Attachment 2_Drawings.pdf
PDF 15 MB Posted
- Solicitation number
- 12639526Q0232
About this file
This file is a 100% submittal set of construction documents for Building 63 Envelope and HVAC Modifications at the USDA APHIS facility located at 13601 Old Cutler Road, Coral Gables, Florida 33158. The project contract number is 12639521D0050 with Contract Modification P00001, prepared by Clark Nexsen as the project architect and structural engineer.
The project involves comprehensive envelope and HVAC system modifications to a 6,304 square-foot laboratory and office building. Key construction elements include removal and replacement of the existing asphalt roof system with a 1.5-inch standing seam metal panel roof system over 4 inches of polyisocyanurate rigid foam insulation, repair of existing roof-to-wall connections, supplemental fastening of existing roof sheathing to trusses, installation of a new 1.5-inch standing seam metal panel roof system with appropriate flashing and crickets, and exterior soffit repairs with EIFS finishing. The HVAC scope encompasses installation of a new air-cooled chiller with capacity of 60 tons, chilled water pumps, new ductwork and VAV terminal units, electric duct heaters, new exhaust fans with capacities ranging from 1 to 2 HP, and a complete direct digital control (DDC) system with BACnet integration for remote monitoring and control. The mechanical systems are designed to serve two air handling units (AHU-1 and AHU-2) with specific CFM requirements ranging from 2,565 to 4,930 CFM depending on the unit and operation mode. The project includes coordination with electrical systems including new motor starters, variable frequency drives for fan control, lightning protection upgrades with new air terminals and grounding systems, and new LED lighting fixtures throughout the facility. All work must comply with the 2023 Florida Building Code and current ASHRAE standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFIs and Responses_08252026.docx | DOCX document | |
| AE201 Rev_A 20260825.pdf | ||
| 12639526Q0232-0003.pdf | ||
| RFIs and responses.pdf | ||
| 12639526Q0232-0002.pdf | ||
| USDA B63 RFI Log.xlsx | XLSX spreadsheet | |
| Site visit attendance.pdf | ||
| 12639526Q0232-0001.pdf | ||
| Final Specifications.pdf | ||
| Final Drawings.pdf | ||
| Attachment 4_Federal Construction Wage Rates_Miami-Dade County.txt | TXT text file | |
| Attachment 3_Specifications.pdf | ||
| Attachment 1_Statement of Work.doc | DOC document | |
| 12639526Q0232.docx | DOCX document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OLD CUTLER RD
SW
0T H
A
VE
SW GUADALAJARA ST
DEERING BAY DR
SW
ST
S
TR
EE
T
DADELAND
O
LD
C
UT
LE
R
R D
PINECREST
RICHMOND
HEIGHTS
US-1
FLA
T
P K
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:0
:5
P M
GI000
COVER SHEET
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
N
BUILDING 63 ENVELOPE AND HVAC MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL AND
PLANT HEALTH INSPECTION SERVICE (APHIS)
100% SUBMITTAL
2026.07.16
OLD CUTLER ROAD
CORAL GABLES, FL 33158
SITE MAP
PROJECT SITE
VICINITY MAP
OWNER
USDA APHIS
13601 OLD CUTLER ROAD
MIAMI, FL 33158
PROJECT TEAM
MECHANICAL, PLUMBING,
& ELECTRICAL
CLARK NEXSEN
3920 ARKWRIGHT ROAD, SUITE 385
MACON, GA 31210
T: 478.743.8415
ARCHITECT
CLARK NEXSEN
3920 ARKWRIGHT ROAD, SUITE 385
MACON, GA 31210
T: 478.743.8415
STRUCTURAL ENGINEER
CLARK NEXSEN
4525 MAIN STREET, SUITE 1400
VIRGINIA BEACH, VA 23462
T: 757.455.5800
SHEET
NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI002 BUILDING CODE SUMMARY
GI003 PHASING PLAN & GENERAL PROJECT SYMBOLOGY
GI101 LEVEL 1 LIFE SAFETY PLAN
STRUCTURAL
S-001 STRUCTURAL NOTES, LEGEND AND ABBREVIATIONS
SF101 ROOF FRAMING PLAN AND DETAILS
ARCHITECTURAL
A-001 ARCHITECTURAL LEGEND, NOTES AND ABBREVIATIONS
AE101 LEVEL 1 FLOOR PLAN
AE111 REFLECTED CEILING PLANS
AE121 ROOF PLANS
AE201 EXTERIOR ELEVATIONS
AE301 BUILDING SECTIONS
PROJECT SITE
SHEET INDEX
SHEET
NUMBER SHEET NAME
MECHANICAL
M-001 MECHANICAL LEGEND
MD101 MECHANICAL DEMOLITION PLANS
MH101 MECHANICAL PLANS
MH102 MECHANICAL ROOF PLAN
M-501 DETAILS
M-601 SCHEDULES
M-801 CONTROLS
M-802 CONTROLS
M-803 CONTROLS
M-804 CONTROLS
ELECTRICAL
E-001 ELECTRICAL LEGEND, NOTES AND ABBREVIATIONS
ED101 ELECTRICAL DEMOLITION PLAN
EG101 LIGHTNING PROTECTION PLAN
EG501 LIGHTNING PROTECTION DETAILS
EL101 LIGHTING PLANS
EL501 LIGHTING DETAILS & LUMINAIRE SCHEDULE
EP101 POWER PLANS
EP601 PANELBOARD SCHEDULES & ENLARGED PLANS
EP701 POWER RISER DIAGRAM
USDA CONTRACT NUMBER:12639521D0050
CONTRACT MODIFICATION: P00001
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:0
:5
P M
GI002
BUILDING CODE SUMMARY
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
2023 FLORIDA BUILDING CODE
CODE SUMMARY
Name of Project: ___________________________________________________________ Address:_____________________________________________________Zip Code:_____ Proposed Use:______________________________________________ Owner/Agent:____________________Phone #:___________Email:__________________
LEAD DESIGN PROFESSIONAL: __________________________________________
Code Enforcement Jurisdiction:
Designer Architectural
2023 FLORIDA BUILDING CODE:
EXISTING:
CONSTRUCTED: (date)_____________ RENOVATED: (date)_______________
BASIC BUILDING DATA
Civil
Electrical
Fire Alarm
Plumbing
Mechanical
Sprinkler-Standpipe
Structural
Retaining Walls >5'
Landscape Arch.
Non-Combustible Construction Type: I-B
Sprinklers:
Standpipes:
Fire District:
Building Area (502.1):
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUBTOTAL
4th Floor 3rd Floor 2nd Floor
Basement
TOTAL
ALLOWABLE AREA
Primary Occupancy:
Assembly (303) Business (304) Educational (305) Factory (306) High-Hazard (307) Institutional (308)
Mercantile (309) Residential (310) Storage (311)
Special Uses (Ch 4):
Mixed Occupancy:
Incidental Use Separation (509) This separation is not exempt as a Non-Separated Use (see exceptions) Non-Separated Mixed Use (508.3.)
Separated Mixed Use (508.4) - See below for area calculations
Actual Area of Occupancy A Allowable Area of Occupancy A
Actual Area of Occupancy B Allowable Area of Occupancy B
≤ 1
≤ 1.00=
STORY
NO. AND
PRIMARY
OCCUPANCY
FLOOR
DESCRIPTION
AND USE(S)
BLDG AREA
PER STORY
(ACTUAL)
ALLOWABLE
AREA FROM
TABLE 506.2
FRONTAGE
INCREASE
TOTAL
ALLOWABLE
AREA
ALLOWABLE
BUILDING
AREA
506.2.1-506.2.4
New Construction
FIRE PROTECTION REQUIREMENTS
ALLOWABLE HEIGHT
ALLOWABLE
BUILDING HT.
(TABLE 504.3)
* Indicate section number permitting reduction
LIFE SAFETY SYSTEM REQUIREMENTS
Emergency Lighting: (1008) Exit Signs: (1013) Fire Alarm: (907, NFPA 72)
Smoke Detection Systems: (907) Panic Hardware: (1010.1.10)
THERMAL ENVELOPE
Method of Compliance:
Roof/Ceiling Assembly (each assembly)
Exterior Walls (each assembly)
Walls below grade (each assembly)
Floors over unconditioned space (each assembly)
Floors slab on grade (each assembly)
Addition Upfit Alteration - Level:
II-B III-B V-B
I-A II-A III-A V-AIV
No Partial Yes NFPA 13 NFPA 13R NFPA 13D No Yes Class I Class II Class III Wet Dry
No Yes Flood Hazard Area: No Yes
I-1 I-2 I-3
A1 A2 A3
F-1 Moderate F-2 Low
H-1 Detonate H-2 Deflagrate
I-4
H-3 Combust H-4 Health H-5 HPM
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High-Piled
Utility/Misc. (312)
No Yes Separation: _____ Hr Exception: _____________
City/County Private State StateCity _____________ County _________
No Yes No Yes No Yes
No Yes No Yes
Prescriptive (Energy Code)
Performance (Energy Code)
Description of assembly ___________________________________________ U-Value of total assembly ___________________________________________ R-Value of insulation ___________________________________________ Skylights in each assembly ___________________________________________
U-Value of skylight ___________________________________________ Total square footage of skylights in each assembly _____________________
Fenestration U-Value of assembly ___________________________________________
SHGC ___________________________________________
Projection factor ___________________________________________ Low-E ___________________________________________
Door U-Value ___________________________________________
Horizontal / vertical requirement ______________________________________ Slab heated ____________________________________________________
Firm Name Lic. # EmailPhone #
I-2/I-3 Condition: 1 2 3 4 5
A4 A5
Partial ____
Accessory Occupancies:
S-2 Parking Garage: Open Enclosed Repair Garage
Incidental Uses Furnace room where any piece of equipment is over 400,000 Btu per hour input Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower Refrigerant machine room Hydrogen cut off rooms, not classified as Group H Incinerator rooms Paint shops, not classified as Group H, located in occupancies other than Group F In Group E occupancies, laboratories and vocational shops not classified as Group H.
