W912QR21R0023_Specs_Vol3-0000.pdf
PDF 20 MB Posted
- Attached to
- Hydrant Fuel Replacement at Niagara ARS, Niagara Falls Federal contract opportunity
- Solicitation number
- W912QR21R0023
About this file
This document outlines a federal contract opportunity for fuel hydrant repair work at Niagara Falls Air Reserve Station in New York. The Army Corps of Engineers is soliciting proposals for replacing hydrant fuel systems with an estimated cost between $10-25 million. The solicitation is a full and open competition under NAICS code 237120 requiring offerors to comply with HUBZone price evaluation, Central Contractor Registration, and System for Award Management requirements. Questions must be submitted through the ProjNet website, and funds are not presently available though no contract will be awarded until appropriated. The closing date was not specified.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W912QR21R0023_Specs-0005.pdf | ||
| W912QR21R0023_Plans-0005.pdf | ||
| W912QR21R0023-0004.pdf | ||
| W912QR21R0023_Plans-0003.pdf | ||
| W912QR21R0023_Specs-0003.pdf | ||
| W912QR21R0023_Specs-0002.pdf | ||
| W912QR21R0023_Plans-0002.pdf | ||
| W912QR21R0023_Plans_Vol1-0001.pdf | ||
| JA - Hydrant Fuel - Andover Continuum (LRL-FY21-69)_Redacted.pdf | ||
| W912QR21R0023_Plans_Vol2-0001.pdf | ||
| W912QR21R0023_Specs_Vol1-0001.pdf | ||
| W912QR21R0023_Specs_Vol2-0001.pdf | ||
| W912QR21R0023_Specs_Vol3-0001.pdf | ||
| Sign in Sheet from Site Visit.pdf | ||
| W912QR21R0023_CID-0000.pdf | ||
| JA - Telemetry and Process Controls (LRL-FY21-06)_Redacted.pdf | ||
| W912QR21R0023_Plans_Vol2-0000.pdf | ||
| JA - Hydrant Project - Simplex Fire Alarm (LRL-FY21-03)_Redacted.pdf | ||
| W912QR21R0023_Plans_Vol1-0000R.pdf | ||
| W912QR21R0023_Specs_Vol1-0000.pdf | ||
| W912QR21R0023_Specs_Vol2-0000.pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Replacement Fuel Bulk Storage Facility Hydrant Repair Niagara Falls ARS, NY
P2: 488039, 488040, 488041
Design Bid Build
Specifications - Vol. 3 of 3 Corrected Final Design Submittal
21 May 2021
W912QR21R0023
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR21R0023-0000
REPLACEMENT FUEL BULK STORAGE FACILITY
HYDRANT REPAIR
NIAGARA FALLS AIR RESERVE STATION, NY
CORRECTED FINAL SUBMITTAL
SPECIFICATIONS VOLUME 3 OF 3
MAY 10, 2021
CONTRACT NO.: W912QR-16-D-0022 | TASK ORDER NO.: W912QR20F7420
P2#: 488039, 488040, 488041
A/E PROJECT NO.: 1210132
Repair of Fuel Hydrant System Niagara Falls ARS, NY
THIS PAGE INTENTIONALLY LEFT BLANK
PROJECT TABLE OF CONTENTS Page 1
FINAL DESIGN SUBMITTAL
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 80 00.00 06 SPECIAL PROVISIONS
00 80 00.00 06A1 SIGN DETAIL
DIVISION 01 - GENERAL REQUIREMENTS
01 32 01.00 06 PROJECT SCHEDULE
01 33 00.00 06 SUBMITTAL PROCEDURES
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 46 00.00 06 TOTAL BUILDING COMMISSIONING
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 20.00 10 ENVIRONMENTAL MANAGEMENT AND PROTECTION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 23.33 OPERATION AND MAINTENANCE MANUALS FOR AVIATION FUEL
SYSTEMS
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
02 61 23 REMOVAL AND DISPOSAL OF PCB CONTAMINATED SOILS
02 81 00 TRANSPORTATION AND DISPOSAL OF HAZARDOUS MATERIALS
02 83 13.00 06 LEAD IN CONSTRUCTION
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 50 14 STRUCTURAL METAL FABRICATIONS
05 51 00 METAL STAIRS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 14 00 FLUID-APPLIED WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
PROJECT TABLE OF CONTENTS Page 2
07 21 29 SPRAYED INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 13 METAL WALL PANELS
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 61 15.00 20 ALUMINUM STANDING SEAM ROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 33 23 OVERHEAD COILING DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 56 53 BLAST RESISTANT TEMPERED GLASS WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 29 00 GYPSUM BOARD
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 67 23.16 FUEL RESISTIVE RESINOUS FLOORING, 5-COAT SYSTEM
09 68 00 CARPETING
09 90 00 PAINTS AND COATINGS
09 96 00 HIGH-PERFORMANCE COATINGS
09 97 13.17 THREE COAT EPOXY INTERIOR COATING OF WELDED STEEL
PETROLEUM FUEL TANKS
09 97 13.27 HIGH PERFORMANCE COATING FOR STEEL STRUCTURES
DIVISION 10 - SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 26 00 WALL AND DOOR PROTECTION
10 44 16 FIRE EXTINGUISHERS
10 73 00 PRE-MANUFACTURED ALUMINUM CANOPIES
DIVISION 11 - EQUIPMENT
11 53 00 LABORATORY EQUIPMENT AND FUMEHOODS
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 36 00 COUNTERTOPS
DIVISION 21 - FIRE SUPPRESSION
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 07 19.00 40 PIPING INSULATION
PROJECT TABLE OF CONTENTS Page 3
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 48.19 BRACING FOR HVAC
23 05 93.00 06 TESTING, ADJUSTING, AND BALANCING (TAB) OF HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 20 FACILITY GAS PIPING
23 23 00 REFRIGERANT PIPING
23 30 00 HVAC AIR DISTRIBUTION
23 82 46.00 40 ELECTRIC UNIT HEATERS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
25 08 10 UTILITY MONITORING AND CONTROL SYSTEM TESTING
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 08 00 APPARATUS INSPECTION AND TESTING
26 12 19.10 THREE-PHASE, LIQUID-FILLED PAD-MOUNTED TRANSFORMERS
26 20 00 ELECTRICAL DISTRIBUTION SYSTEM
26 24 19.00 40 MOTOR CONTROL CENTERS
26 41 00 LIGHTNING PROTECTION SYSTEM
26 42 13.00 20 CATHODIC PROTECTION BY GALVANIC ANODES
26 42 17.00 10 CATHODIC PROTECTION SYSTEM (IMPRESSED CURRENT)
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 70 INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM,
ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00.00 06 EARTHWORK
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 11.51 RUBBER AND PAINT REMOVAL FROM AIRFIELD PAVEMENTS
32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENT
32 01 29.61 PARTIAL DEPTH PATCHING OF RIGID PAVING
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 14.13 CONCRETE PAVING FOR AIRFIELDS AND OTHER HEAVY DUTY
PAVEMENTS
32 13 15.20 CONCRETE PAVEMENT FOR CONTAINMENT DIKES
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 92 19 SEEDING
DIVISION 33 - UTILITIES
PROJECT TABLE OF CONTENTS Page 4
33 01 50.31 LEAK DETECTION FOR FUELING SYSTEMS
33 01 50.55 CLEANING OF PETROLEUM STORAGE TANKS
33 08 53 AVIATION FUEL DISTRIBUTION SYSTEM START-UP
33 08 53A1 EQUIMENT TESTS
33 08 53A2 PERFORMANCE TESTING
33 09 53 AVIATION FUEL PUMP CONTROL AND ANNUNCIATION SYSTEM
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 40 00 STORM DRAINAGE UTILITIES
33 52 23.15 POL SERVICE PIPING WELDING
33 52 43.11 AVIATION FUEL MECHANICAL EQUIPMENT
33 52 43.13 AVIATION FUEL PIPING
33 52 43.14 AVIATION FUEL CONTROL VALVES
33 52 43.23 AVIATION FUEL PUMPS
33 52 80 LIQUID FUELS PIPELINE COATING SYSTEMS
33 56 10 FACTORY-FABRICATED FUEL STORAGE TANKS
33 56 10A1 PETROLEUM BULK STORAGE APPLICATION
33 56 19 FUEL IMPERMEABLE LINER SYSTEM
33 56 21.17 SINGLE WALL ABOVEGROUND FIXED ROOF STEEL POL STORAGE TANK
33 56 21.17A1 API-653 OUT-OF-SERVICE INSPECTION
33 56 21.18 SINGLE WALL POL TANK UNDERTANK INTERSTITIAL SPACE
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
APPENDICES
APPENDIX A HAZARDOUS MATERIALS ASSESSMENT
APPENDIX B PRE-WORK NOTIFICATION
-- End of Project Table of Contents --
SECTION 28 31 70
INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 4 (2018) Standard for Integrated Fire Protection and Life Safety System Testing
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
NFPA 72 (2019; TIA 19-1; ERTA 1 2019) National Fire Alarm and Signaling Code
NFPA 170 (2018) Standard for Fire Safety and Emergency Symbols
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-601-02 (2010) Operations and Maintenance:
Inspection, Testing, and Maintenance of Fire Protection Systems
UFC 4-010-06 (2016; with Change 1, 2017) Cybersecurity of Facility-Related Control Systems
UNDERWRITERS LABORATORIES (UL)
UL 268 (2016; Reprint Oct 2019) UL Standard for Safety Smoke Detectors for Fire Alarm Systems
SECTION 28 31 70 Page 1
UL 464 (2016; Reprint Sep 2017) UL Standard for Safety Audible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories
UL 497A (2001; Bul. 2019) UL Standard for Safety Secondary Protectors for Communications Circuits
UL 497B (2004; Reprint Dec 2012) Protectors for Data Communication Circuits
UL 864 (2014; Reprint May 2020) UL Standard for Safety Control Units and Accessories for Fire Alarm Systems
UL 1283 (2017) UL Standard for Safety Electromagnetic Interference Filters
UL 1449 (2014; Reprint Jul 2017) UL Standard for Safety Surge Protective Devices
UL 1638 (2016; Reprint Sep 2017) UL Standard for Safety Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories
UL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing Impaired
UL Fire Prot Dir (2012) Fire Protection Equipment Directory
1.2 SUMMARY
1.2.1 Scope
a. This work includes designing and providing a new, complete, fire alarm system as described herein and on the contract drawings. Include system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, initiating devices, notification appliances, supervising station fire alarm transmitters, and other accessories and miscellaneous items required for a complete operational system even though each item is not specifically mentioned or described. Provide system complete and ready for operation.
