This is an Asbestos Survey Report prepared by Terracon Consultants, Inc. for the Cincinnati VA Medical Center regarding a planned renovation project to replace dual duct VAV (Variable Air Volume) boxes on the second floor.
The survey was conducted on July 9, 2020, by USEPA-accredited and Ohio EPA-certified asbestos inspectors in accordance with AHERA sampling protocols. Three asbestos-containing materials (ACM) were identified: (1) Tan (Peanut Butter) Duct Mastic containing 2% Chrysotile asbestos found on VAV boxes and associated ductwork in approximately 30 boxes (~200 square feet), classified as Category II Non-Friable in good condition; (2) Black Cork Tar Wrap containing 5% Chrysotile asbestos found on one VAV box in Room A242 (~2 square feet), classified as Category II Non-Friable in good condition; and (3) Grey Mudded Fitting Pipe Insulation containing 1.75% Chrysotile asbestos (by point count analysis) located in Corridor 2-3 and Room A260a on chilled water lines (~30 linear feet or 30 fittings), classified as Regulated Asbestos-Containing Material (RACM) in good condition. Laboratory analysis was performed by EMSL Analytical, Inc. using Polarized Light Microscopy per EPA methodology 600/R-93/116. The report recommends that if identified ACMs will be impacted by the renovation, materials must be properly removed, handled, and disposed in accordance with applicable federal and state asbestos regulations, OSHA regulations, and VA project specifications. The survey scope was limited to accessible areas intended to be impacted by the planned renovation and does not represent a comprehensive building survey.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Atch RFI 4 Lead Paint Report.pdf | ||
| Atch RFI 6 life safety plan.pdf | ||
| 36C25026B0042 0002.docx | DOCX document | |
| 36C25026B0042_1.pdf | ||
| 36C25026B0042 0001.docx | DOCX document | |
| Attachment 12 - Tridium Niagara Redacted.pdf | ||
| Attachment 8 - ICRA.pdf | ||
| Attachment 1 - OH20260082 01022026.pdf | ||
| Attachment 4 - Drawings.pdf | ||
| Attachment 3 - Specs.pdf | ||
| Attachment 2 - VHA Directive 1192.01.pdf | ||
| Attachment 11 -Honeywell Siemens JCI Redacted.pdf | ||
| Attachment 10 - FX Controls Redacted.pdf | ||
| Attachment 9 - PCRA.pdf | ||
| Attachment 6 - EMR Form.docx | DOCX document | |
| Attachment 5 - VAAR 852.219-75.docx | DOCX document | |
| Attachment 7 - Request for Information.docx | DOCX document | |
| 36C25026B0042_1.docx | DOCX document |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Survey VA Project: Replace Dual Duct Boxes on 2nd Floor
VA Project No.: 539-21-201 Cincinnati VA Medical Center
3200 Vine Street Cincinnati, Ohio 45220
July 27, 2020
Terracon Project No.: N1197461
Prepared for:
Levin Porter Associates Inc.
Miamisburg, Ohio 45342
Prepared by:
Terracon Consultants, Inc.
Cincinnati, Ohio 45226
Terracon Consultants, Inc . 611 Lunken Park Dr ive C inc innat i, OH 45226 P 513-321-5816 F 513-321-0294 t er racon.com
July 27, 2020
Levin Porter Associates Inc.
3011 Newmark Drive Miamisburg, Ohio 45342
Attn: Ms. Veronica Pochet, AIA Project Architect T: (937) 224-1931 E: vpochet@levin-portar.com
Re: Asbestos Survey Report VA Project: Replace Dual Duct Boxes on 2nd Floor VA Project No.: 539-21-201 Cincinnati VA Medical Center 3200 Vine Street Cincinnati, Ohio 45220 Terracon Project No.: N1197461
Dear Ms. Pochet:
Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced renovation project to Levin Porter Associates Inc. (Client). The purpose of this report is to present the results of an asbestos survey which was performed on July 9, 2020, and in general accordance with our proposal number PN1197461, dated November 15, 2019. We understand that this survey was requested for the purpose of a planned renovation which will involve the replacement of dual duct VAV boxes on the 2nd floor of the Cincinnati VA Medical Center (CVAMC) (as shown on Client-provided drawings).
