This document provides details regarding a federal contract opportunity for the renovation of the Catalina Headquarters at El Yunque National Forest in Puerto Rico. The USDA Forest Service Southern Region intends to solicit fixed price proposals to reconstruct the two-story 11,016 square foot administrative facility, which was damaged in Hurricanes Irma and Maria in 2017. The solicitation is expected to issue on or around July 15, 2020, and will have a magnitude between $4-10 million. The contractor will be responsible for furnishing all labor, materials, equipment and supplies to complete the building and site renovations according to the construction documents and specifications. The North American Industry Classification System code associated with this project is 236220 for commercial and institutional building construction. Interested parties must register in the System for Award Management to be considered for award.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Forest Services Revitalization of Catalina Headquarters
Detailed Design –Structural Fuel Transfer Canopy Design Development Calculations
Submitted: August 2019 June 2020
Calculations
Structural
Table of Contents
1. Site Location
2. Applicable Codes
3. Wind Loads
4. Seismic Loads
5. RAM Gravity Design
• Beam Gravity Design Summary
• Example Beam Gravity Design
• Example Gravity Column Design
6. RAM Lateral Design
• Lateral Frame Identification
• Code Check Criteria
• Building Story Shear
• Frame Story Shear
• Standard Provisions
• Member Code Check
• HSS Moment Connection
• Member Code Check
7. Diaphragm Design
8. RAM Foundation Design
• Reaction Report
• Spread Footing Design Summary
• Spread Footing Individual Design
9. Base Plate and Pier Design
• Lateral Base Plate Thickness Design
• Lateral Anchor Bolt Design
STRUCTURAL CALCULATION
PACKAGE
FOR
US FOREST SERVICE
REVITALIZATION OF CATALINA
HEADQUARTERS
FUEL TRANSFER CANOPY
BY
T.Y. LIN INTERNATIONAL
4400 LEEDS AVENUE, SUITE 250
NORTH CHARLESTON,
SC 29405
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of South Carolina.
Registration # Date
35451 June 22, 2020
Matthew Perry, PE
Site Location
SITE LOCATION MAP
REVITALIZATION OF CATALINA HEADQUARTERS
LOCATION MAP
VICINITY MAP
Applicable Codes
DESIGN CODES AND STANDARDS
IBC 2016
ASCE7-10
ACI 318-14
AISC 360-10
US Forest Service
Revitalization of Catalina Headquarters – Detailed Design
August 2019
Catalina Headquarters - Fuel Transfer Canopy
June 2020
Dead and Live Loads
DEAD AND LIVE LOADING
ROOF LIVE LOADS: 20 PSF (REDUCIBLE)
LIVE LOADS:
LIVE LOADS APPLIED TO FLOORS AND ROOF WILL BE PER TABLE 1607.1 OF THE IBC.
CLASSROOMS 40 PSF
FIRST FLOOR CORRIDORS 100 PSF
2ND/3RD FLOOR COORIDORS 80 PSF
LABS/MANUFACTURING 125 PSF
DINNING AREAS 100 PSF
STORAGE (LIGHT) 125 PSF
STAIRS AND EXITS 100 PSF
ELEVATED PLATFORMS 100 PSF
Catalina Headquarters – Fuel Transfer Canopy
Wind Loads
WIND LOADING ASSUMPTIONS
The wind loading created internally by Ram Structural Systems (RSS) assumes that the exterior of the building model has full height walls. The program then applies an internally calculated wind pressure to the full height of the assumed walls. Given that the canopies have no walls a customized wind loading work around was needed. Wind loads were first broken into components.
The vertical loads were placed as a surface load on the canopy roof while horizontal components were calculated and placed as nodal loads at the top of the columns.
Furthermore, RSS does not allow for area wind loads to be defined manually. Wind area load, live area load, and roof area load had to be combined into a single load within RSS. A ratio for the wind and live loads were then determined to create an adjustment factor to use for each force’s load combination coefficients.
Due to this unique situation a separate RSS file was created to account for wind uplift forces. These uplift forces were treated similarly to the previously described wind loads and combinations.
Investigating the results has shown that the uplift conditions did not govern in the member or foundation designs.
Catalina Headquarters – Fuel Transfer Canopy
ASCE 7 Hazards Report Address:
No Address at This Location
Standard: ASCE/SEI 7-16
Risk Category: I
Soil Class: D - Stiff Soil
Elevation: 657.2 ft (National Geodetic Vertical Datum of 1929 (NGVD 29))
Latitude:
Longitude:
18.338499
-65.761006
Wind
Results:
Data Source:
Date Accessed:
Wind Speed: 154 Vmph
10-year MRI 72 Vmph
25-year MRI 97 Vmph
50-year MRI 128 Vmph
100-year MRI 138 Vmph
ASCE/SEI 7-16, Fig. 26.5-1A and Figs. CC.2-1–CC.2-4
Mon Jul 01 2019
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 15% probability of exceedance in 50 years (annual exceedance probability = 0.00333, MRI = 300 years).
Site is in a hurricane prone region as defined in ASCE/SEI 7-16 Section 26.2. Glazed openings need not be protected against wind-borne debris.
Mountainous terrain, gorges, ocean promontories, and special wind regions should be examined for unusual wind conditions.
Page 1 of 3https://asce7hazardtool.online/ Mon Jul 01 2019 https://asce7hazardtool.online/
Roof Wind Loading
Canopy Dimension: Width, Wcanopy = 44.5 ft
Length, Lcanopy = 38.5 ft
Slope of Canopy: Slope = 0.5 /12 in/in
Percent Slope = 4.17 % θ = 2.39 degrees
Projected Uplift Load (Low Side): Wup_Project = -44.1 psf
Vertical Component: Wup_vert = Wup_proj*cos(θ) = -44.06 psf
Horizontal Component: Wup_horz = Wup_proj*sin(θ) = -1.84 psf
Projected Uplift Load (High Side): Wup_Project = -58.8 psf
Vertical Component: Wup_vert = Wup_proj*cos(θ) = -58.75 psf
Horizontal Component: Wup_horz = Wup_proj*sin(θ) = -2.45 psf
Projected Downward Load (Low Side): Wdwn_Project = 24.5 psf
Vertical Component: Wdwn_vert = Wdwn_proj*cos(θ) = 24.48 psf
Horizontal Component: Wdwn_horz = Wdwn_proj*sin(θ) = 1.02 psf
Projected Downward Load (High Side): Wdwn_Project = 39.2 psf
Vertical Component: Wdwn_vert = Wdwn_proj*cos(θ) = 39.17 psf
Horizontal Component: Wdwn_horz = Wdwn_proj*sin(θ) = 1.63 psf
Wind Load on sign/Fascia
Sign/Fascia depth: dfascia = 2 ft
Horizontal Wind Pressure: Whorz = 35 psf
Wind Pressure: Wfascia_dwn = Whorz *dfascia = 70.00 plf
Col Location Wind Direction
Trib
Width (ft)
Trib
Length (ft)
Trib
Area (ft
Wind
Pressure
(psf)
Roof Wind
Horz
Load (k)
Sign Wind
Horz Load (k)
Total Horz
Load (k)
B.C-1.C & B.C-2.C Down 21 10.25 215.25 1.63 0.35 N/A 0.35
A.C-1.C & A.C-2.C Down 21 10.25 215.25 1.63 0.35 N/A 0.35
B.C-1.C & B.C-2.C Down 21 10.25 215.25 1.02 0.22 1.47 1.69
A.C-1.C & A.C-2.C Down 21 10.25 215.25 1.02 0.22 1.47 1.69
B.C-1.C & B.C-2.C Uplift 21 10.25 215.25 -2.45 -0.53 N/A -0.53
A.C-1.C & A.C-2.C Uplift 21 10.25 215.25 -2.45 -0.53 N/A -0.53
B.C-1.C & B.C-2.C Uplift 21 10.25 215.25 -1.84 -0.40 1.47 1.87
A.C-1.C & A.C-2.C Uplift 21 10.25 215.25 -1.84 -0.40 1.47 1.87
High Side
Low Side
High Side
Low Side
Horizontal Nodal Loads at Top of Columns
Nodal Loads
RAM Frame 16.00.00.28
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:26:32
Building Code: IBC
NODAL LOAD CASES:
Label Type
Wind Y Wind RAMUSERNODAL_W
NODAL LOAD DEFINITION:
Label Fx Fy Fz Mxx Myy Mzz kips kips kips kip-ft kip-ft kip-ft
Wind Y 0.00 2.00 0.00 0.00 0.00 0.00
APPLIED NODAL LOADS:
Load Case: Wind Y RAMUSERNODAL_W
Level: Roof
Nodal Load Node X Y Z ft ft ft
Wind Y 2 0.000 42.500 22.750
Wind Y 4 40.000 42.500 22.750
Seismic Loads
SS : 0.966
S1 : 0.373
Fa : 1.114
Fv : N/A
SMS : 1.075
SM1 : N/A
SDS : 0.717
SD1 : N/A
TL : 12
PGA : 0.395
PGA M : 0.476
FPGA : 1.205
Ie : 1
Cv : 1.283
Seismic
Site Soil Class:
Results:
Data Accessed:
Date Source:
D - Stiff Soil
USGS Seismic Design Maps
Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8.
