224500 emergency plumbing fixtures.pdf

PDF 16 KB Posted

Attached to
CONSTRUCT USPFO WAREHOUSE
Solicitation number
W91364-09-B-0003
Issued by

About this file

224500 emergency plumbing fixtures.pdf

View the file

Other files

File Type Posted
Bid Abstract 09-B-0003.pdf PDF
SF30Amendment2 09-B-0003.pdf PDF
ADDENDUM NO 03 USPFO Narrative.pdf PDF
ADDENDUM NO 02 USPFO Narrative SENT.pdf PDF
SF30Amendment3 09-B-0003.pdf PDF
09-B-0003 Amendment 3.pdf PDF
ADDENDUM NO 03 CSMS PH II Narrative.pdf PDF
ADDENDUM NO 02 CSMS PH II Narrative SENT.pdf PDF
USPFO WH Addendum.pdf PDF
Bid Questions USPFO WAREHOUSE JACOBS RESPONSES JFK.doc DOC document
e2c23100.PDF PDF
OHARNG-USPFO-G-130W .pdf PDF
OHARNG-USPFO-A-820W .pdf PDF
083730 high speed rolling door.pdf PDF
220523 general duty valves for plumbing piping.pdf PDF
092900 gypsum board.pdf PDF
102113 toilet compartments.pdf PDF
OHARNG-USPFO-A-723W .pdf PDF
270500 common work results for communications.pdf PDF
081113 hollow metal doors and frames.pdf PDF
052100 steel joist framing.pdf PDF
017329 cutting and patching.pdf PDF
220516 expansion fittings and loops for plumbing piping.pdf PDF
104413 fire extinguishing cabinets.pdf PDF
102800 toilet bath and laundry accessories.pdf PDF
077100 roof specialties.pdf PDF
061000 rough carpentry.pdf PDF
USPFO_FA501W.pdf PDF
USPFO_M501W.pdf PDF
USPFO_S252W.pdf PDF
E802.pdf PDF
E104.pdf PDF
055000 metal fabrications.pdf PDF
USPFO_M301W.pdf PDF
OHARNG-USPFO-A-806W .pdf PDF
OHARNG-USPFO-A-213bW .pdf PDF
C603.pdf PDF
263600 transfer switches.pdf PDF
017839 project record documents.pdf PDF
230811 pre-functional checklists mechanical.pdf PDF
093000 tiling.pdf PDF
E401.pdf PDF
013200 construction progress documentation.pdf PDF
260533 raceway and boxes for electrical systems.pdf PDF
OHARNG-USPFO-A-320W .pdf PDF
311000 clearing grubbing.pdf PDF
262413 switchboards.pdf PDF
221319 sanitary waste piping specialties.pdf PDF
USPFO_FA301W.pdf PDF
260500 common work results for electrical.pdf PDF
Show 40 more

Latest 50 of 373 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

EMERGENCY PLUMBING FIXTURES 224500 – 1

SECTION 224500 - EMERGENCY PLUMBING FIXTURES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following emergency plumbing fixtures:

1. Combination units.

B. Related Sections include the following:

1. Division 22 Section "Domestic Water Piping Specialties".

1.3 DEFINITIONS

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

B. Plumbed Emergency Plumbing Fixture: Fixture with fixed, potable-water supply.

C. Tepid: Moderately warm.

1.4 SUBMITTALS

A. Product Data: For each type of product indicated. Include flow rates and capacities, furnished specialties, and accessories.

B. Shop Drawings: Diagram power, signal, and control wiring.

C. Product Certificates: Submit certificates of performance testing specified in "Source Quality Control" Article.

D. Field quality-control test reports.

E. Operation and Maintenance Data: For emergency plumbing fixtures to include in main-tenance manuals.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

EMERGENCY PLUMBING FIXTURES 224500 – 2

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. ANSI Standard: Comply with ANSI Z358.1, "Emergency Eyewash and Shower Equip-ment."

C. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public Law 101-336, "Americans with Disabilities Act"; for plumbing fixtures for people with disabilities.

D. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health Ef-fects," for fixture materials that will be in contact with potable water.

PART 2 - PRODUCTS

2.1 COMBINATION UNITS

A. Combination Units

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Bradley Corporation.

b. Guardian Equipment Co.

c. Haws Corporation.

d. Speakman Company.

