORY
CIVIL ENGINEERING:
GREATWEST ENGINEERING
702 2ND STREET S #2
GREAT FALLS, MT 59405
(406) 604-7547
CONTACT: JOSH SOMMER, jsommer@greatwesteng.com
STRUCTURAL ENGINEERING:
MECHANICAL/ELECTRICAL/
PLUMBING ENGINEERING:
MORRISON MAIERLE INC.
1 ENGINEERING PL
HELENA, MT 59602
(406) 495-3439
MORRISON MAIERLE INC.
1055 MOUNT AVE
MISSOULA, MT 59801
(406) 542-8880
CONTACT: AUBREY YERGER, PE ayerger@M-M.NET
1 68
Coconino County approves these plans for concept only.
All liability resulting from errors or omissions is the responsibility of the designer. The County does not verify or guarantee the measurements, calculations, ownership or conclusions indicated by the creator of these plans.
Coconino County Community Development, Environmental Quality Division has reviewed only the onsite wastewater system shown on these plans. Other agency or division approvals may be required.
It is the responsibility of the property owner / applicant, not the County to determine the correct location of all property lines and easements.
APPROVED
Coconino County Community Development
Environmental Quality
By: ___________________ Date: 05/17/2024
Only the blue highlighted sheets were included with the CCCD EQ issued permit.
395 SF
OPEN OFFICE 388 SF
OPERATIONS
495 SF
READY ROOM
538 SF
FITNESS
289 SF
PILOTS
53 SF
STORAGE
126 SF
CONTRACTOR
754 SF
HALL
92 SF
STOR.
67 SF
COMM.
106 SF
LAUNDRY
42 SF
STORAGE
167 SF
MECH
44 SF
VESTIBULE
137 SF
BASE MGR
220 SF
MEN'S
212 SF
WOMEN'S
GROSS
4386 SF
B
Wmin = 4.4"
532 SF
DAY ROOM
Wmin = 4.4" Wmin = 4.4"
SERVICE YARD
C .P
.E .T
E.A.T.D. - 60'
FEFE
W/D W/D
AD
A
ADA
NONRATED WALL: WITH NO OPENING PROTECTION REQUIRED AT DOORS,
WINDOWS, DUCTS, PENETRATIONS, AND JOINTS UON. SEE WALL TYPES.
EXIT SIGN W/ INTEGRATED DIRECTIONAL ARROW WHERE OCCURS AT ALL
EXITS, EVERY 100' IN CORRIDORS, AND IN SPACES WHERE 2 MEANS OF
EGRESS ARE REQUIRED PER S §1006. SEE ELECTRICAL DRAWINGS. (W/
POCHE IN QUADRANT INDICATING "EXIT" TEXT SIDE OF SIGN.) SIGNS
SHOWN IN CORRIDORS ARE CEILING HUNG. SIGNS SHOWN ON WALL ARE
WALL HUNG.
1-HOUR FIRE WALL, FIRE BARRIER, FIRE PARTITION, OR SMOKE BARRIER
WALL: OR COMBINATION OF (WHERE OCCURS) CONFORMING TO THE MOST
STRINGENT REQUIREMENTS OF EACH. SEE CODE ANALYSIS PLANS FOR
SPECIFIC NAMES OF IBC WALL DESIGNATIONS. ALL WITH FIRE-RESISTIVE
OPENING PROTECTION AT DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS),
PENETRATIONS, AND PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND
WINDOW SCHEDULES, MECHANICAL DRAWINGS, PENETRATION DETAILS, AND
JOINT DETAILS WHERE APPLICABLE.
2-HOUR FIRE WALL OR FIRE BARRIER: OR COMBINATION OF (WHERE
OCCURS) CONFORMING TO THE MOST STRINGENT REQUIREMENTS OF EACH.
SEE CODE ANALYSIS PLANS FOR SPECIFIC NAMES OF IBC WALL
DESIGNATIONS. ALL WITH FIRE-RESISTIVE OPENING PROTECTION AT
DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS), PENETRATIONS, AND
PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND WINDOW
SCHEDULES, MECHANICAL DRAWINGS, PENETRATION DETAILS, AND JOINT
DETAILS WHERE APPLICABLE.
PORTABLE CLASS ABC FIRE EXTINGUISHER IN ADA-COMPLIANT SEMI-
RECESSED CABINET
FE
Wmin MINIMUM EGRESS WIDTH (INCHES) BASED ON ACCUMULATIVE NUMBER OF
OCCUPANTS SERVED AT INDICATED EGRESS COMPONENT, PER SECTION
1005.3: .3 INCHES/OCC FOR STAIRWAYS(NONSPRINKLERED BUILDINGS); .2
INCHES/OCC FOR OTHER EGRESS COMPONENTS (NONSPRINKLERED BLDGS).
MOER:2 MEANS OF EGRESS REQUIRED (QUANTITY). ONLY DESIGNATED WHERE
(2) MEANS OF EGRESS ARE REQUIRED, PER §1006.2.1.
IU INCIDENTAL USE W/ REQUIRED SEPARATION PER TABLE 509.1. SHALL NOT
OCCUPY >10% OF FLOOR AREA OF STORY IN WHICH LOCATED, AND IS
CALCULATED AS PART OF OCCUPANCY IN WHICH IT IS LOCATED.
ACCESSORY OCCUPANCY AREA: W/ NO SEPARATION REQUIRED AND
CALCULATED AS PART OF MAIN OCCUPANCY IF TOTAL ACCESSORY
OCCUPANCIES WITHIN A STORY OCCUPY LESS THAN 10% OF AREA OF THAT
STORY, PER SECTION 508.2.3.
CODE PLAN LEGEND
OCCUPANCY GROUP B AREA
EXIT ACCESS TRAVEL DISTANCE (E.A.T.D.) - MAXIMUM 200' FOR 'B'
OCCUPANCY W/OUT SPRINKLER SYSTEM, PER TABLE 1017.2. MAXIMUM
DISTANCE FOR EACH STORY SHOWN.
COMMON PATH OF EGRESS TRAVEL (C.P.E.T.) - MAXIMUM 75' FOR 'B'
OCCUPANCY W/OUT SPRINKLER SYSTEM, OCC LOAD >30, PER TABLE 1006.2.1.
ROOM AREA
OCCUPANT
LOAD
MAX. FLOOR
AREA PER
OCCUPANT
FROM TABLE
1004.5
SF
ROOM NAME
OCCUPANT LOADS FOR FUNCTIONS DESIGNATED NET
FLOOR AREA IN TABLE 1004.5 ARE IDENTIFIED FOR
ACTUAL OCCUPIED AREAS.
OCCUPANT LOADS FOR FUNCTIONS DESIGNATED GROSS
FLOOR AREA ARE IDENTIFIED FOR ENTIRE AREA OF THE
FUNCTION W/ DEDUCTIONS ONLY FOR AREA OF
EXTERIOR WALLS, VENT SHAFTS AND INTERIOR COURTS.
AO
OCCUPANCY GROUP B WITH ACCESSORY SMALL ASSEMBLY SPACE WITH
OCCUPANT LOAD <50 OR AREA <750 SF, CLASSIFIED AS PART OF GROUP B
OCCUPANCY PER 303.1.2
REQUIRED EXIT AND EXIT EGRESS DIRECTION WITH ACCUMULATIVE
NUMBER OF OCCUPANTS SERVED. (DESIGNATED WHERE (2) MEANS OF
EGRESS ARE REQUIRED PER TABLE §1006.2.1)
OCCUPANCY GROUP S-1 AREA
THIS PROJECT SHALL COMPLY WITH THE CODES ADOPTED BY COCONINO COUNTY:
2021 International Building Code (IBC) 2021 International Mechanical Code (IMC) 2021 International Fuel Gas Code (IFGC) 2021 International Plumbing Code (IPC) 2017 National Electrical Code (NEC) 2018 International Energy Conservation Code (IECC)
APPLICABLE BUILDING CODES
OCCUPANCY GROUPS:
(CHAPTER 3)
• B - BUSINESS
• ACCESSORY OCCUPANCIES PER SEC. 508.2 WHERE OCCUR.
• INCIDENTAL USES PER TABLE 509 WHERE OCCUR.
CONSTRUCTION TYPE:
(TABLE 601)
TYPE V-B, NON-SPRINKLERED
ALLOWABLE FLOOR AREA (At):
(TABLE 506.2)
B: 9,000 SF
ALLOWABLE NO. OF STORIES / HEIGHT:
(TABLE 504.4/504.3)
B: 2 STORIES / 40 FT
OCCUPANT LOAD BY FLOOR: LEVEL 1 66
SEE CODE ANALYSIS PLANS THIS SHEET.
SUMMARY CODE REVIEW
PROJECT DESCRIPTION: NEW HELITACK BASE WORK CENTER, INCLUDING OPERATIONS ROOM,
OFFICES, DAY ROOM, READY ROOM, PILOT LOUNGE, AND RESTROOMS.
ACTUAL NO. OF STORIES / HEIGHT: 1 STORY / 20 FT; OK
OCCUPANT LOADS FOR EGRESS DESIGN:
(SEC. 1004 + TABLE 1004.5)
ASSEMBLY - UNCONCENTRATED 15 NET
BUSINESS: 150 GROSS
SEE CODE ANALYSIS PLAN. OCCUPANT LOADS BASED ON MAX. FLOOR
AREA IN SQ FT PER OCCUPANT FROM TABLE 1004.5:
EGRESS WIDTH PER OCCUPANT SERVED:
(SEC. 1005.3)
STAIRWAYS:
OTHER EGRESS
COMPONENTS:
0.3 INCHES / OCCUPANT (NONSPRINKLERED)
0.2 INCHES / OCCUPANT (NONSPRINKLERED)
INTERIOR FINISH REQUIREMENTS:
(TABLE 803.13 - NONSPRINKLERED)
INTERIOR EXIT STAIRWAYS, EXIT RAMPS & EXIT PASSAGEWAYS: CLASS A.
