This is an Asbestos Survey Report prepared by Terracon Consultants, Inc. for the Cincinnati VA Medical Center regarding a planned renovation project to replace dual duct VAV (Variable Air Volume) boxes on the second floor.

The survey was conducted on July 9, 2020, by USEPA-accredited and Ohio EPA-certified asbestos inspectors in accordance with AHERA sampling protocols. Three asbestos-containing materials (ACM) were identified: (1) Tan (Peanut Butter) Duct Mastic containing 2% Chrysotile asbestos found on VAV boxes and associated ductwork in approximately 30 boxes (~200 square feet), classified as Category II Non-Friable in good condition; (2) Black Cork Tar Wrap containing 5% Chrysotile asbestos found on one VAV box in Room A242 (~2 square feet), classified as Category II Non-Friable in good condition; and (3) Grey Mudded Fitting Pipe Insulation containing 1.75% Chrysotile asbestos (by point count analysis) located in Corridor 2-3 and Room A260a on chilled water lines (~30 linear feet or 30 fittings), classified as Regulated Asbestos-Containing Material (RACM) in good condition. Laboratory analysis was performed by EMSL Analytical, Inc. using Polarized Light Microscopy per EPA methodology 600/R-93/116. The report recommends that if identified ACMs will be impacted by the renovation, materials must be properly removed, handled, and disposed in accordance with applicable federal and state asbestos regulations, OSHA regulations, and VA project specifications. The survey scope was limited to accessible areas intended to be impacted by the planned renovation and does not represent a comprehensive building survey.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Replace Dual Duct Boxes on Second Floor - 539-21-201, newest first.
File Type Posted
Atch RFI 4 Lead Paint Report.pdf PDF
Atch RFI 6 life safety plan.pdf PDF
36C25026B0042 0002.docx DOCX document
36C25026B0042_1.pdf PDF
36C25026B0042 0001.docx DOCX document
Attachment 12 - Tridium Niagara Redacted.pdf PDF
Attachment 8 - ICRA.pdf PDF
Attachment 1 - OH20260082 01022026.pdf PDF
Attachment 4 - Drawings.pdf PDF
Attachment 3 - Specs.pdf PDF
Attachment 2 - VHA Directive 1192.01.pdf PDF
Attachment 11 -Honeywell Siemens JCI Redacted.pdf PDF
Attachment 10 - FX Controls Redacted.pdf PDF
Attachment 9 - PCRA.pdf PDF
Attachment 6 - EMR Form.docx DOCX document
Attachment 5 - VAAR 852.219-75.docx DOCX document
Attachment 7 - Request for Information.docx DOCX document
36C25026B0042_1.docx DOCX document
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asbestos Survey VA Project: Replace Dual Duct Boxes on 2nd Floor

VA Project No.: 539-21-201 Cincinnati VA Medical Center

3200 Vine Street Cincinnati, Ohio 45220

July 27, 2020

Terracon Project No.: N1197461

Prepared for:

Levin Porter Associates Inc.

Miamisburg, Ohio 45342

Prepared by:

Terracon Consultants, Inc.

Cincinnati, Ohio 45226

Terracon Consultants, Inc . 611 Lunken Park Dr ive C inc innat i, OH 45226 P 513-321-5816 F 513-321-0294 t er racon.com

July 27, 2020

Levin Porter Associates Inc.

3011 Newmark Drive Miamisburg, Ohio 45342

Attn: Ms. Veronica Pochet, AIA Project Architect T: (937) 224-1931 E: vpochet@levin-portar.com

Re: Asbestos Survey Report VA Project: Replace Dual Duct Boxes on 2nd Floor VA Project No.: 539-21-201 Cincinnati VA Medical Center 3200 Vine Street Cincinnati, Ohio 45220 Terracon Project No.: N1197461

Dear Ms. Pochet:

Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced renovation project to Levin Porter Associates Inc. (Client). The purpose of this report is to present the results of an asbestos survey which was performed on July 9, 2020, and in general accordance with our proposal number PN1197461, dated November 15, 2019. We understand that this survey was requested for the purpose of a planned renovation which will involve the replacement of dual duct VAV boxes on the 2nd floor of the Cincinnati VA Medical Center (CVAMC) (as shown on Client-provided drawings).

With respect to this project-specific pre-renovation asbestos survey, asbestos was detected by laboratory analysis in material samples collected. Please refer to the attached report for further detail.

Terracon appreciates the opportunity to provide this service to Levin Porter Associates, Inc. If you have any questions regarding this report, please contact the undersigned at 513-321-5816.

Sincerely, Terracon Consultants, Inc.

Josh Vogel Joseph A. Tussey, CHMM Project Manager Sr. Associate / Group Manager

OH AHES #35291 OH AHES #32388

Responsive ■ Resourceful ■ Reliable i

TABLE OF CONTENTS

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

2.0 BUILDING DESCRIPTION

3.0 FIELD ACTIVITIES

3.1 Visual Assessment

3.2 Physical Assessment

3.3 Sample Collection

3.4 Sample Analysis

4.0 REGULATORY OVERVIEW

5.0 FINDINGS AND RECOMMENDATIONS

6.0 LIMITATIONS/GENERAL COMMENTS

APPENDIX A IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)

APPENDIX B ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

APPENDIX C ASBESTOS ANALYTICAL LABORATORY REPORT

APPENDIX D LICENSES AND CERTIFICATIONS

APPENDIX E SAMPLE LOCATION DRAWINGS

APPENDIX F PHOTO LOG

Responsive ■ Resourceful ■ Reliable 1

ASBESTOS SURVEY

VA Project: Replace Dual Duct Boxes on 2nd Floor

VA Project No.: 539-21-201 Cincinnati VA Medical Center Terracon Project No.: N1197461

July 27, 2020

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) conducted an asbestos survey specifically limited to within the boundaries and intent of the planned renovation project entitled “Replace Dual Duct Boxes on the 2nd Floor” at the Cincinnati VA Medical Center (CVAMC). The survey was performed on July 9, 2020 by United States Environmental Protection Agency (USEPA)-accredited asbestos inspectors who were also certified by the Ohio Environmental Protection Agency (OEPA) as Asbestos Hazard Evaluation Specialists (AHES). Accessible areas and building components intended to be impacted by the renovation project were surveyed based upon Client-provided renovation project plans. Homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in USEPA 40 Code of Federal Regulations (CFR) Part 763, Subpart E, known as the Asbestos Hazard Emergency Response Act (AHERA).

Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy

(PLM).

1.1 Project Objective

We understand that this survey was requested for the purposes of a future planned renovation project pertaining to the replacement of dual duct VAV boxes at various locations on the 2nd floor of the CVAMC (see Appendix E for a Client-provided project drawing). Please note that asbestos surveys are required prior to renovation or demolition to satisfy requirements of the USEPA 40 CFR Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (as well as the state NESHAP equivalent).

1.2 Reliance

This report is for the exclusive use of Levin Porter Associates Inc. (Client) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and Levin Porter Associates Inc. Reliance on this report by Levin Porter Associates Inc.

and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal and the agreement between Terracon and Levin Porter Associates Inc.

Project: Replace Dual Duct Boxes on 2nd Floor ■ CVAMC July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable 2

2.0 PROJECT DESCRIPTION

As noted above, the renovation project involves the replacement of dual duct VAV boxes at various locations on the 2nd floor of the CVAMC (see Appendix E for a Client-provided project drawing).

3.0 FIELD ACTIVITIES

The survey was conducted by Terracon representatives Mr. Lemuel Weyer and Mr. Michael Sulken, who are USEPA-accredited asbestos inspectors and who are also OEPA certified AHES.

A copy of their OEPA AHES credential is attached as Appendix C. The survey was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86, AHERA. A summary of survey activities is provided below.

3.1 Visual Assessment

Survey activities were initiated with visual observation of accessible areas and accessible building components to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.

3.2 Physical Assessment

A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

3.3 Sample Collection

Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.

Terracon collected a total of 39 bulk samples from 13 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included as Appendix B.

