043859.053_Umatilla_Golden_Gem_Utility_Improvements_01-30-25.pdf

PDF 7 MB Posted

Attached to
Golden Gem Utility Improvements
Solicitation number
ITB 25-PW-002
Issued by
Lake County, Florida

About this file

This file comprises construction plans and specifications for the City of Umatilla, Florida's N/S Golden Gem Utility Improvements project, prepared by Halff Associates, Inc., with engineering oversight by Brett J. Tobias, P.E. The project involves comprehensive utility infrastructure development located on North/South Golden Gem Drive, extending from Cayman Circle to East/West Golden Gem Drive in Umatilla, Florida (Section 14, Township 18S, Range 26E). The scope of work includes installation of new water lines consisting of 10" and 12" PVC and HDPE water mains, 6" PVC force mains, gate valves, plug valves, tees, and associated appurtenances; directional drilling of 760 linear feet of 12" HDPE water main with 36-inch minimum cover; wet tapping connections to existing 8" PVC and 12" DIP water mains; pavement reconstruction with 2" SP 9.5 asphalt over 8" limerock base and 12" stabilized subgrade; and general site restoration. The mandatory pre-bid conference was held on January 16, 2025, with sealed bids due February 13, 2025, at 2:00 p.m. City Council review is scheduled for March 4, 2025, with contract approval anticipated March 18, 2025, and Notice to Proceed targeted prior to March 31, 2025. Bidders must submit two physical copies and one digital copy of their proposals to DPS Apopka.

The construction documents establish stringent technical requirements including compliance with AWWA standards (C-900, C-905, C-651, C-600, and C-605/M23), NSF certification for all potable water piping, minimum 36-inch cover depth from finish grade, and adherence to Florida Administrative Code utility separation standards. Contractors must perform 2-week advance verification of existing utilities and report conflicts or discrepancies to the Engineer of Record no less than one week prior to work commencement in affected areas. All water mains require hydrostatic pressure testing, disinfection per AWWA C651, and bacteriological clearance for service. The project budget is approximately $900,000 in grant funding, though the final contract amount will be determined through competitive bidding. Contractors must provide a 110% Payment & Performance Bond and comply with General Wage Decision GWD FL20250119 HEAVY 01.03.25 for applicable labor rates. The City reserves the right to waive informalities, reject any or all bids, and select the bid most favorable to its interests. Bid documents are available from DPS Apopka for a non-refundable fee, and all subcontractors must be comprehensively listed on the Section 00301-A form.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER/DEVELOPER:

ENGINEER/SURVEYOR:

902 N. SINCLAIR AVENUE

TAVARES, FL 32778

HALFF ASSOCIATES, INC.

(352) 557-9225

BRETT J. TOBIAS, P.E.

BTOBIAS@HALFF.COM

AMERCER@UMATILLAFL.ORG

CITY OF UMATILLA

1 SOUTH CENTRAL AVE

PHONE: (352) 669-1539

AARON MERCER, DEVELOPMENT & PUBLIC SERVICES DIRECTOR

UMATILLA, FL 32784

FOR

CONSTRUCTION PLANS

N/S GOLDEN GEM UTILITY IMPROVEMENTS

SECTION 14 TOWNSHIP 18S RANGE 26E

SITE

VICINITY MAP

1" = 500'

JA

N

U A

R Y

0, 5, B

ID

S

E T

A D

D E

N D

U M

0 1 2 3 4 5

(INCHES)

ORIGINAL DOCUMENT SIZE 24"x36"

1/

/2

4:

P

M A

H

S

EW

N

INDEX OF SHEETS

C-410 C-400

C-200 C-100

C-300

UTILITY MASTER PLAN

COVER SHEET

DEMO & UTILITY PLAN

GENERAL DETAILS

WATER & SEWER UTILITY DETAILS

PREPARED BY:

902 NORTH SINCLAIR AVE.

TAVARES, FLORIDA 32778

TEL (352) 343-8481 FAX (352) 343-8495

www.halff.com

CERTIFICATE OF AUTHORIZATION NUMBER: 33380

REVISIONDATE

MAYOR

CITY MANAGER

SCOTT BLANKENSHIP

CITY ATTORNEY

KEVIN STONE

VICE MAYOR

COUNCIL MEMBER

SEAT 2

JOHN NICHOLS

CHRIS CREECH

KATHERINE "KAYE" ADAMS

SEAT 4

SEAT 5

COUNCIL MEMBER

CITY COUNCIL

SEAT 1

FRED FETTEROLF

JOHN NICHOLS

SEAT 3

DEVELOPMENT & PUBLIC

AARON MERCER

SERVICES DIRECTOR

01-24-25 ADDENDUM #1

01-30-25 ADDENDUM #2

OHU

O H

U

OHU OHU OHU OHU

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

WM WM

WM WM WM WM WM WM WM WM WM WM WM WM

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

WM

G G

B T

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

B T

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

FO

C

C

TV

C

TV

C

TV

C

TV

C

TV

C

TV

C

TV

C

TV

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U

OHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHU

STUBOUT 2"

STUBOUT 4" PVC

FM

FM

FM

FM

FM

UNK

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K

SD

S D

OHU

OHU

OHU OHU OHU OHU OHU OHU OHU OHU OHU OHU

S00°35'47"W 664.79' S00°35'47"W 664.79'

332.40'

0.

