WWCX151009-RepairArcticFoundationB4002-Drawings.pdf

PDF 7 MB Posted

Attached to
Repair Arctic Foundation Bldg 4002 (WWCX 15-1009) Pituffik Space Base, Greenland - Amendment 0001
Solicitation number
FA252325R0002
Issued by

About this file

These are architectural and engineering drawings for the Improve Arctic Foundation project at Thule Air Base in Greenland, prepared for the United States Space Force (USSF). The comprehensive set of drawings includes electrical, mechanical, and architectural plans for Building 4002, focusing on detailed improvements to the Arctic air distribution and ventilation systems. Key components include:

Electrical and mechanical systems involve installing new Arctic Air Stacks (AAS), Distribution Duct Dividers (DDD), dampers, actuators, and controllers across 31 fan locations. The drawings specify complex temperature-based control logic where dampers and fans automatically operate based on outside air temperature and Arctic air stack temperature, with provisions for manual and automatic modes. The project includes new Trend IQ4 fan/damper controllers, electrical panel upgrades, and precise mounting and installation specifications for extreme Arctic conditions, with extensive notes on coordinating installation, maintaining equipment clearances, and adhering to applicable building and safety codes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

COVER SHEET

NTS

4002_G0.001.dwg

JLE

JLE 4002

G0-001

USSF

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

INDEX TO DRAWINGS

NTS

4002_G0.002.dwg

JLE

JLE 4002

G0-002

DETAIL - PLAN SECTION 1:20

A5-001

DETAIL - VERTICAL CROSS SECTION 1:20

A5-001

DETAIL - VERTICAL CROSS SECTION 1:20

A5-001

NOT USED

A5-001

ARCTIC AIR DISTRIBUTION DUCT (AADD)

CONCRETE MANIFOLD

B

A A

B

ARCTIC AIR STACK

(AAS)

D I S

T R

I B

U T

I O

N

D

U C

T

D

I V

I D

E R

D I S

T R

I B

U T

I O

N

D

U C

T

D

I V

I D

E R

DAMPER

ARCTIC AIR DISTRIBUTION DUCT (AADD)

NEW DISTRIBUTION DUCT DIVIDER (DDD)

ARCTIC AIR STACK

(AAS)

NEW DISTRIBUTION

DAMPER

ARCTIC AIR

DISTRIBUTION

DUCT (AADD)

STEEL HINGE

SEALING/FILLER

35x35 MM STEEL PROFILE

16 MM PLYWOOD PLATE

STEEL WINDER

DUCT DIVIDER (DDD)

ARCTIC AIR STACK

(AAS)

NOTES:REFERENCES: X

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

1:20

400 800 1600

DETAILS

ARCHITECTURE

AS NOTED

4002_A5.001.dwg

A5-001

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

COVER SHEET

ELECTRICAL

NTS

4002_E0.001 (cover).dwg

BPA

RPT 4002

E0-001

SYMBOL DEVICES & POWER

RECEPTACLE - SIMPLEX

RECEPTACLE - DUPLEX

GFI RECEPTACLE - DUPLEX (GROUND FAULT INTERRUPT)

WP

TR

D

IG

RECEPTACLE - DOUBLE DUPLEX

GFI RECEPTACLE - DOUBLE DUPLEX

- SAME INDICATORS AS SHOWN FOR DUPLEX RECEPTACLE

RECEPTACLE - 208V

R

D

W

208V RECEPTACLE IN RECESSED FLOORBOX

DUPLEX RECEPTACLE IN RECESSED FLOORBOX

DOUBLE DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX

J-BOX - BOX INDICATES FLOOR MOUNTING -4"X4"X2-1/8" DEEP

UNLESS OTHERWISE NOTED

SPECIAL PURPOSE CONNECTION - BOX INDICATES FLOOR

MOUNTING - WORK AS NOTED

RECEPTACLE - DUPLEX, MOUNTING IN CEILING

MANUAL MOTOR STARTER/DISCONNECT SWITCH

DISCONNECT SWITCH

ELECTRIC MOTOR CONNECTION

EXISTING PANELBOARD, SURFACE MOUNTED

EXISTING PANELBOARD, FLUSH MOUNTED

ELECTRIC METER, BUILDING MOUNTED

TRANSFORMER

J JJ

CLG

THERMOSTAT BY MC, J-BOX & CONDUIT TO CEILING BY EC

CIRCUIT BREAKER

PANELBOARD, SURFACE MOUNTED

PANELBOARD, FLUSH MOUNTED

M

T

CODE REQUIREMENTS

1. THE PUBLICATIONS AND STANDARDS OF THE FOLLOWING AUTHORITIES, IN

ADDITION TO THOSE SPECIFIED IN RELATED SUPPLEMENTARY CONDITIONS,

SHALL BE OBSERVED DURING CONSTRUCTION AND ARE REFERENCED IN

THE DOCUMENTATION BY THE ABBREVIATIONS NOTED:

1.1. UNITED STATES OF AMERICA STANDARDS INSTITUTE - USASI

1.2. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS - IEEE

1.3. NATIONAL ELECTRICAL CODE - NEC

1.4. NATIONAL FIRE PROTECTION ASSOCIATION - NFPA

1.5. UNDERWRITER'S LABORATORY - UL

1.6. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION - NEMA

1.7. CERTIFIED BALLAST MANUFACTURERS - CBM

1.8. AMERICAN SOCIETY FOR TESTING AND MATERIALS - ASTM

1.9. OCCUPATIONAL SAFETY AND HEALTH ACT - OSHA

2. U.N.O., EQUIPMENT AND DEVICES SHALL BE MOUNTED PER ADA AND TAS

REQUIREMENTS.

2.1. OPERABLE DEVICES (SWITCHES, CARD READERS, ETC) AT OR BELOW

48" AFF

2.2. RECEPTACLES, TELEPHONE AND DATA OUTLETS AT 18" AFF (15" MIN TO

BOTTOM OF DEVICE), UNO

3. ALL WORK SHALL BE PERFORMED PER NEC, AND ALL WORK SHALL BE

PERFORMED IN COMPLIANCE WITH THE LATEST EDITION OF ALL LOCAL

AMENDMENTS AND REGULATIONS.

SCOPE OF WORK

1. THE SCOPE OF WORK SHALL INCLUDE COMPLETE PROVISIONS FOR

ELECTRICAL POWER DISTRIBUTION TO ALL LIGHTING, DEVICES,

APPLIANCES, AND EQUIPMENT SHOWN ON THE CONSTRUCTION

DOCUMENTS.

1.1. PROVISIONS INCLUDE, BUT ARE NOT LIMITED TO, ALL SUPPLIES,

MATERIALS, EQUIPMENT, TOOLS AND LABOR.

1.2. PROVISIONS ALSO INCLUDE ALL MISCELLANEOUS MATERIALS

REQUIRED TO COMPLETE THE WORK SHOWN INCLUDING, BUT NOT

LIMITED TO, SUPPORTS, HANGERS, RACEWAYS, BOXES, SLEEVES,

SEALS, EQUIPMENT PADS, WIRING CONNECTORS, TERMINALS, LABELS,

SIGNS, AND MARKERS.

1.3. THE CONSTRUCTION DOCUMENTS INCLUDE ALL PLANS, ELEVATIONS,

DETAILS, DIAGRAMS, SCHEDULES, AND NOTES ON THE DRAWINGS.

1.4. WHERE USED ON THE PLANS AND WHERE NOT SPECIFICALLY NOTED

OTHERWISE, THE TERM "PROVIDE" AND THE TERM "INSTALL" SHALL

MEAN FURNISH, INSTALL, CONNECT AND TEST.

1.5. UNLESS EXPLICITLY NOTED "BY OTHERS" OR "EXISTING", ALL ITEMS

SHOWN GRAPHICALLY OR SPECIFIED BY NOTES AND DETAILS ON THE

PLANS SHALL BE FURNISHED, INSTALLED, CONNECTED, AND TESTED

AS NEEDED.

2. ADDITIONALLY, THE SCOPE OF WORK SHALL INCLUDE

2.1. APPLICATION FOR TEMPORARY AND PERMANENT ELECTRICAL

SERVICE, PERMITTING, AND INSPECTION.

2.2. TESTING AND COMMISSIONING.

2.3. EQUIPMENT RENTAL.

2.4. TEMPORARY CONSTRUCTION POWER AND LIGHTING.

2.5. PROVISIONS FOR MAINTAINING THE FUNCTIONALITY OF EXISTING TO

REMAIN BUILDING COMMUNICATIONS, FIRE ALARM, SECURITY/ACCESS

CONTROL, PUBLIC ADDRESS, AND BELL SYSTEMS THAT WILL BE

AFFECTED BY THE WORK.

SUBMITTALS

1. PRODUCT DATA: SUBMIT CATALOG DATA SHOWING MANUFACTURER'S

NAME AND CONTACT INFORMATION, ALL STANDARD FEATURES, AMPERAGE,

VOLTAGE, AIC RATINGS, DIMENSIONS, WEIGHTS, LISTINGS & PRODUCT

LABELS, MATERIAL TYPES, FINISHES AND CLEARLY INDICATING WHICH

OPTIONAL FEATURES WILL BE PROVIDED.