UFC 4-010-06 and AFGM 2019-320-02.
b. Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with NFPA 72 , except as modified herein. The system layout on the drawings show the intent of coverage and suggested locations. Final quantity, system layout, and coordination are the responsibility of the Contractor.
c. The fire alarm system must be independent of the building security, building management, and energy/utility monitoring systems other than for control functions.
SECTION 28 31 70 Page 2
1.2.2 Qualified Fire Protection Engineer (QFPE)
Services of the Contractor's QFPE must include:
a. Reviewing SD-02, SD-03, and SD-05 submittal packages for completeness and compliance with the provisions of this specification.
Construction (shop) drawings and calculations must be prepared by, or prepared under the immediate supervision of, the fire protection specialist . The QFPE must review the show drawings and affix their review stamp prior to submitting the shop drawings to the DFPE.
b. Providing a letter documenting that the SD-02, SD-03, and SD-05 submittal package has been reviewed and noting any outstanding comments.
c. Performing in-progress construction surveillance prior to installation of ceilings (rough-in inspection).
d. Witnessing pre-Government functional performance testing and performing a final installation review.
e. Signing applicable certificates under SD-07.
1.3 DEFINITIONS
Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions must be defined as follows:
1.3.1 Interface Device
An addressable device that interconnects hard wired systems or devices to an analog/addressable system.
1.3.2 Fire Alarm Control Unit (FACU)
A master control unit having the features of a fire alarm control unit
(FACU).
1.3.3 Remote Fire Alarm Control Unit
A control unit, physically remote from the fire alarm control unit, that receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm and mass notification control unit.
1.3.4 Terminal Cabinet
A steel cabinet with locking, hinge-mounted door where terminal strips are securely mounted inside the cabinet.
1.3.5 Control Module and Relay Module
Terms utilized to describe emergency control function interface devices as defined by NFPA 72 .
SECTION 28 31 70 Page 3
1.3.6 Designated Fire Protection Engineer (DFPE)
The DoD fire protection engineer that oversees that Area of Responsibility for that project. This is sometimes referred to as the "cognizant" fire protection engineer. Interpret reference to "authority having jurisdiction" and/or AHJ in referenced standards to mean the Designated Fire Protection Engineer (DFPE). The DFPE may be responsible for review of the contractor submittals having a "G" designation, and for witnessing final inspection and testing.
1.3.7 Qualified Fire Protection Engineer (QFPE)
A QFPE is an individual who is a licensed professional engineer (P.E.), who has passed the fire protection engineering written examination administered by the National Council of Examiners for Engineering and Surveying (NCEES) and has relevant fire protection engineering experience.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Shop drawings (SD-02), product data (SD-03) and calculations (SD-05) must be prepared by the fire alarm designer and combined and submitted as one complete package. The QFPE must review the SD-02/SD-03/SD-05 submittal package for completeness and compliance with the Contract provisions prior to submission to the Government. Partial submittals and submittals not reviewed by the QFPE will be returned by the Government disapproved without review.
Submit the following in accordance with Section 01 33 00.00 06 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Qualified Fire Protection Engineer (QFPE) ;
Fire alarm system designer ; G
Supervisor ;
Technician ;
Installer ;
Test Technician ; G
Fire Alarm System Site-Specific Software Acknowledgement ; G
SD-02 Shop Drawings
Nameplates ; G
Instructions ; G
Wiring Diagrams ; G
SECTION 28 31 70 Page 4
System Layout ; G
Notification Appliances ; G
Initiating devices ; G
Battery Power ; G
Voltage Drop Calculations ; G
SD-03 Product Data
Fire Alarm Control Unit (FACU) ; G
Manual Stations ; G
Smoke Detectors ; G
Notification Appliances ; G
Batteries ; G
Battery Chargers ; G
Surge Protective Devices ; G
Alarm Wiring ; G
Back Boxes and Conduit ; G
Terminal Cabinets ; G
Automatic Fire Alarm Transmitters (including housing); G
Digital Alarm Communicator Transmitter (DACT) ; G
Document Storage Cabinet ; G
SD-06 Test Reports
Test Procedures
SD-07 Certificates
Verification of Compliant Installation ;
Request for Government Final Test ; G
SD-10 Operation and Maintenance Data
Operation and Maintenance (O&M) Instructions ;
Instruction of Government Employees ;
SD-11 Closeout Submittals
As-Built Drawings
Spare Parts
SECTION 28 31 70 Page 5
1.5 SYSTEM OPERATION
Fire alarm system components requiring power, except for the FACU(s) power supply, must operate on 24 volts DC unless noted otherwise in this section.
The interior fire alarm system must be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to NFPA 72 , and UL 864 .
Systems meeting UL 2017 only are not acceptable. The system must be activated into the alarm mode by actuation of an alarm initiating device.
The system must remain in the alarm mode until the initiating device is reset and the control unit is reset and restored to normal.
1.5.1 Alarm Initiating Devices and Notification Appliances (Visual, Audible)
a. Connect alarm initiating devices to initiating device circuits (IDC) Class "B", or to signaling line circuits (SLC) Class "B" and installed in accordance with NFPA 72 .
b. Connect notification appliances to notification appliance circuits (NAC) Class "B".