S

°5 4'

"W

9.

O H

U O

H U

O H

U O

H U

O H

U O

H U

O H

U

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

OHE OHE OHE

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE

OHE

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

OHE

OHE

OHE

O H

E O

H E

O H

E O

H E

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE

OHE

OHE

OHE

OHE

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E

OHE

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E

O H

E O

H E

OHE

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

SD

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E O

H E

O H

E

OHE

BT BT BT BT BT BT BT BT BT BT BT BT

BT BT BT BT BT BT BT BT BT BT BT BT BT BT

BT B

T

W M

W M

W M

WM WM WM WM WM WM WM

SD

S D

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

W M

W M

FM

FM

FM

FM

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

WM

WM

WM

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

WM

W M

W M

S00°33'10"E 997.17'

S00°35'47"W 332.40'

S

°5

'5

"W

.8

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM FM FM FM FM FM FM FM FM FM FM FM

FM

FM

FM

W M

WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

W M

WM WM WM WM WM WM

VIEWPORT 3

SHEET C-300

VIEWPORTS 1 & 2

SHEET C-300

W M

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

SCALE IN FEET

Scale: 1"=

80' 80 80 160

1/

/2

4:

P

M A

H

10" DIP

WATER MAIN

10" PVC

WATER MAIN

1 2 3 4 5 6 7 8

043859.053

DKB

TNJ

DKB

MARCH 2023

R E

V

IS

IO

N

D A

T E

JOB NO.:

CHECKED BY.:

DRAWN BY:

DATE:

DESIGNED BY:

FILE NAME:

-2

4-

W M

D

IP

U M

AT

IL

LA

, F

LO

RI

D A

N /S

G O

LD

EN

G

EM

U

TI

LI

TY

IM

PR

O

VE

M

EN

TS

U

TI

LI

TY

M

AS

TE

R

PL

AN

Sheet C-200

BASE

N O

R

TH

S

IN

C

LA

IR

A

VE

TA

VA

R

ES

, F

LO

R

ID

A

TE

L.

(3

) 3

-8

C E

R

TI

FI

C

A

TE

O F

A U

TH

O

R

IZ

A

TI

O N

N U

M B

E R

: 3

BRETT J. TOBIAS, PE

Registered Eng 69017

6" PVC

FORCE MAIN

10" PVC

WATER MAIN

6" PVC

FORCE MAIN

APPARENT ERRORS, DISCREPANCIES, OR OMISSIONS SHALL BE BROUGHT TO

THE ENGINEER OF RECORD'S ATTENTION WITHIN A REASONABLE TIME

FRAME, LESS THAN 48 HOURS AFTER DISCOVERED. ADVANTAGE WILL NOT BE

TAKEN OF APPARENT ERROR OR OMISSION IN THE DRAWINGS OR

SPECIFICATIONS, AND THE ENGINEER SHALL BE PERMITTED TO MAKE

CORRECTIONS AND INTERPRETATIONS AS MAY BE DEEMED NECESSARY FOR

FULFILLMENT OF THE INTENT OF THE DESIGN.

CONTRACTOR SHALL PROVIDE AND PERFORM A 2 WEEK LOOK AHEAD INTO

THE UTILITY WORK TO BE PERFORMED. THIS SHALL INCLUDE THE

VERIFICATION OF EXISTING UTILITIES, BOTH HORIZONTAL AND VERTICAL

POSITIONING, MATCHES WHAT IS SHOWN IN THE CONTRACT DOCUMENTS

AND ANY NEW UTILITIES THAT ARE DISCOVERED DURING THIS LOOK AHEAD.

INFORMATION OF CONFLICTS OR DISCREPANCIES WITH THE CONTRACT

DOCUMENTS SHALL BE PROVIDED TO THE ENGINEER OF RECORD NO LESS

THAN 1 WEEK PRIOR TO COMMENCEMENT OF WORK WITHIN SAID CONFLICT

AREA. ENGINEER OF RECORD SHALL BE ALLOWED AMPLE TIME TO ADDRESS

CONFLICTS/ISSUES AND PROVIDE ADJUSTMENTS TO THE DESIGN TO

ADDRESS CONCERNS WITHOUT CONTRACTOR REQUESTING TIME DELAYS.