1.1. WHERE MULTIPLE SIZES ARE LISTED, INDICATE SIZES TO BE USED.

1.2. WHERE MULTIPLE PRODUCTS ARE SHOWN ON THE SAME PAGE,

INDICATE WHICH PRODUCTS TO BE USED.

COORDINATION

1. ALL POWER OUTAGES SHALL BE COORDINATED IN WRITING WITH OWNER

ONE (1) WEEK (MIN) PRIOR TO THE OUTAGE.

2. COOPERATE FULLY WITH THE OWNER OR HIS REPRESENTATIVE DURING

CONSTRUCTION OPERATIONS TO MINIMIZE CONFLICTS AND TO FACILITATE

OWNER USAGE SO AS NOT TO INTERFERE WITH THE OWNER'S

OPERATIONS.

3. THE DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT SHOW SWITCHES,

POWER AND DATA OUTLETS, SPECIAL SYSTEMS COMPONENTS (FA, ACCESS

CONTROL, A/V, ETC), ELECTRICAL EQUIPMENT, EQUIPMENT CONNECTIONS,

REQUIRED RACEWAY, ETC. IN THEIR EXACT DIMENSIONED LOCATIONS. THE

CONTRACTOR MUST CAREFULLY REVIEW THE ARCHITECTURAL,

STRUCTURAL MECHANICAL, PLUMBING, FIRE PROTECTION, AND SPECIAL

SYSTEMS PLANS TO IDENTIFY CONFLICTS AND AREAS THAT REQUIRE

COORDINATION.

4. COORDINATE ELECTRICAL AND SPECIAL SYSTEMS EQUIPMENT ROUGH-IN

WITH FURNITURE, MILLWORK, SIGNS, MECHANICAL AND PLUMBING

SYSTEMS, SPRINKLER SYSTEMS, ARCHITECTURAL AND STRUCTURAL

ELEMENTS, AND THE OWNER'S REPRESENTATIVE. MINOR CHANGES IN

ELECTRICAL EQUIPMENT LOCATIONS AND LAYOUT THAT ARE REQUIRED BY

SITE CONDITIONS OR ORDERED BY THE DESIGN TEAM PRIOR TO

PERFORMANCE OF WORK SHALL BE MADE BY THE CONTRACTOR WITHOUT

ADDITIONAL CHARGES TO THE OWNER.

5. MAINTAIN REQUIRED NEC WORKING SPACE AND DEDICATED EQUIPMENT

SPACE AROUND ALL ELECTRICAL EQUIPMENT, CONTROLS PANELS, ETC

THAT ARE SUBJECT TO MAINTENANCE, TESTING, OR USER INTERFACE.

COORDINATE WITH OTHER TRADES. IF CLEARANCE CANNOT BE PROVIDED,

THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO ROUGH-IN.

6. COORDINATE COLOR SELECTIONS FOR LUMINAIRES AND ALL DEVICE

PLATES WITH ARCHITECT PRIOR TO INSTALLATION.

QUALIFICATIONS

1. MANUFACTURER: COMPANY SPECIALIZING IN MANUFACTURING PRODUCTS

SHOWN ON THE CONSTRUCTION DOCUMENTS WITH MINIMUM THREE YEARS

DOCUMENTED EXPERIENCE

2. INSTALLER: GREENLAND QUALIFIED LICENSED ELECTRICIAN WITH

DOCUMENTED EXPERIENCE INSTALLING ALL EQUIPMENT SPECIFIED HERE

IN SHALL DIRECTLY SUPERVISE ALL WORK. WHERE NOTED IN THE

SPECIFICATIONS, REQUIRED BY CODE, OR REQUIRED BY THE

MANUFACTURER, INSTALLER SHALL BE A MANUFACTURER TRAINED AND/OR

CERTIFIED INSTALLER OF THE SPECIFIC PRODUCT TO BE INSTALLED.

3. WHERE TESTING IS REQUIRED BY THE CONSTRUCTION DOCUMENTS,

EQUIPMENT MANUFACTURER, OR CODE; TESTING SHALL BE PERFORMED

BY AN AGENCY WITH DOCUMENTED EXPERIENCE AND PROPERLY

CALIBRATED, FULLY FUNCTIONING EQUIPMENT, THAT IS A MEMBER OF THE

INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR IS A NATIONALLY

RECOGNIZED TESTING LABORATORY (NRTL), AND IS ACCEPTABLE TO THE

AUTHORITY HAVING JURISDICTION.

QUALITY ASSURANCE

1. UNLESS OTHERWISE APPROVED, ALL EQUIPMENT SHALL BE NEW,

PROPERLY DESIGNED, FROM A REPUTABLE MANUFACTURER MEETING THE

SPECIFICATION QUALIFICATIONS, IN COMPLIANCE WITH THE SPECIFICATION

REQUIREMENTS, AND IN FULL WORKING ORDER.

2. WHERE TWO OR MORE ITEMS OF THE SAME CLASS OF EQUIPMENT ARE

REQUIRED, THESE ITEMS SHALL BE PRODUCTS OF A SINGLE

MANUFACTURER; HOWEVER, THE COMPONENT PARTS OF THE ITEM NEED

NOT BE THE PRODUCTS OF THE SAME MANUFACTURER UNLESS STATED IN

THE TECHNICAL SECTION.

3. LISTING AND LABELING: WHERE REQUIRED, ALL ELECTRICAL

COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND

LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY

ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND MARKED FOR

THE INTENDED USE. TESTING AGENCY SHALL BE UL UNLESS NOTED

OTHERWISE OR PRE-APPROVED BY OWNER AND AHJ.

4. ALL EQUIPMENT USED FOR TESTING SHALL BE IN FULL WORKING ORDER

AND CALIBRATED PER THE MANUFACTURER'S RECOMMENDATIONS.

DELIVERY AND STORAGE

1. STORE ALL ELECTIRCAL/SPECIAL SYSTEMS EQUIPMENT/MATERIALS IN

CLEAN, DRY SPACE LOCATED ABOVE GRADE. PROTECT FROM DIRT, WATER,

CONSTRUCTION DEBRIS, TRAFFIC, FREEZE, AND DETERIORATION FROM

SUN LIGHT.

2. MAINTAIN FACTORY WRAPPING OR PROVIDE APPROPRIATE COVER FOR ALL

LARGE ELECTRICAL EQUIPMENT. FOLLOW ALL MANUFACTURER

RECOMMENDATIONS FOR HUMIDITY AND MAX/MIN TEMPERATURES FOR

STORING ELECTRICAL EQUIPMENT.

IDENTIFICATION

1. PROVIDE APPROPRIATE LABELS AND WARNING SIGNS FOR ALL EQUIPMENT,

WIRING DEVICES, CONDUCTORS, CABLES, BOX, AND ENCLOSURES.

PROVIDE BURIED DETECTABLE WARNIGN TABLE FOR UNDERGROUND

CONDUITS.

2. CONDUCTOR TAGGING: TAG ALL CONDUCTORS AT MOTOR CONTROLS,

PANELS, TERMINAL CABINETS AND JUNCTION BOXES. TAG CIRCUITS WHICH

PASS THROUGH OTHER DEVICES SUCH AS LIGHTING CONTACTORS.

3. PROVIDE A TYPED PANEL DIRECTORY FOR EACH PANEL PROVIDED OR

MODIFIED FOR THIS PROJECT. DIRECTORY SHALL IDENTIFY THE CIRCUIT

NUMBER, LOADS SERVED, AND LOCATION OF LOADS BY ROOM NUMBER.

MOUNT ON INSIDE OF EACH PANEL AND FILE THEM WITH THE OWNER WHEN

THE WORK IS COMPLETED.

4. PROVIDE EACH PANEL WITH A MANUFACTURER PREPARED ARC FLASH

HAZARD WARNING LABEL.

5. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED BY MEANS OF 3"X1"

(MIN)NAMEPLATES PERMANENTLY ATTACHED TO THE EQUIPMENT, PLATES

SHALL BE METAL, PLASTIC, OR SIMILAR, BLACK WITH 1/4"h (MIN) ENGRAVED

WHITE LETTERS.

6. JUNCTION AND PULL BOXES SHALL BE LABELED WITH PANEL NAME, CIRCUIT

#, AND VOLTAGE.

7. RECEPTACLES SHALL BE LABELED WITH THE PANEL NAME AND CIRCUIT #.

USE WHITE LABELS WITH BLACK TEXT.

8. FIRE ALARM, EMERGENCY/CRITICAL PWR, LIFE SAFETY LABELS, INCLUDING

RECEPTACLES, SHALL BE COLOR CODED & ENGRAVED.