With respect to this project-specific pre-renovation asbestos survey, asbestos was detected by laboratory analysis in material samples collected. Please refer to the attached report for further detail.
Terracon appreciates the opportunity to provide this service to Levin Porter Associates, Inc. If you have any questions regarding this report, please contact the undersigned at 513-321-5816.
Sincerely, Terracon Consultants, Inc.
Josh Vogel Joseph A. Tussey, CHMM Project Manager Sr. Associate / Group Manager
OH AHES #35291 OH AHES #32388
Responsive ■ Resourceful ■ Reliable i
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Project Objective
1.2 Reliance
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Visual Assessment
3.2 Physical Assessment
3.3 Sample Collection
3.4 Sample Analysis
4.0 REGULATORY OVERVIEW
5.0 FINDINGS AND RECOMMENDATIONS
6.0 LIMITATIONS/GENERAL COMMENTS
APPENDIX A IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)
APPENDIX B ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY
APPENDIX C ASBESTOS ANALYTICAL LABORATORY REPORT
APPENDIX D LICENSES AND CERTIFICATIONS
APPENDIX E SAMPLE LOCATION DRAWINGS
APPENDIX F PHOTO LOG
Responsive ■ Resourceful ■ Reliable 1
ASBESTOS SURVEY
VA Project: Replace Dual Duct Boxes on 2nd Floor
VA Project No.: 539-21-201 Cincinnati VA Medical Center Terracon Project No.: N1197461
July 27, 2020
1.0 INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted an asbestos survey specifically limited to within the boundaries and intent of the planned renovation project entitled “Replace Dual Duct Boxes on the 2nd Floor” at the Cincinnati VA Medical Center (CVAMC). The survey was performed on July 9, 2020 by United States Environmental Protection Agency (USEPA)-accredited asbestos inspectors who were also certified by the Ohio Environmental Protection Agency (OEPA) as Asbestos Hazard Evaluation Specialists (AHES). Accessible areas and building components intended to be impacted by the renovation project were surveyed based upon Client-provided renovation project plans. Homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in USEPA 40 Code of Federal Regulations (CFR) Part 763, Subpart E, known as the Asbestos Hazard Emergency Response Act (AHERA).
Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy
(PLM).
1.1 Project Objective
We understand that this survey was requested for the purposes of a future planned renovation project pertaining to the replacement of dual duct VAV boxes at various locations on the 2nd floor of the CVAMC (see Appendix E for a Client-provided project drawing). Please note that asbestos surveys are required prior to renovation or demolition to satisfy requirements of the USEPA 40 CFR Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (as well as the state NESHAP equivalent).
1.2 Reliance
This report is for the exclusive use of Levin Porter Associates Inc. (Client) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and Levin Porter Associates Inc. Reliance on this report by Levin Porter Associates Inc.
and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal and the agreement between Terracon and Levin Porter Associates Inc.
Project: Replace Dual Duct Boxes on 2nd Floor ■ CVAMC July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable 2
2.0 PROJECT DESCRIPTION
As noted above, the renovation project involves the replacement of dual duct VAV boxes at various locations on the 2nd floor of the CVAMC (see Appendix E for a Client-provided project drawing).
3.0 FIELD ACTIVITIES
The survey was conducted by Terracon representatives Mr. Lemuel Weyer and Mr. Michael Sulken, who are USEPA-accredited asbestos inspectors and who are also OEPA certified AHES.
A copy of their OEPA AHES credential is attached as Appendix C. The survey was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86, AHERA. A summary of survey activities is provided below.
3.1 Visual Assessment
Survey activities were initiated with visual observation of accessible areas and accessible building components to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.
3.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.
Terracon collected a total of 39 bulk samples from 13 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included as Appendix B.
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable 3
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of Indianapolis, Indiana for analysis PLM with dispersion staining techniques per USEPA methodology 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. When applicable for friable material samples determined by PLM to have a low asbestos content (<10%), the additional point count (PC) method was utilized.
EMSL is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 200188-0.
The laboratory analytical report is included in Appendix C.
4.0 REGULATORY OVERVIEW
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).
The asbestos NESHAP regulation classifies material subject to demolition or renovation as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM (pre-disturbance), along with Category I non-friable ACM that becomes friable (during disturbance), and Category I non-friable ACM subject to sanding, grinding, cutting, or abrading, or Category II non-friable ACM with a high probability of becoming crumbled, pulverized, or reduced to powder by forces expected to act on the material during disturbance. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials (other than Category I non-friable ACM) that contain more than 1% asbestos. Category II non-friable ACM generally includes (but is not limited to) cementitious material such as: cement pipes, cement siding (Transite™), cement panels, glazing, mortar, and grouts.
The Ohio Environmental Protection Agency (OEPA) adopted Chapter 3745-20 of the Ohio Administrative Code and implements the Asbestos NESHAP. The owner or operator must provide the OEPA district office or local air agency with written notification at least 10 business days prior to the commencement demolition projects and prior to removal of friable ACMs in quantities greater than 50 linear or 50 square feet. The OEPA also regulates friable asbestos abatement activities, asbestos personnel training, and issuance of asbestos professional certifications under OAC 3745-22. OEPA audits asbestos abatement projects and responds to public health emergencies where friable ACMs has been released. Please note that per OEPA regulations, July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable 4 non-friable floor tile if broken into pieces four (4) square inches or smaller are considered friable, and thus as a RACM.
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The USOSHA standard requires that employee exposure to airborne asbestos must not exceed 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA) and not exceed
1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as USOSHA’s asbestos permissible exposure limits (PELs). The USOSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.
5.0 FINDINGS AND RECOMMENDATIONS
Specific to the subject renovation project areas and building systems indicated on Client-provided drawing and based on the analytical results of the collected samples, the following materials were identified to contain asbestos.
ACM
Descriptions Material Locations % and Type
Asbestos Estimated Quantities*
Tan (Peanut Butter)
Duct Mastic
On VAV Boxes and Associated Duct Work in the Following Locations: Waiting Lobby Outside C200, C203, A202a, A215, A215a, A216, A221, A222, A240, A242, A243, A243b, A246, A246a, A248, A248 Restroom, A249, A249b, A251, A252, A253, A256, A257, A258, A259, A260, A 262, A263, A264, and Corridor 2-3
2% Chrysotile
~200 Square Feet (SF) or ~30 Boxes (with the mastic)
Black Cork Tar Wrap On VAV Box in Room A242 - South End of Box 5% Chrysotile ~2 SF or 1 Box
(with the wrap) Grey Mudded Fitting Pipe Insulation
Corridor 2-3 and Room A260a Located on Chilled Water Lines and Close to VAV Box Room A251
1.75% Chrysotile (by point count)
~30 Linear Feet (LF) or ~30
Fittings *Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present outside of the planned renovation areas/materials to be impacted, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions regarding quantities present.
If the identified ACMs will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state asbestos regulations, OSHA regulations, and per VA project specifications.
A listing of the identified ACMs along with conditions and EPA NESHAP material categories is included in Appendix A. A sample and results summary table is included in Appendix B. The laboratory analytical report is included in Appendix C. Sample location drawings are included in Appendix E. A photo log with example photos of the identified ACMs is included in Appendix F.
It should be noted that additional suspect materials such as concealed/inaccessible materials may
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable 5 exist. Should additional suspect materials be uncovered during renovation activities, or if renovation project plans change to include other areas/systems with other suspect materials, those materials must be assumed asbestos-containing until sampling and analysis can refute the positive assumption.
6.0 LIMITATIONS/GENERAL COMMENTS
The survey was project specific and limited to our understanding of the Client’s intended renovation project scope; this survey is not meant to be a comprehensive survey of the entire building/facility. In addition, Terracon did not perform sampling which required demolition or destructive activities such as knocking large holes in walls, dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas which may pose a health or safety risk to Terracon personnel were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.