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable 3

3.4 Sample Analysis

Bulk samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) of Indianapolis, Indiana for analysis PLM with dispersion staining techniques per USEPA methodology 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. When applicable for friable material samples determined by PLM to have a low asbestos content (<10%), the additional point count (PC) method was utilized.

EMSL is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 200188-0.

The laboratory analytical report is included in Appendix C.

4.0 REGULATORY OVERVIEW

The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).

The asbestos NESHAP regulation classifies material subject to demolition or renovation as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM (pre-disturbance), along with Category I non-friable ACM that becomes friable (during disturbance), and Category I non-friable ACM subject to sanding, grinding, cutting, or abrading, or Category II non-friable ACM with a high probability of becoming crumbled, pulverized, or reduced to powder by forces expected to act on the material during disturbance. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials (other than Category I non-friable ACM) that contain more than 1% asbestos. Category II non-friable ACM generally includes (but is not limited to) cementitious material such as: cement pipes, cement siding (Transite™), cement panels, glazing, mortar, and grouts.

The Ohio Environmental Protection Agency (OEPA) adopted Chapter 3745-20 of the Ohio Administrative Code and implements the Asbestos NESHAP. The owner or operator must provide the OEPA district office or local air agency with written notification at least 10 business days prior to the commencement demolition projects and prior to removal of friable ACMs in quantities greater than 50 linear or 50 square feet. The OEPA also regulates friable asbestos abatement activities, asbestos personnel training, and issuance of asbestos professional certifications under OAC 3745-22. OEPA audits asbestos abatement projects and responds to public health emergencies where friable ACMs has been released. Please note that per OEPA regulations, July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable 4 non-friable floor tile if broken into pieces four (4) square inches or smaller are considered friable, and thus as a RACM.

The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The USOSHA standard requires that employee exposure to airborne asbestos must not exceed 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA) and not exceed

1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as USOSHA’s asbestos permissible exposure limits (PELs). The USOSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.

5.0 FINDINGS AND RECOMMENDATIONS

Specific to the subject renovation project areas and building systems indicated on Client-provided drawing and based on the analytical results of the collected samples, the following materials were identified to contain asbestos.

ACM

Descriptions Material Locations % and Type

Asbestos Estimated Quantities*

Tan (Peanut Butter)

Duct Mastic

On VAV Boxes and Associated Duct Work in the Following Locations: Waiting Lobby Outside C200, C203, A202a, A215, A215a, A216, A221, A222, A240, A242, A243, A243b, A246, A246a, A248, A248 Restroom, A249, A249b, A251, A252, A253, A256, A257, A258, A259, A260, A 262, A263, A264, and Corridor 2-3

2% Chrysotile

~200 Square Feet (SF) or ~30 Boxes (with the mastic)

Black Cork Tar Wrap On VAV Box in Room A242 - South End of Box 5% Chrysotile ~2 SF or 1 Box

(with the wrap) Grey Mudded Fitting Pipe Insulation

Corridor 2-3 and Room A260a Located on Chilled Water Lines and Close to VAV Box Room A251

1.75% Chrysotile (by point count)

~30 Linear Feet (LF) or ~30

Fittings *Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present outside of the planned renovation areas/materials to be impacted, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions regarding quantities present.

If the identified ACMs will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state asbestos regulations, OSHA regulations, and per VA project specifications.

A listing of the identified ACMs along with conditions and EPA NESHAP material categories is included in Appendix A. A sample and results summary table is included in Appendix B. The laboratory analytical report is included in Appendix C. Sample location drawings are included in Appendix E. A photo log with example photos of the identified ACMs is included in Appendix F.

It should be noted that additional suspect materials such as concealed/inaccessible materials may

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable 5 exist. Should additional suspect materials be uncovered during renovation activities, or if renovation project plans change to include other areas/systems with other suspect materials, those materials must be assumed asbestos-containing until sampling and analysis can refute the positive assumption.

6.0 LIMITATIONS/GENERAL COMMENTS

The survey was project specific and limited to our understanding of the Client’s intended renovation project scope; this survey is not meant to be a comprehensive survey of the entire building/facility. In addition, Terracon did not perform sampling which required demolition or destructive activities such as knocking large holes in walls, dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas which may pose a health or safety risk to Terracon personnel were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.

This asbestos survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by Levin Porter Associates Inc. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding quantities, further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third-parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.

Responsive ■ Resourceful ■ Reliable

APPENDIX A

VA Project: Replace Dual Duct Boxes on 2nd Floor

VA Project No.: 539-21-201 Cincinnati VA Medical Center

Terracon Project No.: N1197461

IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)

HA

No’s. ACM Descriptions Material Locations % and Type Asbestos

EPA NESHAP

Classification Condition Estimated

Quantities*

2 Tan (Peanut Butter) Duct Mastic

On VAV Boxes and Associated Duct Work in the Following Locations: Waiting Lobby Outside C200, C203, A202a, A215, A215a, A216, A221, A222, A240, A242, A243, A243b, A246, A246a, A248, A248

Restroom, A249, A249b, A251, A252, A253, A256, A257, A258, A259, A260, A 262, A263, A264, and

Corridor 2-3

2% Chrysotile Category II Non-Friable Good ~200 Square Feet (SF) or ~30 Boxes (with the mastic)

11 Black Cork Tar Wrap On VAV Box in Room A242 - South End of Box 5% Chrysotile Category II Non-Friable Good ~2 SF or 1 Box (with the wrap)

12 Grey Mudded Fitting Pipe Insulation

Corridor 2-3 and Room A260a Located on Chilled Water Lines and Close to VAV Box Room A251

1.75% Chrysotile (by point count)

Regulated Asbestos- Containing Material

(RACM)

Good

~30 Linear Feet (LF) or ~30

Fittings

See Appendix B for a summary of samples collected with respective analytical results, Appendix C for the laboratory analytical report, Appendix E for sample location drawings, and Appendix F for photo examples of the above identified materials.

*Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present outside of the planned renovation areas/materials to be impacted, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions regarding quantities present.

It should be noted that inaccessible/concealed suspect materials, other than those identified during this survey, may exist. Should additional suspect materials be uncovered prior to or during renovation activities, those materials must be assumed asbestos-containing until sampled by an Ohio AHES and analysis can deny the positive assumption.

If the identified ACMs will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state asbestos regulations, Occupational Safety and Health Administration (OSHA) regulations, and per VA project specifications.

Responsive ■ Resourceful ■ Reliable

APPENDIX B

VA Project: Replace Dual Duct Boxes on 2nd Floor

VA Project No.: 539-21-201 Cincinnati VA Medical Center

Terracon Project No.: N1197461

ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

Sample # Sample Material Description

Sample Location HA Location(s)

Results (% / Type of Asbestos)HA # SEQ. #

2’x2’ White Ceiling Tile with Small

Fissures

Waiting Lobby outside C200

Throughout Area

No Asbestos Detected (NAD)

02 Outside of Room A224 NAD

03 Center of Room A249 NAD

Tan (Peanut Butter) Duct

Mastic

Waiting Lobby Outside C200

Waiting Lobby outside C200, C203, A202a, A215, A215a, A216, A221, A222, A240, A242, A243, A243b, A246, A246a, A248, A248

Restroom, A249, A249b, A251, A252, A253, A256, A257, A258, A259, A260, A 262, A263, A264 and

Corridor 2-3

2% Chrysotile

05 Room A202a NAD

06 Room A246 NAD

2’x2’ White Drywall Ceiling

Tile

Northeast Corner

A236 Ceiling Tile

NAD

08 Southwest Corner NAD

09 Southeast Corner NAD

Grey Duct Mastic

Center of Room A236

Rooms A224, A227, A227a, A227b, A231, Corridor 2-25, A236, A251b, A265

NAD

11 Outside Room A224 NAD

12 Room A252 NAD

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

Sample # Sample Material Description

Sample Location HA Location(s)

Results (% / Type of Asbestos)HA # SEQ. #

Drywall System:

Drywall and Joint

Compound

North Wall of A231

Offices North of Elevator Lobby

NAD (drywall & joint compound layers)

Northwest Corner of

A224

NAD (drywall & joint compound layers)