WEATHER PROOF

TAMPER RESISTANT

DEVICE RCPT W/ 2 USB PORTS

(HUBBELL USB20X2(X))

ISOLATED GROUND

RANGE - NEMA 14-50R

DRYER - NEMA 10-30R

WELDER - NEMA 14-50R

NEMA CONFIGURATION AS NOTED

SWITCH - SPST

OS

D

T

OS

WP

DIMMER

TIMER SWITCH

THREEWAY

WEATHER PROOF

OS

GENERAL REQUIREMENTS

1. ALL TERMINALS, LUGS AND BUS JOINTS SHALL BE TIGHTENED PER THE MANUFACTURER'S TORQUE

RECOMMENDATIONS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A LETTER TO THE ELECTRICAL

INSPECTOR STATING WHEN IT WAS COMPLETED.

2. NO FOREIGN SYSTEMS SUCH AS PIPING, DUCT WORK, ETC SHALL BE INSTALLED ABOVE ELECTRICAL

EQUIPMENT.

3. PROVIDE SLEEVES FOR PENETRATIONS THROUGH WALLS/FLOORS. SEAL ALL OPENINGS. USE FIRE-RATED

SEALANT FOR OPENINGS IN RATED WALLS.

4. PERFORM GROUND PENETRATING RADAR SCAN BEFORE CUTTING EXISTING STRUCTURES. COORDINATE

LOCATIONS WITH STRUCTURAL ENGINEER/ARCHITECT.

CONDUCTORS AND CABLES

1. ALL BUILDING WIRING SHALL BE INSULATED COPPER CONDUCTORS RUN FROM LOAD TO SOURCE INSIDE

RACEWAY, CONTINUOUS (WITHOUT SPLICES) BETWEEN JUNCTION AND PULL BOXES, AND EXPOSED INSIDE

PANELS ONLY.

2. ALL SINGLE POLE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR ROUTED TO THE SOURCE PANEL.

3. FIELD VERIFY WHETHER A NEUTRAL IS REQUIRED FOR ALL TWO AND THREE POLE CIRCUITS. FOR ALL LOADS

EXCEPT MOTORS, A NEUTRAL IS ASSUMED TO BE REQUIRED UNLESS FIELD DETERMINED TO BE

UNNECESSARY.

4. ALL POWER & CONTROL WIRING ROUTED THROUGH RETURN AIR PLENUMS SHALL BE PLENUM RATED.

5. UP TO 3-20A CIRCUITS MAY SHARE A RACEWAY FOR HOMERUNS WHERE SUITABLE & PER NEC CONDUIT FILL

RULES.

6. 120V, 20A. HOME RUNS LONGER THAN 100' AND 277V, 20A. HOME RUNS LONGER THAN 150' SHALL BE #10 MIN.

GROUNDING AND BONDING

1. ALL RACEWAYS AND CIRCUITS SHALL BE PROVIDED WITH A NEC 250 COMPLIANT GREEN GROUND CONDUCTOR.

2. ALL EQUIPMENT SHALL BE PROPERLY BONDED.

3. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL BE MEGGER TESTED

AND PROVED TO BE FREE OF UNWANTED GROUNDS AND OTHER DEFECTS.

HANGERS AND SUPPORTS

1. SUPPORT RACEWAYS USING GALVANIZED STEEL OR MALLEABLE IRON STRAPS; CHANNEL OR PIPE CLAMPS AS

APPROPRIATE.

2. PROVIDE SUPPORTS AT ALL BOXES, ELEC. EQUIP., LOADS, & AT CODE REQUIRED INTERVALS ALONG

RACEWAYS.

3. GROUP RELATED RACEWAYS AND SUPPORT USING STEEL CHANNEL CONDUIT RACKS WITH 25% SPARE

CAPACITY.

4. SUPPORT LTG, ELEC. EQUIP., RACEWAYS/BOXES, ETC. INDEPENDENTLY. DO NOT USE CEILING SUPPORT

WIRES, PIPING SYSTEMS, ETC.

RACEWAY AND BOXES

1. PROVIDE COMPLETE RACEWAY SYSTEMS FROM SOURCE TO ALL LOADS WITH DEDICATED SUPPORTS FOR

EACH RACEWAY ELEMENT.

2. PROVIDE ALL REQUIRED BOXES & SUPPORTS FOR WIRING DEVICES, TELECOMMUNICATIONS, FIRE ALARM, ACCESS CONTROL, CONTROLS EQUIPMENT, ALARMS, SENSORS, ETC.

3. PROVIDE PULL BOXES AT APPROPRIATE LOCATIONS FOR ALL POWER AND SPECIAL SYSTEMS RACEWAYS

WHETHER SHOWN ON PLANS OR NOT. INSTALL IN CONCEALED, ACCESSIBLE LOCATIONS.

4. DO NOT INSTALL RACEWAY WITH MORE THAN THE EQUIVALENT OF THREE NINETY DEGREE BENDS BETWEEN

PULL POINTS.

5. COORDINATE INTERIOR ROUTING WITH OTHER TRADES; STRUCTURE; NEW AND EXISTING UTILITIES, DUCTWORK, PIPING; AND OTHER EXISTING CONDITIONS AS REQUIRED FOR A COMPLETE, CONFLICT FREE

INSTALLATION.

6. ROUTE RACEWAYS PARALLEL AND PERPENDICULAR TO WALLS, FLOORS, AND CEILINGS.

7. ROUTE EXPOSED CONDUIT PARALLEL AND TIGHT TO STRUCTURAL ELEMENTS. FOLLOW ALL SURFACE

CONTOURS; DO NOT ROUTE IN FREE AIR FROM POINT TO POINT.

8. INSTALL RACEWAYS SO THAT IT DRAINS TO JUNCTION AND PULL BOXES TO AVOID MOISTURE TRAPS AT LOW

POINTS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN CONDUIT SYSTEM.

9. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES SEISMIC, CONTROL, AND EXPANSION JOINTS.

10. INSTALL SUITABLE PULL STRING OR CORD IN EACH EMPTY RACEWAY, LABEL, AND CAP.

11. CLOSE ENDS AND UNUSED OPENINGS IN SURFACE RACEWAYS, WIREWAY, BOXES, AND ENCLOSURES.

12. WHERE POSSIBLE, ALL CONDUIT ROUTED THROUGH ROOF STRUCTURE SHALL SHARE COMMON

PENETRATIONS AS MECHANICAL DUCTWORK OR PIPING. COORDINATE WITH MECHANICAL CONTRACTOR.

13. ALL ROOF AND WALL PENETRATIONS SHALL BE FLASHED AND SEALED TO MAINTAIN THE FIRE RATING AND

WATERPROOFING OF THE STRUCTURE PER THE MANUFACTURER OF THE MATERIAL'S RECOMMENDED

PRACTICES.

14. USE MULTI-GANG BOXES IN ALL POSSIBLE LOCATIONS.

15. ALL CONDUIT SHALL HAVE AN NEC COMPLIANT GROUND AND AN INSULATED THROAT BUSHING IN PLACE FOR

PULLING CONDUCTORS.

16. ALL CONNECTIONS TO MOTORS, INSTRUMENTS, MACHINES, AND EQUIPMENT SUBJECT TO MOVEMENT OR

VIBRATION SHALL BE MADE USING LIQUID-TIGHT, FLEXIBLE METAL CONDUIT (LFMC), (3FT MAX).

WIRING DEVICES

1. PROVIDE A SECOND "ISOLATED" CODE SIZE GROUND IN CIRCUIT THAT IS DEDICATED TO DEVICES IDENTIFIED

AS "I.G".

2. DUPLEX RECEPTACLES MOUNTED ON OPPOSITE SIDES OF A COMMON WALLS SHALL BE A MINIMUM OF 12"

APART. (NO BACK TO BACK OUTLETS) TO REDUCE NOISE TRANSFER, JUNCTION BOXES IN ADJACENT ROOMS

SHALL NOT BE INSTALLED IN THE SAME WALL CAVITY. SEPARATE ALL JUNCTION BOXES BY AT LEAST ONE

FRAMING MEMBER.

3. PROVIDE GFI RECEPTACLES & DIMMERS WITH DEDICATED NEUTRALS INDEPENDENT OF OTHER LOADS ON THE

CIRCUIT.

LIGHTING

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LIGHT FIXTURE LOCATIONS AND

QUANTITIES.

2. EXAMINE THE AREA OF INSTALLATION TO VERIFY ADEQUATE SPACE AND MOUNTING PROVISIONS ARE

PROVIDED FOR THE SPECIFIED LUMINAIRE PRIOR TO ORDERING LUMINAIRES.

3. VERIFY THAT LUMINAIRES WILL NOT INTERFERE WITH REQUIRED CLEARANCES FOR EQUIPMENT INCLUDING

FILTER PULL SPACE, NEC WORKING SPACE IN FRONT OF DISCONNECTS, CONTROL PANELS, ETC.

4. COORDINATE EXIT LIGHT LOCATIONS WITH STRUCTURE AND BUILDING SYSTEMS TO INSURE EXIT SIGNS ARE

VISIBLE.