This asbestos survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by Levin Porter Associates Inc. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding quantities, further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third-parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
Responsive ■ Resourceful ■ Reliable
APPENDIX A
VA Project: Replace Dual Duct Boxes on 2nd Floor
VA Project No.: 539-21-201 Cincinnati VA Medical Center
Terracon Project No.: N1197461
IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)
HA
No’s. ACM Descriptions Material Locations % and Type Asbestos
EPA NESHAP
Classification Condition Estimated
Quantities*
2 Tan (Peanut Butter) Duct Mastic
On VAV Boxes and Associated Duct Work in the Following Locations: Waiting Lobby Outside C200, C203, A202a, A215, A215a, A216, A221, A222, A240, A242, A243, A243b, A246, A246a, A248, A248
Restroom, A249, A249b, A251, A252, A253, A256, A257, A258, A259, A260, A 262, A263, A264, and
Corridor 2-3
2% Chrysotile Category II Non-Friable Good ~200 Square Feet (SF) or ~30 Boxes (with the mastic)
11 Black Cork Tar Wrap On VAV Box in Room A242 - South End of Box 5% Chrysotile Category II Non-Friable Good ~2 SF or 1 Box (with the wrap)
12 Grey Mudded Fitting Pipe Insulation
Corridor 2-3 and Room A260a Located on Chilled Water Lines and Close to VAV Box Room A251
1.75% Chrysotile (by point count)
Regulated Asbestos- Containing Material
(RACM)
Good
~30 Linear Feet (LF) or ~30
Fittings
See Appendix B for a summary of samples collected with respective analytical results, Appendix C for the laboratory analytical report, Appendix E for sample location drawings, and Appendix F for photo examples of the above identified materials.
*Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present outside of the planned renovation areas/materials to be impacted, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions regarding quantities present.
It should be noted that inaccessible/concealed suspect materials, other than those identified during this survey, may exist. Should additional suspect materials be uncovered prior to or during renovation activities, those materials must be assumed asbestos-containing until sampled by an Ohio AHES and analysis can deny the positive assumption.
If the identified ACMs will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state asbestos regulations, Occupational Safety and Health Administration (OSHA) regulations, and per VA project specifications.
Responsive ■ Resourceful ■ Reliable
APPENDIX B
VA Project: Replace Dual Duct Boxes on 2nd Floor
VA Project No.: 539-21-201 Cincinnati VA Medical Center
Terracon Project No.: N1197461
ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY
Sample # Sample Material Description
Sample Location HA Location(s)
Results (% / Type of Asbestos)HA # SEQ. #
2’x2’ White Ceiling Tile with Small
Fissures
Waiting Lobby outside C200
Throughout Area
No Asbestos Detected (NAD)
02 Outside of Room A224 NAD
03 Center of Room A249 NAD
Tan (Peanut Butter) Duct
Mastic
Waiting Lobby Outside C200
Waiting Lobby outside C200, C203, A202a, A215, A215a, A216, A221, A222, A240, A242, A243, A243b, A246, A246a, A248, A248
Restroom, A249, A249b, A251, A252, A253, A256, A257, A258, A259, A260, A 262, A263, A264 and
Corridor 2-3
2% Chrysotile
05 Room A202a NAD
06 Room A246 NAD
2’x2’ White Drywall Ceiling
Tile
Northeast Corner
A236 Ceiling Tile
NAD
08 Southwest Corner NAD
09 Southeast Corner NAD
Grey Duct Mastic
Center of Room A236
Rooms A224, A227, A227a, A227b, A231, Corridor 2-25, A236, A251b, A265
NAD
11 Outside Room A224 NAD
12 Room A252 NAD
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material Description
Sample Location HA Location(s)
Results (% / Type of Asbestos)HA # SEQ. #
Drywall System:
Drywall and Joint
Compound
North Wall of A231
Offices North of Elevator Lobby
NAD (drywall & joint compound layers)
Northwest Corner of
A224
NAD (drywall & joint compound layers)
Northwest Corner of
A224
NAD (drywall & joint compound layers)
Green/Tan Duct Mastic
Room A202a
Room A202a
NAD
17 Room A202a NAD
18 Room A202a NAD
Dark Green/Grey Duct Mastic
Middle of Room A215a
Room A215a
NAD
20 Middle of Room A215a NAD
21 Middle of Room A215a NAD
Black Adhesive under Aluminum
Wrap
Hallway Outside Room
A265 Fiberglass Insulation on CWS and CWR Lines in Corridor 2-3 and Room
A240
NAD
23 Hallway at Room A255 NAD
24 Hallway near A240
NAD
Plaster Walls:
Base Coat and
Finish Coat
Hallway Near Room A240
Throughout Area
NAD (base & finish coat layers)
26 Hallway Near Room A240
NAD (base & finish coat layers)
27 Room A248- South Wall
NAD (base & finish coat layers)
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material Description
Sample Location HA Location(s)
Results (% / Type of Asbestos)HA # SEQ. #
Black Foam with Yellow Mastic
Room A242- South VAV
Box
Room A242 and A243 VAV Boxes
NAD
Room A242- South VAV
Box
NAD
30 Room A243 VAV Box NAD
Black Cork Tar Wrap
Room A242- South VAV
Box
Room A242 South VAV Box
5% Chrysotile
Room A242- South VAV
Box 5% Chrysotile
Room A242- South VAV
Box 5% Chrysotile
Grey Mudded Fitting Pipe Insulation
Hallway at Room A261
Corridor 2-3, Room A260a, and Room A251
2% Chrysotile
(PLM); 1.0%
Chrysotile by Point Count
(PC)
35 Hallway at Room A263
NAD (PLM);
1.5% Chrysotile by PC
Northeast Corner of
Room A260A
2% Chrysotile
(PLM); 1.75%
Chrysotile by
PC
Tar and Cork Pipe Insulation with
Wrap
Northeast Corner of
A251
Room A251 and Adjacent Hallway
NAD
Northeast Corner of
A251
NAD
Northeast Corner of
A251
NAD
OH AHES Signatures:
Lem Weyer, OH AHES #36337 Michael Sulken, OH AHES #34655
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
APPENDIX C
ASBESTOS ANALYTICAL LABORATORY REPORT
EMSL Analytical, Inc.
6340 CastlePlace Dr. Indianapolis, IN 46250
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162013468EMSL Order:
Customer ID: HCNU50
Customer PO: N1197461
Project ID:
Attention: Phone:Lem Weyer (513) 321-5816
Fax:Terracon Consultants, Inc. (513) 321-0294
Received Date:611 Lunken Park Drive 07/13/2020 9:49 AM
Analysis Date:Cincinnati, OH 45226 07/16/2020 - 07/17/2020
Collected Date:
Project: CVAMC - 2nd Floor Duct Boxes - N1197461
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
1-01
162013468-0001
None DetectedPerlite
Non-fibrous (Other)
20%
5%
Cellulose
Min. Wool
60%
15%
Gray/White
Fibrous
Homogeneous
Waiting Lobby
Outside C200 - 2'x2'
White Ceiling Tile
With Small Fissures
1-02
162013468-0002
None DetectedPerlite
Non-fibrous (Other)
20%
5%
Cellulose
Min. Wool
60%
15%
Gray/White
Fibrous
Homogeneous
Outside Of Room
A224 - 2'x2' White
Ceiling Tile With
Small Fissures
1-03
162013468-0003
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
60%
20%
Gray/White
Fibrous
Homogeneous
Center Of Room
A249 - 2'x2' White
Ceiling Tile With
Small Fissures
2-04-Mastic
162013468-0004
None DetectedNon-fibrous (Other)100%Tan/Yellow
Non-Fibrous
Homogeneous
Waiting Lobby
Outside C200 - Tan
(Peanut Butter) Duct
Mastic
2-04-Mastic 2
162013468-0004A
2% ChrysotileNon-fibrous (Other)98%Tan
Non-Fibrous
Homogeneous
Waiting Lobby
Outside C200 - Tan
(Peanut Butter) Duct
Mastic
2-05
162013468-0005
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Room A202a - Tan
(Peanut Butter) Duct
Mastic
2-06
162013468-0006
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Room A246 - Tan
(Peanut Butter) Duct
Mastic
3-07
162013468-0007
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
70%
10%
Gray
Fibrous
Homogeneous
Northeast Corner -
2'x2' White Drywall
Ceiling Tile
3-08
162013468-0008
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
70%
10%
Gray/White
Fibrous
Homogeneous
Soutwest Corner -
2'x2' White Drywall
Ceiling Tile
3-09
162013468-0009
None DetectedPerlite
Non-fibrous (Other)
15%
5%
Cellulose
Min. Wool
70%
10%
Gray/White
Fibrous
Homogeneous
Southeast Corner -
2'x2' White Drywall
Ceiling Tile
4-10
162013468-0010
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Center Of Room
A236 - Grey Duct
Mastic
4-11
162013468-0011
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Outside Room A224 -
Grey Duct Mastic
4-12
162013468-0012
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Room A252 - Grey
Duct Mastic
5-13-Drywall
162013468-0013
None DetectedGypsum
Non-fibrous (Other)
60%
18%
Cellulose
Glass
20%
2%
Brown/White
Fibrous
Heterogeneous
North Wall Of A231 -
Drywall System:
Drywall And Joint
Compound
Initial report from: 07/17/2020 10:07:39
Page 1 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162013468EMSL Order:
Customer ID: HCNU50
Customer PO: N1197461
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
5-13-Joint Compound
162013468-0013A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
North Wall Of A231 -
Drywall System:
Drywall And Joint
Compound
5-14-Drywall
162013468-0014
None DetectedGypsum
Non-fibrous (Other)
70%
8%
Cellulose
Glass
20%
2%
Brown/White
Fibrous
Heterogeneous
Northwest Corner Of
A224 - Drywall
System: Drywall And
Joint Compound
5-14-Joint Compound
162013468-0014A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Northwest Corner Of
A224 - Drywall
System: Drywall And
Joint Compound
5-15-Drywall
162013468-0015
None DetectedGypsum
Non-fibrous (Other)
70%
8%
Cellulose
Glass
20%
2%
Brown/White
Fibrous
Heterogeneous
Northwest Corner Of
A224 - Drywall
System: Drywall And
Joint Compound
5-15-Joint Compound
162013468-0015A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Northwest Corner Of
A224 - Drywall
System: Drywall And
Joint Compound
6-16
162013468-0016
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Room A202a -
Green/Tan Duct
Mastic
6-17
162013468-0017
None DetectedNon-fibrous (Other)100%Gray/Red/Yellow
Non-Fibrous
Homogeneous
Room A202a -
Green/Tan Duct
Mastic
6-18
162013468-0018
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Room A202a -
Green/Tan Duct
Mastic
7-19
162013468-0019
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Middle Of Room
A215a - Dark
Green/Grey Duct
Mastic
7-20
162013468-0020
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Middle Of Room
A215a - Dark
Green/Grey Duct
Mastic
7-21
162013468-0021
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Middle Of Room
A215a - Dark
Green/Grey Duct
Mastic
8-22
162013468-0022
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Hallway Outside
Room A265 - Black
Adhesive Under
Aluminum Wrap
8-23
162013468-0023
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Hallway At Room
A255 - Black
Adhesive Under
Aluminum Wrap
8-24
162013468-0024
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Hallway Near A240 -
Black Adhesive Under
Aluminum Wrap
9-25-Finish Coat
162013468-0025
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
Associated with dark gray plaster base coat
Page 2 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162013468EMSL Order:
Customer ID: HCNU50
Customer PO: N1197461
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
9-25-Base Coat
162013468-0025A
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
Dark gray plaster base coat
9-25-Finish Coat
162013468-0025B
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
Associated with white plaster base coat
9-25-Base Coat
162013468-0025C
None DetectedPerlite
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
White plaster base coat
9-25-Base Coat
162013468-0025D
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
Light gray base coat only, no associated finish coat
9-26-Finish Coat
162013468-0026
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
Associated with dark gray plaster base coat
9-26-Base Coat
162013468-0026A
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
Dark gray plaster base coat
9-26-Base Coat
162013468-0026B
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Hallway Near Room
A240 - Plaster Walls:
Base Coat And Finish
Coat
9-27-Finish Coat
162013468-0027
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Room A248 - South
Wall - Plaster Walls:
Base Coat And Finish
Coat
Associated with dark gray plaster base coat
9-27-Base Coat
162013468-0027A
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Gray
Non-Fibrous
Homogeneous
Room A248 - South
Wall - Plaster Walls:
Base Coat And Finish
Coat
Dark gray plaster base coat
9-27-Base Coat
162013468-0027B
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Gray
Non-Fibrous
Homogeneous
Room A248 - South
Wall - Plaster Walls:
Base Coat And Finish
Coat
Light gray base coat
10-28-Foam
162013468-0028
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black
Foam With Yellow
Mastic
10-28-Mastic
162013468-0028A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black
Foam With Yellow
Mastic
Page 3 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162013468EMSL Order:
Customer ID: HCNU50
Customer PO: N1197461
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
10-29-Foam
162013468-0029
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black
Foam With Yellow
Mastic
10-29-Mastic
162013468-0029A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black
Foam With Yellow
Mastic
10-30-Foam
162013468-0030
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Room A243 BAV Box
- Black Foam With
Yellow Mastic
10-30-Mastic
162013468-0030A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Room A243 BAV Box
- Black Foam With
Yellow Mastic
11-31
162013468-0031
5% ChrysotileNon-fibrous (Other)95%Black
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black Cork
Tar Wrap
11-32
162013468-0032
5% ChrysotileNon-fibrous (Other)95%Black
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black Cork
Tar Wrap
11-33
162013468-0033
5% ChrysotileNon-fibrous (Other)95%Black
Non-Fibrous
Homogeneous
Room A242 - South
BAV Box - Black Cork
Tar Wrap
12-34
162013468-0034
2% ChrysotileNon-fibrous (Other)58%Min. Wool40%Gray
Fibrous
Homogeneous
Hallway At Room
A261 - Grey Mudded
Fittings
12-35-Wrap
162013468-0035
None DetectedNon-fibrous (Other)10%Cellulose90%White
Fibrous
Homogeneous
Hallway At Room
A236 - Grey Mudded
Fittings
12-35-Mudded Fitting
162013468-0035A
2% ChrysotileNon-fibrous (Other)58%Min. Wool40%Gray
Fibrous
Homogeneous
Hallway At Room
A236 - Grey Mudded
Fittings
12-36-Wrap
162013468-0036
None DetectedNon-fibrous (Other)10%Cellulose90%White
Fibrous
Homogeneous
Northeast Corner Of
Room A260A - Grey
Mudded Fittings
12-36-Mudded Fitting
162013468-0036A
2% ChrysotileNon-fibrous (Other)38%Min. Wool60%Gray
Fibrous
Homogeneous
Northeast Corner Of
Room A260A - Grey
Mudded Fittings
13-37-Wrap
162013468-0037
None DetectedNon-fibrous (Other)5%Cellulose95%White
Fibrous
Homogeneous
Northeast Corner Of
A251 - Tar And Cork
Pipe Insulation With
Wrap
13-37-Insulation
162013468-0037A
None DetectedNon-fibrous (Other)100%Brown/Black
Non-Fibrous
Homogeneous
Northeast Corner Of
A251 - Tar And Cork
Pipe Insulation With
Wrap
13-38-Wrap
162013468-0038
None DetectedNon-fibrous (Other)5%Cellulose95%White
