263323 central battery equipment.pdf

PDF 35 KB Posted

Attached to
CONSTRUCT USPFO WAREHOUSE
Solicitation number
W91364-09-B-0003
Issued by

About this file

263323 central battery equipment.pdf

View the file

Other files

File Type Posted
USPFO_P602W.pdf PDF
USPFO_P304W.pdf PDF
USPFO_P701W.pdf PDF
USPFO_F401W.pdf PDF
262923 variable frequency controllers.pdf PDF
224700 drinking fountains and water coolers.pdf PDF
E703.pdf PDF
072100 thermal insulation.pdf PDF
230500 common work results for hvac.pdf PDF
OHARNG_USPFO_Q202W.pdf PDF
USPFO_P303W.pdf PDF
224000 plumbing fixtures.pdf PDF
221123 domestic water pumps.pdf PDF
E504.pdf PDF
074213 metal wall panels.pdf PDF
271300 communications backbone cabling.pdf PDF
OHARNG-USPFO-A-211aW .pdf PDF
096519 resilient tile flooring.pdf PDF
L502.pdf PDF
C000.pdf PDF
223400 fuel-fired domestic water heaters.pdf PDF
USPFO_P301W.pdf PDF
USPFO_S501W.pdf PDF
USPFO_S502W.pdf PDF
260526 grounding and bonding for electrical systems.pdf PDF
OHARNG-USPFO-I-101W .pdf PDF
003 Fly Page.pdf PDF
G140.pdf PDF
061600 sheathing.pdf PDF
271100 communications equipment room fittings.pdf PDF
USPFO_P001W.pdf PDF
OHARNG-USPFO-A-401W .pdf PDF
E304.pdf PDF
012900 payment procedures.pdf PDF
055300 metal gratings.pdf PDF
017900 operational and maintenance training.pdf PDF
OHARNG-USPFO-A-821W .pdf PDF
064023 interior architectural woodwork.pdf PDF
E201.pdf PDF
E301.pdf PDF
033000 cast-in-place concrete.pdf PDF
C501.pdf PDF
OHARNG-USPFO-A-701W .pdf PDF
USPFO_F301W.pdf PDF
USPFO_M502W.pdf PDF
C600.pdf PDF
329200 lawns.pdf PDF
OHARNG-USPFO-A-807W .pdf PDF
096813 tile carpeting.pdf PDF
099123 interior painting.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 1

SECTION 263323 - CENTRAL BATTERY EQUIPMENT

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes central battery inverters with the following features:

1. Output distribution section.

2. Internal maintenance bypass/isolation switch.

3. External maintenance bypass/isolation switch.

4. Multiple output voltages.

5. Emergency-only circuits.

6. Remote monitoring provisions.

1.3 DEFINITIONS

A. LCD: Liquid-crystal display.

B. LED: Light-emitting diode.

C. THD: Total harmonic distortion.

D. UPS: Uninterruptible power supply.

1.4 SUBMITTALS

A. Product Data: For the following:

1. Electrical ratings, including the following:

a. Capacity to provide power during failure of normal ac.

b. Inverter voltage regulation and THD of output current.

c. Rectifier data.

d. Transfer time of transfer switch.

e. Data for specified optional features.

2. Transfer switch.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 2

3. Inverter.

4. Battery charger.

5. Batteries.

6. Battery monitoring.

7. Battery-cycle warranty monitor.

B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, components, and location and identification of each field connection. Show access, workspace, and clearance requirements; details of control panels; and battery arrangement.

1. Wiring Diagrams: Detail internal and interconnecting wiring; and power, signal, and control wiring.

2. Elevation and details of control and indication displays.

3. Output distribution section.

C. Manufacturer Seismic Qualification Certification: Submit certification that central battery inverter equipment will withstand seismic forces defined in Division 26 Section "Vibration and Seismic Controls for Electrical Systems" Include the following:

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

a. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified."

b. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

D. Qualification Data: For testing agency.

E. Source quality-control test reports.

F. Field quality-control test reports.

G. Operation and Maintenance Data: For central battery inverter equipment to include in emergency, operation, and maintenance manuals.

