Building 63 Envelope and HVAC Renovation, Coral Gables

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
12639526Q0232
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Coral Gables, Florida 33158, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The USDA Animal and Plant Health Inspection Service seeks building envelope and HVAC renovation for its Subtropical Horticulture Research Agricultural Research Service Station facility in Coral Gables, Florida, with proposals due August 28, 2026. This is a Total Small Business set-aside.

Place of performance is Palmetto Bay, Florida (13601 Old Cutler Road, Coral Gables, 33158). The facility comprises approximately 6,000 square feet of laboratory and office space. The project addresses condensation accumulation in existing ductwork causing water damage and laboratory humidity levels exceeding acceptable ranges (70% or higher). Scope includes roof replacement with 1.5-inch standing seam metal panels over polyisocyanurate rigid foam insulation; replacement of one air-cooled chiller (60-ton capacity) and associated chilled water pumps; installation of new ductwork and variable air volume terminal units; and implementation of a new direct digital control (DDC) Building Automation System with BACnet integration. Work must comply with the 2023 Florida Building Code and current ASHRAE standards. A&E firm Clark Nexsen provided design and retro commissioning services. All roofing products require current Notice of Acceptance from the State of Florida for High Velocity Hurricane Zone compliance. The NAICS code is 238220 (Plumbing, Heating, and Air-Conditioning Contractors); PSC is Y1JZ (Construction of Miscellaneous Buildings). Construction is phased with a minimum 21-day buffer between phases to maintain building occupancy; work hours are limited to 8 a.m. to 5 p.m. Monday through Friday. Prevailing wage determination applies (General Decision FL20260215, effective May 18, 2026, including Davis-Bacon Act compliance and Executive Order 13706 paid sick leave requirements). The performance period is 240 days, firm-fixed price. Notice to Proceed for Construction is due within 5 days of award. Amendment 3 (August 24) corrected the NAICS code. Amendment 2 (August 17) extended the closing date to August 28, 2026 at 1 p.m. ET. Amendment 1 (July 31) incorporated 100% for-construction drawings and specifications by Clark Nexsen.

Notice text

8 versions

Update #8 · Latest ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Amendment 1 and the final construction documents are posted below.

Site visit attendance list is posted below.

An RFI log is posted below.

Amendment 2 is posted below. It extends the closing date for receipt of proposals.

Amendment 3 is posted below. It corrects the NAICS code. RFIs and responses also posted.

A few more RFIs and responses are in a document posted below, along with a corresponding drawing.

Update #7 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Amendment 1 and the final construction documents are posted below.

Site visit attendance list is posted below.

An RFI log is posted below.

Amendment 2 is posted below. It extends the closing date for receipt of proposals.

Amendment 3 is posted below. It corrects the NAICS code. RFIs and responses also posted.

Update #6 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Amendment 1 and the final construction documents are posted below.

Site visit attendance list is posted below.

An RFI log is posted below.

Amendment 2 is posted below. It extends the closing date for receipt of proposals.

Update #5 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Amendment 1 and the final construction documents are posted below.

Site visit attendance list is posted below.

An RFI log is posted below.

Update #4 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Amendment 1 and the final construction documents are posted below.

Site visit attendance list is posted below.

Update #3 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Amendment 1 and the final construction documents are posted below.

Update #2 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

NOTE: The drawings and specifications below are the A&E's 100% submittal to USDA-APHIS. When internal reviews are complete and returned, the A&E will finalize and send us the stamped, for-construction drawings and specs, at which point they'll be posted here.

Update #1 ·

The facility located at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station has approximately 6,000 square feet of lab and office area. The ductwork is collecting condensation and causing water damage. The HVAC system consists of one air-cooled chiller, associated pumps, and two variable air volume air handling units. The humidity in the labs was tested and determined to be higher than the acceptable range (70% or higher). A&E firm Clark Nexsen provided retro commissioning with TAB services and proposed solutions for the condensation problem, as well as designs for the renovation of the roof, HVAC, BAS, and chiller.

Solicitation documents are posted below.

Files

File Type Posted
RFIs and Responses_08252026.docx DOCX document
AE201 Rev_A 20260825.pdf PDF
12639526Q0232-0003.pdf PDF
RFIs and responses.pdf PDF
12639526Q0232-0002.pdf PDF
USDA B63 RFI Log.xlsx XLSX spreadsheet
Site visit attendance.pdf PDF
12639526Q0232-0001.pdf PDF
Final Drawings.pdf PDF
Final Specifications.pdf PDF
Attachment 2_Drawings.pdf PDF
12639526Q0232.docx DOCX document
Attachment 1_Statement of Work.doc DOC document
Attachment 4_Federal Construction Wage Rates_Miami-Dade County.txt TXT text file
Attachment 3_Specifications.pdf PDF
Show all 15

Notice history

Notice Type Posted
Building 63 Envelope and HVAC Renovation, Coral Gables Award Award Notice
This notice Latest solicitation Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
USCG Station Lake Worth Inlet HVAC Diagnostic and Repairs Riviera Beach, Florida 33404, United States · NAICS 238220 — Total Small Business
HVAC Unit Replacement NAICS 238220 National Oceanic and Atmospheric Administration Total Small Business
Cooling Tower, Roofing, and Structural Construction District of Columbia 20024, United States · NAICS 236220 Bureau of Engraving and Printing Total Small Business
Replace HVAC Rooftop Units at Building 2275 March Air Reserve Base, California 92518, United States · NAICS 238220 Army National Guard No set-aside
Roof Repair Wilmington, North Carolina 28405, United States · NAICS 238160 Animal and Plant Health Inspection Service Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors