233713 diffusers registers and grilles.pdf

PDF 8 KB Posted

Attached to
CONSTRUCT USPFO WAREHOUSE
Solicitation number
W91364-09-B-0003
Issued by

About this file

233713 diffusers registers and grilles.pdf

View the file

Other files

File Type Posted
ADDENDUM NO 02 CSMS PH II Narrative SENT.pdf PDF
USPFO_M001W.pdf PDF
019313 operation and maintenance manuals.pdf PDF
001 Binder Cover Specs Vol 1.pdf PDF
USPFO_S301W.pdf PDF
083613 sectional doors.pdf PDF
E001.pdf PDF
321313 concrete pavement surfacing.pdf PDF
USPFO_F601W.pdf PDF
260548 vibration and seismic controls for elec systems.pdf PDF
OHARNG-USPFO-A-254W .pdf PDF
C607.pdf PDF
051200 structural steel framing.pdf PDF
USPFO_S253W.pdf PDF
053100 steel decking.pdf PDF
344116 traffic control.pdf PDF
013300c attachment substitution request.pdf PDF
105626.13 mobile aisle storage shelving.pdf PDF
C700.pdf PDF
054000 cold-formed metal framing.pdf PDF
260553 electrical identification.pdf PDF
OHARNG-USPFO-A-001W .pdf PDF
E804.pdf PDF
USPFO_M204W.pdf PDF
221116 domestic water piping.pdf PDF
260529 hangers and supports for electrical systems.pdf PDF
274133 cable antenna television system.pdf PDF
264113 lightning protection for structures.pdf PDF
011000 summary —
OHARNG_USPFO_Q601W.pdf PDF
OHARNG-USPFO-G-001W .pdf PDF
C100.pdf PDF
211313 wet-pipe sprinkler systems.pdf PDF
231123 facility natural gas piping.pdf PDF
OHARNG-USPFO-G-110W .pdf PDF
013233 photographic documentation.pdf PDF
260923 lighting control devices .pdf PDF
C605.pdf PDF
087113 automatic door operators.pdf PDF
087100 door hardware.pdf PDF
USPFO_S001W.pdf PDF
312000 earthwork.pdf PDF
220500 common work results for plumbing.pdf PDF
USPFO_M202W.pdf PDF
OHARNG-USPFO-A-720W .pdf PDF
USPFO_M303W.pdf PDF
USPFO_P302W.pdf PDF
USPFO_S254W.pdf PDF
OHARNG-USPFO-G-116W .pdf PDF
010001 affirmative procurement.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

DIFFUSERS, REGISTERS, AND GRILLES 233713 - 1

SECTION 233713 - DIFFUSERS, REGISTERS, AND GRILLES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Round ceiling diffusers.

2. Rectangular and square ceiling diffusers.

3. Perforated diffusers.

4. Louver face diffusers.

5. Drum louvers.

6. Adjustable bar registers and grilles.

7. Fixed face registers and grilles.

B. Related Sections:

1. Division 23 Section "Air Duct Accessories" for fire and smoke dampers and volume-control dampers not integral to diffusers, registers, and grilles.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated, include the following:

1. Data Sheet: Indicate materials of construction, finish, and mounting details;

and performance data including throw and drop, static-pressure drop, and noise ratings.

2. Diffuser, Register, and Grille Schedule: Indicate drawing designation, room location, quantity, model number, size, and accessories furnished.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

DIFFUSERS, REGISTERS, AND GRILLES 233713 - 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Anemostat Products; a Mestek company.

b. Carnes.

c. Hart & Cooley Inc.

d. METALAIRE, Inc.

e. Nailor Industries Inc.

f. Price Industries.

g. Titus.

h. Tuttle & Bailey.

2.2 MANUFACTURED UNITS

A. Diffusers, registers, and grilles are scheduled on Drawings.

2.3 SOURCE QUALITY CONTROL

A. Verification of Performance: Rate diffusers, registers, and grilles according to ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and Inlets."

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas where diffusers, registers, and grilles are to be installed for compliance with requirements for installation tolerances and other conditions affecting performance of equipment.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install diffusers, registers, and grilles level and plumb.

B. Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

DIFFUSERS, REGISTERS, AND GRILLES 233713 - 3

design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practical. For units installed in lay-in ceiling panels, locate units in the center of panel. Where architectural features or other items conflict with installation, notify Contracting Officer for a determination of final location.

C. Install diffusers, registers, and grilles with airtight connections to ducts and to allow service and maintenance of dampers, air extractors, and fire dampers.

3.3 ADJUSTING

A. After installation, adjust diffusers, registers, and grilles to air patterns indicated, or as directed, before starting air balancing.

END OF SECTION 233713