Mon Jul 01 2019
Page 2 of 3https://asce7hazardtool.online/ Mon Jul 01 2019 https://doi.org/10.5066/F7NK3C76
Criteria, Mass and Exposure Data
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
CRITERIA:
Rigid End Zones: Ignore Effects
Member Force Output: At Face of Joint
P-Delta: Yes Scale Factor: 1.00
Ground Level: Base
Mesh Criteria :
Max. Distance Between Nodes on Mesh Line (ft) : 4.00
Merge Node Tolerance (in) : 0.0100
Geometry Tolerance (in) : 0.0050
Walls Out-of-plane Stiffness Not Included in Analysis.
Sign considered for Dynamic Load Case Results.
Rigid Links Included at Fixed Beam-to-Wall Locations
Eigenvalue Analysis : Eigen Vectors (Subspace Iteration)
DIAPHRAGM DATA:
Story Diaph # Diaph Type
Roof 1 Rigid
Disconnect Internal Nodes of Beams: Yes
Disconnect Nodes outside Slab Boundary: Yes
STORY MASS DATA:
Includes Self Mass of:
Beams
Columns (Half mass of columns above and below)
Walls (Half mass of walls above and below)
Slabs/Deck
Calculated Values:
Story Diaph # Weight Mass MMI Xm Ym EccX EccY kips k-s2/ft ft-k-s2 ft ft ft ft
Roof 1 35.40 1.10 461 20.00 21.15 2.17 2.29
Story Diaph # Combine
Roof 1 None
WIND EXPOSURE DATA:
Calculated Values:
Story Diaph # Building Extents (ft) Expose Parapet
Min X Max X Min Y Max Y ft
Roof 1 -1.67 41.67 -1.67 44.17 Full 0.00
STORY GRAVITY LOADS DATA:
Includes Weight of:
Beams
Columns
Walls
Slabs/Deck
Criteria, Mass and Exposure Data
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
Live Load Reduction (Calculated)
Reducible : 0.00 %
Storage : 0.00 %
Roof : 0.00 %
Calculated Values:
Story Diaph # Dead Xc Yc Live Xc Yc kips ft ft kips ft ft
Roof 1 28.71 20.00 21.12 -109.24 20.00 21.25
Story Diaph # Roof Xc Yc Combine kips ft ft
Roof 1 0.00 0.00 0.00 None
Page 2/2
Loads and Applied Forces
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
LOAD CASE: Seismic
Seismic ASCE 7-16 Equivalent Lateral Force
Site Class: D Importance Factor: 1.00 Ss: 0.966 g S1: 0.373 g TL: 8.00 s
Fa: 1.114 Fv: 1.927 SDs: 0.717 g SD1: 0.479 g
Risk Category: II Seismic Design Category: D
Provisions for: Force
Ground Level: Base
Dir Eccent R Ta Equation Building Period-T
X + And - 3.5 Std,Ct=0.030,x=0.75 Calculated
Y + And - 3.5 Std,Ct=0.030,x=0.75 Calculated
Dir Ta Cu T T - used Cs Eq12.8-2 Cs - used k
X 0.313 1.400 0.378 0.378 0.205 0.205 1.000
Dir Ta Cu T T - used Cs Eq12.8-2 Cs - used k
Y 0.313 1.400 0.397 0.397 0.205 0.205 1.000
Exception 2 per Section 11.4.8 is applied for site class D with S1 > 0.2
Total Building Weight (kips) = 35.40
APPLIED DIAPHRAGM FORCES
Type: EQ_ASCE716_X_+E_F
Level Diaph.# Ht Fx Fy X Y ft kips kips ft ft
Roof 1 22.75 7.25 0.00 20.00 23.44
APPLIED STORY FORCES
Type: EQ_ASCE716_X_+E_F
Level Ht Fx Fy ft kips kips
Roof 22.75 7.25 0.00
7.25 0.00
APPLIED DIAPHRAGM FORCES
Type: EQ_ASCE716_X_-E_F
Level Diaph.# Ht Fx Fy X Y ft kips kips ft ft
Roof 1 22.75 7.25 0.00 20.00 18.85
Loads and Applied Forces
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
APPLIED STORY FORCES
Type: EQ_ASCE716_X_-E_F
Level Ht Fx Fy ft kips kips
Roof 22.75 7.25 0.00
7.25 0.00
APPLIED DIAPHRAGM FORCES
Type: EQ_ASCE716_Y_+E_F
Level Diaph.# Ht Fx Fy X Y ft kips kips ft ft
Roof 1 22.75 0.00 7.25 22.17 21.15
APPLIED STORY FORCES
Type: EQ_ASCE716_Y_+E_F
Level Ht Fx Fy ft kips kips
Roof 22.75 0.00 7.25
0.00 7.25
APPLIED DIAPHRAGM FORCES
Type: EQ_ASCE716_Y_-E_F
Level Diaph.# Ht Fx Fy X Y ft kips kips ft ft
Roof 1 22.75 0.00 7.25 17.83 21.15
APPLIED STORY FORCES
Type: EQ_ASCE716_Y_-E_F
Level Ht Fx Fy ft kips kips
Roof 22.75 0.00 7.25
0.00 7.25
RAM Gravity Design
Floor Map
RAM Steel 16.00.00.28
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
Building Code: IBC Steel Code: AISC 360-16 LRFD
Floor Type: Canopy Roof Beam Numbers
1.C 2.C
C.C
A.C
Beam Summary
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
Building Code: IBC Steel Code: AISC 360-16 LRFD
STEEL BEAM DESIGN SUMMARY:
Floor Type: Canopy Roof
Bm # Length +Mu -Mu ΦMn Fy Beam Size Studs ft kip-ft kip-ft kip-ft ksi
17 42.50 26.4 -176.1 233.4 50.0 W21X50
18 42.50 26.4 -176.1 233.4 50.0 W21X50
19 42.50 26.4 -176.1 233.4 50.0 W21X50
20 10.00 0.2 0.0 18.1 50.0 W8X10
21 10.00 0.2 0.0 18.1 50.0 W8X10
22 10.00 0.2 0.0 18.1 50.0 W8X10
23 10.00 0.2 0.0 18.1 50.0 W8X10
30 10.00 0.2 0.0 18.1 50.0 W8X10
31 10.00 0.2 0.0 18.1 50.0 W8X10
32 10.00 0.2 0.0 18.1 50.0 W8X10
33 10.00 0.2 0.0 18.1 50.0 W8X10
* after Size denotes beam failed stress/capacity criteria.