5. PROVIDE GROUND WIRE AND ONE NEUTRAL CONDUCTOR PER CIRCUIT IN ALL LIGHTING CONDUIT.

6. LABEL ALL CIRCUIT BREAKERS SERVING EMERGENCY LIGHTING.

7. UNO, ALL EXIT SIGNS, EMERGENCY EGRESS PATHWAY LIGHT FIXTURES, LIGHTS NOTED "xE", AND LIGHTS

SHOWN CROSS HATCHED SHALL BE CONNECTED TO THE SWITCHED AREA LIGHTING CIRCUIT FOR NORMAL

OPERATION AND AN UNSWITCHED CIRCUIT FROM THE SAME OCPD TO AUTOMATICALLY CONTROL POWER

TRANSFER TO AN INTEGRAL BATTERY PACK FOR 90 MINUTES OF EMERGENCY OPERATION WHEN LOSS OF

NORMAL POWER IS SENSED ON THE UNSWITCHED CIRCUIT. PROVIDE A BATTERY STATUS INDICATOR

MOUNTED IN A VISIBLE LOCATION.

8. INSTALL FIXTURES PLUMB, SQUARE AND LEVEL WITH CEILINGS AND WALLS AND SECURE FIXTURES PER

MANUFACTURER'S PRINTED INSTRUCTIONS.

9. ADJUST AIMABLE FIXTURES, CLEAN, AND PROVIDED ALL FIXTURES WITH LAMPS PRIOR TO OWNER

OCCUPANCY.

10. U.N.O., LIGHTING SWITCHES IN ROOMS SHALL CONTROL ONLY FIXTURES IN THAT ROOM.

11. WHEN MORE THAN ONE(1) LIGHTING SWITCH IS SHOWN AT A LOCATION THEY SHALL BE GANGED TOGETHER.

12. LUMINAIRE WHIPS SHALL BE FLEXIBLE METAL CONDUIT, 6FT MAX. SECURE TO STRUCTURE WITH LISTED

SUPPORTS.

LIGHTING CONTROL REQUIREMENTS

1. OCCUPANCY SENSOR OFF DELAY SHALL BE SET BY EC AT END OF PROJECT TO 15 MINUTES. AMBIENT LIGHT

OVERRIDE SHALL BE SET SUCH THAT THE LUMINAIRES ARE SWITCHED OFF WHEN APPROPRIATE FC LEVEL IS

MEASURED ON THE FLOOR (REGARDLESS OF THE FOOTCANDLES MEASURED AT THE OCCUPANCY SENSOR).

2. INSTALL DIMMER SWITCHES ON THE LOAD SIDE OF VACANCY SENSORS AND OTHER CONTROLS.

USSF

AutoCAD SHX Text

LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS

AutoCAD SHX Text

WALL MOUNT FIXTURE, SIZE ON PLANS

AutoCAD SHX Text

SURFACE MOUNT FIXTURE, SIZE ON PLANS

AutoCAD SHX Text

PENDANT OR SURFACE MOUNTED LIGHT FIXTURE, SIZE ON PLANS

AutoCAD SHX Text SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED, AND ALSO INDICATES EMERGENCY POWER OR EMERGENCY BALLAST.

AutoCAD SHX Text

RECESSED FIXTURE

AutoCAD SHX Text

SURFACE MOUNTED FIXTURE

AutoCAD SHX Text

TRACK FIXTURE, SEE PLAN FOR SIZE AND HEADS

AutoCAD SHX Text

CEILING MOUNT EXIT LIGHT (W/ DIRECTIONAL ARROWS)

AutoCAD SHX Text

WALL MOUNT EXIT LIGHT (W/ DIRECTIONAL ARROWS)

AutoCAD SHX Text

1 HEAD REMOTE EMERGENCY LIGHT BATTERY PACK

AutoCAD SHX Text

LEGEND

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

LIGHTING

AutoCAD SHX Text

2 HEAD EMERGENCY LIGHT BATTERY PACK

AutoCAD SHX Text

1 HEAD REMOTE EMERGENCY LIGHT

AutoCAD SHX Text

2 HEAD LIGHT WITH MOTION SENSOR

AutoCAD SHX Text

WALL MOUNTED FIXTURE

AutoCAD SHX Text

INDIRECT FIXTURE, SIZE ON PLANS

AutoCAD SHX Text

WALL WASH OR DIRECTIONAL FIXTURE

AutoCAD SHX Text

WALL SCONES FIXTURE

AutoCAD SHX Text

CEILING FAN FIXTURE

AutoCAD SHX Text

CLOCK HANGER RECEPTACLE

AutoCAD SHX Text

CABLE TV JACK

AutoCAD SHX Text

SPEAKER

AutoCAD SHX Text VOICE/DATA OUTLET - SUBSCRIPT INDICATES NUMBER OF CABLE/JACKS - NO SUBSCRIPT INDICATES 2 CABLES/JACKS

AutoCAD SHX Text

VOICE OUTLET WALL MOUNTED

AutoCAD SHX Text

COMMUNICATIONS

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text S

AutoCAD SHX Text W

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text

SPEAKER, WALL MOUNTED

AutoCAD SHX Text VOICE/DATA OUTLET MOUNTED IN FLOORBOX- SUBSCRIPT INDICATES NUMBER OF CABLE/JACKS - NO SUBSCRIPT INDICATES 2 CABLES/JACKS

AutoCAD SHX Text

EXISTING VOICE/DATA OUTLET

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ABBREVIATIONS AND MISCELLANEOUS

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

EC

AutoCAD SHX Text

ELECTRICAL CONTRACTOR

AutoCAD SHX Text

MC

AutoCAD SHX Text

MECHANICAL CONTRACTOR

AutoCAD SHX Text

GC

AutoCAD SHX Text

GENERAL CONTRACTOR

AutoCAD SHX Text C

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

GND

AutoCAD SHX Text

GROUND

AutoCAD SHX Text W/

AutoCAD SHX Text

WITH

AutoCAD SHX Text

NL

AutoCAD SHX Text

NIGHT LIGHT

AutoCAD SHX Text a,b,c etc.

AutoCAD SHX Text

SWITCH DESIGNATION

AutoCAD SHX Text

UG

AutoCAD SHX Text

UNDERGROUND

AutoCAD SHX Text

WM

AutoCAD SHX Text

WIRE MOLD

AutoCAD SHX Text

WP

AutoCAD SHX Text

WEATHER PROOF & WATER RESISTANT

AutoCAD SHX Text

BN1L-2,4,6

AutoCAD SHX Text

CIRCUIT DESIGNATION: PANELBOARD - CIRCUITS

AutoCAD SHX Text 1/E5.2

AutoCAD SHX Text

INDICATES DETAIL 1 ON SHEET E5.2

AutoCAD SHX Text

SHEET WORK NOTE

AutoCAD SHX Text

HOME RUN TO PANELS, NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS

AutoCAD SHX Text

CONDUIT CONCEALED IN CEILING OR WALL

AutoCAD SHX Text

CONDUIT CONCEALED UNDER FLOOR

AutoCAD SHX Text CIRCUIT, NUMBER OF HASH MARKS INDICATES NUMBER OF CONDUCTORS IN CABLE/RACEWAY. GROUND WIRE NOT SHOWN BUT SHALL BE INCLUDED. NO HASH MARKS INDICATES 2 CONDUCTORS PLUS GROUND.

AutoCAD SHX Text

BOD

AutoCAD SHX Text

BOTTOM OF DEVICE

AutoCAD SHX Text

COD

AutoCAD SHX Text

CENTER OF DEVICE

AutoCAD SHX Text

TEMPERATURE CONTROL CONTRACTOR

AutoCAD SHX Text

TC

AutoCAD SHX Text

SF

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

AC

AutoCAD SHX Text

ABOVE COUNTER, 4" ABOVE BACK SPLASH

AutoCAD SHX Text (E)

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

TYP

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text (R)

AutoCAD SHX Text

RELOCATED

AutoCAD SHX Text (N)

AutoCAD SHX Text

NEW

AutoCAD SHX Text

UON

AutoCAD SHX Text

UNLESS OTHERWISE NOTED

AutoCAD SHX Text

ATS

AutoCAD SHX Text

AUTOMATIC TRANSFER SWITCH

AutoCAD SHX Text

BLG

AutoCAD SHX Text

BELOW GRADE

AutoCAD SHX Text

AFF

AutoCAD SHX Text

ABOVE FINISHED FLOOR

AutoCAD SHX Text

AFG

AutoCAD SHX Text

ABOVE FINISHED GRADE

AutoCAD SHX Text

CLG

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

EF

AutoCAD SHX Text

EXHAUST FAN

AutoCAD SHX Text

QTY

AutoCAD SHX Text

QUANTITY

AutoCAD SHX Text

TELEPHONE TERMINAL BOARD

AutoCAD SHX Text

TTB

AutoCAD SHX Text

XFMR

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

AutoCAD SHX Text

DVR

AutoCAD SHX Text

DIGITAL VIDEO RECORDER

AutoCAD SHX Text

CCTV

AutoCAD SHX Text

CLOSED CIRCUIT TV

AutoCAD SHX Text

PTZ

AutoCAD SHX Text

PAN-TILT-ZOOM

AutoCAD SHX Text

CU

AutoCAD SHX Text

COPPER

AutoCAD SHX Text 1'-6"

AutoCAD SHX Text 44"

AutoCAD SHX Text 54"

AutoCAD SHX Text T

AutoCAD SHX Text

FINISHED FLOOR

AutoCAD SHX Text

FINISHED CEILING

AutoCAD SHX Text

AC = ABOVE COUNTER, MINIMUM 4" ABOVE BACKSPLASH TO BOTTOM OF DEVICE

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text F

AutoCAD SHX Text

INTERIOR BOX MOUNTING HEIGHTS

AutoCAD SHX Text 80" AFF TO BOTTOM OF DEVICE OR 6" BELOW CEILING TO TOP OF DEVICE WHICHEVER IS LOWER

AutoCAD SHX Text W

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text

BOD

AutoCAD SHX Text

COD

AutoCAD SHX Text

COD

AutoCAD SHX Text

COD

AutoCAD SHX Text

80" MINIMUM TO BOTTOM OF DEVICE

AutoCAD SHX Text

FIRE

AutoCAD SHX Text

FIRE

AutoCAD SHX Text

FIRE

AutoCAD SHX Text

BOD

AutoCAD SHX Text A

AutoCAD SHX Text

GENERAL CONDITIONS

AutoCAD SHX Text

INSTALLATION

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

OCCUPANCY SENSOR (CEILING) - SUBSCRIPT IS SWITCHLEG

AutoCAD SHX Text a

AutoCAD SHX Text

VS

AutoCAD SHX Text P

AutoCAD SHX Text

SINGLE POLE, DOUBLE THROW

AutoCAD SHX Text

MOTOR-RATED

AutoCAD SHX Text

OCCUPANCY SENSOR

AutoCAD SHX Text

VACANCY SENSOR W/ DIMMING

AutoCAD SHX Text

PILOT LIGHT

AutoCAD SHX Text

OCCUPANCY SENSOR (WALL) - SUBSCRIPT IS SWITCHLEG

AutoCAD SHX Text a

S t a i r n o

U p

U p

U p

Up

Stair no 2

Up

Up

Stair no 4

Up

Stair no 13

Up

Stair no 3

Up

Up

ELECTRICAL FIRST FLOOR PLAN 1:200

E1-001

C

B

A

D

E

G

J

K

L

M

N

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

H

F

4318 4318 4877 5029 5029 4877 4318 4318 4318 6096 6096 6096 6096 6096 6096 6096 6096 6096 6096 6096 2057 5359 5359

F5

G5

A F

A D

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A r c t i c

F o u n d a t i o n

A i r

D u c t

A

F A

D

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

A F

AFAD A1

AFAD C2

AFAD C1

AFAD A2

AFAD A3

AFAD C5

AFAD C4

AFAD C3

AFAD A4

AFAD A5

AFAD A6

F-19

37,39

F-18

34,36

F-17

33,25

F-16

30,32

F-15

29,31

F-14

26,28

F-13

25,27

F-12

22,24

F-11

21,23

F-10

18,20

F-09

17,19

F-08

14,16

F-07

13,15

F-06

10,12

F-05

9,11

F-03

5,7

F-02

2,4

F-01

1,3

F-24

46,48

F-25

49,51

F-26

50,52

F-27

53,55

F-28

54,56

F-29

57,59

F-30

58,60

F-31

61,63

F-20

38,40

F-21

41,43

F-22

42,44

F-23

45,47

T5T4

PNL 'WT02'

PNL 'WT01'

(N) FAN CTRL

NOTES:REFERENCES:

1. DEMOLISH EXIST. FAN. REPLACE WITH NEW.

2. PROVIDE AND INSTALL NEW ARCTIC AIR STACK (AAS) FAN AS SCHEDULED. REFER TO 4002_E5.001 FOR INSTALLATION DETAILS.

3. PROVIDE AND INSTALL NEW ARCTIC AIR STACK (AAS) ROUND DAMPER (DMPR-1) AND DAMPER ACTUATOR (DA-1) AS

SCHEDULED. REFER TO 4002_E5.001 FOR INSTALLATION DETAILS.

4. PROVIDE AND INSTALL NEW ARCTIC AIR STACK (AAS) TEMPERATURE SENSOR (T-1 THROUGHT T-6) AS PER PLAN.

5. RE: FAN'S CONTROL DIAGRAM 4002_E7.002.

6. VERIFY CONDITION AND INTEGRITY OF AN EXISTING TEMPERATURE SENSOR. REPLACE WITH NEW AS REQUIRED.

A. FURNISH AND INSTALL ALL ITEMS, INCLUDING EVERY ARTICLE, DEVICE, OR ACCESSORY REASONABLY NECESSARY TO FACILITATE EACH SYSTEM'S FUNCTIONING AS

INDICATED BY THE DESIGN AND THE EQUIPMENT SPECIFIED.

B. DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT NECESSARILY REFLECT ALL WORK REQUIRED TO COMPLETE PROJECT. CONTRACTOR SHALL REQUEST

ADDITIONAL INFORMATION IN CASES OF DOUBT.

C. REFER TO SPECIFICATIONS, SCHEDULES, DETAILS AND GENERAL NOTES SHEET FOR ADDITIONAL ELECTRICAL EQUIPMENT AND SYSTEM INSTALLATION REQUIREMENTS.

D. SPECIAL REQUIREMENTS SUCH AS WATERPROOF (WP), MOUNTING HEIGHT (+XY") ARE NOTED ADJACENT EQUIPMENT/RECEPTACLES .

E. ELECTRICAL CONTRACTOR SHALL PROVIDE POWER TO ALL ITEMS SHOWN FROM THE PANEL AND CIRCUIT NUMBERS THAT ARE SHOWN ADJACENT TO THE LOAD ( FANS, RECEPTACLE, DISCONNECT, JBOX, EQUIPMENT CONNECTION POINT, ETC). SIZE CIRCUIT PER PANEL SCHEDULE. PROVIDE NEUTRAL AND GROUND, U.N.O;

F. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY PANEL SCHEDULES AND AVAILABILITY OF REPLACEMENT PARTS FOR EXISTING PANELS PRIOR TO ORDERING NEW

PARTS FOR EXISTING PANELS OR INSTALLING CONDUIT.

G. UON, ALL CIRCUITS SHOWN ON THIS DRAWING WILL BE FED FROM PANEL 'WT03'.

X

(N)PNL 'WT03'

F-04

6,8

1 111

FAN DESIGNATION

ELECTRIC CIRCUIT#

(TYP.)

AADD West 3

AADD East 2

Arctic Air Distribution

Duct (AADD) East 1

DISTRIBUTION

DUCT DIVIDER

(DDD) 01-25 (TYP.)

DISTRIBUTION

DUCT DIVIDER

(DDD) 26-50 (TYP.)

DISTRIBUTION

DUCT DIVIDER

(DDD) 01-25 (TYP.)

AADD West 1

AADD West 2

DISTRIBUTION

DUCT DIVIDER

(DDD) 26-50 (TYP.)

ARCTIC AIR

STACK (AAS)

01- 31 (TYP.)

ARCTIC AIR STACK

(AAS) 01- 31 (TYP.)

ARCTIC AIR STACK

(AAS) 32-64 (TYP.)

ARCTIC AIR STACK

(AAS) 32- 64 (TYP.)

T3T2T1

T6

DMPR-1 AND DA-1

(TYP.)

AADD East 3

2 3

4 4 4

(E)

(E)

DMPR-1 AND DA-1

(TYP.)

DMPR-1 AND DA-1

(TYP.)

DMPR-1 AND DA-1

(TYP.)

DMPR-1 AND DA-1

(TYP.)

4 4

3 3 3

2 2

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

FIRST FLOOR PLAN

ELECTRICAL

1:200

4002_E1.001 (FP1).dwg

BPA

RPT 4002

E1-001

1:200

4000 8000 16000 0.00°

ACTUATOR ELECTRICAL CONNECTION NTS

E5-001

C

L

C

L

N

A

A

N

TERRAIN/GROUND LEVEL

BUILDING FACADE

ARCTIC AIR STACK (AAS)

AAS32 - AAS64

M20 BOLT L350MM 8EA

DMPR-1

WEATHER AND

WATERPROOF SEALANT

MATERIAL (TYPICAL)

MANIFOLD/PLENUM

CONCRETE

FOUNDATION

DA-1

T-1 THRU T-6

(WHERE APPLICABLE)

PLENUM

STACK (AAS)

PLENUM

STACK (AAS)

C

L

C

L

N

A

A

N

TERRAIN/GROUND LEVEL

ARCTIC AIR STACK (AAS)

AAS01 - AAS31

FAN ACCESS DOOR

MANIFOLD/PLENUM

CONCRETE

FOUNDATION

PLENUM

STACK (AAS)

PLENUM

STACK (AAS)

MOUNT PER MANUFACTURER'S

INSTRUCTIONS

F-01 - 31

AAS FAN ELECTRICAL CONNECTION NTS

E5-001

(*) 1" CONDUIT

1" CONDUIT BODY

CONDUIT PENETRATION

& SEALANT SHALL FOLLOW

BUILDING STANDARDS

JUNCTION BOX NEMA 3R

MC CABLE OR LMFC

RUBBER GROOMET

1" NIPPLE

STRAP SUPPORT

1" CONDUIT RUN

TO NEXT J-BOX/FAN

1" CONDUIT

1" CONDUIT BODY

CONDUIT PENETRATION

& SEALANT SHALL FOLLOW

BUILDING STANDARDS

JUNCTION BOX NEMA 3R

MC CABLE OR AS PER

MANUFACTURER

SPECIFICATION

1" NIPPLE

STRAP SUPPORT

1" CONDUIT RUN

TO NEXT J-BOX/FAN

NOTE:

(*) - MAX 4 FANS CAN BE

SUPPLIED VIA ONE (1)1" C

BUILDING FACADE

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

DETAILS

ELECTRICAL

NTS

4002_E5.001 (details).dwg

BPA

RPT 4002

E5-001

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

SCHEDULES

ELECTRICAL

NTS

4002_E6.001 (schedules).dwg

BPA

RPT 4002

E6-001

1. PER NEC 220.87, THE ACTUAL EXISTING MAXIMUM DEMAND LOAD ON PANEL "WT01' WAS DETERMINED BY TAKING THE MAXIMUM POWER DEMAND FROM POWER METER /LOGGER, MEASURED BETWEEN 05/14/22 TO 06/15 IN 2022. DATA LOG IS AVAILABLE UPON REQUEST.

2. PER POWER METER/LOGGER, THE ACTUAL MAXIMUM DEMAND AT 125% IS 60KVA.

3. ADDITIONAL LOAD ADDJUSTMET OF 30KVA WAS ADDED, REFLECTING SEASONAL WINTERS LOADS.

4. THE NEW DEMAND LOAD TO BE ADDED TO THE PANEL IS 21.4KVA.

5. THE COMBINED TOTAL OF 125% OF THE EXISTING MAXIMUM DEMAND, ADDITIONAL ADDJUSTEMENT, AND LOAD TO BE ADDED

BY THIS PROJECT IS LESS THAN THE RATING OF THE PANEL.

6. TOTAL NEW DEMAND ON PANEL "WT01" IS 309 AMPS.

REVISED ELECTRICAL SERVICE CALCULATION NOTES

ONE LINE DIAGRAM NTS

E7-001

(E)WT02

(E)WT01

208/120V 3Ø, 4W 400A

42CIR

400A/3P

(N)150A/3P 100A/3P

(N)WT03

208/120V 3Ø, 4W

200A PNL

150A MAIN

84CIR

4#1/0

#6 GND

2" C

208/120V 3Ø, 4W

125A PNL

100A MAIN

42CIR

(E)FEEDER

(N)FANS

CONTROL

PANEL

(E)FEEDER

(E)EMCS

(N)CTRL

CABLES

RS485

(N)6"X6"

WIREWAY

NEMA 1

LOAD SUMMARY NTS

E7-001

NOTES:REFERENCES:

1. SHORT CIRCUT RATING OF THE NEW PANEL SHALL MATCH THE SOURCE PANEL "WT001".

2. PROVIDE AND INSTALL NEW 150A/3P CIRCUIT BREAKER TO FEED PANEL "WT003". TYPE AND SHORT CIRCUIT RATING OF THE NEW BREAKER SHALL MATCH

EXISTING BREAKER IN THE PANEL.

3. EXISTING LOAD HAS BEEN DETERMINED USING ACTUAL MAXIMUM POWER DEMAND MEASURED BETWEEN 05/14/22 TO 06/15 IN 2022, IN ACCORDANCE WITH

NEC 220.87. DATA LOG IS AVAILABLE UPON REQUEST.

4. ESTIMATED SEASONAL WINTER'S LOADS (HEAD BOLT HEATHERS, HEAT TRACE); SHALL BE VERIFIED BY CONNECTING POWER LOGGER DURING THE COLDEST

WINTER MONTH (FEBRUARY) AND RESULTS PRESENTED TO THE EOR.

1. COMPLY WITH 2020 NEC, 2015 IECC, AND APPLICABLE CODES/STANDARDS.

2. ALL EQUIPMENT SHOWN IN GRAYSCALE IS EXISTING, SHOWN FOR REFERENCE; EQUIPMENT SHOWN IN BOLD SCALE IS NEW.

3. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL ELECTRICAL EQUIPMENT SHOWN AS NEW, UON

4. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL COSTS ASSOCIATED WITH THE INSTALLATION OF THE NEW ELECTRICAL SERVICE WITH UTILITY AND INCLUDE IN

BID.

5. PROVIDE ARC FLASH LABELING FOR ALL NEW EQUIPMENT AS REQUIRED PER NEC ARTICLE 110.16 AND NFPA-70E.

6. ALL CONDUCTORS SHALL BE COPPER TYPE THWN-2 (EXTERIOR).

7. ALL GROUNDING SHALL BE IN ACCORDANCE WITH NEC REQUIREMENTS.

8. REFER TO SPECIFICATIONS, SCHEDULES, DETAILS AND GENERAL NOTES SHEET FOR ADDITIONAL SITE REQUIREMENTS.

X

LOAD SUMMARY (EXISTING PANEL WT01, 400AMP, 208/120V, 3Ø, 4W)

LOAD TYPE KVA COMMENTS

20.4

SUBTOTAL NEW LOADS:

PANEL WT03 (FANS F-01 THRU F-031)

30 DAY MAXIMUM DEMAND

EXISTING LOAD DEMAND

MAX DEMAND

DEMAND ADJUSTMENT (25%)

TOTAL LOAD DEMAND (EXISTING + NEW)

TOTAL EXISTING DEMAND LOAD

111.4

NEW LOADS

REFLECTS NEC 220.87 ADJUSTMENT

KVA

309 AMPS @ 208V

21.4

CONTINUOUS LOAD

PANEL WT03 (AUX LOADS) 1

CONCLUSION: (400AMP > 310AMP) - THE (E)PANEL WT01, HAS ENOUGH AMPACITY FOR A NEW LOAD DEMAND

(E)HBH-1

208/120V 3Ø, 4W

125A PNL

100A MAIN

42CIR

(E)FEEDER

100A/3P

ADDITIONAL LOADS ADJUSTMENT 30 REFLECTS SEASONAL / WINTER'S LOADS

RF FILTER

FED ROOM

MAIN ELEC. ROOM

BRK 5L4

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

ONE LINE

DIAGRAM

ELECTRICAL

NTS

4002_E7.001 (one line).dwg

BPA

RPT 4002

E7-001

IN

P 1 IN

P 2 IN

P 3 IN

P 4 IN

P 5 IN

P 6 IN

P 7 IN

P 8 IN

P 9 IN

P 10

TX

TX

RX

RX

AU

X

V

OU

T 1 OU

T 2 OU

T 3 OU

T 4 OU

T 5 OU

T 6

GN

D 24V

AAST1

OAT

C1 A1

0-

VD

C

SINGLE

RELAY

MODULE

(TYP.)

TREND

IQ4E/LAN

CONTROLLER

I/0: 10UI (UNIVERSAL INPUTS) 6AO

(ANALOG OUTPUT)

C2 C3 C4 C5 C6

FROM

SS-2

FROM

SS-3

FROM

SS-4

FROM

SS-5

FROM

SS-6

WIRING TYPICAL AS @ "C1"

CONTROL DIAGRAM NTS

E7-002

OUT COIL CONTROLLED FANS REMARX

1 C1 F-01 THRU F-05

2 C2 F-06 THRU F-10

3 C3 F-11 THRU F-16

4 C4 F-17 THRU F-21

5 C5 F-22 THRU F-26

6 C6 F-27 THRU F-31

NOTES:

THERMISTOR/TEMP SENSOR

C1 RELAY COIL

3-POSITION SELECTRO SWITCH

NO, NORMALLY OPEN CONTACT

NO, NORMALLY CLOSED CONTACT

OAT OUTSIDE AIR TEMPERATURE REF. SENSOR

OVERLOAD RELAY

A2

A1

A2

A1

A2

A1

A2

A1

A2

A1

A2

LEGEND:

OL

FAN'S CONTOL SUMMARY

AUXILIARY CONTACTSAUX

FRONT MOUNTED

AUXILIARY CONTACTS

F AUX

G CONTROL LIGHTS

(G - GREEN, R-RED,A-AMBER)

SOUND & LED BEACON COMBO

TIMERT

L2

L3 G

~24V

MA

TC

HL

IN

E "A

RE

: E 7-

4-

H2

A

DS-1

ACTUATORS

POW XMFR, T-2

(E7.003-L13)

T-1

0.8A

CONTROL PANEL LAYOUT

G

POW

ON

RS-485

TO (E) BMS

SYSTEM

AAST2 AAST4 AAST6

AAST5AAST3

ARCTIC AIR STACK TEMPERATUREAAST

FROM

SS-1

(E7.003-H6)

