F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 1
SECTION 077100 - ROOF SPECIALTIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Copings.
2. Roof-edge drainage systems.
3. Counterflashings.
1.2 PERFORMANCE REQUIREMENTS
A. FM Approvals' Listing: Manufacture and install copings that are listed in FM Approvals' "RoofNav" and approved for windstorm classification, Class 1-90. Identify materials with FM Approvals' markings.
B. SPRI Wind Design Standard: Manufacture and install copings tested according to SPRI ES-1 and capable of resisting the following design pressures:
1. Design Pressure: As indicated on Drawings.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: For roof specialties. Include plans, elevations, expansion-joint locations, keyed details, and attachments to other work. Distinguish between plant-and field-assembled work.
C. Samples: For each exposed product and for each color and texture specified.
D. Product test reports.
E. Maintenance data.
F. Warranty: Sample of special warranty.
1.4 QUALITY ASSURANCE
A. Preinstallation Conference: Conduct conference at Project site.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 2
1.5 WARRANTY
A. Special Warranty on Painted Finishes: Manufacturer's standard form in which manufacturer agrees to repair finish or replace roof specialties that show evidence of deterioration of factory-applied finishes within 20 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 EXPOSED METALS
A. Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653/A 653M, G90 coating designation.
1. Surface: Smooth, flat finish.
2. Exposed Coil-Coated Finishes: Prepainted by the coil-coating process to comply with ASTM A 755/A 755M. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions.
a. Three-Coat Fluoropolymer: AAMA 621. System consisting of primer, fluoropolymer color coat, and clear fluoropolymer topcoat, with both color coat and clear topcoat containing not less than 70 percent PVDF resin by weight.
3. Color: As indicated in the Exterior Color Schedule on the drawings.
2.2 CONCEALED METALS
A. Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653/A 653M, G90 coating designation.
2.3 UNDERLAYMENT MATERIALS
A. Self-Adhering, High-Temperature Sheet: Minimum 30 to 40 mils thick, consisting of slip-resisting polyethylene-film top surface laminated to layer of butyl or SBS-modified asphalt adhesive, with release-paper backing; cold applied. Provide primer when recommended by underlayment manufacturer.
1. Thermal Stability: ASTM D 1970; stable after testing at 240 deg F.
2. Low-Temperature Flexibility: ASTM D 1970; passes after testing at minus 20 deg F.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 3
2.4 MISCELLANEOUS MATERIALS
A. General: Provide materials and types of fasteners, protective coatings, sealants, and other miscellaneous items required by manufacturer for a complete installation.
B. Fasteners: Manufacturer's recommended fasteners, suitable for application and designed to meet performance requirements. Furnish the following unless otherwise indicated:
1. Exposed Penetrating Fasteners: Gasketed screws with hex washer heads matching color of sheet metal.
2. Fasteners for Zinc-Coated (Galvanized) Steel Sheet: Series 300 stainless steel or hot-dip zinc-coated steel according to ASTM A 153/A 153M or ASTM F 2329.
C. Elastomeric Sealant: ASTM C 920, elastomeric polymer sealant of type, grade, class, and use classifications required by roofing-specialty manufacturer for each application.
D. Bituminous Coating: Cold-applied asphalt emulsion complying with ASTM D 1187.
E. Asphalt Roofing Cement: ASTM D 4586, asbestos free, of consistency required for application.
2.5 ROOF-EDGE FLASHINGS
A. Roof-Edge Fascia: Manufactured, two-piece, roof-edge fascia consisting of snap-on metal fascia cover in section lengths not exceeding 12 feet and a continuous formed-or extruded-aluminum anchor bar with integral drip-edge cleat to engage fascia cover.
Provide matching corner units.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Hickman Company, W. P.
b. Johns Manville.
c. Metal-Era, Inc.
d. Metal-Fab Manufacturing, LLC.
2. Fascia Cover: Fabricated from the following exposed metal:
a. Zinc-Coated Steel: Nominal thickness as required to meet performance requirements.
3. Corners: Factory mitered and mechanically clinched and sealed watertight.
4. Splice Plates: Concealed, of same material, finish, and shape as fascia cover.
5. Fascia Accessories: As required for complete installation of products as indicated on the drawings.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 4
B. Zinc-Coated Steel Finish: Three-coat fluoropolymer.
1. Color: As indicated in the Exterior Color Schedule on the drawings.
2.6 ROOF-EDGE DRAINAGE SYSTEMS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Hickman Company, W. P.
2. Johns Manville.
3. Metal-Era, Inc.
4. MM Systems Corporation.
5. Petersen Aluminum Corporation.
B. Gutters: Manufactured in uniform section lengths not exceeding 12 feet, with matching corner units, ends, outlet tubes, and other accessories. Elevate back edge at least 1 inch above front edge. Furnish flat-stock gutter straps, gutter brackets, expansion joints, and expansion-joint covers fabricated from same metal as gutters.
1. Fabricate from the following exposed metal:
a. Zinc-Coated Steel: Nominal 0.034-inch thickness.
2. Gutter Profile: Style G according to SMACNA's "Architectural Sheet Metal Manual."
3. Gutter Supports: Manufacturer's standard supports as selected by Architect with finish matching the gutters.
4. Gutter Accessories: Bronze wire ball downspout strainer.
C. Downspouts: Plain round complete with machine-crimped elbows, manufactured from the following exposed metal. Furnish with metal hangers, from same material as downspouts, and anchors.