# after Size denotes beam failed deflection criteria.
u after Size denotes this size has been assigned by the User.
Gravity Beam Design
DataBase: Catalina Canopy -4 Cols_Uplift 08/01/19 13:12:20
Building Code: IBC Steel Code: AISC 360-16 LRFD
Floor Type: Canopy Roof Beam Number = 18
SPAN INFORMATION (ft): I-End (20.00,0.00) J-End (20.00,42.50)
Beam Size (Optimum) = W21X50 Fy = 50.0 ksi
Total Beam Length (ft) = 42.50
Mp (kip-ft) = 458.33
POINT LOADS (kips):
Dist DL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL
14.167 0.05
14.167 0.05
28.333 0.05
28.333 0.05
LINE LOADS (k/ft):
Load Dist DL LL Red% Type PartL
1 0.000 0.027 0.000 --- NonR 0.000
42.500 0.027 0.000 0.000
2 0.000 0.000 -0.550 --- NonR 0.000
42.500 0.000 -0.550 0.000
3 0.000 0.050 0.000 --- NonR 0.000
42.500 0.050 0.000 0.000
SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 16.61 kips 1.00Vn = 237.12 kips
MOMENTS (Ultimate):
Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft
Center Max + 1.4DL 26.4 21.3 0.0 1.00 0.90 412.50
Max - 1.2DL+1.6LL -176.1 21.3 14.2 1.01 0.90 233.39
Controlling 1.2DL+1.6LL -176.1 21.3 14.2 1.01 0.90 233.39
REACTIONS (kips):
Left Right
DL reaction 1.74 1.74
Max -LL reaction -11.69 -11.69
Max +total reaction (factored) 2.44 2.44
Max -total reaction -16.61 -16.61
DEFLECTIONS:
Dead load (in) at 21.25 ft = -0.215 L/D = 2372
Live load (in) at 21.25 ft = 1.415 L/D = 360
Net Total load (in) at 21.25 ft = 1.200 L/D = 425
Gravity Column Design
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:14:07
Building Code: IBC Steel Code: AISC360-16 LRFD
Story level Roof, Column Line 1.C-C.C, Column # 1
Fy (ksi) = 50.00 Column Size = HSS12X12X1/2
Orientation (deg.) = 90.0
INPUT DESIGN PARAMETERS:
X-Axis Y-Axis
Lu (ft) 22.75 22.75
K 1 1
Braced Against Joint Translation Yes Yes
Column Eccentricity (in) Top 8.50 8.50
Bottom 0.00 0.00
CONTROLLING AXIAL COLUMN LOADS - Skip-Load Case 18:
Dead Live Roof
Axial (kip) 7.06 -27.16 0.00
DEMAND CAPACITY RATIO: (1.2DL + 1.6LL + 0.5RF)
Pu (kip) = -34.98 0.90Pnx (kip) = 940.50 Pu/0.90Pnx = 0.037
0.90Pny (kip) = 940.50 Pu/0.90Pny = 0.037
0.90Pn (kip) = 940.50 Pu/0.90Pn = 0.037
CONTROLLING COMBINED COLUMN LOADS - Skip-Load Case 18:
Dead Live Roof
Axial (kip) 7.06 -27.16 0.00
Moments Top Mx (kip-ft) 0.97 -5.52 0.00
My (kip-ft) 2.88 -13.72 0.00
Bot Mx (kip-ft) 0.00 0.00 0.00
My (kip-ft) 0.00 0.00 0.00
Single curvature about X-Axis
Single curvature about Y-Axis
CALCULATED PARAMETERS: (1.2DL + 1.6LL + 0.5RF)
Pu (kip) = -34.98 0.90*Pn (kip) = 940.50
Mux (kip-ft) = -7.66 0.90*Mnx (kip-ft) = 336.00
Muy (kip-ft) = -18.49 0.90*Mny (kip-ft) = 336.00
Rm = 1.00
Cbx = 1.68 Cby = 1.68
Cmx = 0.60 Cmy = 0.60
Pex (kip) = 1755.05 Pey (kip) = 1755.05
B1x = 1.00 B1y = 1.00
INTERACTION EQUATION
Pu/0.90*Pn = 0.037
Eq H1-1b: 0.019 + 0.023 + 0.055 = 0.096
RAM Lateral Design
STEEL/CONCRETE LOAD COMBINATIONS
VERT SURFACE LOAD RESULTSCONVERSIONS
Live Roof Load (Lr) 12 psf INPUT ASCE 7-10 1.40 D
Misc Live Load (LLmisc) 4 psf INPUT RAM 1.40 D 1.4DCASE
Vert. Wind Load 39 psf INPUT ASCE 7-10 1.20 D + 1.60 L
RAM 1.20 D + 0.46 Lp 1.2D+0.463768115942029LpCASE
ASCE 7-10 1.20 D + 1.60 LR + 0.50 W + 1.00 W1
TOTAL LIVE (LLtotal) 55 PSF RAM 1.20 D + 0.46 Lp + 0.36 Lp + 1.00 W1 1.2D+0.463768115942029Lp+0.355072463768116Lp+1W1CASE
ASCE 7-10 1.20 D + 1.60 LR - 0.50 W - 1.00 W1
BASIC LOAD CASE RAM 1.20 D + 0.46 Lp - 0.36 Lp - 1.00 W1 1.2D+0.463768115942029Lp-0.355072463768116Lp-1W1COEFF FOR RAM CASE
D = 1 D ASCE 7-10 1.20 D + 1.00 W + 0.50 L + 1.00 W1
L = 0.290 Lp RAM 1.20 D + 0.71 Lp + 0.14 Lp + 1.00 W1 1.2D+0.710144927536232Lp+0.144927536231884Lp+1W1CASE
W = 0.710 Lp ASCE 7-10 1.20 D + 1.00 W + 0.50 L - 1.00 W1
E_# = 1 E RAM 1.20 D + 0.71 Lp + 0.14 Lp - 1.00 W1 1.2D+0.710144927536232Lp+0.144927536231884Lp-1W1CASE
ASCE 7-10 1.20 D + 1.00 E1 + 1.40 L
RAM 1.20 D + 1.00 E1 + 0.41 Lp 1.2D+1E1+0.405797101449275LpCASE
ASCE 7-10 1.20 D + 1.00 E1 - 1.40 L
RAM 1.20 D + 1.00 E1 - 0.41 Lp 1.2D+1E1-0.405797101449275LpCASE
ASCE 7-10 1.20 D + 1.00 E2 + 1.40 L
RAM 1.20 D + 1.00 E2 + 0.41 Lp 1.2D+1E2+0.405797101449275Lp
NODAL LATERAL LOAD
CASE
BASIC LOAD CASE ASCE 7-10 1.20 D + 1.00 E2 - 1.40 L
W1 = 1 W1 RAM 1.20 D + 1.00 E2 - 0.41 Lp 1.2D+1E2-0.405797101449275Lp
COEFF FOR RAM
CASE
ASCE 7-10 1.20 D + 1.00 E3 + 1.40 L
RAM 1.20 D + 1.00 E3 + 0.41 Lp 1.2D+1E3+0.405797101449275LpCASE
ASCE 7-10 1.20 D + 1.00 E3 - 1.40 L
RAM 1.20 D + 1.00 E3 - 0.41 Lp 1.2D+1E3-0.405797101449275LpCASE
ASCE 7-10 1.20 D + 1.00 E3 + 1.40 L
RAM 1.20 D + 1.00 E4 + 0.41 Lp 1.2D+1E4+0.405797101449275LpCASE
ASCE 7-10 1.20 D + 1.00 E3 + 1.40 L
RAM 1.20 D + 1.00 E4 + 0.41 Lp 1.2D+1E4+0.405797101449275LpCASE
ASCE 7-10 0.90 D + 1.00 W + 1.00 W1
RAM 0.90 D + 0.71 Lp + 1.00 W1 0.9D+0.710144927536232Lp+1W1CASE
ASCE 7-10 0.90 D + 1.00 W - 1.00 W1
RAM 0.90 D + 0.71 Lp - 1.00 W1 0.9D+0.710144927536232Lp-1W1CASE
ASCE 7-10 0.90 D + 1.00 E1
RAM 0.90 D + 1.00 E1 0.9D+1E1CASE
ASCE 7-10 0.90 D - 1.00 E1
RAM 0.90 D - 1.00 E1 0.9D-1E1CASE
ASCE 7-10 0.90 D + 1.00 E2
RAM 0.90 D + 1.00 E2 0.9D+1E2CASE
ASCE 7-10 0.90 D - 1.00 E2
RAM 0.90 D - 1.00 E2 0.9D-1E2CASE
ASCE 7-10 0.90 D + 1.00 E3
RAM 0.90 D + 1.00 E3 0.9D+1E3CASE
ASCE 7-10 0.90 D + 1.00 E3
RAM 0.90 D - 1.00 E3 0.9D-1E3CASE
ASCE 7-10 0.90 D + 1.00 E4
RAM 0.90 D + 1.00 E4 0.9D+1E4CASE
ASCE 7-10 0.90 D - 1.00 E4
RAM 0.90 D - 1.00 E4 0.9D-1E4CASE
L = (Lr+LLmisc/LLtotal) * Lp
W = (Vert/LLtotal) * Lp
Vert Wind Load + Lr=LLtotal
STEEL/CONCRETE LOAD COMBINATIONS
RESULTSCONVERSIONSVERT SURFACE LOAD
Live Roof Load (Lr) 0 psf INPUT ASCE 7-10 1.40 D
Misc Live Load (LLmisc) 4 psf INPUT RAM 1.40 D 1.4DCASE
Vert. Wind Load -59 psf INPUT ASCE 7-10 1.20 D + 1.60 L
RAM 1.20 D + -0.12 Ln 1.2D+-0.11689497716895LnCASE
ASCE 7-10 1.20 D + 1.60 LR + 0.50 W + 1.00 W1
TOTAL LIVE (LLtotal) -55 PSF RAM 1.20 D + -0.12 Ln + 0.54 Ln + 1.00 W1 1.2D+-0.11689497716895Ln+0.536529680365297Ln+1W1CASE
ASCE 7-10 1.20 D + 1.60 LR - 0.50 W - 1.00 W1
BASIC LOAD CASE RAM 1.20 D + -0.12 Ln - 0.54 Ln - 1.00 W1 1.2D+-0.11689497716895Ln-0.536529680365297Ln-1W1CASE
COEFF FOR RAM
D = 1 D ASCE 7-10 1.20 D + 1.00 W + 0.50 L + 1.00 W1
L = -0.0730594 Lp RAM 1.20 D + 1.07 Ln + -0.04 Ln + 1.00 W1 1.2D+1.07305936073059Ln+-0.0365296803652968Ln+1W1CASE
W = 1.07305936 Lp ASCE 7-10 1.20 D + 1.00 W + 0.50 L - 1.00 W1
E_# = 1 E RAM 1.20 D + 1.07 Ln + -0.04 Ln - 1.00 W1 1.2D+1.07305936073059Ln+-0.0365296803652968Ln-1W1CASE
ASCE 7-10 1.20 D + 1.00 E1 + 1.40 L
RAM 1.20 D + 1.00 E1 + -0.10 Ln 1.2D+1E1+-0.102283105022831LnCASE
ASCE 7-10 1.20 D + 1.00 E1 - 1.40 L
RAM 1.20 D + 1.00 E1 - -0.10 Ln 1.2D+1E1--0.102283105022831LnCASE
ASCE 7-10 1.20 D + 1.00 E2 + 1.40 L
RAM 1.20 D + 1.00 E2 + -0.10 Ln 1.2D+1E2+-0.102283105022831LnCASE
5NODAL LATERAL LOAD
BASIC LOAD CASE ASCE 7-10 1.20 D + 1.00 E2 - 1.40 L
W1 = 1 W1 RAM 1.20 D + 1.00 E2 - -0.10 Ln 1.2D+1E2--0.102283105022831LnCASE
5COEFF FOR RAM
ASCE 7-10 1.20 D + 1.00 E3 + 1.40 L
RAM 1.20 D + 1.00 E3 + -0.10 Ln 1.2D+1E3+-0.102283105022831LnCASE
ASCE 7-10 1.20 D + 1.00 E3 - 1.40 L
RAM 1.20 D + 1.00 E3 - -0.10 Ln 1.2D+1E3--0.102283105022831LnCASE
ASCE 7-10 1.20 D + 1.00 E3 + 1.40 L
RAM 1.20 D + 1.00 E4 + -0.10 Ln 1.2D+1E4+-0.102283105022831LnCASE
ASCE 7-10 1.20 D + 1.00 E3 + 1.40 L
RAM 1.20 D + 1.00 E4 + -0.10 Ln 1.2D+1E4+-0.102283105022831LnCASE
ASCE 7-10 0.90 D + 1.00 W + 1.00 W1
RAM 0.90 D + 1.07 Ln + 1.00 W1 0.9D+1.07305936073059Ln+1W1CASE
ASCE 7-10 0.90 D + 1.00 W - 1.00 W1
RAM 0.90 D + 1.07 Ln - 1.00 W1 0.9D+1.07305936073059Ln-1W1CASE
ASCE 7-10 0.90 D + 1.00 E1
RAM 0.90 D + 1.00 E1 0.9D+1E1CASE
ASCE 7-10 0.90 D - 1.00 E1
RAM 0.90 D - 1.00 E1 0.9D-1E1CASE
ASCE 7-10 0.90 D + 1.00 E2
RAM 0.90 D + 1.00 E2 0.9D+1E2CASE
ASCE 7-10 0.90 D - 1.00 E2
RAM 0.90 D - 1.00 E2 0.9D-1E2CASE
ASCE 7-10 0.90 D + 1.00 E3
RAM 0.90 D + 1.00 E3 0.9D+1E3CASE
ASCE 7-10 0.90 D + 1.00 E3
RAM 0.90 D - 1.00 E3 0.9D-1E3CASE
ASCE 7-10 0.90 D + 1.00 E4
RAM 0.90 D + 1.00 E4 0.9D+1E4CASE
ASCE 7-10 0.90 D - 1.00 E4
RAM 0.90 D - 1.00 E4 0.9D-1E4CASE
L = (Lr+LLmisc/LLtotal) * Lp
W = (Vert/LLtotal) * Lp
Vert Wind Load + Lr=LLtotal
RAM RAMFrameAnalysis.RFAn.1 DataBase: Catalina Canopy -4 Cols_Uplift 08/07/2019 14:16:35
RAM RAMFrameAnalysis.RFAn.1 DataBase: Catalina Canopy -4 Cols_Uplift 08/07/2019 14:17:42
Building Story Shears
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
CRITERIA:
Rigid End Zones: Ignore Effects
Member Force Output: At Face of Joint
P-Delta: Yes Scale Factor: 1.00
Ground Level: Base
Mesh Criteria :
Max. Distance Between Nodes on Mesh Line (ft) : 4.00
Merge Node Tolerance (in) : 0.0100
Geometry Tolerance (in) : 0.0050
Walls Out-of-plane Stiffness Not Included in Analysis.
Sign considered for Dynamic Load Case Results.