Laundry rooms over 100 square feet
Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces In Group I-2, physical plant maintenance shops
Stationary storage battery systems having a liquid electrolyte capacity of more than 50 gallons for flooded lead-acid, nickel cadmium or VRLA, or more than 1,000 pounds for lithium-ion and lithium metal polymer used for facility standby power, emergency power or uninterrupted power supplies
(Table 509):
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #: ______________________
Fire and/or smoke rated wall locations (Chapter 7) Assumed and real property line locations Exterior wall opening area with respect to distance to assumed property lines (705.8) Existing structures within 30' of the proposed building Occupancy types for each area as it relates to occupant load calculation (Table 1004.1.2) Occupant loads for each area Exit access travel distance (1016) Common path of travel distances (1014.3 & 1028.8) Dead end lengths (1018.4) Clear exit widths for each exit door Maximum calculated occupant load capacity each exit door can accomodate based on egress width (1005.1) Actual occupant load for each exit door A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of occupancy separation Location of doors with panic hardware (1008.1.10) Location of doors with delayed egress locks and the amount of delay (1008.1.9.7) Location of doors with electromagnetic egress locks (1008.1.9.8) Location of doors equipped with hold-open devices Location of emergency escape windows (1029) The square footage of each fire area (902) The square footage of each smoke compartment (407.4) Note any code exceptions or table notes that may have been utilized regarding the items above
ACCESSIBLE PARKING
LOT OR
PARKING AREA
TOTAL # OF
PARKING
SPACES
# OF ACCESSIBLE SPACES PROVIDED
STANDARD WITH
5' ACCESS AISLE 8' ACCESS AISLE
TOTAL #
ACCESSIBLE
PROVIDED
TOTAL
(SECTION 1106)
Climate Zone:
Prescriptive (ASHRAE 90.1)
Performance (ASHRAE 90.1)
USDA - APHIS - Agricultural Research Service (ARS) Building #63 Envelope & HVAC
Old Cutler Road, Coral Gables, Florida
Laboratory & Office
Xiangbing Yang (305) 278-4881 xianbing.yang@usda.gov
Clark Nexsen . (828) 232-0608 croberson@clarknexsen.com
N/A
Clark Nexsen
Clark Nexsen
Clark Nexsen 5B
33158
GI002
36,000
6,304Lab/StorageLevel 1 - B
CLARK NEXSEN, INC.
N/A
ORIGINAL USE(S)________________________
CURRENT USE(S)________________________
PROPOSED USE(S)_______________________
Owned By:
Type of Construction:______
60'
THIS SECTION REQUIRED TO BE COMPLETED FOR ALL PROJECTS
Life safety systems generator: (2702) No Yes
11' ACCESS AISLE
VAN SPACES WITH:
6,304
7.5'
Smoke Barrier Separation**
Party/Fire Wall Separation
Corridor Ratings (1020.1)
Other
Interior
South
West
East
North
N on be ar in g
Interior
South
West
East
North
Primary Structural Frame
Building Element Rating
Required Provided Reduct*
FIRE RATED CONSTRUCTION SCHEDULE
Exit/Elevator
W al ls a nd
E xt er io r E xt er io r
Fire Sep. Dist: ___
Detail # &
Sheet #
Assembly
Design #
Penetration
Design #
Joint
Design #
Shaft Enclosures (713)
P ar tit io ns
B ea rin g
W al ls a nd P ar tit io ns
Horizontal
VerticalOccupancy
Separation (508.4)
Horizontal
VerticalTenant/Unit
Separation (708.1)
Supporting Structure
Roof Construction
Supporting Structure
Floor Construction
Roofs
Horizontal
VerticalIncidental Use
Separation (509.4)
Floors Above Grade
N/A Completed
Laboratory & Office
Laboratory & Storage
Clark Nexsen
1st Floor
6,304
XX+XX+XX=XX
36,000 36,000N/A
** FIRE PROTECTION SCHEDULE NOTES:
1. EXISTING CORRIDOR SMOKE PARTITIONS NOT WITHIN SCOPE OF WORK.
2. TYPICAL INTERIOR PARTITIONS ARE NOT REQUIRED TO BE RATED.
Voice Communication System: (907) No Yes
Attic insulation = R-38 (R-38 minimum req)
N/A
N/A
N/A
Description of assembly ___________________________________________ U-Value of total assembly ___________________________________________ R-Value of insulation ___________________________________________
Description of assembly ___________________________________________ U-Value of total assembly ___________________________________________ R-Value of insulation ___________________________________________
Description of assembly ___________________________________________ U-Value of total assembly ___________________________________________ R-Value of insulation ___________________________________________
Description of assembly ___________________________________________ U-Value of total assembly ___________________________________________ R-Value of insulation ___________________________________________
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
No
N/A - Existing assembly
Clark Nexsen
In Group I-2 occupancies, laboratories not classified as Group H.
In ambulatory care facilities, laboratories not classified as Group H.
In Group I-2, laundry rooms over 100 square feet
In ambulatory care facilities or Group I-2 occupancies, waste and linen collection rooms with containers that have an aggregate volume of 10 cubic feet or greater In other than ambulatory care facilities or Group I-2 occupancies, waste and linen collection rooms over 100 square feet In ambulatory care facilities or Group I-2 occupancies, storage rooms greater than 100 square feet
PLANNED
BUILDING HT.
32'
Non-Sprinklered (NS)
Sprinklered NFPA 13 (S)
Sprinklered NFPA 13R (S13R)
ALLOWABLE
NO. OF STORIES
(TABLE 504.4)
PLANNED
NO. OF STORIES
Assembly (303) Business (304) Educational (305) Factory (306) High-Hazard (307) Institutional (308)
Mercantile (309) Residential (310) Storage (311)
I-1 I-2 I-3
A1 A2 A3
F-1 Moderate F-2 Low
H-1 Detonate H-2 Deflagrate
I-4
H-3 Combust H-4 Health H-5 HPM
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High-Piled
Utility/Misc. (312)
I-2/I-3 Condition: 1 2 3 4 5
A4 A5
S-2 Parking Garage: Open Enclosed Repair Garage
T A
B L
E
Fire Sep. Dist: ___
Fire Sep. Dist: ___
Fire Sep. Dist: ___
Fire Sep. Dist: ___
Fire Sep. Dist: ___
Fire Sep. Dist: ___
Fire Sep. Dist: ___
5th Floor
Actual Area of Occupancy C Allowable Area of Occupancy C
Area =
Laboratory & Office
Unknown
Combustible Construction Type:
Basement: No YesBuilding Height: ____14' Number of Stories: ____1
Wood trusses with asphalt shingles (add alt. for standing seam metal)
+30'
+30'
N/A -- -- -- --
Clark Nexsen
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
Existing concrete slab on grade
N/A - Existing assembly
(Queuing area only)
N/A
N/A
N/A
0 6,304
N/A
N/A
N/A
N/A
N/A
6,304
0&2
N/A
0&2
Peter Allen 79457 (757) 961-7878 pallen@clarknexsen.com
Christopher Born 65399 (757) 961-7933 cborn@clarknexsen.com
Wade Williams 79612 (478) 743-8415 wwilliams@clarknexsen.com
Wade Williams 79612 (478) 743-8415 wwilliams@clarknexsen.com
James Dinkler 99966 (757).961-7705 james.dinkler@clarknexsen.com
Addition Change of use I II III
N/A
Special Provisions (Ch 5): N/A
+30'
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NOTE: ALL PARKING IS EXISTING - NO NEW PARKING
PLUMBING FIXTURE REQUIREMENTS
LEVEL 1 - B OCC.
USE
QTY PROVIDED:
WATER CLOSETS
OR URINALS
MALE FEMALE
LAVATORIES
MALE FEMALE
SHOWERS
/ TUBS
TOTAL REQUIRED:
DRINKING
FOUNTAINS
SERVICE
SINKS
CLOTHES
WASHER
CONNECT.
0 0101111
NOTE 1
SEE NOTE 1
PLUMBING FIXTURE TABLE NOTES:
1. ALL PLUMBING FIXTURE ARE EXISTING TO REMAIN.
SEE NOTE 1
NOTE 1
ENERGY CODE REQUIREMENTS
1A
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A - Existing assembly
N/A
Federal
STORY
NO.
PROPOSED USE USE TYPE
TBL 1004.5
AREA NET/GROSS
AREA
NO. OF
OCCUPANTS
BusinessLaboratory1
150 Gross
1,762BusinessOffice 150 Gross
SF/PER OCC.
TBL 1004.5
OCCUPANT LOADS
STORY OCC.