H. Warranty: Special warranty specified in this Section.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 3

1.5 QUALITY ASSURANCE

A. Testing Agency Qualifications: Member company of the InterNational Electrical Testing Association or is an NRTL acceptable to authorities having jurisdiction.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

C. Central Battery Inverter System: UL 924 and UL 1778 listed.

D. Comply with NFPA 70 and NFPA 101.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver equipment in fully enclosed vehicles.

B. Store equipment in spaces having environments controlled within manufacturers' written instructions for ambient temperature and humidity conditions for non-operating equipment.

1.7 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace batteries that fail in materials or workmanship within specified warranty period. Special warranty, applying to batteries only, applies to materials only, on a prorated basis, for period specified.

1. Warranty Period: Include the following warranty periods, from date of Substantial Completion:

a. Standard, Valve-Regulated, Recombinant, Lead-Calcium Batteries:

1) Full Warranty: One year.

2) Pro Rata: Nine years.

1.8 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. Deliver extra materials to Owner.

1. Fuses: One for every 10 of each type and rating, but no fewer than two of each.

2. Cabinet Ventilation Filters: One complete set.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 4

3. One spare circuit board for each critical circuit.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Bigbeam Emergency Systems, Inc.; Siltron Division.

2. Chloride Systems.

3. Cooper Industries, Inc.; Sure-Lites Division.

4. Crucial Power Products.

5. Dual-Lite.

6. Hubbell Incorporated; Hubbell Lighting.

7. Lightguard/Chloride Systems.

8. Lithonia Lighting; Emergency Lighting Systems.

9. Thomas & Betts Corporation; Emergi-Lite Division.

10. Thomas & Betts Corporation; Lightalarms Division.

2.2 INVERTER PERFORMANCE REQUIREMENTS

A. Slow-Transfer Central Battery Inverters: Automatically sense loss of normal ac supply and use an electromechanical switch to transfer loads. Transfer in one second or less from normal supply to battery-inverter supply.

B. Fast-Transfer Central Battery Inverters: Automatically sense loss of normal ac supply and use a solid-state switch to transfer loads. Transfer in 0.004 second or less from normal supply to battery-inverter supply.

1. Operation: Unit supplies power to output circuits from a single, external, normal supply source. Unit automatically transfers load from normal source to internal battery/inverter source. Retransfer to normal is automatic when normal power is restored.

C. UPS-Type Central Battery Inverters: Continuously provide ac power to connected electrical system.

1. Automatic Operation:

a. Normal Conditions: Supply the load with ac power flowing from normal ac power input terminals, through rectifier-charger and inverter, with battery connected in parallel with rectifier-charger output.

b. Abnormal Supply Conditions: If normal ac supply deviates from specified and adjustable voltage, voltage waveform, or frequency limits, battery

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 5

supplies constant, regulated, inverter ac power output to the load without switching or disturbance.

c. If normal power fails, battery continues supply-regulated ac power through the inverter to the load without switching or disturbance.

d. When power is restored at normal supply terminals of system, controls automatically synchronize inverter with the external source before transferring the load. Rectifier-charger then supplies power to the load through the inverter and simultaneously recharges battery.

e. If battery becomes discharged and normal supply is available, rectifier-charger charges battery. When battery is fully charged, rectifier-charger automatically shifts to float-charge mode.

f. If any element of central battery inverter system fails and power is available at normal supply terminals of system, static bypass transfer switch transfers the load to normal ac supply circuit without disturbance or interruption of supply.

g. If a fault occurs in system supplied by central battery inverter and current flows in excess of the overload rating of central battery inverter system, static bypass transfer switch operates to bypass fault current to normal ac supply circuit for fault clearing.

h. When fault has cleared, static bypass transfer switch returns the load to central battery inverter system.

i. If battery is disconnected, central battery inverter continues to supply power to the load with no degradation of its regulation of voltage and frequency of output bus.