2. Description: Plumbed, accessible, freestanding, with emergency shower and eyewash equipment.

a. Piping: Galvanized steel.

1) Unit Supply: NPS 1-1/4 minimum from top.

2) Unit Drain: Outlet at side near bottom.

3) Shower Supply: NPS 1 with flow regulator and stay-open control valve.

4) Eyewash Supply: NPS 1/2 with flow regulator and stay-open control valve.

b. Shower Capacity: Deliver potable water at rate not less than 20 gpm for at least 15 minutes.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

EMERGENCY PLUMBING FIXTURES 224500 – 3

1) Control-Valve Actuator: Pull chain.

2) Shower Head: 8-inch minimum diameter, chrome-plated brass or stainless steel.

c. Eyewash Equipment: With capacity to deliver potable water at rate not less than 0.4 gpm for at least 15 minutes.

1) Control-Valve Actuator: Paddle.

2) Receptor: Chrome-plated brass or stainless-steel bowl.

2.2 WATER-TEMPERING EQUIPMENT

A. Water-Tempering Equipment:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Armstrong International, Inc.

b. Bradley Corporation.

c. Encon Safety Products.

d. Haws Corporation.

e. Lawler Manufacturing Co., Inc.

f. Leonard Valve Company.

g. Powers, a Watts Industries Co.

h. Speakman Company.

2. Description: Factory-fabricated, hot- and cold-water-tempering equipment with thermostatic mixing valve.

a. Thermostatic Mixing Valve: Designed to provide 85 deg F tepid, potable water at emergency plumbing fixtures, to maintain temperature at plus or minus 5 deg F throughout required 15-minute test period, and in case of unit failure to continue cold-water flow, with union connections, controls, metal piping, and corrosion-resistant enclosure.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine roughing-in for water and waste piping systems to verify actual locations of pip-ing connections before plumbed emergency plumbing fixture installation.

1. Proceed with installation only after unsatisfactory conditions have been corrected.

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

EMERGENCY PLUMBING FIXTURES 224500 – 4

3.2 EMERGENCY PLUMBING FIXTURE INSTALLATION

A. Assemble emergency plumbing fixture piping, fittings, control valves, and other compo-nents.

B. Install fixtures level and plumb.

C. Fasten fixtures to substrate.

D. Install shutoff valves in water-supply piping to fixtures. Use ball, gate, or globe valve if specific type valve is not indicated. Install valves chained or locked in open position if permitted. Install valves in locations where they can easily be reached for operation.

Valves are specified in Division 22 Section "General-Duty Valves for Plumbing Piping."

1. Exception: Omit shutoff valve on supply to emergency equipment if prohibited by authorities having jurisdiction.

E. Install dielectric fitting in supply piping to fixture if piping and fixture connections are made of different metals. Dielectric fittings are specified in Division 22 Section "Com-mon Work Results for Plumbing."

F. Install thermometers in supply and outlet piping connections to water-tempering equip-ment. Thermometers are specified in Division 22 Section "Meters and Gages for Plumb-ing Piping."

G. Install escutcheons on piping wall and ceiling penetrations in exposed, finished loca-tions. Escutcheons are specified in Division 22 Section "Common Work Results for Plumbing."

H. Install equipment nameplates or equipment markers on fixtures and equipment signs on water-tempering equipment. Identification materials are specified in Division 22 Section "Identification for Plumbing Piping and Equipment."

3.3 CONNECTIONS

A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect hot- and cold-water-supply piping to hot- and cold-water-tempering equipment.

Connect output from water-tempering equipment to emergency plumbing fixtures.

C. Ground equipment according to Division 26 Section "Grounding and Bonding for Electri-cal Systems."

D. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conduc-tors and Cables."

Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final

EMERGENCY PLUMBING FIXTURES 224500 – 5

3.4 FIELD QUALITY CONTROL

A. Mechanical-Component Testing: After plumbing connections have been made, test for compliance with requirements. Verify ability to achieve indicated capacities and tem-peratures.

B. Electrical-Component Testing: After electrical circuitry has been energized, test for compliance with requirements.

1. Test and adjust controls and safeties.

C. Repair or replace malfunctioning units. Retest as specified above after repairs or re-placements are made.

D. Report test results in writing.

3.5 ADJUSTING

A. Adjust or replace fixture flow regulators for proper flow.

B. Adjust equipment temperature settings.

END OF SECTION 224500