G F01-05

G F06-10

G F11-16

G F17-21

G F22-26

G F27-31

R

R

R

R

R

R

FANS

RUN FAIL

SS-1

OFF

ON AUTO

SS-2

OFF

ON AUTO

SS-3

OFF

ON AUTO

SS-4

OFF

ON AUTO

SS-4

OFF

ON AUTO

SS-6

OFF

ON AUTO

SELECTOR

SWITCH

ON

OFF

CTRL POW

G

ALARM

ESTIMATED BOX SIZE:

48"x60"x12"

A

L1

N

~208V 3-ph

FAN'S CONTACTORS POW

(E7.003-G2)

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

CONTROL

DIAGRAM

ELECTRICAL

NTS

4002_E7.002 (control).dwg

BPA

RPT 4002

E7-002

12A

L1

20A

L2

20A

M F-01

EXHAUST FAN

208V, 1Ø, 1.5HP

EQUIP

GND

OL OL

R1

SS-1

120VAC

L1

N

R2 A2

OLOL

R3

OLOL

R4

OLOL

R5

OLOL

SS-2

SS-3

SS-4

SS-5

OFF

MAN

AUT0

SS-6

F-02

F-03

F-04

F-05

W

IR

IN

G

TY

PI

CA

L

AS

"S S-

1"

OP

EN

CL

OS

E

L

DA-1

DAMPER

ACTUATOR

DAMPER

FUSE

HOLDER

6A 6A

208VAC

12A

OFF

MAN

AUT0

OFF

MAN

AUT0

OFF

MAN

AUT0

OFF

MAN

AUT0

OFF

MAN

AUT0

A1

A2 A1

A2 A1

A2 A1

L1

N

L1

N

L1

N

L1

N

L1

N

CONTACTOR

& OVERLOAD

RELAY (TYP.)

F1-05

RUNNINGG

N

CT1

I/0#1

IN:1

R

B1

F1-05

FAIL TO START

BUZZER

B1

B2

B3

B4

B5

B6

FAIL TO START

SOUND ALARMA

K1 (E7.004-H12)

(E7.004-L2)

L1 N

N

~24V

T-2

2.5A

DA

-2

DA

-3

DA

-4

DA

-5

DA

-2

DA

-3

DA

-4

DA

-5

DA

-3

DA

-3

DA

-3

DA

-3

POWER TO DAMPERS

DA-6 THRU DA-29, TYP.

TB1

K1 (E7.004-H12)

TO "C1"

(E7.002-D7)

1 2

FROM

DS-1

(E7.002-L4)

FROM

DS-1

(E7.002-L4)

CONTROL DIAGRAM NTS

E7-003

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

CONTROL

DIAGRAM

ELECTRICAL

NTS

4002_E7.003 (control).dwg

BPA

RPT 4002

E7-003

USSF

AutoCAD SHX Text A1

AutoCAD SHX Text A2

AUXUX

QTY REMARX

1 1 FAN CONTROLLER TREND IQ4E/LAN24VAC 24VAC

2 5 I/O EXPANSION CARD TREND 8UI (FOR CT INPUTS)

3 1 I/O EXPANSION CARD TREND 8AO (FAN FAIL ALARM)

4 12 SINGLE RELAY MODULE TREND SRMV 5A,10VDC

5 6 SELECTOR SWITCH ALLEN-BRADLEY 800T-J2A 3-POSITION, 2 NO

6 6 SELEC. SW. PADLOCKING ALLEN-BRADLEY 800T-NX446 (a.)

7 31 CONTACTOR, 3 POLE SCHNEIDER TesYS D_LC1D12G7 12A, 2HP, 120VAC

8 31 OVERLOAD RELAY SCHNEIDER TesYS D_LRD08 2.5-4A

9 31 FUSE HOLDER SCHNEIDER TeSys LS1D30

10 72 FUSE, CLASS CC BUSSMAN LP-CC-6 (10 SPARES INCLUDED)

11 6 PILOT LIGHTS GREEN ALLEN-BRADLEY 800L-18C10G 120VAC

12 6 PILOT LIGHTS RED ALLEN-BRADLEY 800L-18C10R 120VAC

13 1 SOUNDER, LED BEACON ALLEN-BRADLEY 855PC-B10LE522 120VAC

14 1 CONTROL XMFR SCHNEIDER 9070T75D14 208-24VAC

15 1 CONTROL XMFR SCHNEIDER 9070T300D14 208-24VAC

16 31 CURRENT SENSOR GREYSTONE CS-650-10 0-10Amps, 0-5Vdc OUTPUT

a. SELECTOR SWITCHES EQUIPPED WITH LOCKABLE PADLOCK SHALL SERVE AS A MOTOR CONTROLLER

DISCONNECTING MEANS AS ALLOWED PER NEC 430.102(B)(2) EXCEPTIONS.

b. REFER TO MECHANICAL DRAWINGS FOR THERMISTORS, DAMPERS, AND FANS SPECIFICATION.

PARTS LIST

IN

P 1 IN

P 2 IN

P 3 IN

P 4

IN

P 5 IN

P 6 IN

P 7 IN

P 8

#1

I/0 EXPANSION

MODULE; (8UI)

#5

I/0 EXPANSION

MODULE; (8AO)

OU

T 1 OU

T 2 OU

T 3 OU

T 4

OU

T 6 OU

T 7 OU

T 8OU

T 5

CT1

(E7.003-F9)

IN

P 1 IN

P 2 IN

P 3 IN

P 4

IN

P 5 IN

P 6 IN

P 7 IN

P 8

#2

I/0 EXPANSION

MODULE; (8UI)

IN

P 1 IN

P 2 IN

P 3 IN

P 4

IN

P 5 IN

P 6 IN

P 7 IN

P 8

#3

I/0 EXPANSION

MODULE; (8UI)

IN

P 1 IN

P 2 IN

P 3 IN

P 4

IN

P 5 IN

P 6 IN

P 7 IN

P 8

#4

I/0 EXPANSION

MODULE; (8UI)

INPUTS FROM

CT2-16

INPUTS FROM

CT17-31

K1 A1

A2 K2

A1

A2 K3

A1

A2 K1

A1

A2 K4

A1

A2

A1

A2 K5

A1

A2

A1

A2 K6

A1

A2

WIRING TYPICAL AS @ "K1"

(E7.003-D6) 13 2 46 5 79 8 12 10 11 15 13 14 18 16 17

MA

TC

HL

IN

E "A

" R E:

E 7-

2-

H9

CONTROL DESCRIPTION:

1. SELECTOR SWITCHES SS-1 THRU SS-6 CONTROLS GROUPS OF 5 OR 6 FANS.

2. MODE OF OPERATION ARE:

2.1 MANUAL (OFF)

2.2 MANUAL (ON)

2.3 AUTOMATIC:

a.1. If OATmp ≤ -8°C a.1.1. DAMPERS WILL (OPEN) a.1.2. FANS WILL START (TURN ON) a.1. If OATmp - AASTmp ≤ -3°C a.1.1. DAMPER WILL STAY (OPEN) a.1.2. FANS WILL STAY (ON) c.1. OATmp ≥ -8°C & OATmp - AASTmp ≥ -3°C c.1.1. DAMPERS WILL (CLOSE) c.1.2. FANS WILL STOP (TURN OFF)

3. IF ALL FANS IN ANY SECTION ARE RUNNING:

3.1. APPROPRIATE GREEN INDICATOR LIGHT WILL TURN ON

3.2. CONTROLLER WILL SEND "FANS RUNNING" SIGNAL TO BMS INDICATING

WHICH GROUP OF FANS IS RUNNING.

4. IF ANY OF THE FANS WILL FAIL TO START OR STOP WORKING (IF INPUTS

FROM ANY "CT1 THRU 31" WILL BE ZERO AFTER START):

4.1. THE CONTROLLER SHALL GENERATE 3s "ON DELAY" SIGNAL

4.2. THE ALARM WILL SOUND AND AMBER LIGHT WILL FLASH.

4.3. APPROPRIATE RED INDICATOR LIGHTS WILL TURN ON

4.4. CONTROLLER WILL SEND "ALARM SIGNAL" TO BMS INDICATING WHICH

FAN FAIL TO START.

I/O #5; OUT1 THRU OUT 6;

3s ON DELAY SIGNAL, TYP.

CONTROL DIAGRAM NTS

E7-004

USAF Project Number

Drawing Title

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

CONTROL

DIAGRAM

ELECTRICAL

NTS

4002_E7.004 (control).dwg

BPA

RPT 4002

E7-004

USSF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

MANUFACTURER

PART#

SD

1:1

95%(CD2)

CAD File Name

Drawing Scale

CAD Plot Scale

Phase

35%(DD) 100%(CD3)

60%(BD) IFC

Drawn By

Date

10-1129

Checked By

A/E Project Number

Sheet Number

PM

Hollingsworth-Pack Corporation øster søgade 22 1357 copenhagen k, denmark

WWCX 15-1009

2022.09.27

Rev # Description Date

3 51 7 9 11 13 15 17

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18

M

K

H

F

D

B

3 51 7 9 11 13 15 172 4 6 8 10 12 14 16 18

L

J

G

E

C

A

M

K

H

F

D

B

A Alex Poulsen Arkitekter A/S bragesgade 10 B, stuen 2200 copenhagen N, denmark

S / M / E Hollingsworth-Pack Corporation 3801 S. Congress Suite 110 Austin, TX

78704, US

GENERAL NOTES:

All dimensions given in mm unless otherwise noted.

