USDA B63 RFI Log.xlsx

XLSX spreadsheet 12 KB Posted

Attached to
Building 63 Envelope and HVAC Renovation, Coral Gables
Solicitation number
12639526Q0232
Issued by

About this file

This is a Request for Information (RFI) log documenting technical clarifications submitted by potential bidders for the Building 63 Envelope and HVAC Renovation project at the USDA Subtropical Horticulture Research Agricultural Research Service (ARS) Station in Coral Gables. The log captures eleven RFIs submitted on August 10, 2026, addressing design and specification ambiguities in the solicitation documents prepared by A&E firm Clark Nexsen.

Key technical issues raised include clarification on acoustical ceiling tile scope (existing-to-remain versus new installation), superintendent dual-role authorization under the project's quality control management structure, phasing requirements for chiller and pumps replacement coordination with controls work, fire-alarm system disconnection and reconnection specifications, extent of EIFS (Exterior Insulation and Finish System) work scope, and roof truss structural reinforcement requirements with connection details. Government responses clarified that ACT in non-demolished areas remains existing conditions, a qualified superintendent may hold only one additional responsibility, chiller replacement coordinates with controls rather than phase designations, smoke detector work is governed by specification 013516, and bidders require consistent scope quantification. The log indicates that responses were provided without formal amendments for most clarifications, with some items pending further definition or documentation by the project management team.

View the file

Other files

File Type Posted
RFIs and Responses_08252026.docx DOCX document
AE201 Rev_A 20260825.pdf PDF
12639526Q0232-0003.pdf PDF
RFIs and responses.pdf PDF
12639526Q0232-0002.pdf PDF
Site visit attendance.pdf PDF
12639526Q0232-0001.pdf PDF
Final Specifications.pdf PDF
Final Drawings.pdf PDF
Attachment 4_Federal Construction Wage Rates_Miami-Dade County.txt TXT text file
Attachment 2_Drawings.pdf PDF
Attachment 3_Specifications.pdf PDF
Attachment 1_Statement of Work.doc DOC document
12639526Q0232.docx DOCX document
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PPI Log

PPI #Question DateRFI #QuestionGovernment ResponseRFP / Solicitation Attachment Provided Yes or NoResponse Provided ByTechnical Request for Amendment # (Note this is the Tech Amend # not the ACQ Amend #; tech amend is A, B, C, etc.)PM RELEASE (INITIALS)DATE PM RELEASED TO ACQ FOR ACQ AmendmentACQ Amend #
18/10/20261Reflected ceiling plan AE-111 indicates acoustical ceiling tile (ACT), but the Project Manual contains no acoustical panel ceiling specification section (e.g., 095113). Please confirm the intended ACT product, suspension grid, and performance requirements, or confirm the ceiling is existing-to-remain and not part of this scope.ACT in areas that are not shown to be demolished are exisitng-to-remain. In areas where ACT is being demolished no new ACT is being installed.No
28/10/262Can the superintendent act as the SSHO and QCM if qualified? If not please clarifyA working superintendent may only have one other responsibility.No
38/10/263Is the chiller and piping replacement to occur in phase 1 or phase 2?See notes 3 and 4 on drawing sheet G1003. Chiller and pumps replacement is to be coordinated with controls replacement, not tied to Phase 1 or Phase 2.No
58/10/20264ED-101 indicates disconnection and reconnection of duct smoke detectors and fire-alarm devices, but the Project Manual contains no fire-alarm (Div 28) specification section. Please provide the governing specification/scope and confirm the extent of fire-alarm work required for this project.Any smoke detectors that require removal are to be tested, disconnected, stored, and re-connected when ceiling work is complete. This is governed by spec 013516.No
6No
7No
8No
9No
108/10/202610Please clarify the extent of EIFS work — full replacement versus localized repair — and identify the limits on the drawings so all bidders quantify the scope consistently.No
118/10/202611Structural drawing SF-101 references roof-truss/structural reinforcement. Please confirm the extent of reinforcement required, the responsible trade, and provide connection details where reinforcement is indicated.No
12No

Page &P of &N

Sheet1

File details come from the government source that posted it. Updated .