LOAD
TOTAL BUILDING OCCUPANT LOAD:
Christopher Born 65399 (757) 961-7933 cborn@clarknexsen.com
Chadwick Roberson
DETAIL / PLAN NUMBER
SHEET WHERE SHOWN
ELEVATION DATUM
+12'-0"
FIRST FLOOR
ROOM DESIGNATION
PLAN TITLE AND
NORTH ARROW
ELEVATION NUMBER
SHEET WHERE SHOWN
SECTION NUMBER
SHEET WHERE SHOWN
1E1
EXISTING COLUMN GRID LINE
A1
DETAIL NUMBER
SHEET NUMBER REFERENCE NOTED IN GENERAL NOTES ON SHEET
BUILDING
SHEET WHERE SHOWN
SECTION NUMBER
NAME
SCALE:
A1
NAME
SCALE:
TRUE NORTH INDICATOR
PLAN NORTH INDICATOR
ROOM NAME
BUILDING
A1
AE301
A1
AE201
A1
AE402
A1
AE301
A1
AE311
ADDITIONAL ID INFO
IF USED
VIEW REFERENCE
DETAIL /
ENLARGED PLAN
EXTERIOR
ELEVATION
BUILDING SECTION
DETAIL / WALL
SECTION
DETAIL SECTION
DETAIL, SECTION,
ELEVATION TITLE
REVISION TAG
DEMOLITION KEYNOTENEW WORK KEYNOTE
945 SF
LAB 1
508 SF
OFFICE
207 SF
OFFICE
221 SF
OFFICE
115 SF
CORRIDOR
291 SF
LOUNGE
225 SF
CORRIDOR
527 SF
CORRIDOR
455 SF
LAB 4
460 SF
LAB 3
178 SF
STORAGE
617 SF
MECHANICAL
74 SF
ELECTRICAL
458 SF
LAB 2
103 SF
CORRIDOR
INTERIOR PHASE 1
MAINTAIN FREE EGRESS AT ALL
TIMES BUILDING IS OCCUPIED
UNDISTURBED OCCUPIED AREA:
PROTECT FROM DUST, DEBRIS, DIRT,
AND NOISE INFILTRATION
INTERIOR PHASE 2
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:0
:5
P M
GI003
PHASING PLAN & GENERAL
PROJECT SYMBOLOGY
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
GENERAL PROJECT SYMBOLOGY
SCALE: 1/8" = 1'-0"
A1
PHASING PLAN
1. GENERAL PHASE EXECUTION:
A. EACH PHASE AS INDICATED ON THE PHASING PLAN SHALL
ENCOMPASS ALL REQUIRED TRADES AND ACTIVITIES, INCLUDING
MOBILIZATION, DEMOBILIZATION, FROM THE SPECIFIC WORK AREA,
INSTALLATION AND REMOVAL OF TEMPORARY SYSTEMS, SELECTIVE
DEMOLITION, NEW CONSTRUCTION, TESTING, BALANCING,
COMMISSIONING, AND ACCEPTANCE.
B. ALL WORK WITHIN A PHASE, INCLUDING THE SUBMITTAL AND
APPROVAL OF ALL TEST REPORTS, PUNCH LIST, AND ACCEPTANCE
SHALL BE FULLY COMPLETED BEFORE COMMENCEMENT OF THE
SUBSEQUENT PHASE.
C. REPLACEMENT OF ELECTRIC DUCT HEATERS, LIGHTING FIXTURES,
DUCTWORK (INCLUDING INSULATION AND BALANCING DAMPERS),
AND CEILING SYSTEMS SHALL BE PERFORMED DURING THE PHASE
IN WHICH THEY LOCATED AS INDICATED ON THE PHASING PLAN.
D. PROVIDE A 21 DAY MINIMUM BUFFER BETWEEN CONSTRUCTION
PHASES IN THE PROJECT SCHEDULE. COORDINATE MOVE-IN AND
MOVE-OUT DATES TO ALLOW USDA PERSONNEL SUFFICIENT TIME
TO RELOCATE LABORATORY FURNITURE, EQUIPMENT & MATERIALS.
2. UTILITY/ BUILDING SERVICES OUTAGE COORDINATION AND NOTICE:
A. THIS PROJECT OCCURS WITHIN AN ACTIVE, OCCUPIED FACILITY.
PRIORITIZE PLANNING TO MINIMIZE OUTAGE DURATIONS AND LIMIT
OUTAGE-RELATED WORK DURING NORMALLY UNOCCUPIED HOURS
TO THE GREATEST EXTENT PRACTICAL.
B. COORDINATE ALL UTILITY & SYSTEM OUTAGES DIRECTLY WITH THE
BUILDING USERS.
C. PROVIDE MINIMUM 14 CALENDAR DAY ADVANCED WRITTEN NOTICE
PRIOR TO ANY OUTAGE.
3. BUILDING CONTROLS REPLACEMENT:
A. REPLACEMENT OF THE DIRECT DIGITAL CONTROL (DDC) SYSTEM,
INCLUDING ASSOCIATED WORK OCCURRING IN OCCUPIED
LABORATORY SPACES (E.G., VAV BOX CONTROLS, EXHAUST FAN
VFDS), MAY BE PERFORMED AT ANY TIME, PROVIDED THE EXISTING
DDC SYSTEM MUST REMAINS FULLY ONLINE AND OPERATIONAL
UNTIL THE NEW BACNET CONTROL SYSTEM IS INSTALLED, TESTED,
AND FULLY OPERATIONAL.
B. MAINTAIN BUILDING ENVIRONMENTAL CONDITIONS DURING ALL
PORTIONS OF WORK.
C. COORDINATE WITH CHILLER REPLACEMENT SCOPE.
4. CHILLER REPLACEMENT:
A. REMOVAL AND REPLACEMENT OF THE EXISTING AIR-COOLED
CHILLER AND ASSOCIATED CHILLED WATER PUMPS SHALL BE
PERFORMED IN CONJUNCTION WITH BUILDING CONTROLS
REPLACEMENT.
B. SCHEDULE WORK AND COORDINATE TO MINIMIZE DOWNTIME AND
ENSURE SEAMLESS SYSTEM INTEGRATION UPON STARTUP.
5. REFER TO SPECIFICATION SECTION 074113.16 FOR ROOF
REPLACEMENT SEQUENCE REQUIREMENTS.
6. EGRESS REQUIREMENTS:
A. MAINTAIN BUILDING EGRESS DURING ALL TIMES BUILDING IS
OCCUPIED.
B. COORDINATE PERIODS OF EGRESS DISRUPTIONS WITH
GOVERNMENT AND PROVIDE 14 CALENDAR DAY MINIMUM NOTICE
PRIOR TO ANY CLOSURE.
GRAPHIC SCALE(S)
PHASING SEQUENCE & GENERAL NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
UP
EGRESS TRAVEL PATH
DOOR TAG. REFER TO LIFE SAFETY
EGRESS DOOR SCHEDULE.
STAIR TAG. REFER TO LIFE SAFETY
EGRESS STAIR SCHEDULE
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER BRACKET
FEC
SPACE AREA
SPACE NAME
OCCUPANT LOAD (PEOPLE)
PATH ID
FEB
SPACE NAME
9,876 SF 385 OCC
101A
A1
6,304 SF
BUSINESS
43 OCC
BUSINESS
AREAS
112' - 10"
PATH A
117' - 2"
PATH B
115A
1. COORDINATE ALL FIRE EXTINGUISHERS LOCATIONS SHOWN ON PLANS W/
LOCAL FIRE OFFICIAL'S REQUIREMENTS.
2. PROVIDE & INSTALL ALL BLOCKING IN WALLS AS REQUIRED FOR
MOUNTING FIRE EXTINGUISHERS.
3. COORDINATE INSTALLATION REQUIREMENTS OF EXIT SIGNS, ALL
ASSOCIATED HARDWARE, JUNCTION BOXES, WIRING & REQUIRED EXIT
DEVICES W/ ELECTRICAL DRAWINGS & LOCAL INSPECTOR.
4. RATED WALLS AND PARTITIONS REQUIRED TO HAVE PROTECTED
OPENINGS SHALL BE PERMANENTLY STENCILED EVERY 10'-0" ABOVE THE
CEILING OR CONCEALED SPACE.