12" HDPE

WATER MAIN

10" DIP

WATER MAIN

O H

U

OHU OHU OHU OHU OHU OHU OHU

O H

U

O H

U O

H U

O H

U O

H U

O H

U

WM

WM WM WM

W M

WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

W M

W M

W M

W M

W M

WM WM

G G G

G G

B T

B T

B T

FMFM

FM

FM

FM

FM

W M

W M

W M

W M

W M

W M

BE

B

T

B T

B T

B T

B T

FO

C

FO

C

FO

C

FO

C

FOC

FO

C

FO

C

CTV

C

TV

C

TV

STUBOUT 2"

FM

FM

FM

FM

FM

FM

FM

FM

UNK

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K

S D

S D

OHU

OHU

OHU

OHU OHU OHU OHU OHU OHU OHU OHU OHU OHU OHU

O H

U

S D

S D

S D

S D

OHE OHE OHE OHE OHE

O H

E O

H E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE OHE

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

OHE

OHE

OHE

OHE

OHE

O H

E O

H E

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

O H

E

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

O H

E O

H E

O H

E O

H E

S D

S D

S D

S D

S D

SD

S D

S D

S D

S D

S D

S D

S D

S D

SDO

H

E O

H E

O H

E O

H E

BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT

BT

BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT

BT BT

B T

WM WM WM WM WM WM WM WM WM WM WM WM WM WM

S D

FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM FM FM FM FM FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM

FM FM

FM

FM

FM

FM

FM

W M

W M

W M

WM

WM

W M

W M

W M

WM

W M

W M

EXIST. CITY OF UMATILLA 6" FORCE MAIN

EXIST. CITY OF UMATILLA

6" WATER MAIN

EXIST. CITY OF UMATILLA

6" FORCE MAIN

EXIST. CITY OF

UMATILLA 2"

WATER MAIN

EXIST. CITY OF

UMATILLA 2" WATER MAIN

EXIST. CITY OF

UMATILLA 2"

WATER MAIN

EXIST. CITY

OF UMATILLA

6" FORCE MAIN

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM

FM

FM

FM

FM

W M 23

W M

W M

W M

WM WM WM WM WM WM WM WM WM

FUTURE 10" FM PER CENTRAL

AVENUE PROJECT BY HALFF

EXIST. CITY OF UMATILLA

6" WATER MAIN INTO

MOBILE HOME PARK

EXIST.

FIRE

HYDRANT

EXIST.

WATER

SERVICE

EXIST.

WATER

SERVICE

.0

0' E

XI

S

T.

R

O W

EXIST. CITY OF UMATILLA 12" WATER MAIN

X X

X X

FUTURE 10" DIP WATER MAIN PER

LAKE FERNS ROAD INDUSTRIAL

PARK PROJECT BY HALFF

OPEN CUT, REMOVE,

& REPLACE PAVEMENT

MATCH EXIST. GRADE

SEE TYPICAL PAVING

DETAIL THIS SHEET

M A

TC

H

LI

N E

OHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHUOHU

OHU OHU OHU OHU OHU

BTBTBT

BTBTBTBT

W M

W M

W M

W M

FM

W M

W M WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

FM FM FM FM FM FM FM FM FM FM FM FM FM

EXIST. CITY OF

UMATILLA

8" WATER MAIN

M A

TC

H

LI

N E

M A

TC

H

LI

N E

INSTALL 6" PVC

FORCE MAIN

INSTALL 6"

PLUG VALVE

INSTALL 6"

PLUG VALVE

INSTALL 6" FLUSHING PORT

SEE DETAIL SHEET C-410

INSTALL 6" PLUG

INSTALL 10" PVC

WATER MAIN

INSTALL (2) 10"

45° BENDS

WET TAP EXIST. 8" PVC WATER MAIN

W/ 8" TAPPING SLEEVE & VALVE

INSTALL 8"x10" REDUCER

INSTALL TEMP. JUMPER CONNECTION

OPEN CUT & REPAIR EXIST.

CONCRETE DRIVEWAY.

CONTRACTOR TO COORDINATE

W/ HOME OWNER

FOR DRIVEWAY ACCESS

OHU

OHU

O H

U

OHU OHU OHU OHU OHU OHU OHU

O H

U

O H

U O

H U

O H

U O

H U

O H

U

WM

WM WM WM

W M

WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

W M

W M

W M

W M

W M

WM WM

G G G

G G

B T

B T

B T

FMFM

FM

FM

FM

FM

W M

W M

W M

W M

W M

W M

BE

B

T

B T

B T

B T

B T

FO

C

FO

C

FO

C

FO

C

FOC

FO

C

FO

C

CTV

C

TV

C

TV

STUBOUT 2"

FM

FM

FM

FM

FM

FM

FM

FM

UNK

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K U

N K

U N

K

S D

S D

OHU

OHU

OHU

OHU OHU OHU OHU OHU OHU OHU OHU OHU OHU OHU

O H

U

S D

S D

S D

S D

OHE OHE OHE OHE OHE

O H

E O

H E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE OHE

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

O H

E

OHE

OHE

OHE

OHE

OHE

O H

E O

H E

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

O H

E

O H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

O H

E O

H E

O H

E O

H E

S D

S D

S D

S D

S D

SD

S D

S D

S D

S D

S D

S D

S D

S D

SDO

H

E O

H E

O H

E O

H E

BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT

BT

BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT BT

BT BT

B T

WM WM WM WM WM WM WM WM WM WM WM WM WM WM

S D

FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM FM FM FM FM FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM

FM FM

FM

FM

FM

FM

FM

W M

W M

W M

WM

WM

W M

W M

W M

WM

W M

W M

EXIST. CITY OF UMATILLA 6" FORCE MAIN

EXIST. CITY OF UMATILLA

6" WATER MAIN

EXIST. CITY OF UMATILLA

6" FORCE MAIN

EXIST. CITY OF

UMATILLA 2"

WATER MAIN

EXIST. CITY OF

UMATILLA 2" WATER MAIN

EXIST. CITY OF

UMATILLA 2"

WATER MAIN

EXIST. CITY

OF UMATILLA

6" FORCE MAIN

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FM

FM

FM

FM

FM

W M 23

WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM WM

W M

W M

W M

WM WM WM WM WM WM WM WM WM

FUTURE 10" FM PER CENTRAL

AVENUE PROJECT BY HALFF

EXIST. CITY OF UMATILLA

6" WATER MAIN INTO

MOBILE HOME PARK

EXIST.

FIRE

HYDRANT

EXIST.

WATER

SERVICE

EXIST.

WATER

SERVICE

.0

0' E

XI

S

T.

R

O W

EXIST. CITY OF UMATILLA 12" WATER MAIN

W M

X X

X X

FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM

FUTURE 10" DIP WATER MAIN PER

LAKE FERNS ROAD INDUSTRIAL

PARK PROJECT BY HALFF

M A

TC

H

LI

N E

DIRECTIONAL DRILL 760 LF

OF 12" HDPE WATER MAIN

36" MIN. COVER

INSTALL 6" PVC

FORCE MAIN INSTALL

10"x10" TEE

INSTALL 10"

GATE VALVE &

(2) 10" 45° BENDS

WET TAP TO CONNECT TO EXIST. 12" DIP

WATER MAIN W/ 12"x10" TAPPING

SLEEVE & 10" GATE VALVE

INSTALL 10"

GATE VALVE

INSTALL 10" DIP WATER MAIN

INSTALL

10" GATE

VALVE

REMOVE 90° BEND

INSTALL 6" TEE & 6" PLUG VALVE

CONTRACTOR TO COORDINATE W/ CITY

ON REDIRECTING FLOWS TEMPORARILY

WHILE TEE IS INSTALLED

CONNECT TO 10" DIP WATER MAIN

FOR CONTINUATION SEE LAKE FERNS ROAD

INDUSTRIAL PARK CONSTRUCTION PLANS BY HALFF

INSTALL TEMP. JUMPER CONNECTION

PROP. TRANSITION

FROM 12" HDPE TO 10" DIP

PROP. TRANSITION

FROM 10" DIP TO 12" HDPE

PROP. NEW PAVEMENT

SEE TYPICAL PAVING

DETAIL THIS SHEET

INSTALL 24" WHITE STOP BAR

PROP. TRANSITION

FROM 10" PVC TO 10" DIP

INSTALL 10" PVC

WATER MAIN

INSTALL 10" DIP

WATER MAIN

INSTALL

12"x4" TEE

INSTALL

4" GATE VALVE

& 4" PLUG

INSTALL 4" DIP

WATER MAIN

1/

/2

4:

P

M A

H

SCALE IN FEET

Scale: 1"=

50' 50 50 100

EXISTING GOLDEN GEM DRIVE DEMO PLAN

LEGEND

DRAINAGE / UTILITY EASEMENT

FORCE MAIN

PLUG

SINGLE WATER SERVICE

WATER MAIN

GATE VALVE / PLUG VALVE

TEE

ELBOW

DOUBLE WATER SERVICE

FM FM FM

WM WM WM

EXIST. WETLAND LINE

PROPOSED WETLAND BUFFER

OHU OHU OHU

FOC FOC FOC

CTV CTV CTV

BT BT BT

WM WM WM

FM FM FM

X X X X

RW RW RW

UNK UNK UNK

OHE OHE OHE

BE BE BE

G G G

TYPE 'F' INLET (PER FDOT STANDARD

PLANS INDEX 425-052)

MITERED END SECTION (PER FDOT

STANDARD PLANS INDEX 430-021)

STORM PIPE

STORM MANHOLE (SYMBOL NOT TO

SCALE WITH STRUCTURE SIZE)

EXIST. FORCE MAIN

EXIST. BURIED TELEPHONE LINE

EXIST. WATER MAIN

EXIST. BURIED CABLE TELEVISION LINE

EXIST. FENCE

EXIST. POWER POLE

EXIST. GUY

EXIST. GATE VALVE

EXIST. STORM PIPE

EXIST. BURIED FIBER OPTIC CABLE LINE

EXIST. CONTOUR

EXIST. OVERHEAD UTILITY

EXIST. OVERHEAD ELECTRIC

EXIST. BURIED ELECTRIC

EXIST. REUSE WATER MAIN

EXIST. BURIED GAS LINE

EXIST. UNKNOWN

SD SD SD

REDUCER

EXIST. BENCHMARK

EXIST. GAS UTILITY MARKER

EXIST. CONCRETE MONUMENT

EXIST. WATER METER

EXIST. TELEPHONE VAULT

EXIST. ELECTRIC BOX

EXIST. TELEPHONE PEDESTAL

EXIST. IRON ROD

EXIST. SPRINKLER SPIGOT

EXIST. FIBER OPTIC VAULT

EXIST. BOLLARD

EXIST. AIR RELEASE VALVE

EXIST. REUSE WATER VALVE

EXIST. SEWER VALVE

EXIST. NAIL & DISK

EXIST. WELL

EXIST. SIGN

EXIST. CABLE TV RISER

AIR RELEASE VALVE

MATCHLINE

1 2 3 4 5 6 7 8

043859.053

DKB

TNJ

DKB

MARCH 2023

R E

V

IS

IO

N

D A

T E

JOB NO.:

CHECKED BY.:

DRAWN BY:

DATE:

DESIGNED BY:

FILE NAME:

-2

4-

W M

D

IP

, M O

V E

T E

M P

. J U

M P

E R

C O

N N

E C

TI

O

N U

M

AT

IL

LA

, F

LO

RI

D

A

D

EM

O

U

TI

LI

TY

P

LA

N

Sheet C-300

BASE

N O

R

TH

S

IN

C

LA

IR

A

VE

TA

VA

R

ES

, F

LO

R

ID

A

TE

L.

(3

) 3

-8

C E

R

TI

FI

C

A

TE

O F

A U

TH

O

R

IZ

A

TI

O N

N U

M B

E R

: 3

BRETT J. TOBIAS, PE

Registered Eng 69017

CROSS

WYE

SCALE IN FEET

Scale: 1"=

50' 50 50 100

EXISTING GOLDEN GEM DRIVE UTILITY PLAN

SCALE IN FEET

Scale: 1"=

50' 50 50 100

EXISTING GOLDEN GEM DRIVE UTILITY PLAN

TYPICAL PAVING DETAIL

NOT TO SCALE

2" SP 9.5

ASPHALT

12" STABILIZED SUBGRADE

COMPACTED TO 98% MAX.

DENSITY A.A.S.H.T.O.

T-180, L.B.R.- 40

8" LIMEROCK BASE, PRIMED

(2 LIFTS) 98% MAX. DENSITY,

A.A.S.H.T.O. T-180, L.B.R.- 100

N /S

G O

LD

EN

G

EM

U

TI

LI

TY

IM

PR

O

VE

M

EN

TS

-3

0-

A D

D W

M W

/ T E

E , G

A

TE

V A

LV

E

P

LU

G

1/

/2

4:

P

M A

H

General Water Notes

62-555.314 Location of Public Water System Mains:

For the purpose of this section, the phrase "Water Mains" shall mean Mains, including treatment Plant process piping, conveying either raw, partially treated, or finished drinking water; Fire Hydrant leads; and service lines that are under the control of a Public Water System and that have an inside diameter of three (3") inches or greater.

(1) Horizontal Separation Between Underground Water Mains and Sanitary or Storm Sewers, Wastewater or Storm water Force Mains, Reclaimed Water Pipelines, and On-site Sewage Treatment and Disposal Systems:

(a) New or relocated, underground WATER MAINS shall be laid to provide a horizontal distance of at least (3) Three Feet between the outside of the WATER MAIN and the outside of any existing or proposed Storm Sewer, Storm water Force Main, or pipeline conveying reclaimed water regulated under Part III of Chapter 62-610, F.A.C.

(b) New or relocated, underground WATER MAINS shall be laid to provide a horizontal distance of at least (3) three feet, and preferably (10) Ten Feet, between the outside of the WATER MAIN and the outside of any existing or proposed vacuum-type Sanitary Sewer.

(c) New or relocated, underground WATER MAINS shall be laid to provide a horizontal distance of at least (6) Six Feet, and preferably (10) Ten Feet, between the outside of the WATER MAIN and the outside of any existing or proposed Gravity- or Pressure-type Sanitary Sewer, Wastewater Force Main, or pipeline conveying reclaimed water not regulated under Part III of Chapter 62-610 F.A.C.

The Minimum Horizontal Separation distance between WATER MAINS and Gravity-type Sanitary Sewers shall be reduced to (3) Three Feet where the BOTTOM of the WATER MAIN is laid at least (6) Six Inches above the Top of the Sewer.

(d) New or relocated, underground WATER MAINS shall be laid to provide a horizontal distance of at least (10) Ten Feet between the outside of the WATER MAIN and all parts of any existing or proposed "On site Sewage Treatment and Disposal System" as defined in Section 381.0065(2). F.S. and Rule 64E-6.002. F.A.C.

(2) Vertical Separation Between Underground WATER MAINS and Sanitary or Storm Sewers, Wastewater or Storm water Force Mains, and Reclaimed Water Pipelines:

(a) New or relocated underground WATER MAINS crossing any existing or proposed gravity- or vacuum-type sanitary sewer or storm sewer shall be laid so the outside of the WATER MAIN is at least (6) Six inches, and preferably 12 inches below the outside of the other pipeline. However, it is preferable to lay the WATER MAIN "ABOVE" the other pipeline.

(b) New or relocated, Underground WATER MAINS crossing any existing or proposed pressure-type sanitary sewer, wastewater or stormwater Force Main, or Pipeline conveying reclaimed water shall be laid so the outside of the WATER MAIN is at least (12) inches ABOVE or BELOW the Outside of the other pipeline. However, it is preferable to lay the WATER MAIN above the other pipeline.

(c) At the Utility crossings described in paragraphs (a) & (b) Above, one full length of Water Main Pipe shall be centered above or below the other pipeline so the WATER MAIN Joints will be as far as possible from the other pipeline. Alternatively, at such crossings, the pipes shall be arranged so that all WATER MAIN Joints are at least (3) Three feet from all joints in Vacuum-type Sanitary Sewers, Storm Sewers, Stormwater Force Mains, or pipelines conveying reclaimed water regulated under Part III of Chapter 62-610, F.A.C., and at least (6) Six Feet from all Joints in Gravity- or Pressure-type Sanitary Sewers, Wastewater force mains, or pipelines conveying reclaimed water not regulated under Part III of Chapter 62-610, F.A.C.

(3) Separation Between WATER MAINS and Sanitary or Storm Sewer Manholes:

(a) No WATER MAIN shall pass thru, or come into contact with any part of a Sanitary Manhole or a Storm Sewer Manhole.

(4) Separation Between Fire Hydrant Drains and Sanitary or Storm Sewers, Wastewater or Stormwater Force Mains, reclaimed Water Pipelines, and On-Site Sewage Treatment and Disposal Systems. New or relocated Fire Hydrants with underground Drains shall be located so that the drains are at least (3) Three Feet from any existing or proposed storm sewer, Stormwater force main, or pipeline conveying reclaimed water regulated under Part III of Chapter 62-610, F.A.C.; at least (3) Three Feet, and preferably (10) Ten Feet, from any existing or proposed gravity- or Pressure-type Sanitary Sewer, Wastewater force main, or pipeline conveying reclaimed water not regulated under Part III of Chapter 62-610, F.A.C.; and at least (10) Ten Feet from any existing or proposed "on-site sewage treatment and disposal system" as defined in Section 381.0065(2), F.S. and Rule 64E-6.002, F.A.C.

(5) Exceptions/Mitigation:

Adherence to the above Constraints and Separations in Items 1 through 4 shall be Complied to, "WITHOUT EXCEPTION". If for some reason where it is not technically feasible or Economically Sensible that Items 1 through 4 cannot be complied with, Contractor will Stop Work and Notify the Engineer of record for the appropriate solution, which will be submitted to "The Department of Environmental Protection" for APPROVAL, prior to work commencement.

3.00'

MINIMUM

" M

IN

. C

O

VE

R

FINISH GRADE

PROPOSED

WATER MAIN

Storm Sewer Storm Sewer Force Main Reclaimed Water Main

DETAIL OF ITEM 1.(a) DETAIL OF ITEM 1.(b)

Vacuum-Type Sanitary Sewer

WATER MAIN

PROPOSED

FINISH GRADE

" M

IN

. C

O

VE

R

Preferably 10.00' 3.00' 6.00'

Preferably 10.00'

" M

IN

. C

O

VE

R

FINISH GRADE

PROPOSED

WATER MAIN

Sanitary Force Main

DETAIL OF ITEM 1.(c)

Sanitary Gravity Main

Wastewater Force Main Unregulated Reclaimed Water

DETAIL OF ITEM 2.(a)

Vacuum-Type Sanitary Sewer Sanitary Gravity Main

Storm Sewer

Preferably 12" 6" Minimum

6" Minimum Preferably 12"

Water Main to be Located above Where ever Possible

Water Main

DETAIL OF ITEM 2.(b)

Water Main

Water Main to be Located above Where ever Possible

12" Minimum

Storm Water Force Main

Pressure-Type Sanitary Sewer Wastewater Force Main

12" Minimum

Reclaimed Water Main Unregulated Reclaimed Water Mains

Wastewater Force Main Sanitary Gravity Main

Pressure-Type Sanitary Sewer

Water Main to be Centered @ crossing if possible

Water Main

DETAIL OF ITEM 2.(c)

3.00'

Pipe Joint typical

MINIMUM

Vacuum-Type Sanitary Sewer Storm Sewer Main Stormwater Force Main Regulated Reclaimed Water Mains

6.00'

MINIMUM

Ve rti ca l

H or iz on ta l

U

TI

LI

TY

S E

P A

R A

TI

O

N S

Utility Construction Notes (DEP)

1. WATER SYSTEM COMPONENTS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH ALL LOCAL

CODES AND REGULATIONS, CLEANED, DISINFECTED AND BACTERIOLOGICALLY CLEARED FOR

SERVICE IN ACCORDANCE WITH THE LATEST AWWA STANDARDS AND CHAPTER 62-555 FLORIDA

ADMINISTRATIVE CODE.