Rigid Links Included at Fixed Beam-to-Wall Locations
Eigenvalue Analysis : Eigen Vectors (Subspace Iteration)
Load Case: D DeadLoad RAMUSER
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 -0.00 -0.00
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.00 -0.00 -0.00 -0.00
Load Case: Lp PosLiveLoad RAMUSER
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 0.00 0.00
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 0.00 0.00
Load Case: Ln NegLiveLoad RAMUSER
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 -0.00 0.00
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.00 -0.00 0.00 0.00
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Load Case: W1 Wind Y RAMUSERNODAL_W
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 0.00 4.02
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 4.02 4.02
Load Case: E1 Seismic EQ_ASCE716_X_+E_F
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 7.29 0.00
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 7.29 7.29 0.00 0.00
Load Case: E2 Seismic EQ_ASCE716_X_-E_F
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 7.29 0.00
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 7.29 7.29 0.00 0.00
Load Case: E3 Seismic EQ_ASCE716_Y_+E_F
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 0.00 7.29
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 7.29 7.29
Load Case: E4 Seismic EQ_ASCE716_Y_-E_F
Level Diaph. # Shear-X Shear-Y kips kips
Roof 1 -0.00 7.29
Page 2/3
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Summary - Total Story Shears
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.00 -0.00 7.29 7.29
Page 3/3
Frame Story Shears
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
CRITERIA:
Rigid End Zones: Ignore Effects
Member Force Output: At Face of Joint
P-Delta: Yes Scale Factor: 1.00
Ground Level: Base
Mesh Criteria :
Max. Distance Between Nodes on Mesh Line (ft) : 4.00
Merge Node Tolerance (in) : 0.0100
Geometry Tolerance (in) : 0.0050
Walls Out-of-plane Stiffness Not Included in Analysis.
Sign considered for Dynamic Load Case Results.
Rigid Links Included at Fixed Beam-to-Wall Locations
Eigenvalue Analysis : Eigen Vectors (Subspace Iteration)
Frame #1
Load Case: D DeadLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.96 -0.96 -0.45 -0.45
Load Case: Lp PosLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 0.00 0.00
Load Case: Ln NegLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 4.83 4.83 2.16 2.16
Load Case: W1 Wind Y RAMUSERNODAL_W
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 1.01 1.01
Load Case: E1 Seismic EQ_ASCE716_X_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 1.72 1.72 0.09 0.09
Load Case: E2 Seismic EQ_ASCE716_X_-E_F
Level Shear-X Change-X Shear-Y Change-Y
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55 kips kips kips kips
Roof 1.93 1.93 -0.09 -0.09
Load Case: E3 Seismic EQ_ASCE716_Y_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.10 0.10 1.74 1.74
Load Case: E4 Seismic EQ_ASCE716_Y_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.10 -0.10 1.91 1.91
Frame #2
Load Case: D DeadLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.94 -0.94 0.45 0.45
Load Case: Lp PosLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 0.00 0.00
Load Case: Ln NegLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 4.83 4.83 -2.16 -2.16
Load Case: W1 Wind Y RAMUSERNODAL_W
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 1.01 1.01
Load Case: E1 Seismic EQ_ASCE716_X_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 1.92 1.92 0.09 0.09
Load Case: E2 Seismic EQ_ASCE716_X_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Page 2/5
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Roof 1.71 1.71 -0.09 -0.09
Load Case: E3 Seismic EQ_ASCE716_Y_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.10 -0.10 1.74 1.74
Load Case: E4 Seismic EQ_ASCE716_Y_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.10 0.10 1.91 1.91
Frame #3
Load Case: D DeadLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.94 0.94 0.45 0.45
Load Case: Lp PosLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 0.00 0.00
Load Case: Ln NegLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -4.83 -4.83 -2.16 -2.16
Load Case: W1 Wind Y RAMUSERNODAL_W
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 1.01 1.01
Load Case: E1 Seismic EQ_ASCE716_X_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 1.92 1.92 -0.09 -0.09
Load Case: E2 Seismic EQ_ASCE716_X_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 1.71 1.71 0.09 0.09
Page 3/5
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Load Case: E3 Seismic EQ_ASCE716_Y_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.10 -0.10 1.91 1.91
Load Case: E4 Seismic EQ_ASCE716_Y_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.10 0.10 1.74 1.74
Frame #4
Load Case: D DeadLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.96 0.96 -0.45 -0.45
Load Case: Lp PosLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 0.00 0.00
Load Case: Ln NegLiveLoad RAMUSER
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -4.83 -4.83 2.16 2.16
Load Case: W1 Wind Y RAMUSERNODAL_W
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.00 0.00 1.01 1.01
Load Case: E1 Seismic EQ_ASCE716_X_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 1.72 1.72 -0.09 -0.09
Load Case: E2 Seismic EQ_ASCE716_X_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 1.93 1.93 0.09 0.09
Page 4/5
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Load Case: E3 Seismic EQ_ASCE716_Y_+E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof 0.10 0.10 1.91 1.91
Load Case: E4 Seismic EQ_ASCE716_Y_-E_F
Level Shear-X Change-X Shear-Y Change-Y kips kips kips kips
Roof -0.10 -0.10 1.74 1.74
Page 5/5
Steel Code Check Criteria
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
MEMBER CODE CHECK CRITERIA - GLOBAL:
B1 and B2 Criteria
B1 Factor Not Applied
B2 Factor Not Applied
K-Factor: Columns Beams Braces
Kx: 1.000 1.000 1.000
Ky: 1.000 1.000 1.000
Compression Flange Bracing:
Columns:
Deck Braces Column
Knee Brace Does Not Brace Column
Max Angle for which Beam Braces Column: 60.00 deg
Beams / Horiz Braces:
Top Flange Not Continuously Braced
Bottom Flange Not Continuously Braced
Do Not Consider Point of Inflection as Brace Point
Column Design Moments:
Percent of Gravity Load Moments to include in design of steel columns:
Dead Load: 100.00 %
Live Load: 100.00 %
Roof Load: 100.00 %
Axial Slenderness Limits
Check KL/r exceeds 200 for Compression Members
Check L/r exceeds 300 for Tension Members (excludes rods)
MEMBER CODE CHECK CRITERIA - ASSIGNED
Frame #1:
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
Level: Roof
Steel Column:
# K-Factor Flange Bracing Unbraced Length
Kx Ky Major Minor Lx Ly Lby
1 1.00 1.00 Global Global Global Global Global
Steel Beam:
# K-Factor Flange Bracing Unbraced Length RBS
Kx Ky Major Minor Lx Ly Lby
15 1.00 1.00 Global Global Global Global Global N
Frame #2:
Level: Roof
Steel Column:
# K-Factor Flange Bracing Unbraced Length
Kx Ky Major Minor Lx Ly Lby
3 1.00 1.00 Global Global Global Global Global
Steel Beam:
# K-Factor Flange Bracing Unbraced Length RBS
Kx Ky Major Minor Lx Ly Lby
7 1.00 1.00 Global Global Global Global Global N
Frame #3:
Level: Roof
Steel Column:
# K-Factor Flange Bracing Unbraced Length
Kx Ky Major Minor Lx Ly Lby
6 1.00 1.00 Global Global Global Global Global
Steel Beam:
# K-Factor Flange Bracing Unbraced Length RBS
Kx Ky Major Minor Lx Ly Lby
16 1.00 1.00 Global Global Global Global Global N
Frame #4:
Page 2/4
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
Level: Roof
Steel Column:
# K-Factor Flange Bracing Unbraced Length
Kx Ky Major Minor Lx Ly Lby
4 1.00 1.00 Global Global Global Global Global
Steel Beam:
# K-Factor Flange Bracing Unbraced Length RBS
Kx Ky Major Minor Lx Ly Lby
5 1.00 1.00 Global Global Global Global Global N
JOINT CODE CHECK CRITERIA
Material Properties
Web plate Fy (ksi): 36.00
Stiffner plate Fy (ksi): 36.00
Geometry
Maximum angle between a beam and column to assume the beam frames into column flange: 45.0
One diagonal stiffener designed if the difference in beam depths at a joint is less than (in):
4.00
Design Force
Use actual beam forces
Consider axial load in beam
Optimization
Stiffners
Optimize each stiffner at joint
Minimum Thickness: Per Code
Minimum Width: Max Beam Flange Width at Joint
Thickness Increment (in): 0.125
Width Increment (in): 0.125
Clip (cope) dimension (in): 0.750
Web Plates
Maximum Thickness: Same as Column Web
Page 3/4
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
Minimum Thickness (in): 0.250
Thickness Increment (in): 0.125
CJP groove weld plate to column.