Northwest Corner of

A224

NAD (drywall & joint compound layers)

Green/Tan Duct Mastic

Room A202a

Room A202a

NAD

17 Room A202a NAD

18 Room A202a NAD

Dark Green/Grey Duct Mastic

Middle of Room A215a

Room A215a

NAD

20 Middle of Room A215a NAD

21 Middle of Room A215a NAD

Black Adhesive under Aluminum

Wrap

Hallway Outside Room

A265 Fiberglass Insulation on CWS and CWR Lines in Corridor 2-3 and Room

A240

NAD

23 Hallway at Room A255 NAD

24 Hallway near A240

NAD

Plaster Walls:

Base Coat and

Finish Coat

Hallway Near Room A240

Throughout Area

NAD (base & finish coat layers)

26 Hallway Near Room A240

NAD (base & finish coat layers)

27 Room A248- South Wall

NAD (base & finish coat layers)

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

Sample # Sample Material Description

Sample Location HA Location(s)

Results (% / Type of Asbestos)HA # SEQ. #

Black Foam with Yellow Mastic

Room A242- South VAV

Box

Room A242 and A243 VAV Boxes

NAD

Room A242- South VAV

Box

NAD

30 Room A243 VAV Box NAD

Black Cork Tar Wrap

Room A242- South VAV

Box

Room A242 South VAV Box

5% Chrysotile

Room A242- South VAV

Box 5% Chrysotile

Room A242- South VAV

Box 5% Chrysotile

Grey Mudded Fitting Pipe Insulation

Hallway at Room A261

Corridor 2-3, Room A260a, and Room A251

2% Chrysotile

(PLM); 1.0%

Chrysotile by Point Count

(PC)

35 Hallway at Room A263

NAD (PLM);

1.5% Chrysotile by PC

Northeast Corner of

Room A260A

2% Chrysotile

(PLM); 1.75%

Chrysotile by

PC

Tar and Cork Pipe Insulation with

Wrap

Northeast Corner of

A251

Room A251 and Adjacent Hallway

NAD

Northeast Corner of

A251

NAD

Northeast Corner of

A251

NAD

OH AHES Signatures:

Lem Weyer, OH AHES #36337 Michael Sulken, OH AHES #34655

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

APPENDIX C

ASBESTOS ANALYTICAL LABORATORY REPORT

EMSL Analytical, Inc.

6340 CastlePlace Dr. Indianapolis, IN 46250

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162013468EMSL Order:

Customer ID: HCNU50

Customer PO: N1197461

Project ID:

Attention: Phone:Lem Weyer (513) 321-5816

Fax:Terracon Consultants, Inc. (513) 321-0294

Received Date:611 Lunken Park Drive 07/13/2020 9:49 AM

Analysis Date:Cincinnati, OH 45226 07/16/2020 - 07/17/2020

Collected Date:

Project: CVAMC - 2nd Floor Duct Boxes - N1197461

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

1-01

162013468-0001

None DetectedPerlite

Non-fibrous (Other)

20%

5%

Cellulose

Min. Wool

60%

15%

Gray/White

Fibrous

Homogeneous

Waiting Lobby

Outside C200 - 2'x2'

White Ceiling Tile

With Small Fissures

1-02

162013468-0002

None DetectedPerlite

Non-fibrous (Other)