2. Manual Operation:

a. Turning inverter off causes static bypass transfer switch to transfer the load directly to normal ac supply circuit without disturbance or interruption.

b. Turning inverter on causes static bypass transfer switch to transfer the load to inverter.

D. Maximum Acoustical Noise: 50 dB, "A" weighting, emanating from any UPS component under any condition of normal operation, measured 39 inches from nearest surface of component enclosure.

2.3 SERVICE CONDITIONS

A. Environmental Conditions: Inverter system shall be capable of operating continuously in the following environmental conditions without mechanical or electrical damage or degradation of operating capability:

1. Ambient Temperature for Electronic Components: 32 to 98 deg F.

2. Relative Humidity: 0 to 95 percent, noncondensing.

3. Altitude: Sea level to 2000 feet.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 6

2.4 INVERTERS

A. Description: Solid-state type, with the following operational features:

1. Automatically regulate output voltage to within plus or minus 5 percent.

2. Automatically regulate output frequency to within plus or minus 1 Hz, from no load to full load at unit power factor over the operating range of battery voltage.

3. Output Voltage Waveform of Unit: Sine wave with maximum 10 percent THD throughout battery operating-voltage range, from no load to full load.

a. THD may not exceed 5 percent when serving a resistive load of 100 percent of unit rating.

4. Output Protection: Current-limiting and short-circuit protection.

5. Output Protection: Ferroresonant transformer to provide inherent overload and short-circuit protection.

6. Surge Protection: Panelboard suppressors specified in Division 26 Section

"Transient-Voltage Suppression for Low-Voltage Electrical Power Circuits."

7. Overload Capability: 125 percent for 10 minutes; 150 percent surge.

8. Brownout Protection: Produces rated power without draining batteries when input voltage is down to 75 percent of normal.

2.5 BATTERY CHARGER

A. Description: Solid-state, automatically maintaining batteries in fully charged condition when normal power is available. With LED indicators for "float" and "high-charge" modes.

2.6 BATTERIES

A. Description: Standard, valve-regulated, recombinant, lead-calcium batteries.

1. Capable of sustaining full-capacity output of inverter unit for minimum of 90 minutes.

2.7 ENCLOSURES

A. NEMA 250, Type 1 steel cabinets with access to components through hinged doors with flush tumbler lock and latch.

B. Finish: Manufacturer's standard baked-enamel finish over corrosion-resistant prime treatment.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 7

2.8 SEISMIC REQUIREMENTS

A. Central battery inverter assemblies, subassemblies, components, fastenings, supports, and mounting and anchorage devices shall be designed and fabricated to withstand seismic forces. The term "withstand" is defined in the "Manufacturer Seismic Qualification Certification" Paragraph in Part 1 "Submittals" Article.

2.9 CONTROL AND INDICATION

A. Description: Group displays, indications, and basic system controls on common control panel on front of central battery inverter enclosure.

B. Minimum displays, indicating devices, and controls shall include those in lists below.

Provide sensors, transducers, terminals, relays, and wiring required to support listed items. Alarms shall include an audible signal and a visual display.

C. Indications: Labeled LED.

1. Quantitative Indications:

a. Input voltage, each phase, line to line.

b. Input current, each phase, line to line.

c. System output voltage, each phase, line to line.

d. System output current, each phase.

e. System output frequency.

f. DC bus voltage.

g. Battery current and direction (charge/discharge).

h. Elapsed time-discharging battery.

2. Basic Status Condition Indications:

a. Normal operation.

b. Load-on bypass.

c. Load-on battery.

d. Inverter off.

e. Alarm condition exists.

3. Alarm Indications:

a. Battery system alarm.

b. Control power failure.

c. Fan failure.

d. Overload.

e. Battery-charging control faulty.

f. Input overvoltage or undervoltage.

g. Approaching end of battery operation.

h. Battery undervoltage shutdown.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 8

i. Inverter fuse blown.

j. Inverter transformer overtemperature.

k. Inverter overtemperature.

l. Static bypass transfer switch overtemperature.

m. Inverter power supply fault.

n. Inverter output overvoltage or undervoltage.

o. System overload shutdown.

p. Inverter output contactor open.

q. Inverter current limit.