2. ALL PIPING SHALL BEAR THE "NSF" SEAL FOR POTABLE WATER.

3. WATER MAINS SHALL BE PVC CONFORMING TO AWWA C-900, DR 18 FOR PIPE SIZES 4"-12". PIPES 14"

OR LARGER SHALL BE AWWA C-905, DR 18. ALL COUPLINGS, CLEANING COMPOUNDS, SOLVENTS, LUBRICANTS, AND PIPE PREPARATION, FOR LAYING, SHALL BE IN ACCORDANCE WITH THE PIPE

MANUFACTURERS LATEST RECOMMENDATIONS.

4. DEPTH OF WATER LINES TO BE 36" MINIMUM COVER FROM FINISH GRADE.

5. WATER MAINS TO BE LOCATED 6.00' FROM BACK OF CURB OR EDGE OF PAVEMENT UNLESS

OTHERWISE NOTED.

6. ALL SLEEVES UNDER PAVEMENT SHALL EXTEND 5' BEYOND THE BACK OF CURB.

7. DISINFECTING: FOLLOWING THE PRESSURE TESTING, THE CONTRACTOR SHALL DISINFECT ALL

SECTIONS OF THE WATER DISTRIBUTION SYSTEM. DISINFECTION SHALL BE IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF AWWA STANDARD C651 "DISINFECTING WATER MAINS", AND ALL

APPROPRIATE AGENCY APPROVAL.

8. ALL HYDROSTATIC TEST SHALL BE IN ACCORDANCE WITH AWWA C600 FOR DUCTILE IRON PIPE AND

C605/M23 FOR PVC PIPE.

9. ALL WATER MAINS SHALL BE INSTALLED, PRESSURE AND LEAK TESTED IN ACCORDANCE WITH AWWA C600, (62-555.320(21)(b)1 AND 62-555.330, F.A.C. ALL INSTALLATION, TESTING AND FIELD

PROCEDURES MUST BE PROVIDED AND MUST CONFORM TO THE APPLICABLE AWWA STANDARDS.

10. ALL PIPING MATERIALS AND SPECIFICATIONS COVERING PIPES, JOINTS AND PACKING MATERIALS, INTERNAL COATING AND LININGS, FITTINGS, SPECIALS AND APPURTENANCES SHALL ALL BE IN

ACCORDANCE WITH THE CORRESPONDING AWWA STANDARDS AND BE CONFORMING TO NSF

REQUIREMENTS, AS MAY BE APPLICABLE, WITH EXCEPTIONS ALLOWED ONLY IF DOCUMENTATION AND ASSURANCES ARE PROVIDED IN COMPLIANCE WITH PARAGRAPHS 62-555.320(3) (d) 62-555.320

(3) (b), AND 62-555.320 (21) (c), F.A.C. THE LEAD USE PROHIBITION IN RULE 62-555.322, F.A.C. SHALL ALSO APPLY. POLYETHYLENE TUBING SHALL BE PER AWWA C901. UNDERGROUND SERVICE LINES, AND VALVES SHALL BE PER AWWA C800.

COLOR CODING

All water main pipe, including fittings, installed on or after August 28, 2003, except pipe installed under a construction permit for which the Department received a complete application before August 28, 2003, shall be color coded or marked using blue as a predominate color to differentiate drinking water from reclaimed or other water. Underground plastic pipe shall be solid-wall blue pipe, shall have a co-extruded blue external skin, or shall be white or black pipe with blue stripes incorporated into, or applied to, the pipe wall; and underground metal or concrete pipe shall have blue stripes applied to the pipe wall. Pipe striped during manufacturing of the pipe shall have continuous stripes that run parallel to the axis of the pipe, that are located at no greater than 90° intervals around the pipe, and will remain intact during and after installation of the pipe. If tape or paint is used to stripe pipe during installation of the pipe, the tape or paint shall be applied in a continuous line that runs parallel to the axis of the pipe and that is located along the top of the pipe; for pipes with an internal diameter of 24 inches or greater, tape or paint shall be applied in continuous lines along each side of the pipe as well as along the top of the pipe. Aboveground pipe as drinking water treatment plants shall be color coded and labeled in accordance with subsection 62-555.320(10),F.A.C., and all other aboveground pipe shall be painted blue or shall be color coded or marked like underground pipe.

1 2 3 4 5 6 7 8

043859.053

DKB

TNJ

DKB

MARCH 2023

R E

V

IS

IO

N

D A

T E

JOB NO.:

CHECKED BY.:

DRAWN BY:

DATE:

DESIGNED BY:

FILE NAME:

U M

AT

IL

LA

, F

LO

RI

D A

G

EN

ER

AL

D

ET

AI

LS

Sheet C-400

BASE

N O

R

TH

S

IN

C

LA

IR

A

VE

TA

VA

R

ES

, F

LO

R

ID

A

TE

L.

(3

) 3

-8

C E

R

TI

FI

C

A

TE

O F

A U

TH

O

R

IZ

A

TI

O N

N U

M B

E R

: 3

METER BOX COMPANY, INC.