1. Zinc-Coated Steel: Nominal 0.034-inch thickness.
D. Conductor Heads: Manufactured conductor heads, each with flanged back and stiffened top edge and of dimensions and shape indicated, complete with outlet tube that nests into upper end of downspout.
1. Fabricate from the following exposed metal:
a. Zinc-Coated Steel: Nominal 0.028-inch thickness.
E. Zinc-Coated Steel Finish: Three-coat fluoropolymer.
1. Color: As indicated in the Exterior Color Schedule on the drawings.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 5
2.7 COUNTERFLASHINGS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Fry Reglet Corporation.
2. Heckmann Building Products Inc.
3. Hickman Company, W. P.
4. Metal-Era, Inc.
5. MM Systems Corporation.
B. Counterflashings: Manufactured units of heights to overlap top edges of base flashings by 4 inches and in lengths not exceeding 12 feet designed to snap into reglets or through-wall-flashing receiver and compress against base flashings with joints lapped, from the following exposed metal:
1. Zinc-Coated Steel: Nominal 0.028-inch thickness.
C. Accessories:
1. Flexible-Flashing Retainer: Provide resilient plastic or rubber accessory to secure flexible flashing in reglet where clearance does not permit use of standard metal counterflashing or where reglet is provided separate from metal counterflashing.
2. Counterflashing Wind-Restraint Clips: Provide clips to be installed before counterflashing to prevent wind uplift of counterflashing lower edge.
D. Zinc-Coated Steel Finish: Three-coat fluoropolymer.
1. Color: As indicated in the Exterior Color Schedule on the drawings.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. General: Install roof specialties according to manufacturer's written instructions.
Anchor roof specialties securely in place, with provisions for thermal and structural movement. Use fasteners, solder, protective coatings, separators, sealants, and other miscellaneous items as required to complete roof-specialty systems.
1. Install roof specialties level, plumb, true to line and elevation; with limited oil-canning and without warping, jogs in alignment, buckling, or tool marks.
2. Provide uniform, neat seams with minimum exposure of solder and sealant.
3. Install roof specialties to fit substrates and to result in watertight performance.
Verify shapes and dimensions of surfaces to be covered before manufacture.
4. Torch cutting of roof specialties is not permitted.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 6
5. Install underlayment with adhesive for temporary anchorage. Apply in shingle fashion to shed water, with lapped joints of not less than 2 inches.
B. Metal Protection: Protect metals against galvanic action by separating dissimilar metals from contact with each other or with corrosive substrates by painting contact surfaces with bituminous coating or by other permanent separation as recommended by manufacturer.
1. Underlayment: Where installing metal flashing directly on cementitious or wood substrates, install a course of self-adhering, high-temperature sheet underlayment.
C. Expansion Provisions: Allow for thermal expansion of exposed roof specialties.
1. Space movement joints at a maximum of 12 feet with no joints within 18 inches of corners or intersections unless otherwise shown on Drawings.
2. When ambient temperature at time of installation is between 40 and 70 deg F, set joint members for 50 percent movement each way. Adjust setting proportionately for installation at higher ambient temperatures.
D. Fastener Sizes: Use fasteners of sizes that will penetrate wood blocking not less than 1-1/4 inches (32 mm) for nails and not less than 3/4 inch (19 mm) for wood screws.
E. Seal joints with sealant as required by roofing-specialty manufacturer.
F. Seal joints as required for watertight construction. Place sealant to be completely concealed in joint. Do not install sealants at temperatures below 40 deg F.
3.2 ROOF-EDGE FLASHING INSTALLATION
A. Install cleats, cants, and other anchoring and attachment accessories and devices with concealed fasteners.
B. Anchor roof edgings with manufacturer's required devices, fasteners, and fastener spacing to meet performance requirements.
3.3 ROOF-EDGE DRAINAGE-SYSTEM INSTALLATION
A. General: Install components to produce a complete roof-edge drainage system according to manufacturer's written instructions.
B. Gutters: Join and seal gutter lengths. Allow for thermal expansion. Attach gutters to firmly anchored gutter supports spaced not more than 24 inches apart. Attach ends with rivets and seal with sealant to make watertight. Slope to downspouts.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
ROOF SPECIALTIES 077100 - 7
1. Install gutter with expansion joints at locations indicated but not exceeding 50 feet apart. Install expansion joint caps.
C. Downspouts: Join sections with manufacturer's standard telescoping joints. Provide hangers with fasteners designed to hold downspouts securely to walls and 1 inch away from walls; locate fasteners at top and bottom and at approximately 60 inches o.c.
D. Conductor Heads: Anchor securely to wall with elevation of conductor top edge 1 inch below discharge.
3.4 COUNTERFLASHING INSTALLATION
A. General: Coordinate installation of counterflashings with installation of base flashings.
B. Counterflashings: Insert counterflashings into reglets or other indicated receivers;
ensure that counterflashings overlap 4 inches over top edge of base flashings. Lap counterflashing joints a minimum of 4 inches and bed with sealant. Fit counterflashings tightly to base flashings.
3.5 CLEANING AND PROTECTION
A. Clean exposed metal surfaces of substances that interfere with uniform oxidation and weathering.
B. Clean and neutralize flux materials. Clean off excess solder and sealants.
C. Remove temporary protective coverings and strippable films as roof specialties are installed. On completion of installation, clean finished surfaces including removing unused fasteners, metal filings, pop rivet stems, and pieces of flashing. Maintain roof specialties in a clean condition during construction.
D. Replace roof specialties that have been damaged or that cannot be successfully repaired by finish touchup or similar minor repair procedures.
END OF SECTION 077100