1.5.2 Functions and Operating Features
The system must provide the following functions and operating features:
a. Power, annunciation, supervision, and control for the system.
Addressable systems must be microcomputer (microprocessor or microcontroller) based with a minimum word size of eight bits with sufficient memory to perform as specified.
b. Visual alarm notification appliances must be synchronized as required by NFPA 72 .
c. Electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control unit.
d. An audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal must also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory control unit modules. After the system returns to normal operating conditions, the trouble signal must again sound until the trouble is acknowledged. A smoke detector in the process of being verified for the actual presence of smoke must not initiate a trouble condition.
e. A trouble signal silence feature that must silence the audible trouble signal, without affecting the visual indicator.
f. Program capability via switches in a locked portion of the FACU to bypass the automatic notification appliance circuits, features.
Operation of this programmed action must indicate on the FACU display as a supervisory or trouble condition.
g. Alarm functions must override trouble or supervisory functions.
Supervisory functions must override trouble functions.
SECTION 28 31 70 Page 6
h. The system must be capable of being programmed from the control unit keyboard. Programmed information must be stored in non-volatile memory.
i. The system must be capable of operating, supervising, and/or monitoring non-addressable alarm and supervisory devices.
j. There must be no limit, other than maximum system capacity, as to the number of addressable devices that may be in alarm simultaneously.
k. An alarm signal must automatically initiate the following functions:
(1) Transmission of an alarm signal to a fire station.
(2) Visual indication of the device operated on the FACU
( 3) Actuation of alarm notification appliances.
( 4) Recording of the event electronically in the history log of the
FACU.
l . A trouble condition must automatically initiate the following functions:
(1) Visual indication of the device operated on the FACU .
( 2) Transmission of a trouble signal to a fire station.
( 3) Recording of the event electronically in the history log of the
FACU.
1.6 TECHNICAL DATA AND SITE-SPECIFIC SOFTWARE
Technical data and site-specific software (meaning technical data that relates to computer software) that are specifically identified in this project, and may be required in other specifications, must be delivered, strictly in accordance with the CONTRACT CLAUSES. The fire alarm system manufacturer must submit written confirmation of this contract provision as " Fire Alarm System Site-Specific Software Acknowledgement ". Identify data delivered by reference to the specification paragraph against which it is furnished. Data to be submitted must include complete system, equipment, and software descriptions. Descriptions must show how the equipment will operate as a system to meet the performance requirements of this contract. The site-specific software data package must also include the following:
a. Items identified in NFPA 72, titled "Site-Specific Software".
b. Identification of programmable portions of the system equipment and capabilities.
c. Description of system revision and expansion capabilities and methods of implementation detailing both equipment and software requirements.
d. Provision of operational software data on all modes of programmable portions for fire alarm .
e. Description of Fire Alarm Control Unit equipment operation.
SECTION 28 31 70 Page 7
f. Description of auxiliary and remote equipment operations.
g. Library of application software.
h. Operation and maintenance manuals.
1.7 Existing Equipment
1.7.1 The supervising equipment is existing and consists of the following brands and models: Simplex
1.8 QUALITY ASSURANCE
1.8.1 Submittal Documents
1.8.1.1 Preconstruction Submittals
Within 36 days of contract award but not less than 14 days prior to commencing any work on site, the Contractor must submit the following for review and approval. SD-02, SD-03 and SD-05 submittals received prior to the review and approval of the qualifications of the fire alarm subcontractor and QFPE must be returned disapproved without review. All resultant delays must be the sole responsibility of the Contractor.
1.8.1.2 Shop Drawings
Shop drawings must not be smaller than the Contract Drawings. Drawings must comply with the requirements of NFPA 72 and NFPA 170 . Minimum scale for floor plans must be 1/8"=1'.
1.8.1.3 Nameplates
Nameplate illustrations and data to obtain approval by the Contracting Officer before installation.
1.8.1.4 Wiring Diagrams
1 cop y of point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems that are supervised or controlled by the system. Diagrams must show connections from field devices to the FACU and remote FACU, initiating circuits, switches, relays and terminals, including pathway diagrams between the control unit and shared communications equipment within the protected premises. Point-to-point wiring diagrams must be job specific and must not indicate connections or circuits not being utilized. Provide complete riser diagrams indicating the wiring sequence of all devices and their connections to the control equipment. Include a color-code schedule for the wiring.
1.8.1.5 System Layout
1 cop y of plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, conduit sizes, wire counts, conduit fill calculations, wire color-coding, circuit identification in each conduit, and circuit layouts for all floors. Indicate candela rating of each visual notification appliance.
Clearly identify the locations of isolation modules. Indicate the addresses of all devices, modules, relays, and similar. Indicate if the
SECTION 28 31 70 Page 8 environment for the FACU is within its environmental listing (e.g.
temperature/humidity).
Provide a complete description of the system operation in matrix format similar to the "Typical Input/Output Matrix" included in the Annex of
NFPA 72 .
1.8.1.6 Notification Appliances
Calculations and supporting data on each circuit to indicate that there is at least 25 percent spare capacity for notification appliances. Annotate data for each circuit on the drawings.
1.8.1.7 Initiating Devices
Calculations and supporting data on each circuit to indicate that there is at least 25 percent spare capacity for initiating devices. Annotate data for each circuit on the drawings.