EXAMPLE:
• 1-HOUR RATED BARRIER - PROTECT ALL OPENINGS
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:0
:5
P M
GI101
LEVEL 1 LIFE SAFETY PLAN
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
SCALE: 1/8" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
LIFE SAFETY - EXISTING OCCUPANT CALCULATION
LEVEL PATTERN FUNCTION OF SPACE
SF PER
PERSON OCCUPANCY SF TYPE AREA
*NUMBER OF
OCCUPANTS
FINISH FLOOR BUSINESS AREAS 150 GROSS 6,304 SF 43
FIRST FLOOR TOTALS: 6,304 SF 43
LIFE SAFETY - EXISITNG EGRESS DOOR SCHEDULE
DOOR NO. CLEAR EGRESS
WIDTH PROVIDED
EGRESS WIDTH
FACTOR
OCCUPANT LOAD
MAX PROVIDED REQUIRED
FINISH FLOOR
114 32" 0.15 213 23
115 32" 0.15 213 22
115A 32" 0.15 213 11
(SB)
SMOKE BARRIER (SB), SMOKE PARTITION
(SP), OR PARTITION CAPABLE OF
RESISTING THE PASSAGE OF SMOKE (S)
FOUR HOUR FIRE RATING
THREE HOUR FIRE RATING
TWO HOUR FIRE RATING
ONE HOUR FIRE RATING
ONE HALF HOUR FIRE RATING
* NUMBER OF OCCUPANTS IS AN AGGREGATE AND IS A RESULT OF ROUNDING UP INDIVIDUAL AREAS
GRAPHIC SCALE(S)
GENERAL NOTES
LIFE SAFETY PLAN SYMBOLS LEGEND
RATED PARTITIONS LEGEND
DS
STRUCTURAL ABBREVIATIONS
SYMBOL DESCRIPTION
AB ANCHOR BOLT
AFF ABOVE FINISHED FLOOR
AHR ANCHOR
APPROX APPROXIMATELY
ARCH ARCHITECTURAL
BD BAR DIAMETER
BOC BOTTOM OF CONCRETE
BOM BOTTOM OF MASONRY
BOS BOTTOM OF STEEL
BOSL BOTTOM OF SLAB
BRG BEARING
CFS COLD-FORMED STEEL
CJ SLAB CONSTRUCTION JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
DCJ DOWELED CONSTRUCTION JOINT
DIA, Ø DIAMETER
DN DOWN
DWG(S) DRAWING(S)
(E) EXISTING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
EOS EDGE OF SLAB
EQ EQUAL
ES EACH SIDE
EW EACH WAY
FFE FINISHED FLOOR ELEVATION
FOB FACE OF BRICK
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FS FAR SIDE
FTG FOOTING
GA GAGE
GALV GALVANIZED
HORIZ HORIZONTAL
HS HIGH STRENGTH
JBE JOIST BEARING ELEVATION
KSI KIPS PER SQUARE INCH
KIP (k) 1000 LBS
LBS POUNDS
LG LONG
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MOW MIDDLE OF WALL
NIC NOT IN CONTRACT
No. NUMBER
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OPP OPPOSITE
PJF PREMOLDED JOINT FILLER STRIP
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
REINF REINFORCING
REQD REQUIRED
SCHED SCHEDULE
SD SLAB DEPRESSION
SF STEPPED FOOTING
SIM SIMILAR
SJ SLAB SAWED (CONTRACTION) JOINT
SL SLOPE(D)
SOG SLAB-ON-GRADE
STD STANDARD
SWP SHEAR WALL PANEL
T&B TOP AND BOTTOM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOGB TOP OF GRADE BEAM
TOM TOP OF MASONRY
TOS TOP OF STEEL
TS THICKENED SLAB
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VERT VERTICAL
VIF VERIFY IN FIELD
WP WORKING POINT
WWR WELDED WIRE REINFORCEMENT
SLOPE DIRECTION
BRICK
CONCRETE
EARTH FILL
CONCRETE MASONRY UNIT (CMU)
POROUS FILL
INDICATES ELEVATION
REFERENCED TO FINISHED
FIRST FLOOR
DECK SPAN
KEYED CONSTRUCTION NOTE
COLUMN REFERENCE LINE
(CENTERLINE OF COLUMN)
SPOT ELEVATION
WALL TYPE
GROUT
SLAB DEPRESSION
DN
X
WX
CHANGE IN SLAB ELEVATION
STRUCTURAL LEGEND
SYMBOL DESCRIPTION
1. COORDINATE STRUCTURAL WORK WITH COMPLETE CONTRACT DOCUMENTS AND REPORT
DISCREPANCIES TO THE STRUCTURAL ENGINEER OF RECORD. COORDINATE THE WORK OF OTHER
TRADES INCLUDING, BUT NOT LIMITED TO, THE REQUIREMENTS FOR SLEEVES, INSERTS, HOLES, PRINCIPAL OPENINGS, DEPRESSIONS, EQUIPMENT PADS, HANGERS, AND ANCHORS.
2. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DIFFERENT DRAWINGS TO THE OWNER’S
REPRESENTATIVE PRIOR TO BEGINNING WORK IN AREAS THAT WILL BE AFFECTED. DO NOT SCALE
DIMENSIONS FROM THE DRAWINGS.
3. DIMENSIONS AND ELEVATIONS GIVEN FOR THE EXISTING STRUCTURE AND FOR ASSOCIATED
COMPONENTS THEREOF ARE APPROXIMATE. VERIFY AND COORDINATE EXISTING DIMENSIONS AND
ELEVATIONS BEFORE PROCEEDING WITH THE WORK. TAKE MEASUREMENTS NECESSARY FOR
FABRICATION, ALIGNMENT, AND INSTALLATION OF STRUCTURAL MEMBERS AND COMPONENTS RELATIVE TO THE EXISTING STRUCTURE. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN THE CONTRACT DRAWINGS AND THE EXISTING CONDITIONS TO THE OWNER’S REPRESENTATIVE PRIOR TO BEGINNING
WORK IN AREAS THAT WILL BE AFFECTED.
4. WHERE EXISTING CONDITIONS OR FRAMING DIFFER FROM THOSE SHOWN IN THE DRAWINGS, REPORT
DISCREPANCIES TO THE OWNER'S REPRESENTATIVE.
5. PROVIDE NECESSARY SAFEGUARDS TO CONTINUOUSLY MAINTAIN EACH PORTION OF THE STRUCTURE IN A SAFE CONDITION AND TO PROTECT FROM DAMAGE THOSE PORTIONS OF THE EXISTING FACILITY THAT
ARE TO REMAIN.
6. WHERE EXISTING CONSTRUCTION THAT IS TO REMAIN IN PLACE, BE RE-USED, OR REMAIN THE PROPERTY OF THE OWNER IS DAMAGED DURING CONSTRUCTION, REPLACE WITH NEW OR REPAIR TO ITS ORIGINAL CONDITION. COST ASSOCIATED WITH SUCH REPAIR AND REPLACEMENT IS THE RESPONSIBILITY OF THE
CONTRACTOR.
7. ITEMS SHOWN ON THE STRUCTURAL DRAWINGS ARE NEW CONSTRUCTION UNLESS SPECIFICALLY NOTED
AS EXISTING. EXISTING ITEMS ARE DENOTED WITH '(E)' OR 'EXISTING'.
8. DETAILS AND SECTIONS APPLY NOT ONLY WHERE SPECIFICALLY INDICATED OR REFERENCED, BUT ALSO
IN OTHER LIKE OR SIMILAR CONSTRUCTION THAT REQUIRES THEIR USE.
9. THE STRUCTURAL DRAWINGS CONTAINED HEREIN REPRESENT THE FINISHED STRUCTURE. PROVIDE TEMPORARY SHORING, GUYING, AND BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL STRUCTURAL WORK, INCLUDING CONNECTIONS, IS COMPLETE. THE ANALYSIS, DESIGN, SAFETY, ADEQUACY, AND INSPECTION OF SUCH TEMPORARY SUPPORTS ARE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR.
10. CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND SUPERVISION OF THE WORK ARE THE
SOLE RESPONSIBILITY OF THE CONTRACTOR.
11. REPRODUCTION OF CONTRACT DRAWINGS FOR USE AS SHOP DRAWINGS IS NOT PERMITTED.
12. DO NOT DEVIATE FROM THE STRUCTURAL DRAWINGS WITHOUT WRITTEN APPROVAL OF THE STRUCTURAL
ENGINEER OF RECORD.
13. CONCENTRICALLY FASTEN VERTICALLY- OR LATERALLY-SUPPORTED COMPONENTS TO THE SUPPORTING
STRUCTURAL MEMBER, UNLESS OTHERWISE NOTED.
14. INFORMATION PERTAINING TO THE EXISTING STRUCTURE WAS OBTAINED FROM SITE MEASUREMENTS
AND PHOTOGRAPHS. EXISTING STRUCTURAL DRAWINGS WERE NOT AVAILABLE.
15. DESIGN OF THE ROOF-MOUNTED EQUIPMENT AND ITS ATTACHMENT TO THE ROOF STRUCTURE IS THE
RESPONSIBILITY OF THE CONTRACTOR AND EQUIPMENT MANUFACTURER. REFER TO MECHANICAL
DOCUMENTS FOR REQUIREMENTS.
GENERAL NOTES DESIGN NOTES
1 - 100
ROOF ZONE
101+
COMPONENT TRIBUTARY AREA (FT2)
+47 -131 -71
-151 -73
-227 -119
+35
+35
+47 +35
+47
1 - 100
WALL ZONE
101+
COMPONENT TRIBUTARY AREA (FT2)
+71 -77 -65
-95 -775
+59
+59
+71
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND CRITERIA:
A. 2023 FLORIDA BUILDING CODE, EIGHTH EDITION, EFFECTIVE 31 DECEMBER 2023
B. 2023 FLORIDA BUILDING CODE, EXISTING BUILDING, EIGHTH EDITION, EFFECTIVE 31 DECEMBER 2023 C. ASCE 7-22, MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER
STRUCTURES
D. ANSI/AWC NDS-2018 NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD CONSTRUCTION,
WITH 2018 SUPPLEMENT
2. DESIGN LOAD CRITERIA:
A. LIVE LOADS (UNIFORM)
ROOF 20 PSF
LIVE LOADS (CONCENTRATED)
EXHAUST FAN 900 LB
B. WIND LOADS:
BASIC DESIGN WIND SPEED, V 175 MPH
ALLOWABLE STRESS DESIGN WIND SPEED, VASD 136 MPH
RISK CATEGORY II
ENCLOSURE CLASSIFICATION ENCLOSED
WIND EXPOSURE CATEGORY C
GUST EFFECT FACTOR, G 0.85
INTERNAL PRESSURE COEFFICIENTS, GCpi ±0.18
D. COMPONENTS AND CLADDING WIND PRESSURES:
USE WIND PRESSURES BELOW FOR THE DESIGN OF COMPONENT AND CLADDING ELEMENTS OR
RETAIN A PROFESSIONAL ENGINEER TO DETERMINE WIND PRESSURES FOR SPECIFIC EFFECTIVE
WIND AREAS.