21'33'18"x16"

21'

39'

33'

62'

103'

132'

113' 20"x20"

20"x18"163'

207'

178'

83'

92'

110'

6'

7'

6'

7'

9'

7'

173'

145'

131'11'14'

12'

14'

23'

25'

29'

15'

17'

29'

31'

36'

56'

70'

61'

75'

86'

70, (NO JOINTS ALLOWED)

8' MIN.

L

RUN

8' MIN.

(NO JOINTS ALLOWED)

RESTRAINTS REQ.

B R

A N

C H

@ ALL SIDES (TYP.)

L

L

L

L

45° BEND

11.25° BEND

TEE

21'

DUCTILE

IRON (L)

22'

40'

21'

22'

33'

P.V.C. (L)

REDUCER

6"x4"

PIPE SIZES

34'

63'

33'

12"x10"

16"x12"

10"x8"

8"x6" 34'

45'

DEAD END &

PLUG

10'

DUCTILE

IRON (L) P.V.C. (L)

98'

116'

148'

82'

43'

74'

54'

33'

21' 63'

P.V.C. (L)

15'2'

BEND

11 1/4"

DUCTILE

IRON (L)

68'

84'

116'

52'

3'

4'

5'

3'

2' 33'

TEES

29'

DUCTILE

IRON (L)

52'

63'

74'

94'

40'

ONLY

RESTRAINT REQ.

ON LARGER MAIN

L

LARGER MAIN

L

SMALLER MAIN

DEAD END/PLUG

REDUCER

L

L

L

L

22.5° BEND

90° BEND

3'4'

P.V.C. (L)

BEND

DUCTILE

IRON (L)

22 1/2°

7'

10'

8'

6'

9'

13'

10'

7'

6' 4'

DUCTILE

IRON (L)

7'

45°

BEND

8'

P.V.C. (L)

14'

21'

17'

12'

18'

26'

21'

15'

12' 9'

20'

BEND

90°

SIZE

(inches)

PIPE

P.V.C. (L)

43'

63'

50'

36'

28'

IRON (L)

DUCTILE

34'

29'

40'

22'

51'

16'

ENGINEER.

P.V.C. (L)

TABLE OF THRUST RESTRAINT LENGTHS

THRUST RESTRAINT DESIGN NOTES

1. RESTRAINT JOINTS, FITTINGS, & VALVE REQUIREMENTS CALCULATED BY THE

THRUST RESTRAINT DESIGN PROGRAM PROVIDED BY UNI-FLANGE, THE FORD

2. DATA BASED ON MAX. PRESSURE OF 150 p.s.i., THE UNIFIED

SOILS CLASSIFICATION SYSTEM (SOIL TYPE SP), THE PIPE BEDDED IN

NATIVE SOIL w/ A MINIMUM OF 2.5' COMPACTED FILL OVER THE PIPE, AND USING A SAFETY FACTOR OF 1.5 FOR THE DATA.

3. ALL FITTINGS & VALVES SHALL HAVE RESTRAINED JOINTS PER SPECIFICATIONS

& ALL BELL & SPIGOT JOINTS TO BE RESTRAINED WITH A RESTRAINING

HARNESS WITHIN THE REQUIRED LENGTH OF RESTRAINED PIPE (L).

4. THRUST BLOCKS SHALL BE USED ONLY AS SPECIFIED BY PROJECT

4'

5'

6'

2'

4'

3'

BRETT J. TOBIAS, PE

Registered Eng 69017

N /S

G O

LD

EN

G

EM

U

TI

LI

TY

IM

PR

O

VE

M

EN

TS

1/

/2

4:

P

M A

H

GATE VALVE TO BE MUELLER.6.

1 2 3 4 5 6 7 8

043859.053

DKB

TNJ

DKB

MARCH 2023

R E

V

IS

IO

N

D A

T E

JOB NO.:

CHECKED BY.:

DRAWN BY:

DATE:

DESIGNED BY:

FILE NAME:

U M

AT

IL

LA

, F

LO

RI

D A

W

AT

ER

S

EW

ER

U

TI

LI

TY

D

ET

AI

LS

Sheet C-410

BASE

N O

R

TH

S

IN

C

LA

IR

A

VE

TA

VA

R

ES

, F

LO

R

ID

A

TE

L.

(3

) 3

-8

C E

R

TI

FI

C

A

TE

O F

A U

TH

O

R

IZ

A

TI

O N

N U

M B

E R

: 3

BRETT J. TOBIAS, PE

Registered Eng 69017

N /S

G O

LD

EN

G

EM

U

TI

LI

TY

IM

PR

O

VE

M

EN

TS

Sheets and Views
C-100 Cover
Sheets and Views
043859.053 Umatilla Golden Gem Utility Improvements BASE-C-200 Utility Master Plan
043859.053 Umatilla Golden Gem Utility Improvements BASE-C-300 Demo & Utility Plan
043859.053 Umatilla Golden Gem Utility Improvements BASE-C-400 General Details
043859.053 Umatilla Golden Gem Utility Improvements BASE-C-410 Water & Sewer Details

File details come from the government source that posted it. Updated .