4. Controls:

a. Inverter on-off.

b. Start.

c. Battery test.

d. Alarm silence/reset.

e. Output-voltage adjustment.

D. Dry-form "C" contacts shall be available for remote indication of the following conditions:

1. Inverter on battery.

2. Inverter on-line.

3. Inverter load-on bypass.

4. Inverter in alarm condition.

5. Inverter off (maintenance bypass closed).

E. Include the following minimum array:

1. Ready, normal-power on light.

2. Charge light.

3. Inverter supply load light.

4. Battery voltmeter.

5. AC output voltmeter with minimum accuracy of 2 percent of full scale.

6. Load ammeter.

7. Test switch to simulate ac failure.

F. Enclosure: Steel, with hinged lockable doors, suitable for wall mounting.

Manufacturer's standard corrosion-resistant finish.

2.10 OPTIONAL FEATURES

A. Maintenance Bypass/Isolation Switch: Load is supplied, bypassing central battery inverter system. Normal supply, electromechanical transfer switch, and system load terminals are completely disconnected from external circuits.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 9

B. Maintenance Bypass/Isolation Switch: Switch is interlocked so it cannot be operated unless static bypass transfer switch is in bypass mode. Switch provides manual selection among the following three conditions without interrupting supply to the load during switching:

1. Full Isolation: Load is supplied, bypassing central battery inverter system.

Normal ac input circuit, static bypass transfer switch, and central battery inverter load terminals are completely disconnected from external circuits.

2. Maintenance Bypass: Load is supplied, bypassing central battery inverter system. Central battery inverter ac supply terminals are energized to permit operational checking, but system load terminals are isolated from the load.

3. Normal: Normal central battery inverter ac supply terminals are energized and the load is supplied either through static bypass transfer switch and central battery inverter rectifier-charger and inverter or through battery and inverter.

2.11 OUTPUT DISTRIBUTION SECTION

A. Panelboard: Comply with Division 26 Section "Panelboards" except provide assembly integral to equipment cabinet.

2.12 SYSTEM MONITORING AND ALARMS

A. Remote Status and Alarm Panel: Labeled LEDs on panel faceplate shall indicate five basic status conditions. Audible signal indicates alarm conditions. Silencing switch in face of panel silences signal without altering visual indication.

1. Cabinet and Faceplate: Surface or flush mounted to suit mounting conditions indicated.

B. Provisions for Remote Computer Monitoring: Communication module in unit control panel provides capability for remote monitoring of status, parameters, and alarms specified in Part 2 "Control and Indication" Article. Remote computer and connecting signal wiring will be provided by Owner. Include the following features:

1. Connectors and network interface units or modems for data transmission via RS-232 link.

2. Software shall be designed to control and monitor inverter system functions and to provide on-screen explanations, interpretations, diagnosis, action guidance, and instructions for use of monitoring indications and development of reports.

Include capability for storage and analysis of power-line transient records.

Software shall be compatible with requirements in Division 26 Section "Electrical Power Monitoring and Control" and the operating system and configuration of Owner-furnished computers.

C. Battery Ground-Fault Detector: Initiates alarm when resistance to ground of positive or negative bus of battery is less than 5000 ohms.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 10

1. Annunciation of Alarms: At inverter system control panel.

D. Battery-Cycle Warranty Monitoring: Electronic device, acceptable to battery manufacturer as a basis for warranty action, for monitoring charge-discharge cycle history of batteries covered by cycle-life warranty.

1. Basic Functional Performance: Automatically measures and records each discharge event, classifies it according to duration category, and totals discharges according to warranty criteria, displaying remaining warranted battery life on integral LCD.