NOTES:
1. POSITIVE AND NEGATIVE SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY
FROM A SURFACE, RESPECTIVELY.
2. BUILDING ZONES ARE DEFINED IN ASCE 7
3. WIND PRESSURES INDICATED ARE AT STRENGTH-LEVEL (WIND LOAD FACTOR = 1.0).
MULTIPLY PRESSURES BY 0.6 TO OBTAIN SERVICE-LEVEL PRESSURES.
4. DESIGN WIND PRESSURES FOR DEFLECTION-CONTROLLED COMPONENTS AND
CLADDING MAY UTILIZE A 10-YEAR MEAN RECURRENCE INTERVAL.
E. RAIN LOADS
RAIN INTENSITY, I 5.17 IN/HR (100 YEAR,
1-HOUR RAINFALL,
PRIMARY DRAINAGE)
9.33 IN/HR (100 YEAR,
15 MINUTE RAINFALL,
SECONDARY DRAINAGE)
DESIGN WIND PRESSURE FOR ROOF COMPONENTS (PSF)
DESIGN WIND PRESSURE FOR WALL COMPONENTS (PSF)
1. PROVIDE WOOD FRAMING MEMBERS IN ACCORDANCE WITH NIST PS20 "AMERICAN SOFTWOOD LUMBER
STANDARD" AND THE FOLLOWING REQUIREMENTS:
A. MOISTURE CONTENT: 19 PERCENT MAXIMUM
B. GRADE: NO. 2, OR BETTER
C. SPECIES: SOUTHERN PINE
2. PROVIDE SHEATHING PANELS IN ACCORDANCE WITH NIST PS1 "STRUCTURAL PLYWOOD" AND THE
FOLLOWING REQUIREMENTS:
A. ROOF SHEATHING: 23/32" APA RATED SHEATHING, EXPOSURE 1 (MINIMUM, MATCH EXISTING)
B. INSTALL SHEATHING CONTINUOUS OVER TWO OR MORE SPANS (EXCEPT FOR INFILL OF EXISTING
OPENINGS - REFER TO DETAIL ON THIS SHEET).
C. UNLESS OTHERWISE INDICATED, ATTACH ROOF SHEATHING PANELS TO FRAMING WITH MINIMUM 8d RING SHANK NAILS AT 6" OC AT PANEL EDGES AND ALONG INTERMEDIATE FRAMING MEMBERS. NAILS
MUST HAVE THE FOLLOWING MINIMUM DIMENSIONS:
a. 0.113-INCH NOMINAL SHANK DIAMETER
b. RING DIAMETER A MINIMUM OF 0.012-INCH OVER SHANK DIAMETER
c. 16 TO 20 RINGS PER INCH
d. 0.280-INCH FULL ROUND HEAD DIAMETER
e. 2" MINIMUM NAIL LENGTH
3. USE PRESERVATIVE TREATED WOOD FRAMING MEMBERS FOR MEMBERS PERMANENTLY EXPOSED TO THE WEATHER, SILL PLATES AROUND THE BUILDING PERIMETER, AND OTHER WOOD FRAMING MEMBERS
IN CONTACT WITH CONCRETE OR MASONRY.
4. STEEL PLATE CONNECTORS MUST COMPLY WITH ASTM A36 SPECIFICATIONS (Fy=36 KSI).
BOLTS CONNECTING WOOD MEMBERS MUST COMPLY WITH ASTM A307 COMMON STEEL BOLTS AND
MUST BE 3/4"Ø, UNLESS OTHERWISE NOTED.
5. METAL FRAMING ANCHORS MUST COMPLY WITH ASTM A653, DESIGNATION SS. ANCHORS MUST BE
CAPABLE OF SUPPORTING THE REACTIONS INDICATED.
6. NAIL STRUCTURAL FRAMING MEMBERS IN ACCORDANCE WITH THE "FASTENING SCHEDULE,"
TABLE 2304.10.1 OF THE FLORIDA BUILDING CODE, EIGHTH EDITION, UNLESS OTHERWISE INDICATED.
7. WHERE MULTIPLE FRAMING MEMBERS ARE INDICATED, FASTEN MEMBERS TOGETHER WITH
16d NAILS AT 12" OC, STAGGERED AT 2" FROM OPPOSITE EDGES, UNLESS OTHERWISE INDICATED.
ROUGH CARPENTRY NOTES
1. FASTEN EXISTING ROOF SHEATHING PANELS TO THE EXISTING ROOF TRUSSES IN ACCORDANCE WITH
FLORIDA EXISTING BUILDING CODE (FEBC) SECTION 706.7 AND AS INDICATED.
2. PROVIDE SUPPLEMENTAL FASTENERS CONSISTING OF ASTM F1667 CLASSIFICATION RSRS-01 RING SHANK
NAILS WITH THE FOLLOWING MINIMUM PROPERTIES:
A. 0.113-INCH NOMINAL SHANK DIAMETER
B. RING DIAMETER A MINIMUM OF 0.010-INCH OVER SHANK DIAMETER
C. 16 TO 20 RINGS PER INCH
D. RING SHANK MUST EXTEND A MINIMUM OF 1 1/2" FROM TIP OF NAIL
E. 0.280-INCH FULL ROUND HEAD DIAMETER
F. 2 3/8" MINIMUM NAIL LENGTH
3. INSTALL SUPPLEMENTAL FASTENERS AT 6-INCHES ON CENTER AT ALL EXISTING SHEATHING PANEL EDGES AND INTERMEDIATE FRAMING. INDICATED SPACING IS FOR SUPPLEMENTAL FASTENERS, REGARDLESS OF
EXISTING FASTENER PATTERN.
A. IF EXISTING FASTENER TYPE AND PATTERN ARE VISIBLE AND CAN BE DOCUMENTED, CONTACT
STRUCTURAL ENGINEER FOR DIRECTION ON POSSIBLE ADJUSTMENT TO SUPPLEMENTAL FASTENER
PATTERNS.
B. BASE BID MUST PROVIDE SUPPLEMENTAL FASTENERS AS INDICATED OVER THE ENTIRE ROOF AREA.
SUPPLEMENTAL FASTENING REQUIREMENTS FOR EXISTING
ROOF SHEATHING
1. INSPECT THE ANCHORAGE OF EACH EXISTING TRUSS AT THE FOUR BUILDING CORNERS IN ACCORDANCE WITH FLORIDA BUILDING CODE, EXISTING BUILDING, SECTION 706.8.1.3. SEE ROOF PLAN FOR LOCATIONS.
SUBMIT FINDINGS TO THE STRUCTURAL ENGINEER AS FOLLOWS:
A. AT EACH LOCATION, PROVIDE A PHOTOGRAPH OF THE EXISTING TRUSS CONNECTION TO THE
SUPPORTING STRUCTURE BELOW. PHOTOGRAPHS MUST CLEARLY SHOW FASTENERS INTO TRUSS
AND THE CONNECTION OF THE STRAP TO THE SUPPORTING STRUCTURE.
B. PROVIDE MEASUREMENTS OF STRAP WIDTH AND THICKNESS, AND FASTENER TYPE, DIAMETER, AND
SPACING. DOCUMENT AND PROVIDE ANY VISIBLE PRODUCT INFORMATION.
C. SUBMIT THE ABOVE INFORMATION TO THE STRUCTURAL ENGINEER FOR EVALUATION.
2. BASE BID MUST INCLUDE REPAIR OF THE ANCHORAGE OF TRUSSES AT LOCATIONS INDICATED ON PLAN.
REPAIR IN ACCORDANCE WITH DETAILS ON THIS SHEET. BASE BID MUST INCLUDE FOUR (4) NEW 4'x8' PLYWOOD SHEETS FOR SHEATHING REPAIR AT CORNERS, IN ACCORDANCE WITH NOTE #4 BELOW.
3. THE STRUCTURAL ENGINEER WILL EVALUATE THE EXISTING CONDITIONS, BASED ON INFORMATION
PROVIDE PER NOTE #1 ABOVE, AND WILL PROVIDE DIRECTION ON REPAIRS. WHERE EXISTING
CONNECTIONS ARE DEEMED TO COMPLY WITH APPLICABLE FLORIDA BUILDING CODE REQUIREMENTS, THE EXISTING CONNECTION DOES NOT NEED TO BE REPAIRED.
4. WHERE EXISTING SHEATHING IS REMOVED TO ACCESS THE EXISTING CONNECTIONS, WHETHER FOR OBSERVATION OR REPAIR, THE REMOVED SHEATHING MUST NOT BE REUSED. PROVIDE NEW SHEATHING AND FASTEN IN ACCORDANCE WITH 'TYPICAL EXISTING ROOF OPENING INFILL' DETAIL ON THIS SHEET.
REPAIR OF EXISTING ROOF-TO-WALL CONNECTIONS
EXISTING WOOD
ROOF TRUSS (TYP)
EXISTING ROOF
SHEATHING
INFILL OPENING WITH
WOOD SHEATHING,
23/32" MINIMUM,
MATCH EXISTING
THICKNESS
2x4 BLOCKING EACH
SIDE OF OPENING
(2) 16d COMMON NAILS, EACH END (TYP)
FASTEN INFILL SHEATHING
AND EXISTING SHEATHING
TO BLOCKING WITH
#8 x1 1/4" SCREWS AT 3" OC
EXISTING STEEL
BEAM TOP FLANGE
EXISTING WOOD
ROOF TRUSS
EXISTING 2x NAILER
14ga GALVANIZED ANGLE CONNECTOR
(SIMPSON STRONG-TIE 'HGA10', OR
SIMILAR), WITH (4) 1/4x1 1/2" SCREWS TO
TRUSS AND NAILER. CONNECTOR MUST
HAVE MINIMUM MANUFACTURER RATED
UPLIFT CAPACITY OF 500 LB.
EXISTING ROOF SHEATHING
FASTEN NAILER TO STEEL BEAM
WITH (4) 0.157"Ø POWDER-ACTUATED
FASTENERS WITHIN 4" OF TRUSS
VIRGINIA BEACH, VIRGINIA 23462
4525 MAIN STREET, SUITE 1400
757·455·5800
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
S p a lle n
.r v t
/1
/2
:2
:5
P
M
S-001
STRUCTURAL NOTES, LEGEND
AND ABBREVIATIONS
100% SUBMITTAL
PAA
PAA
MSH
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
NOT TO SCALE
A2
TYPICAL EXISTING ROOF OPENING INFILL
NOT TO SCALE
A4
ROOF TRUSS TO STEEL BEAM CONNECTION
D N
D N
B
A
3 4 5 6
1 2
SF101
B1
3 3
S-001
A2
TYP
OF (3)
FASTEN EXISTING ROOF SHEATHING
PANELS TO EXISTING ROOF TRUSSES
(ENTIRE ROOF AREA).
REFER TO NOTES ON SHEET S-001.
150'-9" ±
'-0
SF101
D4
SF101
D4
1. FRAMING ELEVATIONS ARE INDICATED AS [+X'-X"], REFERENCED TO EXISTING
FINISHED FLOOR DATUM, UNLESS OTHERWISE NOTED.
2. EXISTING ROOF CONSTRUCTION CONSISTS OF METAL-PLATE CONNECTED
WOOD TRUSSES, 2'-0"± OC (TYPICAL), SUPPORTING WOOD SHEATHING AND
ROOFING.
3. DO NOT CUT, DAMAGE, OR MODIFY EXISTING ROOF TRUSSES AND ROOF
SHEATHING DURING ROOF COVERING DEMOLITION WORK.
4. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS.
5. REFER TO MECHANICAL DRAWINGS FOR DEMOLITION OF EXISTING
EQUIPMENT ON ROOF, AND FOR INSTALLATION OF NEW EQUIPMENT.
6. REFER TO ARCHITECTURAL DRAWINGS FOR REMOVAL OF EXISTING ROOF
COVERING AND INSTALLATION OF ROOFING.
7. REFER TO SHEET S-001, "SUPPLEMENTAL FASTENING REQUIREMENTS FOR
EXISTING ROOF SHEATHING", FOR FASTENING EXISTING SHEATHING TO
EXISTING ROOF FRAMING.
6'-0" ± 6'-0" ± 6'-0" ± 6'-0" ±
EXISTING
2x6 TOP CHORD
EXISTING 2x6
BOTTOM CHORD
EXISTING METAL-PLATE
CONNECTED WOOD TRUSS
EXISTING 2x4 WEB
MEMBER (TYP)
ROOFTOP
EQUIPMENT,
SEE MECH DWGS
6x6 x 12'-0" TO EXISTING
TOP CHORD AT
EQUIPMENT, SEE PLAN
SHEATHING AND
ROOFING NOT
SHOWN
2 2 2
TYP
8TYP 9
TYP
TYP
7 7
TYP
TYP
CL FAN CL FANS
6' -0
6'
-0
6' -0
6'
-0
SF101
B3
TYP
10 10
TYP
A1
SF101
EXISTING METAL-PLATE
CONNECTED WOOD TRUSS
2x6x16'-0" SISTERED TO
EXISTING BOTTOM
CHORD, 8d NAILS 8" OC
TOP AND BOTTOM,
STAGGERED
EXISTING DAMAGED
2x6 BOTTOM CHORD
INFILL LOUVER OPENING,
2x4 AT 16" OC, WITH 2x
BLOCKING AT EDGES.
SEE ARCH DWGS FOR
CLADDING
EXISTING FRAMING
TYP
2'-0"
REMOVE EXISTING WALL
BLOCKING TO ACCESS
BOTTOM CHORD. REINSTALL
FOLLOWING 2x6 INSTALLATION
SHEATHING AND
ROOFING NOT SHOWN
EXISTING ROOF TRUSS
EXISTING ROOF TRUSS
NAIL THROUGH TRUSS
CHORD INTO 6x6 WITH 20d NAILS AT 4" OC, STAGGERED, IN TWO
ROWS 3" APART,
FULL LENGTH OF EACH 6x6
6x6 WOOD BLOCKING
FRAMED BETWEEN
TRUSSES
6x6 WOOD BLOCKING
FRAMED BETWEEN
TRUSSES
TRUSS OC SPACING
2'-0" ±
6x6 TOP CHORD
REINFORCEMENT
EXISTING TRUSS AND
REINFORCING BELOW
SECURE CURB THROUGH
SHEATHING TO 6X6 FRAMING
IN ACCORDANCE WITH FAN
AND CURB MANUFACTURER'S
REQUIREMENTS
2'-0" ±
W
IT
H M
E C
H A
N
IC
A L
C O
O R
D
IN
A
TE
C
LE
A R
O P
E N
IN
G
CUT OPENING IN
EXISTING SHEATHING
TRUSS REINFORCEMENT FAN CURB MOUNTING
A3
SF101
EXISTING ROOF
SHEATHING
2x6 FASTENED TO 6x6 BLOCKING WITH #12 x 3" WOOD SCREWS, TWO (2) AT EACH LOCATION AT 3" GAGE
3"
6x6 JOIST HANGER WITH 1200 LB
MIN VERTICAL CAPACITY
FASTENED TO TRUSS AT EACH
END OF BLOCKING (SIMPSON
STRONG-TIE 'HUC66' OR SIMILAR)
FASTEN CURB IN ACCORDANCE WITH
MANUFACTURER'S MIAMI-DADE CERTIFICATION.
BASIS OF DESIGN (GREENHECK):
5/8"Ø 316SS LAG BOLTS (5-7/8" PENETRATION,
3-7/8" THREADS ENGAGED IN 6x6) WITH 1/4x2x2 SQUARE PLATE WASHER (SS) UNDER
BOLT HEAD. PRE-DRILL WOOD.
FAN CURB, SEE MECH
AND ARCH DWGS
6x6 TOP CHORD
REINFORCEMENT, SEE PLAN
EXISTING ROOF TRUSS
EXISTING ROOF
SHEATHING
6x6 BLOCKING, SEE PLAN
3"
MIN
2 1/2"
VIRGINIA BEACH, VIRGINIA 23462
4525 MAIN STREET, SUITE 1400
757·455·5800
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
S p a lle n
.r v t
/1
/2
:2
:5
P
M
SF101
ROOF FRAMING PLAN AND
DETAILS
100% SUBMITTAL
PAA
PAA
MSH
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
SCALE: 1/8" = 1'-0"
D1
ROOF FRAMING PLAN
1/8" = 1' - 0" 0 5' 10' 15' 30'
3/8" = 1' - 0" 0 5' 10'1' 2' 3' 4'
1" = 1' - 0" 0 6" 1' 3'2'
1 1/2" = 1' - 0" 0 6" 1' 2'3" 9"
GRAPHIC SCALE(S)
GENERAL NOTES
# KEY NOTES
1 EXISTING ROOF STRUCTURE, CONSISTING OF WOOD PANEL SHEATHING
OVER METAL-PLATE CONNECTED WOOD TRUSSES SPACED AT 2'-0"± OC,
TYPICAL.
2 ROOF MOUNTED MECHANICAL EQUIPMENT, TYPICAL OF 3
3 REINFORCE EXISTING WATER DAMAGED TRUSS BOTTOM CHORD,
REFER TO 'PARTIAL ELEVATION - GABLE END', THIS SHEET
4 FILL OPENING IN EXISTING ROOF SHEATHING AFTER EXISTING EQUIPMENT
REMOVED, REFER TO DETAIL A2 ON SHEET S-001.
5 REPAIR EXISTING TRUSS-TO-BEAM CONNECTIONS WITHIN 6'-0" OF GABLE
END WALL. REFER TO NOTES AND DETAILS ON SHEET S-001.
6 INFILL EXISTING LOUVER OPENING, REFER TO 'PARTIAL ELEVATION - GABLE
END', THIS SHEET.
7 6x6 x12'-0" FOR FAN SUPPORT AND TRUSS REINFORCING
8 6x6 - FAN SUPPORT FRAMING, REFER TO DETAIL B3, THIS SHEET
9 2x6 BETWEEN EXISTING TRUSS AND NEW WOOD FRAMING MEMBERS.
ALIGN WITH 6x6 FAN SUPPORT FRAMING.
10 2x6 x12'-0", FASTENED TO EXISTING TRUSS WITH 3"x0.128" (10d) NAILS, 24"
OC TOP AND BOTTOM, STAGGERED ON OPPOSITE SIDES
11 2x6 (FLAT), NAILED TO UNDERSIDE OF EXISTING TRUSS CHORD, TO SUPPORT 6x6 REINFORCING MEMBER
SCALE: 3/8" = 1'-0"
A1
TRUSS ELEVATION
SCALE: 3/8" = 1'-0"
B1
ENLARGED ROOF FRAMING PLAN
NOT TO SCALE
D4
PARTIAL ELEVATION - GABLE END
SCALE: 1" = 1'-0"
B3
FAN BASE PLAN DETAIL
SCALE: 1 1/2" = 1'-0"
A3
SECTION
AND&
EXIST EXISTING
VINYL COMPOSITION TILEVCT
AFS
ADJ
AT
APPROX
AFF
BD
ALUM
APPROXIMATE
BOARD
ABOVE FINISH FLOOR
ABOVE FINISH SLAB
ALUMINUM
ADJUSTABLE, ADJUST
CEILING
COL
CLG
DIA
CMU
CONC
DOWNDN
EQUIP
ELEC
ELEV
EQUIPMENT
ELECTRICAL
ELEVATION
CONCRETE MASONRY UNIT
CONCRETE
DIAMETER
COLUMN
FLOOR
FO
FLR
GWB GYPSUM WALLBOARD
FACE OF
EQ EQUAL
CENTER LINE
HORIZ HORIZONTAL
TYPICALTYP
TOC TOP OF CONCRETE
WIDTH / WASHER
VERT
W
VERTICAL
UNLESS OTHERWISE NOTEDUON
HOLLOW METALHM
VIF VERIFY IN FIELD
CL
ALT ALTERNATE
APC ARCHITECTURAL PRECAST CONCRETE
ACT ACOUSTICAL CEILING TILE
BLDG BUILDING
BLKG BLOCKING
BRG BEARING
BUR BUILT-UP ROOFING
CORNER GUARDCG
CONTROL JOINTCJ
CLEARCLR
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
D DEPTH / DRYER
DBL DOUBLE
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DOWNSPOUTDS
DRAWINGDWG
EACHEA
EXPANSION JOINTEJ
EDGE OF SLABEOS
EPS EXPANDED POLYSTYRENE
EXP EXPANSION / EXPOSED
EXT EXTERIOR
FD FLOOR DRAIN
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTINGUISHER CABINET
FGL FIBERGLASS
FF FINISH FLOOR
FIN FINISH
FRT FIRE RETARDANT TREATED
GA GAUGE
GALV GALVANIZED
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GYP GYPSUM
HDW HARDWARE
HDWD HARDWOOD
HT HEIGHT
HVAC HEATING, VENTILATION, & AIR
CONDITIONING
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JT JOINT
L LENGTH / LONG
MATL MATERIAL
SUSPENDEDSUSP
THR THRESHOLD
TOW TOP OF WALL
TP TOILET PARTITION
TOP & BOTTOMT & B
VINYL BASEVB
VTR VENT THRU ROOF
WITHW/
WITHOUTW/O
WALLCOVERINGWC
WOODWD
WINDOWWDW
WINDOW OPENINGWO
WORK POINTWP
WEIGHTWT
EXTRUDED POLYSTYRENEXPS
METALMTL
NIC
MISC
OC
MISCELLANEOUS
ON CENTER
NOT IN CONTRACT
ROOM
SIMILAR
R
RM
REF
SIM
RO
SS
RADIUS
STAINLESS STEEL
ROUGH OPENING
REFRIGERATORMAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MO MASONRY OPENING
MTG MOUNTING
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED
OFOI OWNER FURNISHED
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
PL PLATE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PR PAIR
PTD PAINTED
RD ROOF DRAIN
REINF REINFORCING
REQ'D REQUIRED
RWL RAIN WATER LEADER
SAFB SOUND ATTENUATING FIRE BLANKET
SF SQUARE FEET
SQUARESQ
STRUCTURALSTRUCT
STD STANDARD
STL STEELCONTRACTOR INSTALLED
OWNER INSTALLED
TTL TOTAL
PH PANIC HARDWARE
KO KNOCK OUT
GC GENERAL CONTRACTOR
IGU INSULATING GLASS UNIT
POLYISO POLYISOCYANURATE
INSULATION
SAB SOUND ATTENUATING BLANKET
FP FIRE PROTECTION
TELE TELECOMMUNICATION
BSJ BUILDING SEPARATION JOINT
COLUMN LINECL
WOOD BLOCKING - INTERRUPTEDINSULATION - BATT / LOOSE / BLANKET
PLYWOOD / MDF
WOOD BLOCKING / FRAMING -
CONTINUOUSINSULATION - RIGID
INSULATION - SPRAY FOAM
GWB / GROUT / SPRAY FIREPROOFING
DIRECTION OF SLOPE
ROOF SLOPE
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER BRACKET
FEC
FEB
DOOR NUMBER
CJ BSJ EJ
CONTROL
JOINT
EXPANSION
JOINT
BUILDING
SEPARATION JOINT
REFER TO THE GENERAL "G" SERIES SHEETS FOR
GENERAL PROJECT SYMBOLOGY
XXXn
EXTERIOR ASSEMBLY TYPE
2' x 2' ACOUSTICAL
TILE LAY-IN CEILING
GWB
CEILING / SOFFIT
OS
S
H P
LIGHT FIXTURES
CEILING MOUNTED
EXIT LIGHT
FIRE ALARM STROBE
CEILING MOUNTED
OCCUPANCY SENSOR
CARBON MONOXIDE DETECTOR
HEAT DETECTOR
SMOKE DETECTOR
CEILING HEIGHT EXPOSED CEILING
SPRINKLER HEAD
CO
8'-0"
S
S
EXP
SUPPLY GRILLE
V F
EXHAUST FAN
CEILING MOUNTED
SECURITY CAMERA
CEILING MOUNTED
EXIT LIGHT W/ ARROW
EMERGENCY EGRESS LIGHT FIXTURES
INDICATES BRACKET, WALL MOUNTED
ELECTRICAL LIGHT / FIXTURE / EQUIPMENT, ETC
INDICATES BRACKET, WALL MOUNTED
FIRE PROTECTION FIXTURE / EQUIPMENT, ETC
PHOTO DETECTOR
SPEAKER SPEAKER W/ STROBE
FIRE ALARM HORN STROBE
RETURN GRILLE
1. PLAN DIMENSIONS SHOWN ARE TO FACE OF FRAMING MEMBERS, FACE OF MASONRY, FACE OF EXISTING WALL AND TO
CENTERLINE OF COLUMNS.
2. ALL NOTES, DETAILS, AND FEATURES DRAWN AS APPLICABLE FOR ONE CONDITION ARE APPLICABLE TO SIMILAR
CONDITIONS, WHETHER OR NOT SPECIFICALLY INDICATED.
3. ALL ELEVATIONS ARE MEASURED FROM THE REFERENCE ELEVATION +0'-0", WHICH IS THE TOP OF THE EXISTING FIRST
FLOOR SLAB, UON.
4. DO NOT SCALE DRAWINGS TO DETERMINE DIMENSIONS OR SIZES OF BUILDING ELEMENTS.
5. ALL WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN DETAILS AND SECTIONS SHALL BE CONTINUOUS, UON.
6. USE FIRE-RETARDANT TREATED WOOD PRODUCTS FOR ALL CONCEALED WOOD BLOCKING, UON.
7. USE PRESERVATIVE-TREATED WOOD PRODUCTS FOR ALL WOOD BLOCKING IN CONTACT WITH EXTERIOR MASONRY OR CONCRETE WALLS, AND FOR ALL WOOD BLOCKING IN CONTACT WITH CONCRETE SLABS ON GRADE.
8. VERIFY ALL DIMENSIONS. BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE GOVERNMENT.
9. ANY CONFLICTING INFORMATION BETWEEN THE ARCHITECTURAL DRAWINGS AND ANY OTHER DRAWINGS, SPECIFICATIONS, AND/OR EXISTING CONDITIONS SHALL BE NOTED IN WRITING TO THE GOVERNMENT FOR REVIEW
AND MUST BE CLARIFIED PRIOR TO COMMENCING THE CONSTRUCTION IN QUESTION.
10. PROVIDE WOOD OR METAL BLOCKING BEHIND GWB AT THE FOLLOWING LOCATIONS:
A. ALL WALL-MOUNTED CABINETRY, SHELVING, AND SIMILAR ITEMS.
B. ALL WALL-MOUNTED VIDEO MONITORS, AND SIMILAR ITEMS.
11. ALL MATERIALS USED IN THE PROJECT SHALL BE NEW AND PROVIDED BY THE CONTRACTOR, UON.
12. USE BITUMINOUS MEMBRANE TO SEPARATE PRESERVATIVE-TREATED WOOD PRODUCTS FROM CONTACT WITH ANY
METAL SURFACE.
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:0
:5
P M
A-001
ARCHITECTURAL LEGEND,
NOTES AND ABBREVIATIONS
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
ARCHITECTURAL GENERAL NOTES
ARCHITECTURAL ABBREVIATIONS
ARCHITECTURAL SYMBOLOGY
MATERIAL LEGEND
RCP LEGEND
NOT ALL ABBREVIATIONS, SYMBOLS, AND
LEGEND GRAPHICS LISTED ARE NECESSARILY
USED ON THIS PROJECT. REFER TO
DOCUMENTS FOR SPECIFIC INFORMATION.
E
LE
C T
R
IC
A L
F
IR
E P
R O
T E
C T
IO
N
A R
C H
IT
E
C T
U R
A L
M E
C H
A N
IC
A
L
UP
1. ALL DIMENSIONS TO BE FIELD VERIFIED PRIOR TO INSTALLATION OF
EQUIPMENT / SHELVING / CASEWORK.
2. VERIFY AND COORDINATE PENETRATIONS THROUGH ROOF DECK AND
PARTITIONS WITH PM&E DRAWINGS.