Fibrous
Homogeneous
Northeast Corner Of
A251 - Tar And Cork
Pipe Insulation With
Wrap
13-38-Insulation
162013468-0038A
None DetectedNon-fibrous (Other)100%Brown/Black
Non-Fibrous
Homogeneous
Northeast Corner Of
A251 - Tar And Cork
Pipe Insulation With
Wrap
13-39-Wrap
162013468-0039
None DetectedNon-fibrous (Other)10%Cellulose90%White
Fibrous
Homogeneous
Northeast Corner Of
A251 - Tar And Cork
Pipe Insulation With
Wrap
Page 4 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162013468EMSL Order:
Customer ID: HCNU50
Customer PO: N1197461
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
13-39-Insulation
162013468-0039A
None DetectedNon-fibrous (Other)100%Brown/Black
Non-Fibrous
Homogeneous
Northeast Corner Of
A251 - Tar And Cork
Pipe Insulation With
Wrap
Analyst(s)
Amanda Straw (42)
Ross Matlock (19)
Richard Harding, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN NVLAP Lab Code 200188-0, AZ0939, CA 2575, CO AL-15132, TX 300262
Page 5 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
APPENDIX D
LICENSES AND CERTIFICATIONS
Phone/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
EMSL Order: 162013468
Customer ID: HCNU50
Customer PO: N1197461
Project ID:
Attention: Lem Weyer Phone: (513) 321-5816
Terracon Consultants, Inc. Fax: (513) 321-0294
611 Lunken Park Drive Received: 07/13/2020 9:49 AM
Cincinnati, OH 45226 Analysis Date: 07/16/2020 - 07/17/2020
Collected:
Project: CVAMC - 2nd Floor Duct Boxes - N1197461
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Polarized Light Microscopy. Quantitation using 400 Point Count Procedure
Sample Description Appearance % Fibrous % Non-Fibrous % Type
Non-Asbestos Asbestos
Gray
Fibrous
Homogeneous
Hallway At Room A261
- Grey Mudded Fittings
12-34
162013468-0034
Non-fibrous (Other)59.0%40% MinWool 1.00%Chrysotile
Gray
Fibrous
Homogeneous
Hallway At Room A236
- Grey Mudded Fittings
12-35-Mudded
Fitting
162013468-0035A
Non-fibrous (Other)58.5%40% MinWool 1.50%Chrysotile
Gray
Fibrous
Homogeneous
Northeast Corner Of
Room A260A - Grey
Mudded Fittings
12-36-Mudded
Fitting
162013468-0036A
Non-fibrous (Other)38.3%60% MinWool 1.75%Chrysotile
Analyst(s)
Amanda Straw (2)
Ross Matlock (1)
Richard Harding, Laboratory Manager or other approved signatory
Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. The limit of detection as stated in the method is 0.25%. EMSL Analytical Inc suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM . The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of EMSL Analytical Inc. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government . EMSL
Analytical Inc., bears no responsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. EMSL Analytical
Inc., liability is limited to the cost of sample analysis.The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN
Initial report from: 07/17/2020 10:07:47
ASB_PLMPC_0006_0003 Printed 7/17/2020 10:26:24AM Page 1 of 1
OrderID: 162013468
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
APPENDIX E
SAMPLE LOCATION DRAWINGS
Project No. N1197461 Date: July 9, 2020 2nd Floor Duct Boxes – Area A Exhibit
Project Manager: Josh Vogel Cincinnati VA Medical Center 3200 Vine Street Cincinnati, Ohio 1
Consulting Engineers and Scientists
Location: Cincinnati, OH
611 Lunken Park Drive Cincinnati, Ohio 45226 APR: Joe Tussey PH. (513) 321-05816 FAX (513) 321-0294
01 04
21 05
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
APPENDIX F
PHOTO LOG
July 27, 2020 ■ Terracon Project No. N1197461
Responsive ■ Resourceful ■ Reliable
Photo #1: HA 1 Asbestos-Containing Tan (Peanut Butter) Duct Mastic
Photo #2: HA 11 Asbestos-Containing Black Cork Tar Wrap
Photo #3: HA 12 Asbestos-Containing Grey Mudded Pipe Fitting Insulation