1.8.1.8 Battery Power
Calculations and supporting data as required in paragraph Battery Power Calculations for alarm, alert, and supervisory power requirements.
Calculations including ampere-hour requirements for each system component and each control unit component, and the battery recharging period, must be included on the drawings.
1.8.1.9 Voltage Drop Calculations
Voltage drop calculations for each notification circuit indicating that sufficient voltage is available for proper operation of the system and all components, at a minimum rated voltage of the system operating on batteries. Include the calculations on the system layout drawings.
1.8.1.10 Product Data
1 cop y of annotated descriptive data to show the specific model, type, and size of each item. Catalog cuts must also indicate the NRTL listing. The data must be highlighted to show model, size, and options that are intended for consideration. Data must be adequate to demonstrate compliance with all contract requirements. Product data for all equipment must be combined into a single submittal.
Provide an equipment list identifying the type, quantity, make, and model number of each piece of equipment to be provided under this submittal.
The equipment list must include the type, quantity, make and model of spare equipment. Types and quantities of equipment submitted must coincide with the types and quantities of equipment used in the battery calculations and those shown on the shop drawings.
1.8.1.11 Operation and Maintenance (O&M) Instructions
Six copies of the Operation and Maintenance Instructions. The O&M Instructions must be prepared in a single volume or in multiple volumes, with each volume indexed, and may be submitted as a Technical Data Package. Manuals must be approved prior to training. The Interior Fire Alarm System Operation and Maintenance Instructions must include the following:
SECTION 28 31 70 Page 9
a. Operating manual outlining step-by-step procedures required for system startup, operation, and shutdown. The manual must include the manufacturer's name, model number, service manual, parts list, and preliminary equipment list complete with description of equipment and their basic operating features.
b. Maintenance manual listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. The manuals must include conduit layout, equipment layout and simplified wiring, and control diagrams of the system as installed.
c. Complete procedures for system revision and expansion, detailing both equipment and software requirements.
d. Software submitted for this project on CD/DVD media utilized.
e. Printouts of configuration settings for all devices.
f . Routine maintenance checklist. The routine maintenance checklist must be arranged in a columnar format. The first column must list all installed devices, the second column must state the maintenance activity or state no maintenance required, the third column must state the frequency of the maintenance activity, and the fourth column provided for additional comments or reference. All data (devices, testing frequencies, and similar) must comply with UFC 3-601-02 .
g. A final Equipment List must be submitted with the Operating and Maintenance (O&M) manual.
1.8.1.12 As-Built Drawings
The drawings must show the system as installed, including deviations from both the project drawings and the approved shop drawings. These drawings must be submitted within two weeks after the final Government test of the system. At least one set of the as-built (marked-up) drawings must be provided at the time of, or prior to the final Government test , furnished by the contractor.
1.8.2 Qualifications
1.8.2.1 Fire Alarm System Designer
The fire alarm system designer must be certified as a Level III (minimum) Technician by National Institute for Certification in Engineering Technologies (NICET) in the Fire Alarm Systems subfield of Fire Protection Engineering Technology or meet the qualifications for a QFPE.
1.8.2.2 Supervisor
A NICET Level III or IV fire alarm technician must supervise the installation of the fire alarm system . A fire alarm technician with a minimum of eight years of experience must supervise the installation of the fire alarm system. The fire alarm technicians supervising the installation of equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
SECTION 28 31 70 Page 10
1.8.2.3 Technician
Fire alarm technicians with a minimum of four years of experience must be utilized to install and terminate fire alarm devices, cabinets and control units. The fire alarm technicians installing the equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.8.2.4 Installer
Fire alarm installer with a minimum of two years of experience utilized to assist in the installation of fire alarm devices, cabinets and control units NICET Level II technician to assist in the installation of fire alarm devices, cabinets and control units. A licensed electrician must be allowed to install wire, cable, conduit and backboxes for the fire alarm system system. The fire alarm installer must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.8.2.5 Test Technician
Fire alarm technicians with a minimum of eight years of experience and NICET Level III or IV utilized in testing and certification of the installation of the fire alarm devices, cabinets and control units. The fire alarm technicians testing the equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment installed as part of this project.
1.8.2.6 Manufacturer
Components must be of current design and must be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to NFPA 72 , except as specified herein.
1.8.3 Regulatory Requirements
Equipment and material must be listed or approved. Listed or approved, as used in this Section, means listed, labeled or approved by a Nationally Recognized Testing Laboratory (NRTL) such as UL Fire Prot Dir or FM APP GUIDE. The omission of these terms under the description of any item of equipment described must not be construed as waiving this requirement. All listings or approvals by testing laboratories must be from an existing ANSI or UL published standard. The recommended practices stated in the manufacturer's literature or documentation must be considered as mandatory requirements.
1.9 DELIVERY, STORAGE, AND HANDLING
Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.
1.10 MAINTENANCE
1.10.1 Spare Parts
Furnish the following spare parts in the manufacturers original unopened containers:
SECTION 28 31 70 Page 11
a. Five complete sets of system keys.
b. Two of each type of fuse required by the system.
c. One manual stations.
d. Two of each type of detector installed.
e. Two of each type of audible and visual alarm device installed.
f . Two of each type of addressable monitor module installed.
g. Two low voltage, and one 120 VAC surge protective device.