CORRIDORS & ENCLOSURE FOR EXIT ACCESS STAIRWAYS & EXIT ACCESS
RAMPS: CLASS B. ROOMS AND ENCLOSED SPACES: CLASS C
ACTUAL FLOOR AREA: 4,921 SF < 15,750 ALLOWABLE; OK
44" AT STAIRWAYS (36" WHERE OCC LOAD < 50) [IBC §1011.2];
32" CLEAR AT DOORS [§1010.1.1],
44" AT CORRIDORS, AISLES & EXIT PASSAGEWAYS (36" for occupant load
<50) [§ 1020.3; 1018.3; 1018.5; 1024.2 RESPECTIVELY], PROVIDED.
EGRESS WIDTH MINIMUMS BY
COMPONENT (USE WHERE EXCEED
MINIMUMS BY OCCUPANT LOAD):
CORRIDOR FIRE RESISTANCE RATING:
(TABLE 1020.2)
B OCCUPANCY, OCC LOAD <30:
B OCCUPANCY, OCC LOAD >30:
ALL CORRIDOR OCCUPANT LOADS ARE <30; NO FIRE RATING REQ'D
NOT REQUIRED (NONSPRINKLERED)
1-HOUR (NONSPRINKLERED)
OPENING PROTECTIVES:
(TABLE 716.1(2))
20 MINUTE
D-20
DH-OH-20
45 MINUTE
OH-45 OR W-60
1-HR FIRE PARTITIONS (CORRIDOR WALLS):
FIRE DOOR RATING:
DOOR VISION PANEL GLAZING MARKING:
SIDELIGHT/TRANSOM ASSEMBLY MARKING:
FIRE WINDOW ASSEMBLY RATING:
WINDOW ASSEMBLY MARKING:
(TABLE 716.1(3))
FRONTAGE INCREASE (If):
(TABLE 506.3.3)
>30' OPEN SPACE FOR 100% OF BLDG PERIMETER:
If = .75
ALLOWABLE FLOOR AREA:
1 STORY BLDG: (Aa)
(SEC. 506.2.1)
B: Aa = At + [NS x If] Aa = 9,000 + [9,000 x .75] Aa = 15,750 SF
(CHAPTER 6) CONSTRUCTION TYPE V-B; GROUP B OCCUPANCY
BUILDING ELEMENT
TABLE 601 STRUCTURAL FRAME
RATING
0 HR
TABLE 705.5 EXTERIOR BEARING WALLS: FIRE SEP <5' 1 HR - N/A
TABLE 601 INTERIOR BEARING WALLS 0 HR
TABLE 705.5 EXTERIOR NONBEARING WALLS: FIRE SEP <5' 1 HR - N/A
TABLE 601 FLOORS 0 HR
EXTERIOR BEARING WALLS: FIRE SEP <10' 0 HREXTERIOR BEARING WALLS: FIRE SEP ≥10' 0 HR
EXTERIOR NONBEARING WALLS: FIRE SEP ≥5',<10' 1 HR - N/A
TABLE 601 ROOFS 0 HR
EXTERIOR BEARING WALLS: FIRE SEP ≥5',<10' 1 HR - N/A
EXTERIOR NONBEARING WALLS: FIRE SEP ≥10' 0 HR
MAXIMUM AREA OF EXTERIOR OPENINGS
(CHAPTER 7) MAXIMUM AREA OF EXTERIOR OPENINGS PER TABLE 705.8: NONSPRINKLERED
EAST WALL - SEPARATION ≥30 FT
UNPROTECTED NO LIMIT
PROTECTED NO LIMIT
FIRE-RESISTANCE RATING REQUIREMENTS
TYPE OF CONSTRUCTION
WEST WALL - SEPARATION ≥30 FT
UNPROTECTED NO LIMIT
PROTECTED NO LIMIT
NORTH WALL - SEPARATION ≥30 FT
UNPROTECTED NO LIMIT
PROTECTED NO LIMIT
SOUTH WALL - SEPARATION ≥30 FT
UNPROTECTED NO LIMIT
PROTECTED NO LIMIT
REQUIRED SPECIAL INSPECTIONS:
IN ADDITION TO REGULAR INSPECTIONS, THE FOLLOWING ITEMS WILL ALSO REQUIRE SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH SECTIONS 1704 AND 1705 OF THE 2018 INTERNATIONAL BUILDING CODE.
SEE STRUCTURAL FOR SPECIFIC REQUIREMENTS. COPIES OF 3RD PARTY REPORTS TO BE SENT TO
ENGINEER & COPIES KEPT ON-SITE FOR INSPECTOR REVIEW.
a) SPECIAL INSPECTIONS:
- INSPECTION OF FABRICATORS (1704.2.5)
- STEEL CONSTRUCTION (1705.2)
- CONCRETE CONSTRUCTION (1705.3)
- MASONRY CONSTRUCTION (1705.4)
- WOOD CONSTRUCTION (1705.5)
- SOILS (1705.6)
- SPECIAL CASES (1705.1.1)
EPOXY SET ANCHORS
POWDER-ACTUATED FASTENERS
CONCRETE EXPANSION ANCHORS
b) SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE (1705.12):
- STRUCTURAL STEEL (1705.12.1)
- STRUCTURAL WOOD (1705.12.2)
- COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION (1705.12.3)
IECC COMPLIANCE FOR COMMERCIAL PROJECTS
CLIMATE ZONE: 5
INSULATION REQUIREMENTS - IECC 2021 TABLE C402.1.3/C402.4
ROOFS R-30 CONTINUOUS ABOVE DECK, R-49 AT ATTICS
METAL FRAMED WALLS, ABOVE GRADE R-13 CAVITY + R-10 CONTINUOUS
WOOD FRAMED WALLS, ABOVE GRADE R-13 CAVITY + R-7.5 CONTINUOUS OR R-20 + R3.8 CONTINUOUS
MASS WALLS, ABOVE GRADE: R-11.4 CONTINUOUS
BELOW GRADE WALLS: R-7.5 CONTINUOUS
FLOORS - JOIST/FRAMING: R-30
UN-HEATED SLAB: R-15 VERTICAL FOR 24" BELOW (FULL HEIGHT OF THICKENED SLAB EDGE)
HEATED SLAB: R-15 FOR 36" BELOW + R-5 FULL SLAB
OPAQUE SWINGING DOORS: 0.37
SKYLIGHT U-FACTOR: 0.50 MAXIMUM
FIXED FENESTRATION U-FACTOR: 0.36 MAXIMUM
OPERABLE FENESTRATION U FACTOR 0.45 MAXIMUM
ENTRANCE DOOR: 0.63 MAXIMUM
SHGC 0.38 FIXED; 0.33 OPERABLE WITH ADJUSTMENT FOR PROJECTION
FACTOR >.2
INSULATION TO BE PROVIDED - REQUIREMENTS IN OTHER AREAS OF DRAWINGS OR SPECIFICATIONS TAKE
PRECEDENCE OVER THE FOLLOWING REQUIREMENTS:
ROOFS R-49 SPRAY FOAM ATTIC INSULATION
WOOD FRAMED WALLS: R-21 CAVITY + R3.8 CONTINUOUS
UNHEATED SLAB: R-15 VERTICAL FOR 24" BELOW (FULL HEIGHT OF THICKENED SLAB EDGE)
OPAQUE SWINGING DOORS: 0.37
FENESTRATION U-FACTOR (FIXED): 0.36 MAXIMUM
FENESTRATION U-FACTOR (OPERABLE): 0.45 MAXIMUM
ENTRANCE DOOR: 0.63 MAXIMUM
SHGC 0.38 FIXED; 0.33 OPERABLE WITH PROJECTION FACTOR <.2
PLUMBING FIXTURE COUNTS
(CHAPTER 4 OF 2021 IPC - TABLE 403.1)
FIXTURE TYPE
WC, MALE:
WC, FEMALE:
FIXTURES
REQUIRED
1:25
1:25BU
SI
N
ES
S NO.
OCC.
TOTAL
REQUIRED
FIXTURES
PROVIDED
2 WC + 1 UR
2 WC
LAVS, MALE:
LAVS, FEMALE:
DF:
1:40 1:40
1:100
OCCUPANT LOAD = 66
@ at A.B. anchor bolt A/C air conditioning ACC PNL access panel ACOUST acoustical ACT acoustical ceiling tile AD area drain ADJ adjacent AFF above finished floor AIB air infiltration barrier ALT alternate ALUM aluminum ANOD anodized APPROX approximate ARCH architect AUTO automatic BBD bulletin board BD board BITUM bituminuous BL building line BLDG building BLK block BLKG blocking BM beam/bench mark BO by owner B.O. bottom of BOT bottom BRG bearing BSBD baseboard BTWN between B.O.W. bottom of wall BU built up CAB cabinet CAP capacity CB catch basin CL centerline C.C. center to center CDX exterior grade plywood CG corner guard CH channel CI cast iron/cubic inches CJ control joint CLG ceiling C.L.L. contract limit line CL center line
ABBREVIATIONS:
GA gauge GB grab bar GALV galvanized G.C. general contractor GEN general GFRG glass fiber reinforced gypsum GI galvanized iron GL glass GLU LAM or G.L.B. glue laminated beam GRD grade/grid GWB gypsum wall board GYP gypsum HB hose bib HC hollow core/handicapped HD BD Hard board HDR header HOR horizontal HR hour HT height HTG heating HVAC heating, ventilation, air conditioning HW hot water
PART.BD.particle board PART’N partition PC precast concrete PFM prefinished metal PL plate P.LAM plastic laminate PLWD plywood PNL panel PR pair PSL parallel strand lumber PT point PTD paper towel dispenser
T tread/thermostat TB towel bar TEL telephone TEMP temperature
CONN connection CONST construction CTRD centered CONT continuous CONTR contractor CORR corridor CPT carpet CT ceramic tile CW curtain wall system CY cubic yard DBL double DEPT department DF drinking fountain DIA diameter DIAG diagonal DIM dimension DISP dispenser DN down DR door DWR drawer DS downspout DTL detail DWG drawing E east EA each EIFS exterior insulation finish system E.J. expansion joint EL/ELEV elevation - height/elevator ELEC electrical ENCL enclosure EO electrical outlet EP electrical panel EQ equal EQUIP equipment EW exterior wall assembly EWC electrical water cooler EWH electrical water heater (E)/EXISTexisting EXH exhaust EXP expansion EXT exterior
INSUL insulation INT interior IWA/IW interior wall assembly
T.O. top of T.O.B. top of beam T.O.C. top of concrete T.O.P. top of plate T.O. FTG top of footing T.O.S. top of steel T.O.SL. top of slab T.O.W. top of wall TPD toilet paper dispenser TR tread TS tubular steel TV television TYP typical UG underground UNO unless noted otherwise UR urinal VAC vacuum outlet VAR varies VB vapor barrier VCT vinyl composition tile VERT vertical VEST vestibule VFY verify VT vinyl tile VWC vinyl wall covering W west/women/width W/ with W/O without WC water closet WD wood W/D washer/dryer WH water heater WNDW window WP waterproof WR water resistant WRB weather resistive barrier WT weight WWF welded wire fabric WWM welded wire mesh X by YD yard
REINF reinforcing REQD required RES resilient RM room RO rough opening RV roof vent R&S rod and shelf S south SACT suspended acoustical ceiling tile SC solid core SCD seat cover dispenser SCHED schedule SD soap dispenser SECT section SF square feet SGL single SHT sheet SHTG sheathing SHWR shower SIM. similar S.I.P. structural insulated panel SLNT sealant SOG slab on grade SPEC specifications S.S. stainless steel SS service sink SSM solid surface material STD standard STF storefront STL steel STOR storage STRUCT structural SUBFLR subfloor SUSP suspended SV sheet vinyl SY square yard
MEZZ mezzanine MFR manufacturer MH manhole MIN minimum MIR mirror MISC miscellaneous MO masonry opening MTL metal MULL mullion N north NA not applicable NIC not in contract NO number NTS not to scale OFCI owner furnished/contractor installed OC on center OD outside diameter OH overhead/opposite hand OPNG opening OPP opposite
FLR/FL floor FLUOR fluorescent FND feminine napkin dispenser/disposal FO face of FOC face of concrete
QTY quantityJAN janitor JST joist JT joint
FA fire alarm/floor-ceiling assembly FAH fire alarm horn FAS fire alarm station
PTD/R paper towel dispenser/receptacle PVMT pavement PVC polyvinylchloride
M men's MAT material MAX maximum MECH mechanical MDF medium density fiber board
FOF face of finish FOS face of stud FOW face of wall FT foot or feet FTG footing
CLR clear CMU concrete masonry unit CO clean out
FH fire hydrant FIN. FLR top of floor sheathing FIN finish FIXT fixture
T&G tongue and groove THK thick THRU through TJI Truss Joist Incorporated
R/RAD radius R riser RA roof/ceiling assembly RB rubber base RD roof drain RE regarding REF reference/refrigerator
LAV lavatory LF lineal foot LTG lighting
FD floor drain FDN/FND foundation FE fire extinguisher FEC fire extinguisher cabinet FF finished floor FFHB frost free hose bib FG finish grade
IN inch INCL included INFO information
COL column CONC concrete COND condition CONF conference
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO.
317 Cruse Avenue Suite 201 Helena, Montana 59601 406.449.2013
SHEET OF 20
3/
/2
9:
:3
A
M C
:\U se rs \M ar kR
\D oc um en ts \G re en
B as e W or k
C en te r_ r2 4_ m ro yl an ce .rv t
A001 mgr mgr jrd
6260855010602
CODE SUMMARY &
PROJECT
ABBREVIATIONS
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
1/8" = 1'-0"
LEVEL 1 CODE PLAN
N
1. THE GENERAL CONDITIONS TO THE CONTRACT FOR THE CONSTRUCTION OF BUILDINGS:
DOCUMENT A-201, ISSUED BY THE AMERICAN INSTITUTE OF ARCHITECTS HEREINAFTER REFERRED
TO AS THE "GENERAL CONDITIONS" RELATES TO THE WORK OF THIS PROJECT AND IS HEREBY
MADE A PART OF THE CONTRACT AS THOUGH FULLY CONTAINED IN THESE SPECIFICATIONS.
2. CONTRACT DOCUMENTS INCLUDE THE ARCHITECT'S DRAWINGS, SPECIFICATIONS, GENERAL
CONDITIONS, AGREEMENT (BUILDING CONTRACT) AND ALL ADDENDA. THEY ARE TO INCLUDE ALL
LABOR, EQUIPMENT, AND MATERIALS NECESSARY FOR THE PROPER EXECUTION OF THE WORK
EXCEPT AS MAY BE SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS OR FOR WHICH
SEPARATE PRICES MAY BE ASKED IN THE BID PROPOSAL.
3. REGULATIONS, TAXES AND PERMITS: THE WHOLE OF THE WORK IS TO BE EXECUTED IN STRICT
ACCORDANCE WITH THE REGULATIONS AND CODES OF THE GOVERNMENTAL AGENCIES WHOSE
JURISDICTION IS APPLICABLE.
GENERAL CONDITIONS:
1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING DIMENSIONS & CONDITIONS.
EXISTING DIMENSIONS SHOWN ARE APPROXIMATE AND MUST BE FIELD VERIFIED.
2. REFER TO SPECIFICATIONS FOR DETAILED DESCRIPTIONS & REQUIREMENTS OF
CONSTRUCTION.
3. GENERAL CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES, PROVIDE ON-SITE
SUPERVISION & BE RESPONSIBLE FOR COMPLIANCE WITH ALL SAFETY PRECAUTIONS, CODES
AND REGULATIONS.
4. PROTECT EXISTING UTILITIES, SITE IMPROVEMENTS & PLANTING TO REMAIN.
5. PATCH ANY SURFACES DAMAGED DURING CONSTRUCTION. SURFACES ARE TO BE PATCHED
FLUSH WITH EXISTING. MATCH EXISTING ADJACENT FINISH OR APPLY NEW FINISH AS
SCHEDULED.
6. PROVIDE SOLID BACKING FOR ALL WALL-MOUNTED ITEMS.
7. IN GENERAL, REPETITIVE DETAILS DRAWN ARE SHOWN IN FULL ONLY ONCE. REPETITIONS MAY
NOT BE COMPLETE IN EVERY DETAIL AS SHOWN IN THE ORIGINAL DETAIL.
8. DIMENSIONS ARE SHOWN ON THE DRAWINGS. DO NOT SCALE THE DRAWINGS.
9. ALL HEIGHTS ARE DIMENSIONED FROM THE TOP OF SUBFLOOR UNLESS NOTED OTHERWISE.
10. WHERE COLUMNS & STUD WALLS ALIGN, GYPSUM BOARD TO BE CONTINUOUS OVER COLUMNS
OR BOXED AROUND COLUMN IF COLUMN PROJECTS BEYOND WALL.
11. BRING TO THE ATTENTION OF THE ARCHITECT ANY CONDITION OR AREA OF FINISH THAT IS IN
QUESTION OR NOT NOTED.
12. SEAL ALL PENETRATIONS OF WALLS, FLOORS AND CEILINGS WITH A FIRE RATING EQUIVALENT
TO THE CONSTRUCTION PENETRATED AND PER DETAILS & SPECIFICATIONS.
13. DUST BARRIERS MUST BE INSTALLED WHEREVER NEW WORK IS ADJACENT TO OCCUPIED
AREAS. BARRIERS MUST BE SEALED TO INSURE NO DUST TRANSMISSION TO OCCUPIED SPACES.
14. COORDINATE LAYOUT, CLEARANCES, PENETRATIONS, BACKING & FASTENERS WITH WORK TO
FOLLOW.
15. HEATING, PLUMBING AND ELECTRICAL PLANS WHERE SHOWN DIAGRAMMATICALLY ARE
INTENDED TO INDICATE CAPACITY, SIZE, LOCATION & GENERAL ARRANGEMENTS. ALL
NECESSARY FEATURES OF RELATED CONSTRUCTION WILL BE REQUIRED AS IF SHOWN IN
DETAIL.
16. WHERE MECHANICAL & ELECTRICAL EQUIPMENT LOCATIONS CONFLICT ELECTRICAL, LIGHT
FIXTURE LOCATIONS SHALL TAKE PRECEDENCE.
17. PROVIDE SUFFICIENT STUD DEPTH TO CONCEAL MECHANICAL & ELECTRICAL WORK IN WALLS.
18. PROVIDE ALL NEW MATERIALS (U.N.O.) AND QUALIFIED CRAFT PERSONS TO COMPLETE THE
WORK.
19. CONSTRUCTION DOCUMENTS SHOW THE DESIGN INTENT OF THE PROJECT AND MAY NOT SHOW
MINOR DETAILS OF PROPOSED INSTALLATIONS. THE INCLUSION OF THESE MINOR DETAILS IS
IMPLIED TO PROVIDE A COMPLETE PROJECT AND ARE TO BE INCLUDED AS A PART OF A BID.
20. REFER TO MECHANICAL & ELECTRICAL DRAWINGS FOR COORDINATION OF WORK.
21. IN THE CASE OF CONTRADICTIONS BETWEEN DRAWINGS OR BETWEEN DRAWINGS &
SPECIFICATIONS, ASSUME THE MORE COSTLY APPROACH FOR BIDDING PURPOSES. BRING ALL
CONTRADICTIONS TO THE ATTENTION OF THE ARCHITECT.
22. CONTRACTOR SHALL PROMPTLY REMOVE ALL WASTE MATERIALS AND LEAVE PREMISES AND
SITE CLEAN.
23. THE CONTRACTOR SHALL PROVIDE ALL CEILING AND/OR WALL ACCESS PANELS/DOORS AS
REQUIRED BY THE AIR CONDITIONING, PLUMBING & ELECTRICAL SYSTEMS, PROVIDE APPROVED ASSEMBLIES W/ SELF-CLOSING DEVICES IN RATED CONSTRUCTION. (PAINT TO MATCH ADJACENT
WALL COLOR)
24. ELECTRICAL OUTLETS AND LIGHTING ARE ONLY SHOWN ON ARCHITECTURAL "A" SHEETS WHERE
PLACEMENT OF SUCH IS CRITICAL TO PARTICULAR AESTHETICS. SEE ELECTRICAL DRAWINGS
FOR ALL ELECTRICAL AND DATA FEATURES.
DRAWING SET NOTE: THESE DRAWINGS ARE TO BE UTILIZED AS A COMPLETE SET FOR BIDDING &
CONSTRUCTION. INDIVIDUAL SECTIONS OF DRAWINGS SHOULD NOT BE SEPARATED FROM THE
ENTIRE SET. IMPORTANT NOTES FOR ONE AREA OF WORK MAY BE INCLUDED IN OTHER AREAS IN
THE DRAWINGS. ALL CONTRACTORS & SUPPLIERS MUST REVIEW ENTIRE DRAWING SET &
SPECIFICATIONS.
GENERAL NOTES: GENERAL WALL NOTES
1. WALL TYPE CONSTRUCTION IS CONTINUOUS FROM SLAB TO ROOF FRAMING ABOVE
UNLESS INDICATED OTHERWISE.
2. IF A WALL TYPE IS NOT INDICATED, PROVIDE WALL TYPE OF MOST SIMILAR CONDITION -
VERIFY WITH ARCHITECT.
3. IN CASES OF CONFLICT BETWEEN SECTIONS AND WALL TYPES, CLARIFY WITH ARCHITECT
PRIOR TO BIDDING WHEN TIME ALLOWS, OTHERWISE ASSUME THE MOST EXPENSIVE
CONDITION FOR BIDDING PURPOSES.
4. STRUCTURAL NOTES, SPECIFICATIONS, STUD GAUGE NOTATIONS ETC. TAKE
PRECEDENCE OVER ARCHITECTURAL WALL TYPES.
5. FOR LIGHT GAUGE (NON-STRUCTURAL) METAL FRAMING, PROVIDE MIN. 22 GAUGE STUDS
UNLESS THE CONTRACTOR CAN PROVIDE MANUFACTURER'S DATA SUPPORTING LIGHTER
GAUGE STUDS BASED ON HEIGHT AND FINISH MATERIALS.
6. ALL VOIDS IN EXTERIOR WALLS - INCLUDING IN NON-VISIBLE LOCATIONS - TO BE FILLED
TIGHT WITH INSULATION. SMALL CRACKS & VOIDS TO BE CAULKED OR SPRAY-FOAMED
FOR TIGHT SEAL.
7. ALL EXTERIOR WALLS TO RECEIVE VAPOR BARRIER UNDER INTERIOR FINISH. ALL SEAMS
OF VAPOR BARRIER MUST BE TAPED/SEALED TIGHT AND ALL JOINTS MUST BE TAPED/
SEALED TIGHT WITH MATERIALS AND METHODS APPROVED BY VAPOR BARRIER MFR.
8. TYPE "X" GYPSUM WALL BOARD SPECIFIED THROUGHOUT. PROVIDE WATER-RESISTANT
TYPE "X" GYPSUM BOARD ON ENTIRE WALL WHERE PLUMBING FIXTURES OCCUR.
PROVIDE TILE BACKER BOARD TYPE "X" ON ALL WALLS WITH TILE.
9. WALLS INDICATED WITH ACOUSTICAL INSULATION TO MEET AN STC RATING OF 48 OR
MORE, UNLESS OTHERWISE INDICATED.
10. PROVIDE SOUND ATTENUATION INSULATION ON TOP OF ACT WHERE WALLS TERMINATE
AT CEILING OR 6" ABOVE CEILING. EXTEND 5 FEET TO BOTH SIDES OF WALL. HOLD
INSULATION 7" AWAY FROM LIGHT FIXTURES.
11. PROVIDE BACKER ROD & CAULKING JOINT AT ABUTMENT OF ALL DISSIMILAR MATERIALS.
12. PROVIDE STEEL "J" EDGE METAL AND 1/4" CAULK JOINT AT PERIMETER OF ALL GYPSUM
BOARD WALLS WHERE ABUTTING DIFFERENT MATERIALS.
13. PROVIDE CORNER BEADS AT ALL EXTERNAL GYPSUM BOARD CORNERS.
14. PENETRATIONS OF FIRE-RESISTIVE WALLS, HORIZONTAL ASSEMBLIES SHALL BE
PROTECTED AS REQUIRED IN IBC SECTION 714.
15. PROVIDE FIRE, SMOKE AND CEILING RADIATION DAMPERS AT DUCT PENETRATIONS AND
AIR TRANSFER OPENINGS IN FIRE RATED ASSEMBLIES PER IBC SECTION 717.
SCALE
BUILDING SECTIONS
WALL SECTIONS
EXTERIOR ELEVATION
DETAIL CALLOUT
INTERIOR ELEVATION
DOOR NUMBER
WINDOW TYPE
ROOM NAME, NUMBER, AND
AREA
GRID LINES:
LETTERS LEFT TO RIGHT
NUMBERS TOP TO BOTTOM
WALL TYPE
ELEVATION TAG, FLOOR = 100' - 0"
REFERENCE SYMBOLS:
DRAWING TITLE
STOREFRONT/CURTAINWALL
CALLOUT
TEXT INDICATES STOREFRONT
SYSTEM:
iSF = INTERIOR STOREFRONT
SF = EXTERIOR STOREFRONT
CW = CURTAINWALL
FIRE EXTINGUISHER, SEE CODE
PLANS
SHEET
NUMBER
DRAWING
NUMBER
SHEET
NUMBER
DRAWING
NUMBER
SHEET NUMBER
DRAWING
NUMBER
SHEET NUMBER
DRAWING
NUMBER
SHEET NUMBER
DRAWING NUMBER
FE
WITH CABINET
WALL-HUNG, NO
CABINET
ROOF TYPE
-SEE ELEVATIONS FOR HEIGHTS
"SIM" INDICATES SIMILAR
CONDITION; SEE NOTES
FLOOR TYPE
A7-14
A3-8
A5-2
VIEW NAME
1/8" = 1'-0"
A
Room name
A
101A
A1-1
A1-1
FA1
Name
Elevation
RA1
SIM
cw1 i1
FE
e2s
WALL TYPE
WALL HEIGHT
WALL STUD & FINISH HEIGHT
c GWB TO 6" ABOVE CEILING; FRAME
OR BRACE TO STRUCTURE
p PARTIAL HEIGHT s TO STRUCTURE x SHAFT - CONTINUOUS THROUGH
FLOOR ASSEMBLIES
WALL TYPE TAG
5/8" GYPSUM BOARD
TYPE X
2X4 WD STUDS @ 16"
O.C.
(2) 5/8" GYPSUM
BOARD TYPE X
3 1/2" ACOUSTICAL
BATT INSULATION
5/8" GYPSUM BOARD
TYPE X
2X6 WD STUDS @
16" OC
(2) 5/8" GYPSUM
BOARD TYPE X
2X6 WD STUDS @
16" OC
1/2" MIN. PLYWD
SHEATHING - SEE
STRUCTURAL DWGS
NOTE: SEE ELEVATIONS AND FINISH SCHEDULES FOR
WALL FINISHES, TYPICAL ALL WALL TYPES
5/8" GYPSUM
BOARD TYPE X
(2) 5/8" GYPSUM
BOARD TYPE X
5 1/2" ACOUSTICAL
BATT INSULATION
5/8" GYPSUM
BOARD TYPE X
2X4 WD STUDS
@ 16" O.C.