No web plate plug weld.
Page 4/4
Code Check Summary
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
CRITERIA:
Rigid End Zones: Ignore Effects
Member Force Output: At Face of Joint
P-Delta: Yes Scale Factor: 1.00
Ground Level: Base
Mesh Criteria :
Max. Distance Between Nodes on Mesh Line (ft) : 4.00
Merge Node Tolerance (in) : 0.0100
Geometry Tolerance (in) : 0.0050
Walls Out-of-plane Stiffness Not Included in Analysis.
Sign considered for Dynamic Load Case Results.
Rigid Links Included at Fixed Beam-to-Wall Locations
Eigenvalue Analysis : Eigen Vectors (Subspace Iteration)
LOAD CASE DEFINITIONS:
D DeadLoad RAMUSER
Ln NegLiveLoad RAMUSER
W1 Wind Y RAMUSERNODAL_W
E1 Seismic EQ_ASCE716_X_+E_F
E2 Seismic EQ_ASCE716_X_-E_F
E3 Seismic EQ_ASCE716_Y_+E_F
E4 Seismic EQ_ASCE716_Y_-E_F
LOAD COMBINATIONS: User Specified
1 * 1.4D
2 * 1.2D-0.130612244897959Ln
3 * 1.2D-0.130612244897959Ln+0.540816326530612Ln+1W1
4 * 1.2D-0.130612244897959Ln-0.540816326530612Ln-1W1
5 * 1.2D+1.08163265306122Ln-0.0408163265306122Ln+1W1
6 * 1.2D+1.08163265306122Ln-0.0408163265306122Ln-1W1
7 * 1.2D+1E1-0.114285714285714Ln
8 * 1.2D+1E1+0.114285714285714Ln
9 * 1.2D+1E2-0.114285714285714Ln
10 * 1.2D+1E2+0.114285714285714Ln
11 * 1.2D+1E3-0.114285714285714Ln
12 * 1.2D+1E3+0.114285714285714Ln
13 * 1.2D+1E4-0.114285714285714Ln
14 * 1.2D+1E4-0.114285714285714Ln
15 * 0.9D+1.08163265306122Ln+1W1
16 * 0.9D+1.08163265306122Ln-1W1
17 * 0.9D+1E1
18 * 0.9D-1E1
19 * 0.9D+1E2
20 * 0.9D-1E2
21 * 0.9D+1E3
22 * 0.9D-1E3
Code Check Summary
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
23 * 0.9D+1E4
* = Load combination currently selected to use
Frame #1:
Level: Roof
Col. Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
1 27.46 37.89 -62.56 -3.00 4.39 4 0.32 H1-1b 50 HSS12X12X1/2
Beam Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
15 0.00 46.28 0.00 7.47 -0.00 4 0.13 H1-1b 50 W21X55
Frame #2:
Level: Roof
Col. Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
3 -23.37 37.04 62.30 -0.93 -4.37 16 0.31 H1-1b 50 HSS12X12X1/2
Beam Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
7 0.00 -162.41 0.00 -17.70 -0.00 15 0.24 H1-1b 50 W24X68
Frame #3:
Level: Roof
Col. Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
6 -23.37 37.04 -62.30 -0.93 4.37 16 0.31 H1-1b 50 HSS12X12X1/2
Beam Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
16 0.00 46.28 0.00 7.47 -0.00 4 0.13 H1-1b 50 W21X55
Frame #4:
Level: Roof
Col. Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
4 27.46 37.89 62.56 -3.00 -4.39 4 0.32 H1-1b 50 HSS12X12X1/2
Beam Pu Mux Muy Vux Vuy LC Interact. Fy Size
# kip kip-ft kip-ft kip kip ksi
5 0.00 -161.85 0.00 -17.81 -0.00 15 0.24 H1-1b 50 W24X68
Member Code Check
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC360-16 LRFD
BEAM INFORMATION:
Story Level = Roof Frame Number = 2 Beam Number = 7
Fy (ksi) = 50.00
Beam Size = W24X68
INPUT DESIGN PARAMETERS:
X-Axis Y-Axis
Lu for Axial (ft) 40.00 10.00
Lu for Bending (ft) 40.00 10.00
K 1.00 1.00
Top Flange Continuously Braced No
Bottom Flange Continuously Braced No
CONTROLLING BEAM SEGMENT FORCES - SHEAR
Load Combination: 1.2D-0.130612244897959Ln-0.540816326530612Ln-1W1
Segment distance (ft) i - end 30.00 j - end 40.00
SHEAR CHECK:
Vux (kip) = -17.70 1.00Vnx (kip) = 295.07 Vux/1.00Vnx = 0.060
Vuy (kip) = -0.00 0.90Vny (kip) = 283.36 Vuy/0.90Vny = 0.000
CONTROLLING BEAM SEGMENT FORCES - AXIAL
Load Combination: 1.4D
Segment distance (ft) i - end 0.00 j - end 10.00
AXIAL CHECK:
Pu (kip) = 0.00 0.90Pnx (kip) = 904.50 Pu/0.90Pnx = 0.000
0.90Pny (kip) = 904.50 Pu/0.90Pny = 0.000
0.90Pn (kip) = 904.50 Pu/0.90Pn = 0.000
CONTROLLING BEAM SEGMENT FORCES - FLEXURE
Load Combination: 0.9D+1.08163265306122Ln+1W1
Segment distance (ft) i - end 10.00 j - end 20.00
CALCULATED PARAMETERS:
Pu (kip) = 0.00 0.90Pn (kip) = 904.50
Mux (kip-ft) = -162.41 0.90Mnx (kip-ft) = 663.75
Muy(kip-ft) = 0.00 0.90Mny (kip-ft) = 91.88
Cbx = 1.16
INTERACTION EQUATION:
Pu/0.90*Pn=0.000
Mrx/Mcx = 0.245
Seismic Provisions Member Code Check Summary
RAM Structural System 16.00.00.28
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC341-16 - LRFD
Criteria
Cd/Ie = 4.0
BRBF and SCBF - Required Column Strength based on Larger of Strength and Capacity Limited Seismic
Forces.
Frame #1:
Story:Roof Column: 1 Type: Intermediate Moment Resisting Frame
Size:HSS12X12X1/2 Fy (ksi): 50.00
D1.4a Required Strength --- OK
D2.5b Column Splices - Required Strength
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
E2.6g Column Splices
Story:Roof Beam: 15 Type: Intermediate Moment Resisting Frame
Size:W21X55 Fy (ksi): 50.00
E2.4a Lateral Bracing of Beams (D1.1 Moderately Ductile) --- OK
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
E2.6b Beam-to-Column Connection Requirements
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC341-16 - LRFD
Frame #2:
Story:Roof Column: 3 Type: Intermediate Moment Resisting Frame
Size:HSS12X12X1/2 Fy (ksi): 50.00
D1.4a Required Strength --- OK
D2.5b Column Splices - Required Strength
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
E2.6g Column Splices
Story:Roof Beam: 7 Type: Intermediate Moment Resisting Frame
Size:W24X68 Fy (ksi): 50.00
E2.4a Lateral Bracing of Beams (D1.1 Moderately Ductile) --- OK
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
Page 2/4
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC341-16 - LRFD
Frame #3:
Story:Roof Column: 6 Type: Intermediate Moment Resisting Frame
Size:HSS12X12X1/2 Fy (ksi): 50.00
D1.4a Required Strength --- OK
D2.5b Column Splices - Required Strength
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
E2.6g Column Splices
Story:Roof Beam: 16 Type: Intermediate Moment Resisting Frame
Size:W21X55 Fy (ksi): 50.00
E2.4a Lateral Bracing of Beams (D1.1 Moderately Ductile) --- OK
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
Page 3/4
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC Steel Code: AISC341-16 - LRFD
Frame #4:
Story:Roof Column: 4 Type: Intermediate Moment Resisting Frame
Size:HSS12X12X1/2 Fy (ksi): 50.00
D1.4a Required Strength --- OK
D2.5b Column Splices - Required Strength
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
E2.6g Column Splices
Story:Roof Beam: 5 Type: Intermediate Moment Resisting Frame
Size:W24X68 Fy (ksi): 50.00
E2.4a Lateral Bracing of Beams (D1.1 Moderately Ductile) --- OK
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
Page 4/4
Member Code Check
DataBase: Catalina Canopy -4 Cols_Uplift 08/07/19 14:18:55
Building Code: IBC
Beam Parameters
Story: Roof Frame No: 2 Member No: 7
Fy (ksi): 50.00 Size: W24X68
Frame Type: Intermediate Moment Resisting Frame
E2.4a Stability Bracing of Beams (D1.2a Moderately Ductile) --- OK
Max Lu (in) = 120.00 Lu Limit = 187.49 OK
Lateral Bracing Requirements along Beam
Required strength of lateral brace along beam = 8.42 kip
Required stiffness of bracing (A-6-8) = 5615.40 kip / Lb
Lateral Bracing Requirements at Plastic Hinge
Required strength of lateral brace at hinge = 25.27 kip
Required stiffness of bracing (A-6-8) = 5615.40 kip / Lb
Cd = 1.0 assumed for eqns (A-6-7/8)
Lb = distance between braces (in)
The brace closest to the point of inflection should be designed for two times these values (Cd=2)
E2.5a Basic Requirements (D1.1 Moderately Ductile) --- OK
Flange b/tf = 7.67 Limit = 9.18 OK
Web h/tw = 51.86 Limit = 90.93 OK
E2.6b Beam-to-Column Connection Requirements
Beam-to-column connection must be capable of sustaining a 0.02 radian interstory drift ratio.
All beam-to-column joints to demonstrate conformance with E2.6b(1) as indicated in E2.6b(2)
Concentrated Force Distributed Transversely at Center of the HSS Width Rectangular HSS Column
Shape HSS12X12X1/2
E = 29000 ksi
Fy = 46 ksi
Fu = 58 ksi
Ag = 20.9 in.
Sx= 76.2 in.
Sy = 76.2 in.
(about axis perp. To plane of conx)
Bx = 12 in.
By = 12 in.
t = 0.465 in.
S = 76.2 in.
B = 12 in. (width of HSS at face of conx, measured perp. to plane of plate in conx)
H = 12 in. (width of HSS NOT at face of conx, measured parallel to plane of plate in conx)
Column Demand Pr = 17.5 kips (acting parallel to axis of HSS)
Mr = 678 in. x kips (acting about axis perpendicular to plane of connection)
Connecting Plate
Fy = 46 ksi
Bp = 9 in. (width of plate attached to HSS) tp = 0.01 in. (thickness of plate attached to HSS)
N = 24 in. (bearing length of the load, measured parallel to the axis of the HSS)
Pr = 28.25 kips (acting perpendicular to axis of HSS)
Vr =
Local Yielding
Beta, Bp/B 0.75
B/t 25.80645161
Applicable? 1 φ = 0.95 φRn = 3.933 kips (K1-2)
RESULT = NO GOOD!
Shear Yielding (Punching)
B-2t 11.07 in.
Check Limit State? 0
Bep = 3.4875 in.
φ = 0.95 φRn = 85.2851385 kips (K1-3)
RESULT = No Check Req'd
Sidewall Local Yielding
Applicable? 1 k = 0.6975 in.
φ = 1 φRn = 1175.91525 kips (K1-4)
RESULT =
Sidewall Local Crippling
U = 0.21162953
Qf = 1 (K2-10) φ = 0.75 φRn = 2334.321818 kips (K1-5)
RESULT =
Sidewall Local Buckling (in cross-connections) (forces pass through HSS) φ = 0.75 φRn = 394.2108754 kips (K1-6)
RESULT =
Weld Size (θ=90)
Le = 9 in. (K1-7 w/ modification) (one-sided weld)
Le = 18 (K1-7) (two-sided weld) φ = 0.75
Fexx = 70 ksi groove weld thickness = 0.039858907 in.
base metal fillet weld, Dmin = 0.751649638 (two-sided weld)
U p d a te
T h e se
C e ll s
W h e n
S a p
C a n g s
Diaphragm Design
Company: T.Y. Lin International
Phone | Fax:
e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 1 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Project Details
T.Y. Lin InternationalCompany:
Contact:
Address:
/ Phone / Fax:
Comments:
e-Mail:
USFS Catalina_CanopyProject Title:
Project Number:
Structural Plan Sheet Number:
Contract Number:
RCSChecked by:
MTPPrepared by:
8/7/2019Date:
Design Settings
LRFDDesign Method:
WindRelevant Loads:
Resistance Factors:
= 0.70
= 0.50
= 0.80
= 0.70
= 0.50
= 0.50 = 0.50 e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 2 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Area A
38.50 ftLength L:
44.50 ftWidth B:
X - DirectionZone Orientation:
3 in.Sidelap Connector Spacing from:
36 in.Sidelap Connector Spacing to:
3 in.Sidelap Connector Spacing incr.:
BeamsSupport Construction:
10.00 ftJoist / Beam Spacing:
0.2500 in.Joist / Beam Thickness:
3" N-Deck - Deep Rib or
3DR
Deck Panel:
NestablePanel Type:
24.000 in.Panel Width:
Panel Moment of Inertia (16 ga):
Panel Moment of Inertia (18 ga):
Panel Moment of Inertia (20 ga):
Panel Moment of Inertia (22 ga):
Lateral Load Uplift Load
45 ksi / 33 ksi
Steel Roof DeckDeck Type:
e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 3 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Zone A - 1
10 ftLength L:
120 plfDiaphragm Shear Q: 56 psfNet Uplift T:
20 ga (0.0358 in.)Deck Thickness:
Hilti X-HSN 24Frame Fastener:
Hilti #8 Drill ScrewSidelap Connector:
36 in.Sidelap Connector Spacing:
24/4Pattern:
318 plfDesign Shear: 126 psfDesign Uplift:
30.8 kip/in.Shear Stiffness G': 32.4 micro-in./lbFlexibility Factor F:
Design OK
Required Input Loads
Proposed Diaphragm System
Proposed System Diaphragm Shear and Stiffness/Flexibility
Design Checks
Design Shear
Design Uplift
Shear & Tension Interaction:
e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 4 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 1
Frame Fastener Strength: Reference:
SDI DDM, Third Edition t = 0.0358 in.
= 1.795 kip = 1795 lb
Sidelap Connector Strength:
SDI DDM, Third Edition dt = 0.164 in.= 0.0358 in.
= 0.673 kip = 673 lb
Shear Strength Calculation:
= 0.375
SDI DDM, Third Edition (Eq. 2.2-2)
= 1.333
= 2
= 1.333
= 3 * 10.00 ft * 12 / 36.00 in. = 10.000 l = 3 * 10.00 ft = 30.00 ft
= 917 plf e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 5 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 1
Reference:
SDI DDM, Third Edition (Eq. 2.2-4)
A
D
= 1
= 3.000 in.
= 10.00 ft
= 3 * 10.00 ft * 12 / 36.00 in. = 10.000
W = 24.000 in.
= 0.5556
= 0.5556 l = 0.700
B = 8.195
= 454 plf
SDI DDM, Third Edition (Eq. 2.2-5)
N
= 482 plf e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 6 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear Strength:
Reference:
= 454 plf
= 454 plf * 0.70 = 318 plf
Design Shear / Stiffness Calculation for Zone A - 1
Check for Buckling:
SDI DDM, Third Edition (Eq. 2.3-3)
I
= 10.00 ft t = 0.0358 in.
d / s = 8.000 in. / 13.296 in.