All changes are to be coordinated with Facilities Engineering prior to execution.

All safety and health requirements must be followed at all times throughout the project.

BUILDING 4002

IMPROVE ARCTIC

FOUNDATION

at

THULE AIR BASE

GREENLAND

COVER SHEET

MECHANICAL

NTS

4002_M0.001 (COVER).dwg

BHK

GMA 4002

M0-001

MECHANICAL LEGEND AND SYMBOLS

MECHANICAL ABBREVIATIONS

MECHANICAL DESIGN CRITERIA MECHANICAL GENERAL NOTES

GENERAL NOTES

MECHANICAL DESIGN CONDITIONS:

PROJECT LOCATION: THULE, GREENLAND

CLIMATE ZONE: 1A

SUMMER:

OUTDOOR DESIGN: 50.3°F DB / 43°F WB

INDOOR DESIGN: 75°F DB / 50% RH

WINTER:

OUTDOOR DESIGN: -31.3°F DB

INDOOR DESIGN: 72°F DB

BUILDING WALL & ROOF CONSTRUCTION INFORMATION:

NO LOAD CALCULATIONS REQUIRED FOR

THIS PROJECT

AFF ABOVE FINISHED FLOOR

ACFM ACTUAL CFM

AHU AIR HANDLING UNIT

ANSI AMERICAN NATIONAL STANDARDS

INSTITUTE

AMP AMPERE (AMP,AMPS)

APD AIR PRESSURE DROP

APPROX APPROXIMATE

BHP BRAKE HP, BOILER HP

BTU BRITISH THERMAL UNIT

MBH BTU PER HOUR (THOUSAND)

CU FT CUBIC FEET

CU IN CUBIC INCH

CFM CUBIC FEET PER MINUTE

SCFM CFM, STANDARD CONDITIONS

DB DECIBEL

DIA, Ø DIAMETER

ID DIAMETER, INSIDE

OD DIAMETER, OUTSIDE

DBT DRY-BULB TEMPERATURE

EAT ENTERING AIR TEMPERATURE

E.C. ELECTRICAL CONTRACTOR

EDR EQUIVALENT DIRECT RADIATION

EXP EXPANSION

EWT ENTERING WATER TEMPERATURE

F FAHRENHEIT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FOOT OR FEET

HZ FREQUENCY

GA GAGE OR GAUGE

GAL GALLONS

G.C. GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPD GALLONS PER DAY

HD HEAD

HGT HEIGHT

HP HORSEPOWER

RH HUMIDITY, RELATIVE

KW KILOWATT

KWH KILOWATT HOUR

LAT LEAVING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

LF LINEAR FEET

MAX MAXIMUM

M.C. MECHANICAL CONTRACTOR

MIN MINIMUM

N O NORMALLY OPEN

N C NORMALLY CLOSED

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO. NUMBER

OBD OPPOSED BLADE DAMPER

OA OUTSIDE AIR

PH PHASE (ELECTRICAL)

LBS POUNDS

PSI POUNDS PER SQUARE INCH

PSIA PSI ABSOLUTE

PD PRESSURE DROP

PSIG PSI GAUGE

RH RELATIVE HUMIDITY

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

SH SENSIBLE HEAT

SPEC SPECIFICATION

SP VOL SPECIFIC VOLUME

STD STANDARD

SP STATIS PRESSURE

SUCT SUCTION

SA SUPPLY AIR

TEMP TEMPERATURE

TD TEMPERATURE DIFFERENCE

T STAT THERMOSTAT

TONS TONS OF REFRIGERATION

T.C. TEMPERATURE CONTROL

VAC VACUUM

VAV VARIABLE AIR VOLUME

VEL VELOCITY

V VOLT

VOL VOLUME

VFD VARIABLE FREQUENCY DRIVE

WPD WATER PRESSURE DROP

W/ WITH

DRAIN

HEATING WATER SUPPLY

HEATING WATER RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

REFRIGERANT SUCTION LINE

REFRIGERANT LIQUID LINE

REFRIGERANT HOT GAS LINE

GATE VALVE

BALL VALVE

BUTTERFLY VALVE

GLOBE VALVE

TRIPLE DUTY VALVE

SWING CHECK VALVE

STRAINER

FLEX CONNECTOR

HOSE END DRAIN VALVE

PRESSURE REDUCING VA.

SAFETY RELIEF VALVE

UNION

MOTORIZED T.C. VA/2-WAY

MOTORIZED T.C. VA/3-WAY

ECCENTRIC PLUG BALANCING

VALVE

VALVE IN RISER

TEE UP

TEE DOWN

ELBOW UP

ELBOW DOWN

PIPE SIZE CHANGE

MANUAL FLOW BALANCING VALVE

(CIRCUIT SETTER)

AUTOMATIC FLOW BALANCING

VALVE

PIPE GUIDE

PIPE ANCHOR

PRESSURE/TEMP. TEST PLUG

DIAL THERMOMETER

T

A

M

HG

RL

RS

CWR

CWS

HWR

HWS

D

PRESSURE GAUGE W/ SNUBBER

P

ELECTRIC THERMOSTAT

ELECTRIC THERMOSTAT W/GUARD

PNEUMATIC THERMOSTAT OR DDC

TEMPERATURE SENSOR

(JOB SPECIFIC)

PNEUMATIC RECESSED ASPERATING

THERMOSTAT

PNEUMATIC STAT W/GUARD

ACOUSTICALLY LINED SHEET

METAL DUCT

MANUAL BALANCING DAMPER

FLEX CONNECTOR

ACCESS DOORS

FIRE DAMPER

FIRE/SMOKE DAMPER

MOTORIZED DAMPER

TURNING VANE ELL

45° LOW-LOSS TAKE-OFF FITTING W/

DAMPER & FLEX DUCT

45° LOW-LOSS TAKE-OFF FITTING W/

DAMPER & RIGID ROUND DUCT

90° TEE TAKE-OFF FITTING

CONICAL 90° TEE TAKE-OFF FITTING

45° TEE TAKE-OFF FIITTING

45°-90° TEE TAKE-OFF FITTING

SUPPLY AIR DUCT (SINGLE LINE)

RETURN AIR DUCT (SINGLE LINE)

EXHAUST AIR DUCT (SINGLE LINE)

DIFFUSER, REGISTER, OR GRILLE

THROW PATTERN SHOWN ON DWGS.

CONNECT NEW WORK TO EXISTING

SD-1 (PLAN CODE)

8x8 (NECK SIZE)

200 (CFM)

AD

AD

FD

FSD

T

T

T

T

T

A

SA

RA

EA

M

EXISTING

(E)

1. BUILDING CODE - UFC 1-200-01

2. FIRE CODE - UFC 3-600-01 PER UFC 1-200-01

3. ELECTRICAL CODE - UFC 1-200-01

4. MECHANICAL CODE - UFC 1-200-01

5. PLUMBING CODE - UFC 1-200-01

6. OTHER - UFC 1-200-01

7. OTHER - LIFE SAFETY CODE (NFPA 101) 2021 EDITION

APPLICABLE CODES AND STANDARDS

UFC 1-200-02 HIGH PERFORMANCE AND

SUSTAINABLE BUILDING REQUIREMENTS

1. FURNISH AND INSTALL ALL ITEMS NECESSARY TO PROVIDE FULLY FUNCTIONING SYSTEM'S AS INDICATED BY THE DESIGN AND THE

EQUIPMENT SPECIFIED. ELEMENTS OF THE WORK SHALL INCLUDE, BUT ARE NOT LIMITED TO, MATERIALS, LABOR, SUPERVISION, SUPPLIES, EQUIPMENT, TRANSPORTATION, HOISTING/RIGGING, STORAGE, UTILITIES, AND ALL REQUIRED PERMITS AND LICENSES.

2. DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT REFLECT ALL WORK AND MATERIALS REQUIRED TO COMPLETE PROJECT.

CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR AND EQUIPMENT AS REQUIRED TO COMPLETE PROJECT WITHIN DESIGN.

CONTRACTOR SHALL REQUEST ADDITIONAL INFORMATION AND DETAILS WHERE SCOPE IS UNCLEAR.

3. ALL WORK SHALL COMPLY WITH THE MOST RECENT ADOPTED VERSION OF ALL APPLICABLE LAWS, RULES, REGULATIONS AND

ORDINANCES OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES. IF CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND THE

LOCAL ENFORCING AUTHORITY EXISTS, THE LOCAL ENFORCING AUTHORITY SHALL APPLY. ANY MODIFICATIONS TO THE DESIGN

SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER OR ARCHITECT/ENGINEER. THE CONTRACTOR SHALL REPORT TO THE

ARCHITECT/ENGINEER AND SECURE HIS APPROVAL BEFORE PROCEEDING WITH ANY MODIFICATIONS.

4. WHERE THE REQUIREMENTS OF THE CONTRACT DOCUMENTS EXCEED THE…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .