233300 air duct accessories.pdf

PDF 32 KB Posted

Attached to
CONSTRUCT USPFO WAREHOUSE
Solicitation number
W91364-09-B-0003
Issued by

About this file

233300 air duct accessories.pdf

View the file

Other files

File Type Posted
USPFO_P602W.pdf PDF
USPFO_P304W.pdf PDF
USPFO_P701W.pdf PDF
USPFO_F401W.pdf PDF
262923 variable frequency controllers.pdf PDF
224700 drinking fountains and water coolers.pdf PDF
E703.pdf PDF
072100 thermal insulation.pdf PDF
230500 common work results for hvac.pdf PDF
OHARNG_USPFO_Q202W.pdf PDF
USPFO_P303W.pdf PDF
224000 plumbing fixtures.pdf PDF
221123 domestic water pumps.pdf PDF
E504.pdf PDF
074213 metal wall panels.pdf PDF
271300 communications backbone cabling.pdf PDF
OHARNG-USPFO-A-211aW .pdf PDF
096519 resilient tile flooring.pdf PDF
L502.pdf PDF
C000.pdf PDF
223400 fuel-fired domestic water heaters.pdf PDF
USPFO_P301W.pdf PDF
USPFO_S501W.pdf PDF
USPFO_S502W.pdf PDF
260526 grounding and bonding for electrical systems.pdf PDF
OHARNG-USPFO-I-101W .pdf PDF
003 Fly Page.pdf PDF
G140.pdf PDF
061600 sheathing.pdf PDF
271100 communications equipment room fittings.pdf PDF
USPFO_P001W.pdf PDF
OHARNG-USPFO-A-401W .pdf PDF
E304.pdf PDF
012900 payment procedures.pdf PDF
055300 metal gratings.pdf PDF
017900 operational and maintenance training.pdf PDF
OHARNG-USPFO-A-821W .pdf PDF
064023 interior architectural woodwork.pdf PDF
E201.pdf PDF
E301.pdf PDF
033000 cast-in-place concrete.pdf PDF
C501.pdf PDF
OHARNG-USPFO-A-701W .pdf PDF
USPFO_F301W.pdf PDF
USPFO_M502W.pdf PDF
C600.pdf PDF
329200 lawns.pdf PDF
OHARNG-USPFO-A-807W .pdf PDF
096813 tile carpeting.pdf PDF
099123 interior painting.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 1

SECTION 233300 - AIR DUCT ACCESSORIES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Backdraft and Pressure Relief Dampers

2. Manual volume dampers.

3. Control dampers.

4. Fire Dampers.

5. Flange connectors.

6. Turning vanes.

7. Duct-mounted access doors.

8. Flexible connectors.

9. Flexible ducts.

10. Duct accessory hardware.

B. Related Sections:

1. Division 23 Section "Instrumentation and Control for HVAC" for duct-mounted smoke detectors.

2. Division 23 Section "Instrumentation and Control for HVAC" for electric damper actuators.

3. Division 08 Section "Louvers and Vents” for electric damper actuators.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. LEED Submittal:

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1-2004, Section 5 - "Systems and Equipment."

C. Shop Drawings: For duct accessories. Include plans, elevations, sections, details and attachments to other work.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 2

D. Operation and Maintenance Data: For air duct accessories to include in operation and maintenance manuals.

1.4 QUALITY ASSURANCE

A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."

B. Comply with AMCA 500-D testing for damper rating.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.

B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.

1. Galvanized Coating Designation: G90.

2. Exposed-Surface Finish: Mill phosphatized.

C. Aluminum Sheets: Comply with ASTM B 209, Alloy 3003, Temper H14; with mill finish for concealed ducts and standard, 1-side bright finish for exposed ducts.

D. Extruded Aluminum: Comply with ASTM B 221, Alloy 6063, Temper T6.

E. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on galvanized sheet metal ducts; compatible materials for aluminum and stainless-steel ducts.

F. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less;

3/8-inch minimum diameter for lengths longer than 36 inches.

2.2 BACKDRAFT AND PRESSURE RELIEF DAMPERS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. American Warming and Ventilating; a division of Mestek, Inc.

2. Greenheck Fan Corporation.

3. Nailor Industries Inc.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 3

4. Ruskin Company.

5. Vent Products Company, Inc.

B. Description: Gravity balanced.

C. Maximum Air Velocity: 2000 fpm.

D. Maximum System Pressure: 1-inch wg.

E. Frame: Minimum 0.052-inch thick, aluminum, with welded corners.

F. Blades: Multiple single-piece blades, maximum 6-inch width, 0.025-inch thick, roll-formed aluminum with sealed edges.

G. Blade Action: Parallel.

H. Blade Seals: Extruded vinyl, mechanically locked.

I. Blade Axles: Corrosion-resistant, long-life, synthetic, locked to blade

J. Tie Bars and Brackets: Aluminum.

K. Counterbalances: Adjustable zinc plated steel weights mechanically attached to blade enabling damper to operate over wide range of pressures.

L. Bearings: Dustproof ball bearings pressed into hole in frame

M. Accessories:

1. Adjustment device to permit setting for varying differential static pressure.

2. Screen Mounting: Front mounted in sleeve.

3. Screen Material: Aluminum.

4. Screen Type: Insect.

5. 90-degree stops.

2.3 MANUAL VOLUME DAMPERS

A. Standard, Steel, Manual Volume Dampers:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Air Balance Inc.; a division of Mestek, Inc.

b. American Warming and Ventilating; a division of Mestek, Inc.

c. Flexmaster U.S.A., Inc.

d. McGill AirFlow LLC.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 4

e. METALAIRE, Inc.

f. Nailor Industries Inc.

g. Pottorff; a division of PCI Industries, Inc.

h. Ruskin Company.

i. Trox USA Inc.

j. Vent Products Company, Inc.

2. Standard leakage rating, with linkage outside airstream.

3. Suitable for horizontal or vertical applications.

4. Frames:

a. Hat-shaped, galvanized-steel channels, 0.064-inch minimum thickness.

b. Mitered and welded corners.

c. Flanges for attaching to walls and flangeless frames for installing in ducts.

5. Blades:

a. Multiple or single blade.

b. Parallel- or opposed-blade design.

c. Stiffen damper blades for stability.

d. Galvanized-steel, 0.064 inch thick.

6. Blade Axles: Galvanized steel

7. Bearings:

a. Molded synthetic.

b. Dampers in ducts with pressure classes of 3-inch wg or less shall have axles full length of damper blades and bearings at both ends of operating shaft.

8. Tie Bars and Brackets: Galvanized steel.

B. Standard, Aluminum, Manual Volume Dampers:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Air Balance Inc.; a division of Mestek, Inc.

b. American Warming and Ventilating; a division of Mestek, Inc.

c. Flexmaster U.S.A., Inc.

d. McGill AirFlow LLC.

e. METALAIRE, Inc.

f. Nailor Industries Inc.

g. Pottorff; a division of PCI Industries, Inc.

h. Ruskin Company.

i. Trox USA Inc.

j. Vent Products Company, Inc.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 5

2. Standard leakage rating, with linkage outside airstream.

3. Suitable for horizontal or vertical applications.

4. Frames: Hat-shaped, 0.10-inch- thick, aluminum sheet channels; frames with flanges for attaching to walls and flangeless frames for installing in ducts.

5. Blades:

a. Multiple or single blade.

b. Parallel- or opposed-blade design.

c. Stiffen damper blades for stability.

d. Extruded-Aluminum Blades: 0.050-inch- thick extruded aluminum.

6. Blade Axles: Galvanized steel.

7. Bearings:

a. Molded synthetic.

b. Dampers in ducts with pressure classes of 3-inch wg or less shall have axles full length of damper blades and bearings at both ends of operating shaft.

8. Tie Bars and Brackets: Aluminum.

2.4 CONTROL DAMPERS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. American Warming and Ventilating; a division of Mestek, Inc.

2. Greenheck Fan Corporation.

3. Lloyd Industries, Inc.

4. Nailor Industries Inc.

5. Ruskin Company.

6. Vent Products Company, Inc.

B. Low-leakage rating, with linkage outside airstream, and bearing AMCA's Certified Ratings Seal for both air performance and air leakage.

C. Frames:

1. Hat shaped.

2. Extruded aluminum channels, 0.125 inch thick.

3. Mitered and welded or machining staked corners.

D. Blades:

1. Multiple blades with maximum blade width of 6 inches.

2. Parallel- or opposed -blade design.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 6

3. Aluminum.

4. 0.064 inch thick.

5. Blade Edging: Inflatable seal blade edging, or replaceable rubber seals.

E. Blade Axles: 1/2-inch- diameter; galvanized steel; blade-linkage hardware of zinc-plated steel and brass; ends sealed against blade bearings.

1. Operating Temperature Range: From minus 40 to plus 200 deg F.

F. Bearings:

1. Molded synthetic.

2. Dampers in ducts with pressure classes of 3-inch wg or less shall have axles full length of damper blades and bearings at both ends of operating shaft.

3. Thrust bearings at each end of every blade.

2.5 FIRE DAMPERS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Air Balance Inc.; a division of Mestek, Inc.

2. Greenheck Fan Corporation.

3. Nailor Industries Inc.

4. Ruskin Company.

5. Vent Products Company, Inc.

B. Type: Static; rated and labeled according to UL 555 by an NRTL.

C. Fire Rating: 1-1/2 hours.

D. Frame: Curtain type with blades outside airstream; fabricated with roll-formed, 0.034-inch- thick galvanized steel; with mitered and interlocking corners.

E. Mounting Sleeve: Factory- or field-installed, galvanized sheet steel.

1. Minimum Thickness: 0.052 inch thick, as indicated, and of length to suit application.

2. Exception: Omit sleeve where damper-frame width permits direct attachment of perimeter mounting angles on each side of wall or floor; thickness of damper frame must comply with sleeve requirements.

F. Mounting Orientation: Vertical or horizontal as indicated.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 7

G. Blades: Roll-formed, interlocking, 0.034-inch thick, galvanized sheet steel. In place of interlocking blades, use full-length, 0.034-inch thick, galvanized-steel blade connectors.

H. Heat-Responsive Device: Electric resettable link and switch package, factory installed, 165 deg F rated.

2.6 FLANGE CONNECTORS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Ductmate Industries, Inc.

2. Nexus PDQ; Division of Shilco Holdings Inc.

3. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Description: Add-on or roll-formed, factory-fabricated, slide-on transverse flange connectors, gaskets, and components.

C. Material: Galvanized steel.

D. Gage and Shape: Match connecting ductwork.

2.7 TURNING VANES

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Ductmate Industries, Inc.

2. Duro Dyne Inc.

3. METALAIRE, Inc.

4. SEMCO Incorporated.

5. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Manufactured Turning Vanes for Metal Ducts: Curved blades of galvanized sheet steel; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting.

1. Acoustic Turning Vanes: Fabricate airfoil-shaped aluminum extrusions with perforated faces and fibrous-glass fill.

C. General Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"; Figures 2-3, "Vanes and Vane Runners," and 2-4, "Vane Support in Elbows."

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 8

D. Vane Construction: Single wall for ducts up to 48 inches wide and double wall for larger dimensions.

2.8 DUCT-MOUNTED ACCESS DOORS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. American Warming and Ventilating; a division of Mestek, Inc.

2. Cesco Products; a division of Mestek, Inc.

3. Ductmate Industries, Inc.

4. Flexmaster U.S.A., Inc.

5. Greenheck Fan Corporation.

6. McGill AirFlow LLC.

7. Nailor Industries Inc.

8. Pottorff; a division of PCI Industries, Inc.

9. Ventfabrics, Inc.

10. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Duct-Mounted Access Doors: Fabricate access panels according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"; Figures 2-10, "Duct Access Doors and Panels," and 2-11, "Access Panels - Round Duct."

1. Door:

a. Double wall, rectangular.

b. Galvanized sheet metal with insulation fill and thickness as indicated for duct pressure class.

c. Hinges and Latches: 1-by-1-inch butt or piano hinge and cam latches.

d. Fabricate doors airtight and suitable for duct pressure class.

2. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.

3. Number of Hinges and Locks:

a. Access Doors up to 18 Inches Square: Two hinges and two sash locks.

2.9 FLEXIBLE CONNECTORS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Ductmate Industries, Inc.

2. Duro Dyne Inc.

3. Ventfabrics, Inc.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 9

4. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Materials: Flame-retardant or noncombustible fabrics.

C. Coatings and Adhesives: Comply with UL 181, Class 1.

D. Metal-Edged Connectors: Factory fabricated with a fabric strip 3-1/2 inches wide attached to 2 strips of 2-3/4-inch- wide, 0.028-inch- thick, galvanized sheet steel or 0.032-inch- thick aluminum sheets. Provide metal compatible with connected ducts.

E. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.

1. Minimum Weight: 26 oz./sq. yd..

2. Tensile Strength: 480 lbf/inch in the warp and 360 lbf/inch in the filling.

3. Service Temperature: Minus 40 to plus 200 deg F.

F. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with weatherproof, synthetic rubber resistant to UV rays and ozone.

1. Minimum Weight: 24 oz./sq. yd..

2. Minimum Tensile Strength: 500 lbf/inch in the warp and 440 lbf/inch in the filling.

3. Service Temperature: Minus 50 to plus 250 deg F.

4. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure.

5. Elastomeric Element: Molded, oil-resistant rubber or neoprene.

6. Coil Spring: Factory set and field adjustable for a maximum of 1/4-inch movement at start and stop.

2.10 FLEXIBLE DUCTS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Flexmaster U.S.A., Inc.

2. McGill AirFlow LLC.

3. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Insulated, Flexible Duct: UL 181, Class 1, 2-ply vinyl film supported by helically wound, spring-steel wire; fibrous-glass insulation; polyethylene vapor-barrier film.

1. Pressure Rating: 10-inch wg positive and 1.0-inch wg negative.

2. Maximum Air Velocity: 4000 fpm.

3. Temperature Range: Minus 10 to plus 160 deg F.

4. Insulation R-value: Comply with ASHRAE/IESNA 90.1-2004.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 10

C. Flexible Duct Connectors:

1. Clamps: Stainless-steel band with cadmium-plated hex screw to tighten band with a worm-gear action in sizes 3 through 18 inches, to suit duct size.

2.11 DUCT ACCESSORY HARDWARE

A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to suit duct-insulation thickness.

B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline and grease.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install duct accessories according to applicable details in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for metal ducts and in NAIMA AH116, "Fibrous Glass Duct Construction Standards," for fibrous-glass ducts.

B. Install duct accessories of materials suited to duct materials; use galvanized-steel accessories in galvanized-steel and fibrous-glass ducts, stainless-steel accessories in stainless-steel ducts, and aluminum accessories in aluminum ducts.

C. Install control dampers at inlet of exhaust fans or exhaust ducts as close as possible to exhaust fan unless otherwise indicated.

D. Install volume dampers at points on supply, return, and exhaust systems where branches extend from larger ducts. Where dampers are installed in ducts having duct liner, install dampers with hat channels of same depth as liner, and terminate liner with nosing at hat channel.

1. Install steel volume dampers in steel ducts.

E. Set dampers to fully open position before testing, adjusting, and balancing.

F. Install test holes at fan inlets and outlets and elsewhere as indicated.

G. Install smoke dampers according to UL listing.

H. Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining accessories and equipment at the following locations:

1. On both sides of duct coils.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

AIR DUCT ACCESSORIES 233300 - 11

2. At outdoor-air intakes and mixed-air plenums.

3. Downstream from manual volume dampers, control dampers, backdraft dampers, and equipment.

4. Adjacent to and close enough to smoke dampers, to reset or reinstall fusible links. Access doors for access to smoke dampers having fusible links shall be pressure relief access doors and shall be outward operation for access doors installed upstream from dampers and inward operation for access doors installed downstream from dampers.

5. At each change in direction and at maximum 50-foot spacing.

6. Control devices requiring inspection.

I. Install access doors with swing against duct static pressure.

J. Access Door Sizes:

1. One-Hand or Inspection Access: 8 by 5 inches.

2. Two-Hand Access: 12 by 6 inches.

3. Head and Hand Access: 18 by 10 inches.

K. Label access doors according to Division 23 Section "Identification for HVAC Piping and Equipment" to indicate the purpose of access door.

L. Install flexible connectors to connect ducts to equipment.

M. Connect terminal units or diffusers to supply ducts with maximum lengths of flexible duct as indicated in the drawings. Do not use flexible ducts to change directions.

N. Connect flexible ducts to metal ducts with draw bands.

O. Install duct test holes where required for testing and balancing purposes.

3.2 FIELD QUALITY CONTROL

A. Tests and Inspections:

1. Operate dampers to verify full range of movement.

2. Inspect locations of access doors and verify that purpose of access door can be performed.

3. Operate smoke dampers to verify full range of movement and verify that proper response device is installed.

4. Inspect turning vanes for proper and secure installation.

5. Operate remote damper operators to verify full range of movement of operator and damper.

END OF SECTION 233300