1.10.2 Special Tools
Software, connecting cables and proprietary equipment, necessary for the maintenance, testing, and reprogramming of the equipment must be furnished to the Contracting Officer, prior to the instruction of Government employees.
PART 2 PRODUCTS
2.1 GENERAL PRODUCT REQUIREMENT
All fire alarm equipment must be listed for use under the applicable reference standards.
2.2 MATERIALS AND EQUIPMENT
2.2.1 Standard Products
Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory and listed for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials. Material and equipment must be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least 2 years prior to bid opening.
2.2.2 Nameplates
Major components of equipment must have the manufacturer's name, address, type or style, model or serial number, catalog number, date of installation, installing Contractor's name and address, and the contract number provided on a new name plate permanently affixed to the item or equipment. Major components include, but are not limited to, the following:
a. FACU
Nameplates must be etched metal or plastic, permanently attached by screws to control units or adjacent walls.
2.2.3 Keys
Keys and locks for equipment, control units and devices must be identical.
SECTION 28 31 70 Page 12
2.2.4 Instructions
Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a stainless steel or aluminum frame.
Install the instructions on the interior of the FACU. The card must show those steps to be taken by an operator when a signal is received as well as the functional operation of the system under all conditions, normal, alarm, supervisory, and trouble. The instructions and their mounting location must be approved by the Contracting Officer before being posted.
2.3 FIRE ALARM CONTROL UNIT
Provide a complete fire alarm control unit (FACU) fully enclosed in a lockable steel cabinet as specified herein. Operations required for testing or for normal care, maintenance, and use of the system must be performed from the front of the enclosure. If more than a single unit is required at a location to form a complete control unit, the unit cabinets must match exactly. The system must be capable of defining any module as an alarm module and report alarm trouble, loss of polling, or as a supervisory module, and reporting supervisory short, supervisory open or loss of polling such as waterflow switches, valve supervisory switches, fire pump monitoring, independent smoke detection systems, relays for output function actuation.
a. Each control unit must provide power, supervision, control, and logic for the entire system, utilizing solid state, modular components, internally mounted and arranged for easy access. Each control unit must be suitable for operation on a 120 volt, 60 hertz, normal building power supply. Provide each control unit with supervisory functions for power failure, internal component placement, and operation.
b. Visual indication of alarm, supervisory, or trouble initiation on the FACU must be by liquid crystal display or similar means with a minimum of 80 characters.
2.3.1 Cabinet
Install control unit components in cabinets large enough to accommodate all components and also to allow ample gutter space for interconnection of control units as well as field wiring. The cabinet must be a sturdy steel housing, complete with back box, hinged steel door with cylinder lock, and semi-recessed mounting provisions. The enclosure must be identified by an engraved phenolic resin nameplate. Lettering on the nameplate must say "Fire Alarm control unit" and must not be less than 1-inch high. Provide prominent rigid plastic or metal identification plates for lamps, circuits, meters, fuses, and switches.
2.3.2 Silencing Switches
2.3.2.1 Alarm Silencing Switch
Provide an alarm silencing switch at the FACU that must silence the audible and visual notification appliances. Subsequent activation of initiating devices must cause the notification appliances to re-activate.
SECTION 28 31 70 Page 13
2.3.2.2 Supervisory/Trouble Silencing Switch
Provide supervisory and trouble silencing switch(es) that must silence the audible trouble and supervisory signal(s), but not extinguish the visual indicator. This switch must be overridden upon activation of a subsequent supervisory or trouble condition. Audible trouble indication must resound automatically every 24 hours after the silencing feature has been operated if the supervisory or trouble condition still exists.
2.3.3 Non-Interfering
Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from any other device. Initiating devices must be manually reset by switch from the FACU after the initiating device or devices have been restored to normal.
2.3.4 Memory
Provide each control unit with non-volatile memory and logic for all functions. The use of long life batteries, capacitors, or other age-dependent devices must not be considered as equal to non-volatile processors, PROMS, or EPROMS.
2.3.5 Field Programmability
Provide control units and control units that are fully field programmable for both input and output of control, initiation, notification, supervisory, and trouble functions. The system program configuration must be menu driven. System changes must be password protected. Any proprietary equipment and proprietary software needed by qualified technicians to implement future changes to the fire alarm system must be provided as part of this contract.
2.3.6 Input/Output Modifications
The FACU must contain features that allow the bypassing of input devices from the system or the modification of system outputs. These control features must consist of a control unit mounted keypad. Any bypass or modification to the system must indicate a trouble condition on the FACU.
2.3.7 Resetting
Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the alarm, supervisory or trouble condition on the system still exists.
2.3.8 Walk Test
The FACU must have a walk test feature. When using this feature, operation of initiating devices must result in limited system outputs, so that the notification appliances operate for only a few seconds and the event is indicated in the history log, but no other outputs occur.
2.3.9 History Logging
The control unit must have the ability to store a minimum of 400 events in a log. These events must be stored in a battery-protected memory and must remain in the memory until the memory is downloaded or cleared manually.
Resetting of the control unit must not clear the memory.
SECTION 28 31 70 Page 14
2.3.10 Manual Access
An operator at the control unit, having a proper access level, must have the capability to manually access the following information for each initiating device.
a. Primary status.
b. Device type.
c. Present average value.
d. Present sensitivity selected.
e. Detector range (normal, dirty).
