Z2DA--Replace Dual Duct Boxes on Second Floor - 539-21-201
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 36C25026B0042
- Agency
- Veterans Integrated Service Network 10 Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 238220 Plumbing, Heating, and Air-Conditioning Contractors
- Points of contact
-
- Ronald T Heidemann ronald.heidemann@va.gov (513) 559-3708
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Network Contracting Office (NCO) 10 seeks to replace dual duct mixing boxes on the second floor of the Cincinnati VA Medical Center, with sealed bids due June 16, 2026 at 1:00 PM EDT. This procurement is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs), limiting competition to VA-certified firms meeting NAICS code 238220 with a $19 million size standard.
Place of performance is 3200 Vine Street, Cincinnati, Ohio. The contract is firm-fixed-price with an estimated magnitude between $1,000,000 and $2,500,000 and a mandatory performance period of 365 calendar days from receipt of Notice to Proceed, or 350 calendar days if Deduct Alternate #2 is selected. The project scope includes replacement of dual duct mixing boxes with fan coil or terminal units, installation of new chilled water pump and lines, asbestos abatement of approximately 250 square feet of tan duct mastic, 2 square feet of cork tar wrap, and 48 linear feet of grey mudded pipe insulation, and electrical work in an occupied hospital facility.
Critical requirements include OSHA compliance for lead-based paint remediation on white-painted plaster walls (480 ppm lead), Class III infection control containment with negative air pressure at -0.02" water column gauge, weekend-only corridor abatement work (8 PM Friday to 6 AM Monday), pre-functional and systems functional performance testing, and operational training for VA personnel. All on-site workers must comply with VHA Directive 1192.01 mandatory seasonal influenza vaccination or masking requirements. Contractors must submit a bid bond of not less than 20 percent of bid price, performance and payment bonds within 10 days of award, proof of current SDVOSB certification in the Dynamic Small Business Search database at submission and prior to award, and a completed Certificate of Compliance with 75% subcontracting limitations for special trade construction (material costs excluded). A mandatory organized site visit is scheduled for May 19, 2026 at 11:00 AM EST. Requests for Information were due May 27, 2026 and responses have been posted. Davis-Bacon prevailing wage rates apply; hourly rates range from $22.28 to $57.41 depending on labor classification.
Notice text
3 versions
Update #3 · Latest ·
REPLACE DUAL DUCT BOXES
ON THE SECOND FLOOR
FOR THE
VETERANS AFFAIRS MEDICAL CENTER (VAMC) CINCINNATI, OH
PROJECT NUMBER: 539-21-201
QUESTIONS AND ANSWERS (RFIs)
TO REQUEST FOR INVITATION FOR BID (IFB) NUMBER:
36C25026B0042
QUESTIONS AND ANSWERS
:
RFI #1 Question: spec 01 00 00 lay down and dumpster area: Where will the laydown and dumpsters area be located?
Answer: There is no guarantee of laydown space, contractors shall plan accordingly to support their material. Yes, power is available. Dumpster location will be coordinated with COR.
RFI #2 Question: Parking: How many parking spaces will be provided?
Answer: Per specification 010000 section: 1.5F2. There will be no parking by any contractors on the VA campus
RFI #3 Question: spec 01 35 26 SSHO: Can the superintendent be dual-hatted and fulfill the role of SSHO?
Answer: Yes, the superintendent and SSHO can perform both roles
RFI #4 Question: spec 02 83 33.13 LBP: Can the government please identify the location and quantities of LBP (lead-based paint) remediation?
Answer: The samples tested pertained to painted plaster (white) walls. The analytical results indicated that the white-painted plaster walls contain 480 parts per million (ppm) of lead. If white painted plaster walls are
Impacted by the project, contractors should be aware and take the appropriate precautions to comply with OSHA regulations and VA project specifications see lead paint report attached.
RFI #5 Question: Procore software: Will the government accept the use of Procore construction management software?
Answer: Yes.
RFI #6 Question: Life safety drawings: Can the government please provide life safety drawing showing existing smoke and fire walls within the project boundaries?
Answer: Existing smoke and fire walls are shown on the drawings. No changes in the safety plan see attached life safety plan.
RFI #7 Question: spec 02 82 11 asbestos abatement 1.1.2 extent of work: Is all the ACM removal associated with the mechanical demo? I.E. no abatement is expected to remove mastic etc. on duct, pipe boxes that are not shown for removal.
Answer: Yes, the abatement scope is associated with the mechanical demo- see mechanical drawings - see attachment.
RFI #8 Question: spec 02 82 11 asbestos abatement 1.1.2 extent of work material locations table: Where is Corridor A-2-15 located?
Answer: Contractor to bid quantities for removal. Corridor is C*2*3. Also, corridor A-2-15 is to the north.
RFI #9 Question: spec 02 82 11 3.2 removal of ACM/phasing: As the specs call for critical barriers, an attached 3-stage decontamination unit, drop cloths beneath the work, and negative pressure requirements of this specification for any level of abatement. Would the Government allow the phasing for the abatement to include "owning" both sides of the corridors (closed to traffic) for the abatement in the corridors?
Answer: All work within corridors shall occur during weekends, between 8PM Friday and 6AM Monday. The corridors shall be opened for normal operations outside of these hours. It is permissible to own both sides (closing traffic) during weekend work. Coordinate with COR.
RFI #10 Question: Drawing 1-A001 detail 16 and note 2: 1) Note 2 calls for new wall covering. Does the VA have attic stock to match? If not, can we paint, or please provide the wallpaper manufacturer series and color? 2) detail 16 labels room as C242 is this mislabeled and should be A242?
Answer: Paint is an acceptable finish coordinate with COR to match attic stock; the contractor is to provide a level 5 finish from corner to corner. Detail 16 label is mislabeled and should be A242.
Update #2 ·
Replace Dual Duct Mixing Boxes on the Second Floor 539-21-201
Update #1 ·
Replace Dual Duct Mixing Boxes on Second Floor 539-21-201
Attachments
| File | Type | Posted |
|---|---|---|
| 36C25026B0042 0002.docx | DOCX document | |
| Atch RFI 6 life safety plan.pdf | ||
| Atch RFI 7 ACM SURVEY REPORT.pdf | ||
| Atch RFI 4 Lead Paint Report.pdf | ||
| 36C25026B0042_1.pdf | ||
| 36C25026B0042 0001.docx | DOCX document | |
| Attachment 7 - Request for Information.docx | DOCX document | |
| 36C25026B0042_1.docx | DOCX document | |
| Attachment 4 - Drawings.pdf | ||
| Attachment 3 - Specs.pdf | ||
| Attachment 2 - VHA Directive 1192.01.pdf | ||
| Attachment 11 -Honeywell Siemens JCI Redacted.pdf | ||
| Attachment 10 - FX Controls Redacted.pdf | ||
| Attachment 9 - PCRA.pdf | ||
| Attachment 6 - EMR Form.docx | DOCX document | |
| Attachment 5 - VAAR 852.219-75.docx | DOCX document | |
| Attachment 12 - Tridium Niagara Redacted.pdf | ||
| Attachment 8 - ICRA.pdf | ||
| Attachment 1 - OH20260082 01022026.pdf |
Show all 19
Notice history
| Notice | Type | Posted |
|---|---|---|
| Z2DA--Replace Dual Duct Boxes on Second Floor - 539-21-201 | Award Notice | |