20%

5%

Cellulose

Min. Wool

60%

15%

Gray/White

Fibrous

Homogeneous

Outside Of Room

A224 - 2'x2' White

Ceiling Tile With

Small Fissures

1-03

162013468-0003

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

60%

20%

Gray/White

Fibrous

Homogeneous

Center Of Room

A249 - 2'x2' White

Ceiling Tile With

Small Fissures

2-04-Mastic

162013468-0004

None DetectedNon-fibrous (Other)100%Tan/Yellow

Non-Fibrous

Homogeneous

Waiting Lobby

Outside C200 - Tan

(Peanut Butter) Duct

Mastic

2-04-Mastic 2

162013468-0004A

2% ChrysotileNon-fibrous (Other)98%Tan

Non-Fibrous

Homogeneous

Waiting Lobby

Outside C200 - Tan

(Peanut Butter) Duct

Mastic

2-05

162013468-0005

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Room A202a - Tan

(Peanut Butter) Duct

Mastic

2-06

162013468-0006

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Room A246 - Tan

(Peanut Butter) Duct

Mastic

3-07

162013468-0007

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

70%

10%

Gray

Fibrous

Homogeneous

Northeast Corner -

2'x2' White Drywall

Ceiling Tile

3-08

162013468-0008

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

70%

10%

Gray/White

Fibrous

Homogeneous

Soutwest Corner -

2'x2' White Drywall

Ceiling Tile

3-09

162013468-0009

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

70%

10%

Gray/White

Fibrous

Homogeneous

Southeast Corner -

2'x2' White Drywall

Ceiling Tile

4-10

162013468-0010

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Center Of Room

A236 - Grey Duct

Mastic

4-11

162013468-0011

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Outside Room A224 -

Grey Duct Mastic

4-12

162013468-0012

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room A252 - Grey

Duct Mastic

5-13-Drywall

162013468-0013

None DetectedGypsum

Non-fibrous (Other)

60%

18%

Cellulose

Glass

20%

2%

Brown/White

Fibrous

Heterogeneous

North Wall Of A231 -

Drywall System:

Drywall And Joint

Compound

Initial report from: 07/17/2020 10:07:39

Page 1 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162013468EMSL Order:

Customer ID: HCNU50

Customer PO: N1197461

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

5-13-Joint Compound

162013468-0013A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

North Wall Of A231 -

Drywall System:

Drywall And Joint

Compound

5-14-Drywall

162013468-0014

None DetectedGypsum

Non-fibrous (Other)

70%

8%

Cellulose

Glass

20%

2%

Brown/White

Fibrous

Heterogeneous

Northwest Corner Of

A224 - Drywall

System: Drywall And

Joint Compound

5-14-Joint Compound

162013468-0014A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Northwest Corner Of

A224 - Drywall

System: Drywall And

Joint Compound

5-15-Drywall

162013468-0015

None DetectedGypsum

Non-fibrous (Other)

70%

8%

Cellulose

Glass

20%

2%

Brown/White

Fibrous

Heterogeneous

Northwest Corner Of

A224 - Drywall

System: Drywall And

Joint Compound

5-15-Joint Compound

162013468-0015A

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Northwest Corner Of

A224 - Drywall

System: Drywall And

Joint Compound

6-16

162013468-0016

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room A202a -

Green/Tan Duct

Mastic

6-17

162013468-0017

None DetectedNon-fibrous (Other)100%Gray/Red/Yellow

Non-Fibrous

Homogeneous

Room A202a -

Green/Tan Duct

Mastic

6-18

162013468-0018

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room A202a -

Green/Tan Duct

Mastic

7-19

162013468-0019

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Middle Of Room

A215a - Dark

Green/Grey Duct

Mastic

7-20

162013468-0020

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Middle Of Room

A215a - Dark

Green/Grey Duct

Mastic

7-21

162013468-0021

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Middle Of Room

A215a - Dark

Green/Grey Duct

Mastic

8-22

162013468-0022

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Hallway Outside

Room A265 - Black

Adhesive Under

Aluminum Wrap

8-23

162013468-0023

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Hallway At Room

A255 - Black

Adhesive Under

Aluminum Wrap

8-24

162013468-0024

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Hallway Near A240 -

Black Adhesive Under

Aluminum Wrap

9-25-Finish Coat

162013468-0025

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

Associated with dark gray plaster base coat

Page 2 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162013468EMSL Order:

Customer ID: HCNU50

Customer PO: N1197461

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

9-25-Base Coat

162013468-0025A

None DetectedQuartz

Non-fibrous (Other)

25%

75%

Cellulose<1%Gray

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

Dark gray plaster base coat

9-25-Finish Coat

162013468-0025B

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

Associated with white plaster base coat

9-25-Base Coat

162013468-0025C

None DetectedPerlite

Non-fibrous (Other)

15%

85%

White

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

White plaster base coat

9-25-Base Coat

162013468-0025D

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Cellulose<1%Gray

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

Light gray base coat only, no associated finish coat

9-26-Finish Coat

162013468-0026

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

Associated with dark gray plaster base coat

9-26-Base Coat

162013468-0026A

None DetectedQuartz

Non-fibrous (Other)

25%

75%

Cellulose<1%Gray

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

Dark gray plaster base coat

9-26-Base Coat

162013468-0026B

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Cellulose<1%Gray

Non-Fibrous

Homogeneous

Hallway Near Room

A240 - Plaster Walls:

Base Coat And Finish

Coat

9-27-Finish Coat

162013468-0027

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room A248 - South

Wall - Plaster Walls:

Base Coat And Finish

Coat

Associated with dark gray plaster base coat

9-27-Base Coat

162013468-0027A

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Room A248 - South

Wall - Plaster Walls:

Base Coat And Finish

Coat

Dark gray plaster base coat

9-27-Base Coat

162013468-0027B

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Room A248 - South

Wall - Plaster Walls:

Base Coat And Finish

Coat

Light gray base coat

10-28-Foam

162013468-0028

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black

Foam With Yellow

Mastic

10-28-Mastic

162013468-0028A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black

Foam With Yellow

Mastic

Page 3 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162013468EMSL Order:

Customer ID: HCNU50

Customer PO: N1197461

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

10-29-Foam

162013468-0029

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black

Foam With Yellow

Mastic

10-29-Mastic

162013468-0029A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black

Foam With Yellow

Mastic

10-30-Foam

162013468-0030

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Room A243 BAV Box

- Black Foam With

Yellow Mastic

10-30-Mastic

162013468-0030A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Room A243 BAV Box

- Black Foam With

Yellow Mastic

11-31

162013468-0031

5% ChrysotileNon-fibrous (Other)95%Black

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black Cork

Tar Wrap

11-32

162013468-0032

5% ChrysotileNon-fibrous (Other)95%Black

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black Cork

Tar Wrap

11-33

162013468-0033

5% ChrysotileNon-fibrous (Other)95%Black

Non-Fibrous

Homogeneous

Room A242 - South

BAV Box - Black Cork

Tar Wrap

12-34

162013468-0034

2% ChrysotileNon-fibrous (Other)58%Min. Wool40%Gray

Fibrous

Homogeneous

Hallway At Room

A261 - Grey Mudded

Fittings

12-35-Wrap

162013468-0035

None DetectedNon-fibrous (Other)10%Cellulose90%White

Fibrous

Homogeneous

Hallway At Room

A236 - Grey Mudded

Fittings

12-35-Mudded Fitting

162013468-0035A

2% ChrysotileNon-fibrous (Other)58%Min. Wool40%Gray

Fibrous

Homogeneous

Hallway At Room

A236 - Grey Mudded

Fittings

12-36-Wrap

162013468-0036

None DetectedNon-fibrous (Other)10%Cellulose90%White

Fibrous

Homogeneous

Northeast Corner Of

Room A260A - Grey

Mudded Fittings

12-36-Mudded Fitting

162013468-0036A

2% ChrysotileNon-fibrous (Other)38%Min. Wool60%Gray

Fibrous

Homogeneous

Northeast Corner Of

Room A260A - Grey

Mudded Fittings

13-37-Wrap

162013468-0037

None DetectedNon-fibrous (Other)5%Cellulose95%White

Fibrous

Homogeneous

Northeast Corner Of

A251 - Tar And Cork

Pipe Insulation With

Wrap

13-37-Insulation

162013468-0037A

None DetectedNon-fibrous (Other)100%Brown/Black

Non-Fibrous

Homogeneous

Northeast Corner Of

A251 - Tar And Cork

Pipe Insulation With

Wrap

13-38-Wrap

162013468-0038

None DetectedNon-fibrous (Other)5%Cellulose95%White

Fibrous

Homogeneous

Northeast Corner Of

A251 - Tar And Cork

Pipe Insulation With

Wrap

13-38-Insulation

162013468-0038A

None DetectedNon-fibrous (Other)100%Brown/Black

Non-Fibrous

Homogeneous

Northeast Corner Of

A251 - Tar And Cork

Pipe Insulation With

Wrap

13-39-Wrap

162013468-0039

None DetectedNon-fibrous (Other)10%Cellulose90%White

Fibrous

Homogeneous

Northeast Corner Of

A251 - Tar And Cork

Pipe Insulation With

Wrap

Page 4 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162013468EMSL Order:

Customer ID: HCNU50

Customer PO: N1197461

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

13-39-Insulation

162013468-0039A

None DetectedNon-fibrous (Other)100%Brown/Black

Non-Fibrous

Homogeneous

Northeast Corner Of

A251 - Tar And Cork

Pipe Insulation With

Wrap

Analyst(s)

Amanda Straw (42)

Ross Matlock (19)

Richard Harding, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim

Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN NVLAP Lab Code 200188-0, AZ0939, CA 2575, CO AL-15132, TX 300262

Page 5 of 5ASB_PLM_0008_0001 - 1.78 Printed: 7/17/2020 10:07 AM

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

APPENDIX D

LICENSES AND CERTIFICATIONS

Phone/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

EMSL Order: 162013468

Customer ID: HCNU50

Customer PO: N1197461

Project ID:

Attention: Lem Weyer Phone: (513) 321-5816

Terracon Consultants, Inc. Fax: (513) 321-0294

611 Lunken Park Drive Received: 07/13/2020 9:49 AM

Cincinnati, OH 45226 Analysis Date: 07/16/2020 - 07/17/2020

Collected:

Project: CVAMC - 2nd Floor Duct Boxes - N1197461

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using

Polarized Light Microscopy. Quantitation using 400 Point Count Procedure

Sample Description Appearance % Fibrous % Non-Fibrous % Type

Non-Asbestos Asbestos

Gray

Fibrous

Homogeneous

Hallway At Room A261

- Grey Mudded Fittings

12-34

162013468-0034

Non-fibrous (Other)59.0%40% MinWool 1.00%Chrysotile

Gray

Fibrous

Homogeneous

Hallway At Room A236

- Grey Mudded Fittings

12-35-Mudded

Fitting

162013468-0035A

Non-fibrous (Other)58.5%40% MinWool 1.50%Chrysotile

Gray

Fibrous

Homogeneous

Northeast Corner Of

Room A260A - Grey

Mudded Fittings

12-36-Mudded

Fitting

162013468-0036A

Non-fibrous (Other)38.3%60% MinWool 1.75%Chrysotile

Analyst(s)

Amanda Straw (2)

Ross Matlock (1)

Richard Harding, Laboratory Manager or other approved signatory

Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. The limit of detection as stated in the method is 0.25%. EMSL Analytical Inc suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM . The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of EMSL Analytical Inc. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government . EMSL

Analytical Inc., bears no responsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. EMSL Analytical

Inc., liability is limited to the cost of sample analysis.The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.

Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN

Initial report from: 07/17/2020 10:07:47

ASB_PLMPC_0006_0003 Printed 7/17/2020 10:26:24AM Page 1 of 1

OrderID: 162013468

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

APPENDIX E

SAMPLE LOCATION DRAWINGS

Project No. N1197461 Date: July 9, 2020 2nd Floor Duct Boxes – Area A Exhibit

Project Manager: Josh Vogel Cincinnati VA Medical Center 3200 Vine Street Cincinnati, Ohio 1

Consulting Engineers and Scientists

Location: Cincinnati, OH

611 Lunken Park Drive Cincinnati, Ohio 45226 APR: Joe Tussey PH. (513) 321-05816 FAX (513) 321-0294

01 04

21 05

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

APPENDIX F

PHOTO LOG

July 27, 2020 ■ Terracon Project No. N1197461

Responsive ■ Resourceful ■ Reliable

Photo #1: HA 1 Asbestos-Containing Tan (Peanut Butter) Duct Mastic

Photo #2: HA 11 Asbestos-Containing Black Cork Tar Wrap

Photo #3: HA 12 Asbestos-Containing Grey Mudded Pipe Fitting Insulation