INTERIOR WALL TYPES
INTERIOR PARTITION INTERIOR PARTITION
INTERIOR SHEAR WALL INTERIOR FURRED PARTITION
5 1/2" ACOUSTICAL
BATT INSULATION
NON-RATED SOUND WALL NON-RATED SOUND WALL
NON-RATED SOUND WALL, LOAD-BEARING NON-RATED
5/8" GYPSUM
BOARD TYPE X
WD STUDS @ 16" O.C.:
• 2X4 @ i3
• 2X6 @ i4
5/8" GYPSUM
BOARD TYPE X
INTERIOR PARTITION
NON-RATED
i1 i2 i6 i9 i3 i4
2X4 WD STUDS @
16" OC
1/2" MIN. PLYWD
SHEATHING WHERE
OCCURS - SEE
STRUCTURAL DWGS
5/8" GYPSUM
BOARD TYPE X
(2) 5/8" GYPSUM
BOARD TYPE X
INTERIOR SHEAR WALL
3 1/2" ACOUSTICAL
BATT INSULATION
NON-RATED SOUND WALL, LOAD-BEARING
i5
2X6 WD STUDS @
16" OC
1/2" MIN. PLYWD
SHEATHING - SEE
STRUCTURAL DWGS
5/8" GYPSUM
BOARD TYPE X
5/8" GYPSUM
BOARD TYPE X
INTERIOR SHEAR WALL
NON-RATED, LOAD-BEARING
i7
2X6 WD STUDS @
16" OC
1/2" MIN. PLYWD
SHEATHING - SEE
STRUCTURAL DWGS
1x4 VERT. SHIPLAP
WD BOARDS - SEE
FINISH SCHEDULE
5/8" GYPSUM
BOARD TYPE X
INTERIOR SHEAR WALL
NON-RATED, LOAD-BEARING (EXC. @ i8c) i8
5/8" GYPSUM
BOARD TYPE X
e1
NOTE: SEE STRUCTURAL FOR ADDITIONAL
INFORMATION FOR ALL WALL TYPESEXTERIOR WALL TYPES
EXTERIOR WALL - NON RATED
e2
EXTERIOR WALL - NON-RATED
INTERIOR EXTERIOR
WOOD SHIPLAP SIDING / WD STUDS
INTERIOR EXTERIOR
METAL SIDING PER ELEVS
VAPOR BARRIER
2X6 WOOD STUDS @ 16" OC
SHEATHING PER STRUCTURAL
WEATHER RESISTIVE
BARRIER - TAPE ALL SEAMS
5/8" GYP. BD.
1" (R-3.8 MIN.) WATER RESISTANT
RIGID INSUL - TAPE ALL JOINTS
FIRE BLOCKING - MAX.
SPACING 10'-0"
R-21 BATT INSULATION
METAL SIDING / WD STUDS
VERTICAL, BLIND-NAILED T&G
WOOD SIDING PER ELEVATIONS.
VAPOR BARRIER
2X6 WOOD STUDS @ 16" OC
SHEATHING PER
STRUCTURAL
WEATHER RESISTIVE BARRIER -
TAPE ALL SEAMS
5/8" GYP. BD.
1" (R-3.8 MIN.) WATER RESISTANT
RIGID INSULATION - TAPE ALL JOINTS
FIRE BLOCKING - MAX.
SPACING 10'-0"
R-21 BATT INSULATION
1 1/4" x4 MIN. HORIZ CEDAR FURRING
STRIPS @ 24" OC. ATTACH @ 16" OC
TO STUDS (OR SOLID BLOCKING) W/
1.5" MIN PENETRATION. SLOPE TOP
EDGE
VERTICAL SUBGIRT @ EA STUD
HORIZONTAL SUBGIRT @ 24" OC
ROOF/CEILING ASSEMBLY
ROOF ASSEMBLY
RA1
MIN. R-49 CLOSED-CELL SPRAY
POLYURETHANE INSULATION.
I-JOISTS PER
STRUCTURAL
8 MIL REINFORCED
POLYETHYLENE VAPOR
BARRIER
PREFINISHED, CONCEALED
FASTENER STANDING SEAM
METAL ROOFING SYSTEM
FINISHED CEILING - SEE
REFLECTED CEILING PLAN
FOR TYPE & HEIGHT
ROOF SHEATHING
PER STRUCTURAL
ROOFING UNDERLAYMENT:
• ICE AND WATER SHIELD AT EAVE
EDGES TO 36" INSIDE EXTERIOR
WALL LINE.
• ICE AND WATER SHIELD FOR 60"
EACH SIDE OF VALLEY
• COATED WOVEN SYNTHETIC
UNDERLAYMENT AT BALANCE OF
ROOF
CONTINUOUS 5/8" TYPE X GWB (FIRE
TAPED) ATTACHED TO UNDERSIDE OF
ROOF FRAMING
ENKAMAT 7020
VENTILATION MAT
MEN
5/8" MIN. - 2" MAX. HEIGHT
1/32" RAISED CHARACTERS
UPPERCASE, SANS SERIF
PICTOGRAMS
6"
BRAILLE CHARACTERS
6"
3"
WOMEN
6"
6"
3"
PICTOGRAMS
BRAILLE CHARACTERS
A
B
MEN'S HC
RESTROOM
WOMEN'S HC
RESTROOM
5/8" MIN. - 2" MAX. HEIGHT
1/32" RAISED CHARACTERS
UPPER-CASE, SANS SERIF
PROVIDE SIGN AT EACH ROOM ENTRY DOOR
AS NOTED AND EACH EXIT AS FOLLOWS:
SIGNAGE NOTES:
1. SEE SPECIFICATIONS FOR SPECIFIC SIGNAGE DETAILS,
DIMENSIONS, FONT, COLORS, MATERIALS, ETC.
2. ALL SIGNAGE INDICATED BELOW SHALL COMPLY WITH ICC
A117.1.
ROOM SIGNAGE
UNISEX
6"
6"
3"
PICTOGRAMS
BRAILLE CHARACTERS
C
UNISEX HC
RESTROOM
5/8" MIN. - 2" MAX. HEIGHT
1/32" RAISED CHARACTERS
UPPERCASE, SANS SERIF
ROOM SIGN PANEL TO BE POSTED ADJACENT TO THE LATCH SIDE OF
THE DOOR, 60 INCHES ABOVE THE FINISH FLOOR TO THE CENTERLINE
OF THE SIGN. 18" X 18" CLEAR FLOOR SPACE CENTERED ON TACTILE
CHARACTERS SHALL BE PROVIDED
EXIT
1" TALL, 1/32" RAISED
CHARACTERS, UPPER-
CASE, SAN SERIF
6"
1/
2"
BRAILLE
CHARACTERS
E
EXIT
ROOM NAME
3/4" TALL, 1/32" RAISED
CHARACTERS, UPPER-CASE,
SAN SERIF. VERIFY ROOM
NAMES WITH ARCHITECT
BEFORE PRODUCTION.
6"
1/
2"
BRAILLE CHARACTERS
D
ALL OTHER
ROOMS
G
FIRE ALARM
CONTROL
PANEL
FIRE ALARM
CONTROL PANEL
INSIDE
6"
1/
2"
1/
2"
NOTICE
FOR YOUR SAFETY
OCCUPANCY
IS LIMITED TO
PERSONS
BY ORDER OF THE CODE
OFFICIAL
Keep Posted Under Penalty Of Law
5/8" TALL
CHARACTERS
3/8" TALL
CHARACTERS
5/8" TALL
CHARACTERS
3/8" TALL
CHARACTERS
5/8" TALL
CHARACTERS
3/8" TALL
CHARACTERS
1/4" TALL
CHARACTERS
F
ASSEMBLY
ROOM
1" TALL
CHARACTERS,
WHITE ON RED
BACKGROUND
3.
EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY HAVING AN
OCCUPANT LOAD OF 50 OR MORE SHALL HAVE THE OCCUPANT LOAD OF THE
ROOM OR SPACE POSTED IN A CONSPICUOUS PLACE, NEAR THE MAIN EXIT.
NOT USED
NOT USED
NOT USED
SUSPENDED CEILING
ACOUSTIC INSULATION
WHERE OCCURS - SEE WALL
TYPE
PROVIDE SEALANT @ BASE OF
ALL WALLS W/ ACOUSTIC
INSUL.
WALL TYPE PER PLANS
2" X 2" X 1/8" ANGLE BRACING
(SHOWN) OR 3 1/2" 25 GA MTL STUD
BRACING TO STRUCTURE @ MAX
8'-0" OC, ALTERNATING SIDES.
STRUCTURE
45° MAX
6"
ATTACH TO STRUCTURE W/
3/8"Ø EXPANSION ANCHORS
@ CONCRETE OR 3/8"Ø X 3"
LAG BOLTS @ WOOD
2 NO. 12 SCREWS
PARTITION WALL BRACING
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO.
317 Cruse Avenue Suite 201 Helena, Montana 59601 406.449.2013
SHEET OF 20
3/
/2
9:
:3
A
M C
:\U se rs \M ar kR
\D oc um en ts \G re en
B as e W or k
C en te r_ r2 4_ m ro yl an ce .rv t
A002 mgr mgr jrd
6260855010602
GENERAL INFORMATION
& ASSEMBLY TYPES
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
1. SEE CIVIL DRAWINGS FOR LIMIT OF WORK, SITE DEMOLITION, ALL SITE
HORIZONTAL CONTROLS, GRADING AND DRAINAGE, PARKING LOT &
DRIVE LAYOUT & DIMENSIONS, PAVING AND UTILITIES.
2. SEE LANDSCAPE DRAWINGS FOR ALL PLANTING, IRRIGATION, SITE
FURNITURE AND PAVING SCORING LAYOUT.
3. SEE MECHANICAL DRAWINGS FOR ALL SITE MECHANICAL.
4. SEE PLUMBING DRAWINGS FOR ALL SITE PLUMBING.
5. SEE ELECTRICAL DRAWINGS FOR ALL SITE ELECTRICAL AND LIGHTING.
6. SEE TECHNOLOGY DRAWINGS FOR ALL SITE TECHNOLOGY.
7. DETERMINE LOCATION OF ALL UNDERGROUND UTILITIES PRIOR TO
DEMO, EXCAVATION OR PLANTING. MAINTAIN 10' MIN DISTANCE FROM
ALL TREES TO UTILITY LINES.
8. PROTECT ALL EXISTING ITEMS TO REMAIN. EXISTING ELEMENTS
DAMAGED DURING CONSTRUCTION TO BE REPAIRED OR REPLACED BY
CONTRACTOR AS DIRECTED BY THE ARCHITECT AT NO COST TO
OWNER.
9. PROTECT EXISTING TREES TO REMAIN WITH TEMPORARY
CONSTRUCTION FENCE LOCATED 3 FEET OUTSIDE DRIP LINE.
