104413 fire extinguishing cabinets.pdf
PDF 9 KB Posted
- Attached to
- CONSTRUCT USPFO WAREHOUSE
- Solicitation number
- W91364-09-B-0003
About this file
104413 fire extinguishing cabinets.pdf
View the file
Other files
Show 40 more
Latest 50 of 373 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE EXTINGUISHER CABINETS 104413 - 1
SECTION 104413 - FIRE EXTINGUISHER CABINETS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes fire protection cabinets for fire extinguishers.
1.2 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: For fire protection cabinets. Include plans, elevations, sections, details, and attachments to other work.
C. Samples: For each exposed product and for each color and texture specified.
D. Maintenance data.
1.3 QUALITY ASSURANCE
A. Fire-Rated, Fire Protection Cabinets: Listed and labeled to comply with requirements in ASTM E 814 for fire-resistance rating of walls where they are installed.
B. Coordinate size of fire protection cabinets to ensure that type and capacity of fire extinguishers indicated are accommodated.
C. Coordinate sizes and locations of fire protection cabinets with wall depths.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B.
B. Tempered Float Glass: ASTM C 1048, Kind FT, Condition A, Type I, Quality q3, 3 mm thick, Class 1 (clear).
2.2 FIRE PROTECTION CABINET
A. Cabinet Type: Suitable for fire extinguisher.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE EXTINGUISHER CABINETS 104413 - 2
1. Basis-of-Design Product: Subject to compliance with requirements, provide J.
L. Industries, Inc model C3017F17 or comparable product by one of the following:
a. Fire End & Croker Corporation.
b. Kidde Residential and Commercial Division, Subsidiary of Kidde plc.
c. Larsen's Manufacturing Company.
d. Potter Roemer LLC.
B. Cabinet Construction: Nonrated.
C. Cabinet Material: Steel sheet.
D. Semirecessed Cabinet: Cabinet box partially recessed in walls of sufficient depth to suit style of trim indicated; with one-piece combination trim and perimeter door frame overlapping surrounding wall surface with exposed trim face and wall return at outer edge (backbend). Provide where walls are of insufficient depth for recessed cabinets but are of sufficient depth to accommodate semirecessed cabinet installation.
1. Rolled-Edge Trim: 2-1/2-inch backbend depth.
E. Cabinet Trim Material: Steel sheet.
F. Door Material: Steel sheet.
G. Door Style: Fully glazed panel with frame.
H. Door Glazing: Tempered float glass (clear).
I. Door Hardware: Manufacturer's standard door-operating hardware of proper type for cabinet type, trim style, and door material and style indicated.
J. Accessories:
1. Mounting Bracket: Manufacturer's standard steel, designed to secure fire extinguisher to fire protection cabinet, of sizes required for types and capacities of fire extinguishers indicated, with plated or baked-enamel finish.
K. Finishes:
1. Manufacturer's standard baked-enamel paint for the following:
a. Exterior of cabinet, door, and trim, except for those surfaces indicated to receive another finish.
b. Interior of cabinet and door.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE EXTINGUISHER CABINETS 104413 - 3
2.3 FABRICATION
A. Fire Protection Cabinets: Provide manufacturer's standard box (tub), with trim, frame, door, and hardware to suit cabinet type, trim style, and door style indicated. Miter and weld joints and grind smooth.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Examine walls and partitions for suitable framing depth and blocking where semirecessed cabinets will be installed and prepare recesses as required by type and size of cabinet and trim style.
B. Install fire protection cabinets in locations and at mounting heights indicated or, if not indicated, at heights acceptable to authorities having jurisdiction.
C. Fire Protection Cabinets: Fasten cabinets to structure, square and plumb.
D. Adjust fire protection cabinet doors to operate easily without binding. Verify that integral locking devices operate properly.
E. Replace fire protection cabinets that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.
END OF SECTION 104413
File details come from the government source that posted it. Updated .