2.4 MANUAL STATIONS
Provide metal or plastic, semi-flush mounted, double-action, addressable manual stations, that are not subject to operation by jarring or vibration. Stations must be equipped with screw terminals for each conductor. Stations that require the replacement of any portion of the device after activation are not permitted. Stations must be finished in red with molded raised lettering operating instructions of contrasting color. The use of a key must be required to reset the station.
2.5 SMOKE DETECTORS
2.5.1 Spot Type Detectors
Provide addressable photoelectric smoke detectors as follows:
a. Provide analog/addressable photoelectric smoke detectors utilizing the photoelectric light scattering principle for operation in accordance with UL 268 . Smoke detectors must be listed for use with the FACU.
b. Provide self-restoring type detectors that do not require any readjustment after actuation at the FACU to restore them to normal operation. The detector must have a visual indicator to show actuation.
c. Vibration must have no effect on the detector's operation. Protect the detection chamber with a fine mesh metallic screen that prevents the entrance of insects or airborne materials. The screen must not inhibit the movement of smoke particles into the chamber.
d. The detector address must identify the particular unit, its location within the system. Detectors must be of the low voltage type rated for use on a 24 VDC system.
2.6 NOTIFICATION APPLIANCES
2.6.1 Audible Notification Appliances
Audible appliances must conform to the applicable requirements of UL 464 .
Appliances must be connected into notification appliance circuits.
Surface mounted audible appliances must be painted red. Recessed audible appliances must be installed with a grill that is painted red.
SECTION 28 31 70 Page 15
2.6.1.1 Horns
Horns must be semi-flush mounted. Horns must produce a sound rating of at least 85 dBA at 10 feet . Horns used in exterior locations must be specifically listed or approved for outdoor use and be provided with metal housing and protective grilles.
2.6.2 Visual Notification Appliances
Visual notification appliances must conform to the applicable requirements of UL 1638 , UL 1971 and conform to the Architectural Barriers Act (ABA).
Visual Notification Appliances must have clear high intensity optic lens, xenon flash tubes, or light emitting diode (LED) and be marked "Alert" in letters of contrasting color. The light pattern must be disbursed so that it is visible above and below the strobe and from a 90 degree angle on both sides of the strobe. Strobe flash rate must be 1 flash per second and a minimum of 15 candela based on the UL 1971 test. Strobe must be semi-flush mounted.
2.7 ELECTRIC POWER
2.7.1 Primary Power
Power must be 120 VAC 60 Hz service for the FACU from the AC service to the building in accordance with NFPA 72 .
2.8 SECONDARY POWER SUPPLY
Provide for system operation in the event of primary power source failure. Transfer from normal to auxiliary (secondary) power or restoration from auxiliary to normal power must be automatic and must not cause transmission of a false alarm.
2.8.1 Batteries
Provide sealed, maintenance-free, sealed lead acid batteries as the source for emergency power to the FACU. Batteries must contain suspended electrolyte. The battery system must be maintained in a fully charged condition by means of a solid state battery charger. Provide an automatic transfer switch to transfer the load to the batteries in the event of the failure of primary power.
2.8.1.1 Capacity
Battery size must be the following capacity. This capacity applies to every control unit associated with this system, including fire alarm transmitters.
a. Sufficient capacity to operate the fire alarm system under supervisory and trouble conditions, including audible trouble signal devices for 48 hours and audible and visual signal devices under alarm conditions for an additional 15 minutes.
2.8.1.2 Battery Power Calculations
a. Verify that battery capacity exceeds supervisory and alarm power requirements for the criteria noted in the paragraph "Capacity" above.
SECTION 28 31 70 Page 16
(1) Substantiate the battery calculations for alarm and supervisory power requirements. Include ampere-hour requirements for each system component and each control unit component, and compliance with UL 864 .
(2) Provide complete battery calculations for both the alarm and supervisory power requirements. Submit ampere-hour requirements for each system component with the calculations.
(3) Provide voltage drop calculations to indicate that sufficient voltage is available for proper operation of the system and all components. Calculations must be performed using the minimum rated voltage of each component.
b. For battery calculations assume a starting voltage of 24 VDC for starting the calculations to size the batteries. Calculate the required Amp-Hours for the specified standby time, and then calculate the required Amp-Hours for the specified alarm time. Using 20.4 VDC as starting voltage, perform a voltage drop calculation for circuits containing device and/or appliances remote from the power sources.
2.8.2 Battery Chargers
Provide a solid state, fully automatic, variable charging rate battery charger. The charger must be capable of providing 120 percent of the connected system load and must maintain the batteries at full charge. In the event the batteries are fully discharged (20.4 Volts dc), the charger must recharge the batteries back to 95 percent of full charge within 48 hours after a single discharge cycle as described in paragraph CAPACITY above. Provide pilot light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.
2.9 SURGE PROTECTIVE DEVICES
Surge protective devices must be provided to suppress all voltage transients which might damage fire alarm control unit components. Systems having circuits located outdoors, communications equipment must be protected against surges induced on any signaling line circuit. Cables and conductors, that serve as communications links, must have surge protection circuits installed at each end. The surge protective device must wire in series to the power supply of the protected equipment with screw terminations. Line voltage surge arrestor must be installed directly adjacent to the power panel where the FACU breaker is located.
a. Surge protective devices for nominal 120 VAC must be UL 1449 listed with a maximum 500 volt suppression level and have a maximum response time of 5 nanoseconds. The surge protective device must also meet IEEE C62.41.1 and IEEE C62.41.2 category B tests for surge capacity.
The surge protective device must feature multi-stage construction and be provided with a long-life indicator lamp (either light emitting diode or neon) which extinguishes upon failure of protected components. Any unit fusing must be externally accessible.
b. Surge protective devices for nominal 24 VAC, fire alarm telephone dialer, or ethernet connection must be UL 497B listed, meet IEEE C62.41.1 and have a maximum response time of 1-nanosecond. The surge protective device must feature multi-stage construction and be self-resetting. The surge protective device must be a base and plug
SECTION 28 31 70 Page 17 style. The base assembly must have screw terminals for fire alarm wiring . The base assembly must accept "plug-in" surge protective module.
c. All surge protective devices (SPD) must be the standard product of a single manufacturer and be equal or better than the following:
(1) For 120 VAC nominal line voltage: UL 1449 and UL 1283 listed, series connected 120 VAC, 20A rated, surge protective device in a NEMA 4x enclosure. Minimum 50,000 amp surge current rating with EMI/RFI filtering and a dry contact circuit for remote monitoring of surge protection status.
(2) For 24-volt nominal line voltage: UL 497B listed, series connected low voltage, 24-volt, 5A rated, loop circuit protector, base and replaceable module.
(3) For alarm telephone dialers: UL 497A listed, series connected, 130-volt, 150 mA rated with self-resetting fuse, dialer circuit protector with modular plug and play.
(4) For IP-DACTS: UL 497B listed, series connected, 6.4-volt, 1.5A rated with 20 kA/pair surge current, data network protector with modular plug and play.
2.10 WIRING
Provide wiring materials under this section as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM with the additions and modifications specified herein.
2.10.1 Alarm Wiring
IDC and SLC wiring must be solid copper cable in accordance with the manufacturers requirements. Copper signaling line circuits and initiating device circuit field wiring must be No. 16 AWG size conductors at a minimum. Visual notification appliance circuit conductors, that contain audible alarm appliances, must be copper No. 14 AWG size conductors at a minimum. Wire size must be sufficient to prevent voltage drop problems.
Circuits operating at 24 VDC must not operate at less than the listed voltages for the detectors and/or appliances. Power wiring, operating at 120 VAC minimum, must be a minimum No. 12 AWG solid copper having similar insulation. Acceptable power-limited cables are FPL, FPLR or FPLP as appropriate with red colored covering. Nonpower-limited cables must comply with NFPA 70 .
2.11 AUTOMATIC FIRE ALARM TRANSMITTERS
2.11.1 Digital Alarm Communicator Transmitter (DACT)
Provide DACT that is compatible with the existing supervising station firealarm system. Transmitter must have a means to transmit alarm, supervisory, and trouble conditions via a signle transmitter. Transmitter must have a source of power for operation that conforms to NFPA 72.
Transmitter must be capable of initiating a rest signal daily at any selected time. Transmitter must be arranged to seize telephone circuitsin accordance with NFPA 72.
SECTION 28 31 70 Page 18
2.11.1.1 Operation
Operate each transmitter from 120-volt ac power. In the event of 120-volt ac power loss, the transmitter must automatically switch to battery operation. Switchover must be accomplished with no interruption of protective service, and must automatically transmit a trouble message.
Upon restoration of ac power, transfer back to normal ac power supply must also be automatic.
2.11.1.2 Battery Power
Transmitter standby battery capacity must provide sufficient power to operate the transmitter in a normal standby status for a minimum of 72 hours and be capable of transmitting alarms during that period.
2.11.1.3 Transmitter Housing
Use NEMA Type 1 for housing. The housing must contain a lock that is keyed identical to the fire alarm system for the building. Radio alarm transmitter housing must be factory painted with a suitable priming coat and not less than two coats of a hard, durable weatherproof enamel.
2.11.2 Signals to Be Transmitted to the Base Receiving Station
The following signals must be sent to the base receiving station:
a. Manual pull stations
b. Smoke detectors
PART 3 EXECUTION
3.1 VERIFYING ACTUAL FIELD CONDITIONS
Before commencing work, examine all adjoining work on which the contractor's work is in any way dependent for perfect workmanship according to the intent of this specification section, and report to the Contracting Officer's Representative any condition which prevents performance of first class work. No "waiver of responsibility" for incomplete, inadequate or defective adjoining work will be considered unless notice has been filed before submittal of a proposal.
3.2 INSTALLATION
3.2.1 Fire Alarm Control Unit (FACU)
Locate the FACU where indicated on the drawings. Semi-recess the enclosure with the top of the cabinet 6 feet above the finished floor or center the cabinet at 5 feet , whichever is lower. Conductor terminations must be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection must be permanently mounted in the FACU. Locate the document storage cabinet adjacent to the FACU unless the Contracting Officer directs otherwise.
3.2.2 Battery Cabinets
When batteries will not fit in the FACU, locate battery cabinets below or adjacent to the FACU. Battery cabinets must be installed at an accessible location when standing at floor level. Battery cabinets must not be
SECTION 28 31 70 Page 19 installed lower than 12 inches above finished floor, measured to the bottom of the cabinet, nor higher than 36 inches above the floor, measured to the top of the cabinet. Installing batteries above drop ceilings or in inaccessible locations is prohibited.