This is a Questions and Answers document (Amendment 0003) for a Request for Quotations solicitation issued by the USDA Forest Service for the Lucky Peak Nursery New Greenhouse project (Solicitation No. 1240LT26Q0137). The solicitation is administered by the USDA-FS CSA Intermountain region located in Ogden, Utah.
The document addresses 20 submitted questions regarding the design and construction of a new greenhouse facility at Boise National Forest's Lucky Peak Nursery. Key technical clarifications provided include: the new greenhouse measures 38,701 square feet and must meet or exceed 2024 IBC design loads with 102-mph wind speed requirements; a 6-inch reinforced concrete slab with #4 bars at 16 inches on center is required across the full width of the first 25 feet at main entrance bays to support 3.5-ton forklift loads; both gas-fired blower/heater systems and 48 LP-fired radiant-tube infrared heaters are required; all ceiling, roof, and shade curtains must be fire-retardant material per Specification 133413; carbon-monoxide detectors must be commercial-grade 120V hardwired units with 10-year sealed lithium battery backup and dry contacts wired to the Arcus control panel; the 3-inch irrigation service has been stubbed to the facility with line-size reductions to follow plan details; and compressed air should terminate at 44 inches above ground per Sheet P102. The contractor is responsible for providing design calculations for heating and ventilation systems subject to Contracting Officer approval. The quote due date was extended to October 2, 2026, at 4:00 PM MT, with a period of performance from October 15, 2026, through July 31, 2028.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(x)
1240LT26Q0137
x x
1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
40LT
OGDEN UT 84401-2310
324 25TH ST
USDA-FS CSA INTERMOUNTAIN 8
09/11/20260003
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.
Items 8 and 15, and returning
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended,
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
FACILITY CODE CODE
10B. DATED (SEE ITEM 13)
10A. MODIFICATION OF CONTRACT/ORDER NO.
9B. DATED (SEE ITEM 11)
9A. AMENDMENT OF SOLICITATION NO.
CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY
PAGE OF PAGES
4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)
1. CONTRACT ID CODE
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
08/06/2026
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.
ORDER NO. IN ITEM 10A.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Boise National Forest
Lucky Peak Nursery New Greenhouse
Amendment 0003
This amendment answers submitted questions. All posted amendments will become a part of any resulting award.
The quote due date is extended to 10/02/2026, at 4:00 PM MT.
Period of Performance: 10/15/2026 to 07/31/2028
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
LONNIE D. ROOT
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
Previous edition unusable
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
09/25/2026
X
Lucky Peak Nursery New Greenhouse - 1240LT26Q0137 Questions and Answers 003
Note: Questions were copied as they were received with some spelling errors corrected. Some questions mention “bid” “pre-bid” etc. That terminology was left in the questions, but this solicitation is a Request for Quotations under the Revolutionary FAR Part 12.
1. Greenhouse #2 Scope and Area
Section 000503 contains language describing repair of an existing wood-framed facility, while the drawings require construction of a new greenhouse. The contract identifies the new greenhouse as 38,701 SF, while Cravo’s four 42-foot by 228-foot houses total 38,304 SF.
Please confirm that Section 000503 is intended to govern construction of the new Greenhouse #2 and identify the controlling dimensions and contract area.
- Already answered in amendment 0001 (A76)
2. Cravo Structural Design Criteria
Sheet G1.03b identifies the 2024 IBC and a 102-mph wind speed. Cravo’s proposal is based on the 2018 IBC and a 90-mph wind speed.
Please confirm the required building code, wind speed, exposure, snow load, crop/equipment load, and other structural design criteria. Confirm that Cravo must revise its engineered design to comply with the contract requirements.
- Greenhouse must meet or exceed designs loads outlined in specifications
3. Greenhouse #2 Foundation Design
Cravo excludes foundation design, reinforcing, and stamped foundation drawings. The available Cravo installation drawing is marked “Not for Construction” and applies to Greenhouse #1.
Please provide the Greenhouse #2 foundation design or confirm the party responsible for its delegated design. Confirm the required pier diameter, depth, reinforcement, concrete strength, frost protection, stub embedment, and connection details.