= 1830 plf * 0.80 = 1464 plf
Governing:
Frame Fastener Flexibility:
SDI DDM, Third Edition t = 0.0358 in.
= 0.0066 in./kip e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 7 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 1
Sidelap Connector Flexibility: Reference:
SDI DDM, Third Edition t = 0.0358 in.
= 0.0159 in./kip
Shear Stiffness / Flexibility Factor Calculation:
SDI DDM, Third Edition (Eq. 3.3-3)
SDI DDM, Third Edition, Simplified Equation (Appendix IV)
E = 29500 ksi t = 0.0358 in.
W = 24.000 in.
K1 s / d = 13.296 in. / 8.000 in. = 1.662
D = 5839.78 in.
G' = 30.8 kip/in.
F = 32.4 micro-in./lb l = 3 * 10.00 ft = 30.00 ft = 360.00 in.
e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 8 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Uplift Calculation for Zone A - 1
Nominal Uplift Resistance: Reference:
Roof Deck Construction Handbook
= 10.00 ft
C = 2.00 ft
K = 3.00
Hilti 2014 PTG Supplement, Section
1.2.3 and 1.3.3
= 1680 lb
= 252 psf
Shear - Uplift Interaction Check:
SDI DDM, Third Edition, section 4.10
Design Uplift Resistance:
= 252 psf * 0.50 = 126 psf >= T = 56 psf e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 9 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Zone A - 2
19 ftLength L:
120 plfDiaphragm Shear Q: 56 psfNet Uplift T:
20 ga (0.0358 in.)Deck Thickness:
Hilti X-HSN 24Frame Fastener:
Hilti #8 Drill ScrewSidelap Connector:
36 in.Sidelap Connector Spacing:
24/4Pattern:
318 plfDesign Shear: 126 psfDesign Uplift:
30.8 kip/in.Shear Stiffness G': 32.4 micro-in./lbFlexibility Factor F:
Design OK
Required Input Loads
Proposed Diaphragm System
Proposed System Diaphragm Shear and Stiffness/Flexibility
Design Checks
Design Shear e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 10 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 2
Frame Fastener Strength: Reference:
SDI DDM, Third Edition t = 0.0358 in.
= 1.795 kip = 1795 lb
Sidelap Connector Strength:
SDI DDM, Third Edition dt = 0.164 in.= 0.0358 in.
= 0.673 kip = 673 lb
Shear Strength Calculation:
= 0.375
SDI DDM, Third Edition (Eq. 2.2-2)
= 1.333
= 2
= 1.333
= 3 * 10.00 ft * 12 / 36.00 in. = 10.000 e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 11 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 2
Reference:
SDI DDM, Third Edition (Eq. 2.2-4)
A
D
= 1
= 3.000 in.
= 10.00 ft
= 3 * 10.00 ft * 12 / 36.00 in. = 10.000
W = 24.000 in.
= 0.5556
= 0.5556 l = 0.700
B = 8.195
= 454 plf
SDI DDM, Third Edition (Eq. 2.2-5) e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 12 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear Strength:
Reference:
= 454 plf
= 454 plf * 0.70 = 318 plf
Design Shear / Stiffness Calculation for Zone A - 2
Check for Buckling:
SDI DDM, Third Edition (Eq. 2.3-3)
I
= 10.00 ft t = 0.0358 in.
d / s = 8.000 in. / 13.296 in.
= 1830 plf * 0.80 = 1464 plf
Governing:
Frame Fastener Flexibility:
SDI DDM, Third Edition e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 13 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 2
Sidelap Connector Flexibility: Reference:
SDI DDM, Third Edition t = 0.0358 in.
= 0.0159 in./kip
Shear Stiffness / Flexibility Factor Calculation:
SDI DDM, Third Edition (Eq. 3.3-3)
SDI DDM, Third Edition, Simplified Equation (Appendix IV)
E = 29500 ksi t = 0.0358 in.
W = 24.000 in.
K1 s / d = 13.296 in. / 8.000 in. = 1.662
D = 5839.78 in.
G' = 30.8 kip/in.
e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 14 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Uplift Calculation for Zone A - 2
Nominal Uplift Resistance: Reference:
Roof Deck Construction Handbook
= 10.00 ft
C = 2.00 ft
K = 3.00
Hilti 2014 PTG Supplement, Section
1.2.3 and 1.3.3
= 1680 lb
= 252 psf
Shear - Uplift Interaction Check:
SDI DDM, Third Edition, section 4.10 e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 15 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Zone A - 3
10 ftLength L:
120 plfDiaphragm Shear Q: 56 psfNet Uplift T:
20 ga (0.0358 in.)Deck Thickness:
Hilti X-HSN 24Frame Fastener:
Hilti #8 Drill ScrewSidelap Connector:
36 in.Sidelap Connector Spacing:
24/4Pattern:
318 plfDesign Shear: 126 psfDesign Uplift:
30.8 kip/in.Shear Stiffness G': 32.4 micro-in./lbFlexibility Factor F:
Design OK
Required Input Loads
Proposed Diaphragm System
Proposed System Diaphragm Shear and Stiffness/Flexibility
Design Checks
Design Shear e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 16 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 3
Frame Fastener Strength: Reference:
SDI DDM, Third Edition t = 0.0358 in.
= 1.795 kip = 1795 lb
Sidelap Connector Strength:
SDI DDM, Third Edition dt = 0.164 in.= 0.0358 in.
= 0.673 kip = 673 lb
Shear Strength Calculation:
= 0.375
SDI DDM, Third Edition (Eq. 2.2-2)
= 1.333
= 2
= 1.333
= 3 * 10.00 ft * 12 / 36.00 in. = 10.000 e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 17 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 3
Reference:
SDI DDM, Third Edition (Eq. 2.2-4)
A
D
= 1
= 3.000 in.
= 10.00 ft
= 3 * 10.00 ft * 12 / 36.00 in. = 10.000
W = 24.000 in.
= 0.5556
= 0.5556 l = 0.700
B = 8.195
= 454 plf
SDI DDM, Third Edition (Eq. 2.2-5) e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 18 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear Strength:
Reference:
= 454 plf
= 454 plf * 0.70 = 318 plf
Design Shear / Stiffness Calculation for Zone A - 3
Check for Buckling:
SDI DDM, Third Edition (Eq. 2.3-3)
I
= 10.00 ft t = 0.0358 in.
d / s = 8.000 in. / 13.296 in.
= 1830 plf * 0.80 = 1464 plf
Governing:
Frame Fastener Flexibility:
SDI DDM, Third Edition e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 19 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Shear / Stiffness Calculation for Zone A - 3
Sidelap Connector Flexibility: Reference:
SDI DDM, Third Edition t = 0.0358 in.
= 0.0159 in./kip
Shear Stiffness / Flexibility Factor Calculation:
SDI DDM, Third Edition (Eq. 3.3-3)
SDI DDM, Third Edition, Simplified Equation (Appendix IV)
E = 29500 ksi t = 0.0358 in.
W = 24.000 in.
K1 s / d = 13.296 in. / 8.000 in. = 1.662
D = 5839.78 in.
G' = 30.8 kip/in.
e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 20 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Design Uplift Calculation for Zone A - 3
Nominal Uplift Resistance: Reference:
Roof Deck Construction Handbook
= 10.00 ft
C = 2.00 ft
K = 3.00
Hilti 2014 PTG Supplement, Section
1.2.3 and 1.3.3
= 1680 lb
= 252 psf
Shear - Uplift Interaction Check:
SDI DDM, Third Edition, section 4.10 e-Mail:
Project Number:
Project Title: USFS Catalina_Canopy
Page: 21 / 21
Date: 8/7/2019
PROFIS DF Diaphragm 2.7.0
Contact:
www.hilti.us
Address:
Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application.