10. SITE GRADING IS BASED ON FINISH FLOOR ELEVATION OF 100.00: IS
EQUAL TO SITE GRADE OF 6937.8 FEET
GENERAL SITE PLAN NOTESPROPERTY INFORMATION
1782 COUNTY RD 74,
WILLIAMS, AZ
GREEN BASE WORK CENTER (PITTMAN
VALLEY HELIBASE) IS LOCATED IN THE
KAIBAB NATIONAL FOREST, EAST OF
WILLIAMS, ARIZONA.
STREET ADDRESS:
SITE DESCRIPTION:
NEW CONSTRUCTION
EXISTING ELEMENTS TO REMAIN
LINEWORK LEGEND
NEW WORK
CENTER
NEW STORMWATER
RETENTION POND -
SEE CIVIL DRAWINGS
25' - 0" 100' - 0"
10' - 0"
5' - 0"
10' - 0"
(2) ADA SP.
(10) 10'W SPACES
(4) 10'W SPACES
20' - 0"
EXISTING GRAVEL
TURNAROUND
GRAVEL DRIVE
SERVICE
YARD
(8) 10'W SPACES
(8) 10'W SPACES
DS
DS
MECH EQUIP -SEE MEP
GRAVEL, TYP
ROUGH-IN FOR FUTURE
DUAL-PORT EV
CHARGING STATIONS
40' - 0"
165' - 0"
WOOD FENCE
7' - 6" 5' - 0"
6°
37' - 8" 10' - 0"
30' - 4" 6' - 0"
20' - 0"
18' - 2"
126' - 6"
ELECTRICAL
SERVICE - SEE ELEC.
NEW DRIP
FIELD
SS
PLANTING MULCH
CONC. WALK
LANDSCAPE
STONE 1 1/2"
RIVER ROCK
U.G. ROOF DRAIN PIPING
FROM DOWNSPOUTS
80' - 0"
80' - 0"
18' - 6" 6' - 6" 15' - 0" 12' - 6" 40' - 0" 34' - 0"
5' - 0" 9' - 0"
5' - 0" 84'- 0"
5' - 0" 9' - 0"
5' - 0"
LIGHT POLE, TYP -
SEE ELECTRICAL
15' - 8" 10' - 0"
15' - 0"
EMERG. GENERATOR
A101
6' - 0"
TRANSFORMER
DUMPSTER BY
OWNER
DUMPSTER
PAD
10' - 0"
12' - 0"
NEW WASTEWATER
TREATMENT SYSTEM
NEW WORK
CENTER
Existing Office
Exstg Shed
Exstg Pump House
Exstg Water Tank
Exstg Quarters
Exstg Quarters
Exstg Helipad
NEW DRIP FIELD
Exstg Ware-house
Exstg Secured Metal Storage
Exstg Propane Tank
Exstg Gravel Turnaround
GRAVEL DRIVE
NEW PAVED
PARKING AREA
NEW PAVED
PARKING AREA
Exstg Helipad
Exstg Paved Entry Drive
FUTURE REPLACEMENT
DRIP FIELD AREA
Existing Fence
NEW WASTEWATER
TREATMENT SYSTEM
1/
2" 6'
0"
2"
6'
1/
2"
1X4 WESTERN RED CEDAR 6'
CLEAR FENCE BOARDS @ 4"
O.C. (1/2" GAPS)
2X4 FENCE RAIL
2'
8" 2'
8"
CONCRETE FOOTING
10"
2'
6"
2'
0"
2X6 WESTERN RED CEDAR 6'
CLEAR FENCE BOARDS @ 4"
O.C. (1/2" GAPS)
MASTER-HALCO STEEL LINE POST
@ 8'-0" OC MAX. GALVANIZED 0.10
INCH A653 SS GRADE 50
STEEL POST - SEE ABOVE
MASTER-HALCO 3" X 3" STEEL
CORNER POST. GALVANIZED
0.12 INCH A653 SS GRADE 50
BUILDING SIDE
PLAN DETAIL
SECTION DETAIL
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO.
317 Cruse Avenue Suite 201 Helena, Montana 59601 406.449.2013
SHEET OF 20
3/
/2
9:
:3
A
M C
:\U se rs \M ar kR
\D oc um en ts \G re en
B as e W or k
C en te r_ r2 4_ m ro yl an ce .rv t
A101 mgr mgr jrd
6260855010602
SITE PLAN
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
N
1/16" = 1'-0"
PROJECT SITE PLAN
1" = 80'-0"
SITE PLAN - OVERALL
N
1" = 1'-0"
FENCE DETAILS
1. WALL DIMENSIONS ARE TYPICALLY TO FACE OF STUD OR FACE OF
CONCRETE UNLESS NOTED OTHERWISE.
2. DOOR OPENINGS ARE TO CENTERLINE OR EDGE OF OPENING (NOT
OUTSIDE OF FRAME). VERIFY ALL OPENINGS WITH ROUGH OPENING
REQUIREMENTS.
3. ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE
WALL FRAMING U.N.O.
4. SEE SHEET A-002 FOR WALL TYPES. ALL WALLS TO BE ASSUMED TO
RUN TO B.O. ROOF FRAMING U.N.O. IN AREAS WITH EXPOSED
STRUCTURE CONTINUE GYPSUM BOARD TO UNDERSIDE OF
STRUCTURE.
5. SEE DETAILS FOR RELATIONSHIP OF WALLS TO GRID LINES
GENERAL FLOOR PLAN NOTES
A201
A201
A A
C C
OPERATIONS
101BASE MGR
OPEN OFFICE
STOR.
DAY ROOM
CONTRACTOR
PILOTS
READY ROOM
WOMEN'S
COMM.
MECH
LAUNDRY
FITNESS
220 SF
MEN'S
A301
A301
36"x24"x72" locker, typ of 28
STORAGE
STORAGE
A301
A301
A301
A301
A801
A402
AV CAB.
6'x4' Whiteboard TV
6'x4' Whiteboard
6'x4' Whiteboard
A301
A301
6°
B B
A401
5' - 0 1/2"
10' - 0"
10' - 0"
5' - 1 1/2" 6 1/2"
109B 109A
115A
108A
100B
100A
111 110
114B
FECFEC
A80115
A801 9
101A
101B
25' - 4" 6' - 7"
31' - 11"
3/
4"
1/
2"
HALL
VESTIBULE
114A
A401
A402
103' - 8"
4' - 0" 60' - 5" 39' - 3"
0"
0"
D
D
E E
C
D
B AA
SF8
SF2
SF1
SF3
SF9
SF11
0"
6" 5' - 0 1/2" 14' - 9" 5' - 0 1/2"
A801
3'
0" 1'
0"
C
LR
C
LR
3'
1/
8" 3'
1/ 8"
1'
1/
8"
R .O
V
FY
R
.O
V
FY
5'
0" C
LR
3' - 8"
CLR
3' - 8"
CLR
3'
1"
3'
1"
1/
2"
1'
4" 3'
4"
1'
4"
6'
0"
5' - 0 1/2" 5' - 0 1/2" 9' - 8 1/2" 6' - 0" 6' - 5" 6' - 0 1/2"
3' - 0" 3' - 5"
9' - 0" 9' - 0"
20' - 10" 18' - 7" 5' - 0" 5' - 2 1/2"
26' - 7" 4' - 11" 6' - 2 1/2" 22' - 8 1/2" 10' - 1 1/2" 23' - 11 5/8"
3'
4" 5'
3/ 4"
5'
0"
A801
A801A801A801A801
20202020
11' - 7" 12' - 11" 4' - 8" 4' - 1" 3' - 3" 4' - 8" 16' - 0" 3' - 4" 2' - 8" 3' - 4" 15' - 2" 15' - 6" 2' - 8" 3' - 10"
A801A801A801A801 14141414
FACE OF ROOF ABOVE
1'
6"
A801 4
8'
6" 3'
2"
8'
3"
/4
6'
3/
4"
4'
/2
3' - 9 1/4" 2' - 8" 3' - 4" 5' - 4" 2' - 8" 5' - 4" 1 1/2" 30' - 8 1/2"
9' - 6 1/2"
5' - 11 3/4"
21' - 0 1/8" i2s i1s i6si6s i5s i5s i1s e1e i1 i1 i3c i4 i3
3' - 8"
CLR
SHOWER
CURTAIN &
ROD, TYP
3' - 8" i3c i4c i3c i7s i7s i8s i8c i8s i8c i9c i9c i1c i6s i3c i3c i3c i3c i3c i5s i1c i1s i4 i6s i6s
2' -1
1/
8"
2'-8 1/8"
6°
7' - 4" SF6
SF10
SF12
SF7
A503
A503
7'
1/
4" 3'
1/ 4"
1'
1/
2" 1'
3"
5'
1/
4"
8'
3/
4"
6'-0" X 8'-0"H
FRAMED
WALL
OPENING
2' - 4" i4c
REF
REF
DS
DS
Stacked W/DStacked W/D
4'-10 1/2" i3s
5' -2
8'
-0
2' -0
3'
-4
4' -1
7/
8"
DF
8' - 1 1/2" 5' - 6" R.O. 9' - 1"
5'
8"
A801
FACE
OF
ROOF
ABOVE
115B
W/D Exhaust & Access Space Per Mfr Reqts
F
Laundry Carts by Owner
HOSE BIBB
HOSE
BIBB
HOSE
BIBB
HOSE
BIBB
HOSE
BIBB
SF4
SF5
28' - 11 3/16"
A B
DD
D
D
D
D
D
D
D EE
D
D D
D
D
D
E
CLR
42"Lx24W"x18"H Accessible Bench
72"Lx12W"x18"H movable bench
108B e2e e1e e1e e2e e2e e2e e1e e1e e1e e1e e1e e1e e1e e1e e1e
A801 3 i4c
96°3" 6' - 1" 3"
INSULATED WALLS: ACOUSTIC BATTS AT
INTERIOR WALLS; THERMAL BATTS AT EXTERIOR
BEARING WALLS - SEE STRUCTURAL
WALL LEGEND
NON-BEARING, NON-INSULATED WALLS
e2s
WALL TYPE DESIGNATION - SEE A002 FOR
WALL TYPES
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO.
317 Cruse Avenue Suite 201 Helena, Montana 59601 406.449.2013
SHEET OF 20
3/
/2
9:
:3
A
M C
:\U se rs \M ar kR
\D oc um en ts \G re en
B as e W or k
C en te r_ r2 4_ m ro yl an ce .rv t
A102 mgr mgr jrd
6260855010602
FLOOR PLAN
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
1/4" = 1'-0"
LEVEL 1 FLOOR PLAN
N
U G
P
UGP
UGP
UG
P
UG
P
G
UGP SS
G
W
W
W W
W
W W
UGP UGP
UGP
UGT
UGT
UGT UGT UGT UGT UGT UGT UGT UGT UGT
W
SS
SS
W S
W S
W
SWS
W S
W S
WS
G G
G G
SS
W W
W
W W
UGP
U G
P
U G
P
N O R T H
LEGEND
EXISTING UNDERGROUND POWER LINE
EXISTING SEWER SERVICE
EXISTING WATERLINE
EXISTING PROPANE LINE
EXISTING TELEPHONE LINE
EXISTING FENCING
NEW WATER SERVICE
NEW SEWER SERVICE
NEW UNDERGROUND POWER LINE
NEW PROPANE LINE
SURVEY CONTROL
EXISTING CONCRETE
EXISTING ASPHALT
EXISTING GRAVEL
NEW CONCRETE
NEW ASPHALT
NEW GRAVEL
G
UGP
W
SS
WS WS WS
SS SS SS
UGP
EXISTING
HELIPADS
EXISTING WORK CENTER
BUILDING TO BE DEMOLISHED
SEE SHEET C101 FOR
ENLARGED GRADING PLAN
CP21 CP18
CP5
CONSTRUCTION NOTES
1. COMPACT ALL SUBGRADE, FILL, AND BASE COURSE TO 95% OF MAXIMUM DRY DENSITY BELOW ALL NEW SIDEWALKS, CURB AND GUTTER, ASPHALT PAVING, AND CONCRETE.
2. THE CONTRACTOR IS RESPONSIBLE FOR PREPARING A STORM WATER POLLUTION PREVENTION PLAN (SWPPP), AS WELL AS SUBMITTING THE SWPPP TO THE ARIZONA DEQ. ASSOCIATED FEES WILL BE PAID FOR BY THE CONTRACTOR.
3. THE EXISTING UTILITIES ARE SHOWN AT APPROXIMATE LOCATIONS AND HAVE NOT BEEN INDEPENDENTLY VERIFIED BY THE ENGINEER.
THE CONTRACTOR SHALL DETERMINE THE LOCATIONS OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. LOCATES OF UNDERGROUND UTILITIES SHALL BE MADE USING THE "ONE CALL" SYSTEM AND THROUGH PRIVATE LOCATING SERVICES IF NECESSARY.
4. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND EXISTING UTILITIES PRIOR TO CONSTRUCTION. IF THE SITE IS FOUND TO BE DIFFERENT THAN THE CONSTRUCTION PLANS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF THE DISCREPANCY.
5. THE CONTRACTOR SHALL PROTECT EXISTING UTILITIES, PAVEMENT, ETC. THAT IS NOT SCHEDULED FOR DEMOLITION. ANY DAMAGE TO
THE SITE FEATURES SHALL BE REPAIRED AT NO COST TO THE OWNER.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MINIMIZING TRACKING OF SOIL AND DEBRIS ONTO ADJACENT PROPERTIES AND
ROADWAYS. CLEAN UP OF TRACKING DEBRIS MUST BE PERFORMED BY THE END OF EACH DAY.
7. SEE SHEET C102 FOR UTILITIES PLAN.
8. EXISTING DRAINFIELD AND SEPTIC TANK ABANDONMENT REQUIREMENTS:
· REMOVE ALL SEWAGE FROM THE FACILITY AND DISPOSE OF THE SEWAGE IN A LAWFUL MANNER;
· DISCONNECT AND REMOVE ELECTRICAL AND MECHANICAL COMPONENTS;
· REMOVE OR COLLAPSE THE TOP OF THE SEPTIC TANK.
a. PUNCH A HOLE IN THE BOTTOM OF THE TANK IF THE BOTTOM IS BELOW THE SEASONAL HIGH GROUNDWATER TABLE. SEASONAL HIGH GROUNDWATER IS APPROXIMATELY 32-INCHES BELOW THE
GROUND SURFACE;
b. FILL THE TANK STRUCTURE OR ANY CAVITY RESULTING FROM ITS REMOVAL WITH EARTH, SAND, GRAVEL, CONCRETE, OR OTHER APPROVED MATERIAL; AND
c. REGRADE THE SURFACE TO PROVIDE DRAINAGE AWAY FROM THE CLOSED AREA;
· CUT AND PLUG BOTH ENDS OF THE ABANDONED SEWER DRAIN PIPE BETWEEN THE BUILDING AND THE ONSITE
WASTEWATER TREATMENT NOT MORE THAN 5 FEET OUTSIDE THE BUILDING FOUNDATION.
9. ELECTRONIC CADD FILES WILL BE PROVIDED TO THE CONTRACTOR FOR CONSTRUCTION STAKING PURPOSES.
10. THE NATIVE SOILS ARE EXPANSIVE WITH AN INCREASE IN MOISTURE CONTENT. FOLLOW RECOMMENDATIONS OF THE GEOTECHNICAL REPORT PREPARED BY WESTERN TECHNOLOGIES FOR ALL EARTHWORK, INCLUDING EXCAVATION, EMBANKMENT, SUBGRADE PREP AND
BACKFILL.
ENGINEER FURNISHED CONTROL
POINT # NORTHING EASTING ELEVATION
CP5 1,555,698.9431 656,114.7951 6935.090
CP18 1,556,103.5676 657,733.1949 6937.221
CP21 1,556,102.9559 657,633.3643 6935.959
C O
R O
AD
EXISTING PUMP
HOUSE
EXISTING
WAREHOUSE
EXISTING SECURED
METAL STORAGE
EXISTING
WATER TANK
EXISTING
PROPANE TANKS
EXISTING
HOUSING
QUARTERS
EXISTING
CONTOURS
EXISTING GRAVEL
TURNAROUND
NEW GRAVEL DRIVE
NEW PARKING AREA
NEW PARKING
AREA
NEW WATER
SERVICE
741 LF OF SWALE
S = 0.21%
NEW STORMWATER
RETENTION POND
NEW GREEN BASE
WORK CENTER
OFFICE
FUTURE REPLACEMENT
DRIP FIELD AREA
G
EL = 6935.84
EL = 6934.45
EL = 6936
NEW PROPANE
GAS SERVICE
EXISTING SEPTIC TANK AND
DRAIN FIELD TO BE
ABANDONED PER ADEQ
REQUIREMENTS, SEE NOTE 8
UGT
WASTEWATER
TREATMENT SYSTEM
AND DRIP FIELD, SEE
SHEET C103
RETENTION POND .
RELIEF SWALE
(1" = 60' ON 24x36 SHEET)
NATURAL
DRAINAGE
PATH
EXTEND CHAIN LINK MESH
FABRIC TO DITCH GRADE
TO PREVENT GAP
EXISTING BURIED POWER,
SEE ELECTRICAL SITE PLAN
EXISTING SEPTIC
TANK AND DRAINFIELD
TO REMAIN
.8
7'16 1.
9.
212.82'
WASTEWATER SETBACKS
FEATURES REQUIRING SETBACKS
SETBACK FOR ONSITE WASTEWATER
TREATMENT FACILITY, INCLUDING
RESERVE AREA (IN FEET)
BUILDING 10
PROPERTY LINE SHARED WITH ANY
ADJOINING LOT OR PARCEL NOT
SERVED BY A COMMON DRINKING
WATER SYSTEM OR EXISTING WATER
WELL
PUBLIC OR PRIVATE WATER SUPPLY
WELL 100
WATER MAIN OR BRANCH WATER LINE 10
DOMESTIC SERVICE WATER LINE 5
DRIVEWAY 5
APPROVED
Coconino County Community Development
Environmental Quality
By: Date:
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO. SHEET OF 8
4/4 /20
:42 :22
A M
C:
\U se rs\
Ma rkR
\D oc um en ts\ Gr ee n B as e W or k C en ter
_r
_m ro yla nc e.r vt
JCL/JRS
JCL
JRS
6260855010602
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
C100
OVERALL SITE PLAN
UGP
UGP
U G
P U
G P
U G
P
UGP
UG
P
UGP
W
W
G
G G
G
G
G
U G
P U
G P
UGP
U G
P
UG
P
UGP
SS
SS
SS
SS
W
W
W
W W W W W
W
W
W
W
W W
UGP UGP UGP UGP UGP
UGP
UGP
UGP
UGP
UGP
UGPUGT
UGT
UGT
UGT
UGT
UGT
UGT UGT UGT UGT
W
W S
W S
W S
W S
W S
W S
W S
W S
WSWSWSWS
W S
W S
W S
W S
W S
W S
W S
W
S WS WS
G G
G G
G G
GG
G G
G G
G G
SS SS SS
SD
W W W W W
W
W
W
W
W W
U G
P
UGP
UGP
UGP
U G
P U
G P
U G
P
UGP UGP
SD
FM
U G
P U
G P
U G
P U
G P
UGP
WS WS WS WS WS WS WS WS WS
W S
G G G G G
G
SD
SD
SD
SD
SD
SD
SD
SD
UGP
UGP
N O R T H
SAWCUT ASPHALT (TYP.) 8" SCH. 40 PVC
WYE IE = 6935.29
9.5 LF OF NEW 8" SCH. 40 PVC
ROOF DRAIN @ 3.07%
23.1 LF OF NEW 8"
SCH. 40 PVC
ROOF DRAIN @ 3.07%
3.0 LF OF NEW 8" SCH. 40
PVC ROOF DRAIN @ 2.25%
45° ~ 8" SCH. 40 PVC
BEND IE = 6935.93
28.5 LF OF NEW 8" SCH. 40
PVC ROOF DRAIN @ 2.25%
115.2 LF OF NEW 1 12"
HDPE WATER SERVICE
61.3 LF OF NEW 1 12" HDPE
WATER SERVICE
90° ~ 1 12" HDPE
BEND
99.5 LF OF NEW
1 12" HDPE WATER SERVICE
90° ~ 1 12" HDPE BEND
31.0 LF OF NEW
1 12" HDPE
WATER SERVICE
90° ~ 1 12"
HDPE BEND
SAWCUT ASPHALT
DRIP FIELD, SEE
SHEET C103
NEW UNDERGROUND
POWER, SEE
ELECTRICAL SITE PLANS
5.0 LF OF
NEW 1 12"
HDPE WATER
SERVICE
90° ~ 1 12" HDPE BEND
EMERGENCY
GENERATOR
NEW ELEC.
TRANSFORMER
CONSTRUCTION NOTES
1. PROPANE LINE SHALL HAVE A MINIMUM BURY DEPTH OF 36
INCHES.
2. ALL NEW WATERLINES SHALL HAVE A MINIMUM OF 48
INCHES OF BURY DEPTH AND ALL NEW SEWER LINES
SHALL HAVE A MINIMUM OF 36 INCHES OF BURY DEPTH TO
INVERT OF PIPE.
3. SEE DETAIL 5/C106 FOR THE STANDARD UTILITY TRENCH
FOR NEW WATER AND SEWER LINES.
4. SEE ELECTRICAL SITE PLAN FOR ADDITIONAL
INFORMATION.
365 LF OF NEW 1 12" HDPE
PROPANE GAS SERVICE
FUTURE REPLACEMENT
DRIPFIELD AREA
CONNECT NEW
WATER SERVICE TO
EXISTING WATERLINE
CONNECT NEW
PROPANE SERVICE
TO EXISTING
PROPANE LINE
13.0' WIDE TRENCH, PATCH
ASPHALT AND BASE COURSE
TO MATCH EXISTING
15.0' WIDE TRENCH, PATCH
ASPHALT AND BASE COURSE
TO MATCH EXISTING
NEW LIGHT
POST (TYP.)
SEE SHEET C103 FOR
WASTEWATER SYSTEM
PLAN
WASTEWATER
TREATMENT SYSTEM,
SEE SHEET C103 AND
C104
LEGEND
EXISTING UNDERGROUND POWER LINE
EXISTING SEWER SERVICE
EXISTING WATERLINE
EXISTING PROPANE LINE
EXISTING TELEPHONE LINE
EXISTING FENCING
NEW WATER SERVICE
NEW SEWER SERVICE
NEW UNDERGROUND POWER LINE
NEW PROPANE LINE
SURVEY CONTROL
EXISTING CONCRETE
EXISTING ASPHALT
EXISTING GRAVEL
NEW CONCRETE
NEW ASPHALT
NEW GRAVEL
G
UGP
W
SS
WS WS WS
SS SS SS
UGP
G
UGT
(1" = 20' ON 24x36 SHEET)
SHUT-OFF
VALVE W/ BOX
EXISTING
PROPANE
TANK
1 12" CURB STOP W/ BOX
5.0' (TYP.)
3.0' (TYP.)
2.0'
WIDE
TRENCH
16.0'
.5
SEE ROOF DRAIN DETAIL
ON THIS SHEET
ROOF DRAIN DETAIL
DOWNSPOUT .
CONNECTION
IE = 6936.00
DOWNSPOUT .
CONNECTION
IE = 6936.00
OUTFALL TO
STROMWATER POND
IE = 6935.00
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO. SHEET OF 8
4/4 /20
:42 :22
A M
C:
\U se rs\
Ma rkR
\D oc um en ts\ Gr ee n B as e W or k C en ter
_r
_m ro yla nc e.r vt
JCL/JRS
JCL
JRS
6260855010602
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
C102
UTILITIES PLAN
WS WS
G
SS SS SS SS SS SS
SD
SD
SD
FM FM
N O R T H
45.0 LF OF NEW 4" SCH. 40 PVC
SEWER SERVICE @ 2.00%
NEW 1" SCH. 40 PVC
SUPPLY LINE FORCE MAIN
SEWER SERVICE
INVERT ELEV. = 6932.85
FUTURE REPLACEMENT
DRIP FIELD AREA
NEW DRIP FIELD
RETURN LINE CONNECTION .
(TYP. OF 6)
NEW 1" SCH. 40 PVC
RETURN LINE FORCE MAIN
(1" = 10' ON 24x36 SHEET)
DRIP LINE SUPPLY LINE CONNECTION .
(TYP. OF 6)
NEW GREEN BASE
WORK CENTER OFFICE
IE = 6931.95
SEE SHEET C104 FOR
WASTEWATER SYSTEM DETAILS
24.0' 24.0'
0.
0'
0.
0'
2" I.D. ~ "GEOTUBE" DRIPLINE (TYP.)
41.25' 46.75'
"ORENCO
ADVANTEX"
TREATMENT
POD (TYP. OF 4)
6937 69
69366936
FRP
WASTEWATER
TANK
.8
TEST HOLE #2
TEST HOLE #1
TEST HOLE #3
.0
AIR/VACUUM RELIEF .
(2 EACH)
MANUAL HEADWORKS BOX .
WASTEWATER SYSTEM MATERIALS LIST
ITEM QUANTITY
FRP TANK (3 CHAMBERS - 11,680 GALLONS TOTAL) 1 EA
24" DIA. TANK RISERS W/ INSULATED LIDS 2 EA
30" DIA. TANK RISERS W/ INSULATED LIDS 3 EA
RECIRCULATING VALVE 1 EA
RECIRCULATION PUMPS 2 EA
EFFLUENT DISCHARGE PUMPS 2 EA
FLOAT SYSTEMS FOR RECIRCULATION AND EFFLUENT PUMPS 2 EA
"ORENCO ADVANTEX AX20" FILTER PODS W/ INSULATED
COVERS 4 EA
VENTILATION FAN ASSEMBLY 1 EA
CONTROL PANEL 1 EA
EFFLUENT SPLITTER BASIN W/ INSULATED LID 1 EA
EFFLUENT UV BASIN W/ TWO UV DISINFECTION UNITS AND
INSULATED LID 1 EA
"GEOFLOW" HEADWORKS SYSTEM 1 EA
AIR/VACUUM RELIEF VALVES W/ INSULATED LIDS 2 EA
"GEOFLOW" DRIPLINE 1,200 LF
NOTE: CONTRACTOR TO CONFIRM MATERIALS LIST
PRIOR TO ORDERING AND CONSTRUCTION.
REVISION/ISSUE
NO. DATE
United States Department of Agriculture Forest Service
R-03 Southwestern
Region
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
DATE ARCHIVE NUMBER
DESIGNER DRAWING SHEET NO.
DRAWN
CHECKED
PROJECT NO. SHEET OF 8
4/4 /20
:42 :22
A M
C:
\U se rs\
Ma rkR
\D oc um en ts\ Gr ee n B as e W or k C en ter
_r
_m ro yla nc e.r vt
JCL/JRS
JCL
JRS
6260855010602
GREEN BASE WORK
CENTER (PITTMAN VALLEY
HELIBASE) OFFICE
REPLACEMENT
1782 Co Rd 74, Williams, AZ 86046
CONSTRUCTION DOCUMENTS
WILLIAMS RANGER DISTRICT
KAIBAB NATIONAL
FOREST
3/20/2024
C103
WASTEWATER SYSTEM PLAN
1' X 1' X 18' CONCRETE .
DEADMEN (4 TOTAL)
3" FILTRATE RETURN .
LINE
SEPTIC
TANK
RETICULATION
TANK
DISCHARGE
TANK
DUPLEX DISCHARGE
PUMPING ASSEMBLY
IN 30" Ø RISER
.5
0'
37.04'
DESIGN NOTES:
(BASED ON RESIDENTIAL STRENGTH EFFLUENT)
EXPECTED FLOWS
QMAX. ≤ 2,000 gpd
EXPECTED INFLUENT QUALITY
GREASE AND OIL: 20 mg/L BOD: 150 mg/L TSS: 40 mg/L TN: 65 mg/L
TYPICAL EFFLUENT QUALITY
BOD: 7 mg/L TSS: 3 mg/L TN: 15 mg/L
SUPPLY LINE
TO DRIP FIELD
RETURN LINE
FROM DRIP FIELD
FROM NEW
GREEN BASE
WORK CENTER
1.00'
(TYP.)
7.
AIR/VACUUM RELIEF .
(SUPPLY LINE)
WASTEWATER TREATMENT SYSTEM - PLAN VIEW
WASTEWATER TREATMENT SYSTEM - PROFILE VIEW
37.04'
16.75"
(TYP.)
5.23' 8.38'
17.50"
9.83' 6.98'
Ø 7.67' Ø 8.00'
GUID…