- Already answered in amendment 0001 (A76)
4. Slab Reinforcement and Thickened Areas
Sheet A1.02b requires a typical 5-inch fiber-reinforced slab and a 6-inch reinforced slab with #4 bars at 24 inches on center each way within the first 25 feet of each greenhouse house.
Please confirm the limits of the 6-inch reinforced areas, reinforcing details, transitions to the typical slab, joint requirements, and whether additional reinforcing is required around greenhouse piers, trench drains, equipment, and door openings.
- 6” thickened slab across the full width of the first 25’ at the main entrance bays, where forklift traffic occurs. Use #4 bars @16” O.C. both ways per detail A7.01b, to support the 3.5 ton forklift load noted on Sheet A1.01a.
5. Personnel-Door Quantity
Sheet A1.02b shows three Type 105 personnel doors, matching the three insulated doors and frames included in Cravo’s proposal. Cravo drawing 2023-112-A04 appears to show five personnel-door locations.
Please confirm the final number and locations of personnel doors and associated exterior concrete pads.
- Already answered in amendment 0001 (A76)
6. Exterior Sliding-Door Dimensions
Sheet A2.02b identifies the exterior sliding doors as 12 feet wide by 11 feet high. Cravo’s proposal identifies 10-foot-high exterior sliding doors.
Please confirm the required clear opening dimensions and whether Cravo must revise its door assemblies.
- Already answered in amendment 0001 (A76)
7. Greenhouse #2 Heating Systems
Sheet M1.01b indicates that heating will include both gas-fired blower/heater systems and infrared radiant-tube heaters. The later heater markup identifies 48 LP-fired radiant-tube heaters but does not show the blower/heater systems or fabric distribution ducts.
Please confirm whether both heating systems are required. If the blower/heater system remains required, provide the required equipment count, capacity, fabric-duct quantity, routing, and installation elevation.
- Both systems are required as shown in the drawings and specifications.
8. Heating Design and Propane Requirements
Cravo’s proposal describes Greenhouse #2 as unheated, while the contract drawings require a complete heating system.
Please confirm the required indoor design temperature, outdoor design condition, heating-load criteria, equipment redundancy, total propane demand, available service pressure, regulator arrangement, connection point, and whether all heating equipment must be capable of simultaneous operation.
- Already answered in amendment 0001 (A58)
9. Greenhouse Gutter and Storm Drainage
Cravo excludes downspouts and piping required to convey water from the greenhouse gutters.
The drawings also require trench drains to connect to an existing storm-sewer line leading to a drainage pond, but the complete route and final connection point are not clearly identified.
Please provide the required downspout quantity, locations, sizes, routing, and connection details.
Also identify the trench-drain discharge route, pipe sizes, invert elevations, connection point, and referenced drainage pond or manhole.
- Already answered in amendment 0001 (A61, A62, A63)
10. Irrigation Service Requirements
Sheet A1.02b identifies a 3-inch irrigation service, while related details appear to indicate a smaller connection.
Please confirm the irrigation-service size, available flow and pressure, backflow requirements, final connection point, and required simultaneous demand for the four irrigation-boom systems.
- The 3-inch irrigation service has been stubbed to the facility, follow plans for any reductions in line sizes that may be required.
11. Cravo Motor and Control Schedule
The Cravo package includes greenhouse motors but excludes wiring, conduit, contactor panels, and environmental controls. Final motor quantities and electrical characteristics are not provided.
Please provide a coordinated motor schedule identifying every roof, shade, exterior roll-up, interior partition, sliding-curtain, and blackout motor. Include voltage, phase, amperage, horsepower, control grouping, limit switches, contactor requirements, and required interface with the Argus system.
- Already answered in amendment 0001 (A18)
12. Radiant-Heater Electrical Circuits
The heater markup identifies 48 radiant-tube heaters, while Panel H shows four minimum infrared-heating section circuits.
Please confirm whether the 48 heaters are powered individually, grouped by greenhouse section, or served through local control panels. Provide the final circuit count, connected load, conductor size, overcurrent protection, disconnect requirements, and control arrangement.
- Already answered in amendment 0001 (A18)
13. Grow-Lighting Scope
Sheets EG01, EG10, and EG20 require grow-light circuits, disconnects, and control coordination, but a complete grow-light fixture schedule and layout are not provided.
Please confirm whether grow-light fixtures are contractor-furnished. If required, provide the fixture manufacturer and model, quantity, layout, voltage, connected load, mounting requirements, control zoning, and interface with the greenhouse environmental-control system.
- Already answered in amendment 0001 (A18)
14. Electrical Service and Feeder Allocation
The electrical documents indicate shared infrastructure serving the Headhouse, Existing Greenhouse #1, and New Greenhouse #2, including the new service and greenhouse feeders.
Please confirm the complete limits of the 400A service work, feeder sizes and routing, Panel G and Panel H connections, and which equipment serves each building. Provide a coordinated one-line diagram showing all required service, feeder, disconnect, grounding, and metering work.
- Already answered in amendment 0001 (A18)
15. Communications Backbone
Sheet EG20 references an optical-fiber pair, while other project requirements indicate a larger multimode fiber backbone between the Existing Greenhouse, Headhouse, and New Greenhouse.
Please confirm the fiber type, strand count, conduit size, routing, termination locations, LIU requirements, data-cabinet requirements, Category 6 cabling, and responsibility for network switches, routers, and other active equipment.
- Already answered in amendment 0001 (A18)
16. Carbon-Monoxide Detection
Sheet A1.02b requires four carbon-monoxide detectors at locations selected by the COR but does not provide complete system requirements.
Please confirm whether the detectors are standalone, interconnected, connected to Argus, or connected to another alarm system. Provide the required listing, environmental rating, power source, notification method, alarm-interface requirements, and mounting criteria.
- Carbon-Monoxide Detectors shall be commercial-grade, 120V hardwired units with 10-year sealed lithium battery backup. Detectors shall feature local audible / visual alarms and include dry contacts wired back to the Arcus control panel for remote emergency notification.
17. Fire-Retardant Curtain Material
Cravo’s base cooling and heat-retention curtain material is not fire retardant. Fire-retardant material is offered as a separate option.
Please confirm whether fire-retardant material is required for the roof curtains, shade curtains, interior partition curtains, blackout curtains, or other greenhouse fabric systems.
- All ceiling, roof, and shade curtains must be fire-retardant material. See Spec 133413
18. Signed and Sealed Greenhouse Documents
Cravo includes stamped structural calculations but excludes stamped foundation drawings and stamped installation drawings.
Please confirm which structural calculations, foundation drawings, shop drawings, erection drawings, mechanical designs, electrical coordination drawings, and other delegated-design documents must be signed and sealed by Idaho-licensed design professionals.
- Already answered in amendment 0001 (A76)
19. I cannot find any specs on the Radiant Heat system for the two greenhouses. General note #1 on M1.01b says for the contractor to provide a design for heating and ventilation according to the specifications. There are no specifications for the radiant heat or the floor heat in the spec book. I do not know what these buildings would require for heating. And without specs or a supplier for the radiant heat and floor heat I am at a lost as to what and how much material to bid.
- Per General Note #1 on Sheet M1.01b, the Contractor shall provide a design for heating and ventilation of the existing greenhouse and new greenhouse. The systems shall be approved by the Contracting Officer per the specifications. The general notes and keyed notes on Sheet M1.101b, project specifications, and plans provide a basis for the Contractor’s design. The final quantity takeoffs and materials for the heating and ventilation system in the greenhouses is dependent upon the Contractor provided design.
20. On the PDF’s there is a discrepancy on the air system. On P102 the plumbing print shows 6 air drops terminating approximately at 44” above grade and 1 hose reel. On the architectural print A3.02a the architectural sheet shows 7 hose reels terminating at +/- 10’. Which of the two plans is correct.
- Sheet P102 is correct, the air should be at 44 inches above the ground.