2. Additional monitoring functions and features shall include the following:

a. Measuring and recording of total voltage at battery terminals; providing alarm for excursions outside proper float voltage level.

b. Monitoring of ambient temperature at battery and initiating an alarm if temperature deviates from normally acceptable range.

c. Keypad on device front panel provides access to monitored data using front panel display.

d. Alarm contacts arranged to provide local alarm for abnormal battery voltage or temperature.

e. Memory device to store recorded data in nonvolatile electronic memory.

f. RS-232 port to permit downloading of data to a portable personal computer.

g. Modem to make measurements and recorded data accessible to remote personal computer via telephone line. Computer will be provided by Owner.

2.13 SOURCE QUALITY CONTROL

A. Factory test complete inverter system, including battery, before shipment. Include the following:

1. Functional test and demonstration of all functions, controls, indicators, sensors, and protective devices.

2. Full-load test.

3. Transient-load response test.

4. Overload test.

5. Power failure test.

B. Observation of Test: Give 14 days' advance notice of tests and provide access for Owner's representative to observe tests at Owner's option.

C. Report test results. Include the following data:

1. Description of input source and output loads used. Describe actions required to simulate source load variation and various operating conditions and malfunctions.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 11

2. List of indications, parameter values, and system responses considered satisfactory for each test action. Include tabulation of actual observations during test.

3. List of instruments and equipment used in factory tests.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and conditions for compliance with requirements for ventilation, temperature, humidity, and other conditions affecting performance.

1. Verify that manufacturer's written instructions for environmental conditions have been permanently established in spaces where equipment will be installed, before installation begins.

B. Examine roughing-in for electrical connections to verify actual locations of connections before installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install system components on concrete base and attach by bolting.

1. Design each fastener and support to carry load indicated by seismic requirements and according to seismic-restraint details. See Division 26 Section "Vibration and Seismic Controls for Electrical Systems" for seismic-restraint requirements.

2. Concrete Bases: 4 inches high, reinforced, with chamfered edges. Extend base no more than 3 inches in all directions beyond the maximum dimensions of switchgear unless otherwise indicated or unless required for seismic anchor support. Construct concrete bases according to Division 26 Section "Hangers and Supports for Electrical Systems."

3. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

4. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

5. Use 3000-psi, 28-day compressive-strength concrete and reinforcement as specified in Division 03 Section "Cast-in-Place Concrete."

B. Maintain minimum clearances and workspace at equipment according to manufacturer's written instructions and NFPA 70.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 12

3.3 CONNECTIONS

A. Connections: Interconnect system components. Make connections to supply and load circuits according to manufacturer's wiring diagrams, unless otherwise indicated.

B. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems."

1. Separately Derived Systems: Make grounding connections to grounding electrodes and bonding connections to metallic piping systems as indicated;

comply with NFPA 70.

C. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors and Cables."

3.4 IDENTIFICATION

A. Identify equipment and components according to Division 26 Section "Identification for Electrical Systems."

3.5 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections and prepare test reports.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. Report results in writing.

C. Perform tests and inspections and prepare test reports.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

D. Tests and Inspections:

1. Inspect interiors of enclosures for integrity of mechanical and electrical connections, component type and labeling verification, and ratings of installed components.

2. Test manual and automatic operational features and system protective and alarm functions.

3. Test communication of status and alarms to remote monitoring equipment.

4. Perform each visual and mechanical inspection and electrical test stated in

NETA Acceptance Testing Specifications. Certify compliance with test parameters.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

CENTRAL BATTERY EQUIPMENT 263323 - 13

5. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

E. Remove and replace malfunctioning units and retest as specified above.

3.6 STARTUP SERVICE

A. Engage a factory-authorized service representative to perform startup service.

B. Verify that central battery inverter is installed and connected according to the Contract Documents.

C. Verify that electrical wiring installation complies with manufacturer's submittal and installation requirements in Division 26 Sections.

D. Complete installation and startup checks according to manufacturer's written instructions.

3.7 ADJUSTING AND CLEANING

A. Set field-adjustable switches and circuit-breaker trip ranges as indicated.

B. Install new filters in each equipment cabinet within 14 days from date of Substantial Completion.

3.8 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain central battery inverters. Refer to Division 01 Section "Demonstration and Training."