A
AE201
C3
4 5 62
B
D3
AE301
D3
AE301
OFFICE
OFFICE
OFFICE
CORRIDOR
LOUNGE
LAB 4
LAB 3
STORAGE
IT/ COMM
MECHANICAL
ELECTRICAL
CORRIDOR
TOILET
TOILET
JANITOR
LAB 1
CORRIDOR
LAB 2
CORRIDOR
TOILET
TOILET
SHOWER
SHOWER
108REINSTALL WALL-MOUNTED
CASEWORK IN EXISTING
LOCATIONS, TYP
REINSTALL WALL-
MOUNTED CASEWORK
IN EXIST LOC, TYP
EXISTING
CASEWORK
TO REMAIN
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:0
:5
P M
AE101
LEVEL 1 FLOOR PLAN
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN
GRAPHIC SCALE(S)
GENERAL NOTES
3 4 5 62
B
D3
AE301
D3
AE301
EIFS ON EXTERIOR GYPSUM
BD SOFFIT, PAINTED, TYP
EXISTING COOLER
LAB 1
LAB 2
CORRIDOR
SHOWER
SHOWER
TOILET
TOILET
CORRIDOR
MECHANICAL
ELECTRICAL
STORAGE
LAB 3
LAB 4
LOUNGE
OFFICE
OFFICE
OFFICE
CORRIDOR
TOILET
TOILET
JANITOR
CORRIDOR
IT/ COMM
7'-11" 7'-11"
7'-11"
7'-9"
7'-9" 7'-9 1/2"
8'-0"
7'-7 1/2"
7'-8 1/2"
7'-10"
7'-11 1/2"
EIFS ON EXTERIOR GYPSUM
BD SOFFIT, PAINTED, TYP
EQ TYP EQ TYP
CONTROL JOINT AT
COLUMN GRID LINE, TYP
CONTROL JOINT, TYP
EXIST FUME HOOD
PENETRATING CEILING SYSTEM
EXIST FUME HOOD- EXTEND
INSTALL SHROUD TO EXTEND
ABOVE CEILING SYSTEM
7' -2
/8
'-0
'-7
/4
'-0
7' -2
/8
1. REFER TO SHEET A-001 FOR RCP LEGEND
2. HVAC, ELECTRICAL, & LIGHTING DEVICES ARE SHOWN FOR GENERAL
COORDINATION PURPOSES ONLY. REFER TO ELECTRICAL & MECHANICAL
DRAWING FOR FULL SCOPE. NOTIFY GOVERNMENT IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
3. COORDINATE ALL EXTERIOR SOFFIT/ BULKHEAD FRAMING WITH FINAL
LIGHTING FIXTURE LOCATIONS & EXISTING FIRE SUPPRESSION HEADS.
4. FIELD VERIFY CEILING HEIGHTS SHOWN ON RCP DRAWINGS PRIOR TO
INSTALLATION OF ALL MECHANICAL DUCTWORK, SPRINKLER PIPING,
ELECTRICAL EQUIPMENT, CONDUITS, ETC. NOTIFY GOVERNMENT
IMMEDIATELY OF ANY CONFLICTS OR DISCREPANCIES.
5. INSTALL WIRE HANGERS @ ALL CORNERS OF LIGHT FIXTURES,
REGISTERS, & GRILLES.
6. REFER TO INTERIOR & EXTERIOR SECTIONS FOR ADDITIONAL CEILING
DETAILS NOT NOTED ON THIS SHEET.
7. ALL RECESSED LIGHTING SHALL BE CENTERED WITHIN THE SOFFIT
DIMENSIONS, UON.
8. ALL FIXTURES INCLUDING BUT NOT LIMITED TO LIGHTING, MOTION
DETECTORS, FIRE ALARM DEVICES, & SPRINKLER HEADS SHALL BE
CENTERED WITHIN ACOUSTICAL CEILING TILE, UON.
9. WHERE GYPSUM BOARD CEILINGS SPAN LONGER THAN 30'-0", CONTROL
JOINTS SHALL BE LOCATED IN GWB SOFFIT EVERY 30'-0". ALIGN WITH
CONTROL JOINTS IN GWB WALLS WHERE PRESENT.
10. ALL NOTED CEILING ELEVATIONS ARE EXISTING, UON
A
3 4 5 62
B
B3
AE301
B3
AE301
EXIST EIFS FASCIA TO REMAIN, TYP
EXIST GUTTER &
DOWNSPOUT TO REMAIN, TYP
REMOVE EXIST
EXTERIOR SOFFIT
& FRAMING, TYP
TEMPORARILY REMOVE
EXIST WALL-MOUNTED
CASEWORK, TYP
TEMPORARILY REMOVE EXIST
WALL-MOUNTED CASEWORK, TYP
TEMPORARILY REMOVE EXIST
WALL-MOUNTED CASEWORK, TYP
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING ELEMENT TO BE REMOVED IN ITS ENTIRETY
EXISTING HVAC TERMINALS TO BE REMOVED
DENOTES EXISTING LIGHT FIXTURE TO BE REMOVED
DENOTES EXISTING CEILING GRID TO BE REMOVED
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:1
:0
P M
AE111
REFLECTED CEILING PLANS
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE
(APHIS)
OLD CUTLER ROAD
CORAL GABLES, FL 33158
2026.07.16
CN 10858
SCALE: 1/8" = 1'-0"
LEVEL 1 REFLECTED CEILING PLAN
SCALE: 1/8" = 1'-0"
REFLECTED CEILING DEMOLITION PLAN
GRAPHIC SCALE(S)
GENERAL NOTES
DEMOLITION SYMBOLS
3 4 5 62
B
D3
AE301
D3
AE301
2' -9
2'-9"
C1
ROOF TOP MECHANICAL
EQUIPMENT, TYP
ROOF CURB TO 8"
ABOVE TOP OF
CRICKET, TYP
GALV STL FLASHING
ON ROOF CRICKET-
SLOPE 4:12, TYP
2' -9
2'-9"3'-1"
3' -1
RFA 1
ROOF SYSTEM METAL
CAP FLASHING
DS-EX DS-EX DS-EX DS-EX DS-EX DS-EX
DS-EX DS-EX DS-EX DS-EX DS-EX DS-EX
REINSTALL EXISTING
GUTTERS AT NEW ROOF
EDGE ELEVATION, TYP
EXISTING VENT
PENETRATION
EXISTING VENT
PENETRATION
1. ALL ROOF SLOPES ARE EXISTING 4:12.
2. COORDINATE WITH MECHANICAL DRAWINGS FOR LOCATION OF ROOF
PENETRATIONS THAT MAY NOT BE SHOWN ON THIS DRAWING.
3. FOR EACH ROOF-MOUNTED EQUIPMENT CURB, PROVIDE A 4:12
PREFABRICATED ALUMINUM CRICKET INSTALLED TO MAINTAIN POSITIVE
SLOPE TO ROOF EDGE. THICKNESS: 0.050". JOINTS SHALL BE FULLY
WELDED. APPLY BITUMINOUS BOND BREAKER WHERE CRICKET MEETS
DISSIMILAR METALS. SIZE CRICKET TO WIDTH OF CURB.
4. CONFIRM ROOF OPENING SIZE AND LOCATION W/ MECHANICAL & EXISTING
ROOF TRUSS LOCATIONS.
A
3 4 5 62
B
B3
AE301
B3
AE301
REMOVE PORTION OF ROOF
SYSTEM AND ROOF SHEATHING
FOR MECHANICAL EQUIPMENT
PENETRATION
REMOVE EXISTING ASPHALT
ROOF SYSTEM, TRIM,
ACCESSORIES, & UNDERLAYMENT
REMOVE EXISTING MECHANICAL
EQUIPMENT & CAP EXISTING
CURBS- PROTECT EXISTING
OPENINGS FROM WATER
INFILTRATION DURING WORK
REMOVE EXISTING RIDGE CAP
SHINGLES AND RIDGE VENT
REMOVE EXISTING RIDGE
CAP SHINGLES AND RIDGE
VENT- PROTECT OPENINGS
FROM WATER INFILTRATION
DURING WORK
REMOVE EXISTING GUTTERS-
CLEAN, & SET ASIDE FOR
REINSTALLATION, TYP
EXISTING VENT PENETRATION
EXISTING VENT PENETRATION
1 1/2" STANDING SEAM
METAL PANEL ROOF SYSTEM
4" POLYISOCYANURATE RIGID
FOAM INSULATION BOARD
EXISTING ROOF SHEATHINGRFA1
HIGH-TEMPERATURE SELF-
ADHERED ROOF UNDERLAYMENT
SLIP SHEET
1/2" HIGH DENSITY
POLYISOCYANURATE
COVER BOARD
MACON, GEORGIA 31210
3920 ARKWRIGHT ROAD, SUITE 385
478·743·8415
1 2 3 4 5 6
A
B
C
D
E
DESIGN:
DRAWN:
REVIEW:
SHEET
SUBMITTAL
PROFESSIONAL SEAL
DESIGNER
REVISIONS
NOT F
OR C
ONSTRUCTIO
N
C
R e v it P ro je c ts
\1
C o ra l G a b le s A
P H
IS
B ld g
E n v lp a n d H
V A
C
A
J a y .M c C u s k e r8 S
Z N
G .r v t
/1
/2
:1
:0
P M
AE121
ROOF PLANS
100% SUBMITTAL
JAM
JAM
CSR
BUILDING 63
ENVELOPE AND HVAC
MODIFICATIONS
U.S. DEPARTMENT OF AGRICULTURE- ANIMAL
AND PLANT HEALTH INSPECTION SERVICE