This solicitation document describes a federal construction contract opportunity for fuel hydrant repair work at Niagara Falls Air Reserve Station in New York. The project involves replacing the base's fuel hydrant system and has an estimated cost between $10-25 million. It will be conducted as a full and open competitive procurement according to Federal Acquisition Regulation 19.1307, requiring 10% of the cost to be allocated to HUBZone small businesses. The soliciting agency is the Department of the Army Corps of Engineers Louisville District. The NAICS code is 237120 and size determination is $39.5 million. No contract award will be made until funds are appropriated. Offerors must register with SAM and comply with various CCR/ORCA requirements. Technical questions should be submitted through ProjNet.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Replacement Fuel Bulk Storage Facility Hydrant Repair Niagara Falls ARS, NY
P2: 488039, 488040, 488041, 495422
Design Bid Build
Specifications - Vol. 2 of 3 Certified Final Design Submittal
17 June 2021
W912QR21R0023
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR21R0023-0001
REPLACEMENT FUEL BULK STORAGE FACILITY
HYDRANT REPAIR
NIAGARA FALLS AIR RESERVE STATION, NY
CERTIFIED FINAL DESIGN SUBMITTAL
SPECIFICATIONS VOLUME 2 OF 3
JUNE 10, 2021
CONTRACT NO.: W912QR-18-D-0011| TASK ORDER NO.: W912QR21F0109
P2#: 488039, 488040, 488041, and 495422
A/E PROJECT NO.: 1210132
Repair of Fuel Hydrant System
Niagara Falls ARS, NY
PROJECT TABLE OF CONTENTS Page 1
CERTIFIED FINAL DESIGN SUBMITTAL
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 80 00.00 06 SPECIAL PROVISIONS
00 80 00.00 06A1 SIGN DETAIL
DIVISION 01 - GENERAL REQUIREMENTS
01 32 01.00 06 PROJECT SCHEDULE
01 33 00.00 06 SUBMITTAL PROCEDURES
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 46 00.00 06 TOTAL BUILDING COMMISSIONING
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 20.00 10 ENVIRONMENTAL MANAGEMENT AND PROTECTION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 23.33 OPERATION AND MAINTENANCE MANUALS FOR AVIATION FUEL
SYSTEMS
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
02 61 23 REMOVAL AND DISPOSAL OF PCB CONTAMINATED SOILS
02 81 00 TRANSPORTATION AND DISPOSAL OF HAZARDOUS MATERIALS
02 83 13.00 06 LEAD IN CONSTRUCTION
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 50 14 STRUCTURAL METAL FABRICATIONS
05 51 00 METAL STAIRS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 14 00 FLUID-APPLIED WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
PROJECT TABLE OF CONTENTS Page 2
CERTIFIED FINAL DESIGN SUBMITTAL
07 21 29 SPRAYED INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 13 METAL WALL PANELS
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 61 15.00 20 ALUMINUM STANDING SEAM ROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 33 23 OVERHEAD COILING DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 56 53 BLAST RESISTANT TEMPERED GLASS WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 29 00 GYPSUM BOARD
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 67 23.16 FUEL RESISTIVE RESINOUS FLOORING, 5-COAT SYSTEM
09 68 00 CARPETING
09 90 00 PAINTS AND COATINGS
09 96 00 HIGH-PERFORMANCE COATINGS
09 97 13.17 THREE COAT EPOXY INTERIOR COATING OF WELDED STEEL
09 97 13.27
PETROLEUM FUEL TANKS
HIGH PERFORMANCE COATING FOR STEEL STRUCTURES
DIVISION 10 - SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 26 00 WALL AND DOOR PROTECTION
10 44 16 FIRE EXTINGUISHERS
10 73 00 PRE-MANUFACTURED ALUMINUM CANOPIES
DIVISION 11 - EQUIPMENT
11 53 00 LABORATORY EQUIPMENT AND FUMEHOODS
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 36 00 COUNTERTOPS
DIVISION 21 - FIRE SUPPRESSION
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 07 19.00 40 PIPING INSULATION
PROJECT TABLE OF CONTENTS Page 3
CERTIFIED FINAL DESIGN SUBMITTAL
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 48.19 BRACING FOR HVAC
23 05 93.00 06 TESTING, ADJUSTING, AND BALANCING (TAB) OF HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 20 FACILITY GAS PIPING
23 23 00 REFRIGERANT PIPING
23 30 00 HVAC AIR DISTRIBUTION
23 82 46.00 40 ELECTRIC UNIT HEATERS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
25 08 10 UTILITY MONITORING AND CONTROL SYSTEM TESTING
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 08 00 APPARATUS INSPECTION AND TESTING
26 12 19.10 THREE-PHASE, LIQUID-FILLED PAD-MOUNTED TRANSFORMERS
26 20 00 ELECTRICAL DISTRIBUTION SYSTEM
26 24 19.00 40 MOTOR CONTROL CENTERS
26 41 00 LIGHTNING PROTECTION SYSTEM
26 42 13.00 20 CATHODIC PROTECTION BY GALVANIC ANODES
26 42 17.00 10 CATHODIC PROTECTION SYSTEM (IMPRESSED CURRENT)
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 70 INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM,
ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00.00 06 EARTHWORK
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 11.51 RUBBER AND PAINT REMOVAL FROM AIRFIELD PAVEMENTS
32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENT
32 01 29.61 PARTIAL DEPTH PATCHING OF RIGID PAVING
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 14.13 CONCRETE PAVING FOR AIRFIELDS AND OTHER HEAVY DUTY
PAVEMENTS
32 13 15.20 CONCRETE PAVEMENT FOR CONTAINMENT DIKES
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 92 19 SEEDING
DIVISION 33 - UTILITIES
PROJECT TABLE OF CONTENTS Page 4
CERTIFIED FINAL DESIGN SUBMITTAL
33 01 50.31
33 01 50.55
33 08 53
33 08 53A1
33 08 53A2
33 09 53
33 11 00
33 40 00
33 52 23.15
33 52 43.11
33 52 43.13
33 52 43.14
33 52 43.23
33 52 80
33 56 10
33 56 10A1
33 56 19
33 56 21.17
33 56 21.17A1
33 56 21.18
33 71 02
LEAK DETECTION FOR FUELING SYSTEMS
CLEANING OF PETROLEUM STORAGE TANKS
AVIATION FUEL DISTRIBUTION SYSTEM START-UP
EQUIPIMENT TESTS
PERFORMANCE TESTING
AVIATION FUEL PUMP CONTROL AND ANNUNCIATION SYSTEM
WATER UTILITY DISTRIBUTION PIPING
STORM DRAINAGE UTILITIES
POL SERVICE PIPING WELDING
AVIATION FUEL MECHANICAL EQUIPMENT
AVIATION FUEL PIPING
AVIATION FUEL CONTROL VALVES
AVIATION FUEL PUMPS
LIQUID FUELS PIPELINE COATING SYSTEMS
FACTORY-FABRICATED FUEL STORAGE TANKS
PETROLEUM BULK STORAGE APPLICATION
FUEL IMPERMEABLE LINER SYSTEM
SINGLE WALL ABOVEGROUND FIXED ROOF STEEL POL STORAGE TANK
API-653 OUT-OF-SERVICE INSPECTION
SINGLE WALL POL TANK UNDERTANK INTERSTITIAL SPACE
UNDERGROUND ELECTRICAL DISTRIBUTION
APPENDICES
APPENDIX A HAZARDOUS MATERIALS ASSESSMENT
APPENDIX B PRE-WORK NOTIFICATION
APPENDIX C STORMWATER POLLUTION PREVENTION PLAN
-- End of Project Table of Contents --
SECTION 10 14 00.20
INTERIOR SIGNAGE
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AA PK-1 (2015) Pink Sheets: Designations and Chemical Composition Limits for Aluminum Alloys in the Form of Castings & Ingot
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test
AMERICAN WELDING SOCIETY (AWS)
AWS D1.2/D1.2M (2014) Structural Welding Code - Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00.00 06 SUBMITTAL
PROCEDURES:
SECTION 10 14 00.20 Page 1
CERTIFIED FINAL DESIGN SUBMITTAL
SD-02 Shop Drawings
Detail Drawings ; G
SD-03 Product Data
Installation ; G Warranty ; G
SD-04 Samples
Interior Signage ; G
SD-10 Operation and Maintenance Data
Approved Manufacturer's Instructions ; G
Protection and Cleaning ; G
Software ; G
1.3 EXTRA MATERIALS
Provide 5 extra frames and extra stock of the following: blank plates of each color and size for all sign types. 5 changeable message strips for sign type. Provide 10 paper inserts and one copy of the software for user produced signs and inserts after project completion and equipment necessary for removal of signage parts and pieces.
1.4 QUALITY ASSURANCE
1.4.1 Samples
Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: Directional sign, Standard Room sign, Changeable message strip sign. The samples may be installed in the work, provided each sample is identified and location recorded.
1.4.2 Detail Drawings
Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.
1.5 DELIVERY, STORAGE, AND HANDLING
Materials must be packaged to prevent damage and deterioration during shipment, handling, storage and installation. Product must be delivered to the jobsite in manufacturer's original packaging and stored in a clean, dry area in accordance with manufacturer's instructions.
1.6 WARRANTY
Warrant the interior signage for a period of 2 years against defective workmanship and material. Warranties must be signed by the authorized representative of the manufacturer. Submit warranty accompanied by the document authenticating the signer as an authorized representative of the guarantor. Guarantee that the signage products and the installation are
SECTION 10 14 00.20 Page 2 free from any defects in material and workmanship from the date of delivery.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
Signs, plaques, directories, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letterforms and graphics true and clean.
2.2 ROOM IDENTIFICATION/DIRECTIONAL SIGNAGE SYSTEM
2.2.1 Standard Room Signs
Signs must consist of acrylic plastic 0.080 inch thickness minimum conforming to ANSI Z97.1 and must conform to the following:
a. Frames must be molded acrylic, flat 1/8 inch thick.
b. End caps must be molded acrylic with square style corners.
2.2.2 Changeable Message Strip Signs
Changeable message strip signs must be of same construction as standard room signs to include a clear sleeve that will accept a paper or plastic insert identifying changeable text. The insert must be prepared die-cut vinyl letters applied to 0.015 inch rigid vinyl film . Provide paper and software for creating text and symbols for computers identified by owner for Owner production of paper inserts after project completion. Furnish one suction device to assist in removing face sheet. Sliding inserts or slide knobs that slide horizontally exposing different graphic information must be provided as identified in the signage placement schedule and drawings
2.2.3 Type of Mounting For Signs
Provide extruded aluminum brackets for hanging, projecting, and double-sided signs. Mounting for framed, hanging, and projecting signs must be by mechanical fasteners. Surface mounted signs must be mounted with 1/16 inch thick closed cell vinyl foam with adhesive backing.
Adhesive must be transparent, long aging, high tech formulation on two sides of the vinyl foam. fabricated from materials that are not corrosive to sign material and mounting surface.
2.2.4 Graphics
Signage graphics for modular signs must conform to the following:
2.2.4.1 Subsurface Copy
Copy is transferred to the back face of clear acrylic sheeting forming the panel face to produce precisely formed opaque image. This method bonds all sign elements (color, graphics, lettering, Braille and substrate) into a single unit.
SECTION 10 14 00.20 Page 3
2.2.4.2 First Surface Copy Direct Print or Silkscreened (Non-Tactile)
Message may be applied to panel using the silkscreen process.
Silkscreened images must be executed with photo screens prepared from original art. Handcut screens will not be accepted. Original art is defined as artwork that is a first generation reproduction of the specified art. Edges and corners must be clean.
2.2.4.3 Surface Applied Photopolymer
Integral graphics and Braille achieved by photomechanical stratification processes. Photopolymer used for ADA compliant graphics must be of the type that has a minimum durometer reading of 90. Tactile graphics must be raised 1/32 inch from the first surface of plaque by photomechanical stratification process.
2.2.4.4 Graphic Blast Raised Copy
Background is sandblasted to a uniform depth of 1/32 inch leaving raised text and Braille. Background must be painted with polyurethane paint.
2.2.5 Character Proportions and Heights
Letters and numbers on signs conform to 36 CFR 1191 .
2.2.6 Tactile Letters, Symbols and Braille
Raised letters and numbers on signs must conform to 36 CFR 1191 .
2.3 ALUMINUM ALLOY PRODUCTS
Aluminum extrusions must be at least 1/8 inch thick, and aluminum plate or sheet must be at least 0.0508 inch thick. Extrusions must conform to ASTM B221; plate and sheet must conform to ASTM B209. Where anodic coatings are specified, alloy must conform to AA PK-1 alloy designation
514.0. Exposed anodized aluminum finishes must be as shown. Welding for aluminum products must conform to AWS D1.2/D1.2M .
2.4 ANODIC COATING
Anodized finish must conform to AA DAF45 as follows:
a. Clear (natural) designation AA-M10-C22-A31, Architectural Class II 0.4 mil or thicker.
2.5 FABRICATION AND MANUFACTURE
2.5.1 Factory Workmanship
Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Exposed surfaces of work must have a smooth finish and exposed riveting must be flush.
Fastenings must be concealed where practicable.
2.5.2 Dissimilar Materials
Where dissimilar metals are in contact, the surfaces will be protected to prevent galvanic or corrosive action.
SECTION 10 14 00.20 Page 4
2.6 COLOR, FINISH, AND CONTRAST
Color must be as indicated on drawings . Finish of all signs must be eggshell, matte, or other non-glare finish as required in handicapped-accessible buildings.
2.7 TYPEFACE
ADA-ABA compliant font for Room SignsHelvetica Regular.
PART 3 EXECUTION
3.1 INSTALLATION
Signs must be installed plumb and true and in accordance with approved manufacturer's instructions at locations shown on the detail drawings .
Submit six copies of operating instructions outlining the step-by-step procedures required for system operation. The instructions must include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Each set must be permanently bound and must have a hard cover. The following identification must be inscribed on the covers: the words "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Mounting height and mounting location must conform to 36 CFR 1191 . Required blocking must be installed. Signs on doors or other surfaces must not be installed until finishes on such surfaces have been installed. Signs installed on glass surfaces must be installed with matching blank back-up plates in accordance with manufacturer's instructions.
Do not install items that show visual evidence of biological growth.
3.1.1 Anchorage
Anchorage must be in accordance with approved manufacturer's instructions. In high humidity interior spaces (for example, bathrooms, locker rooms, pools, trainers) and unconditioned spaces, use corrosion-resistant anchors/fasteners or with approval by the manufacturer, waterproof silicone adhesive. Anchorage not otherwise specified or shown must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Exposed anchor and fastener materials must be compatible with metal to which applied and must have matching color and finish. At interior applications in heavy traffic areas, firmly attach signage to structure walls with tamper-proof fasteners.
a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.
b. Mount signs mounted to lay-in ceiling grids with clip connections to ceiling tees.
c. Install signs mounted on metal surfaces with magnetic tape.
d. Install signs mounted on fabric surfaces with hook and loop tape or pin mount.
SECTION 10 14 00.20 Page 5
3.1.2 Protection and Cleaning
Protect the work against damage during construction. Hardware and electrical equipment must be adjusted for proper operation. Glass, frames, and other sign surfaces must be cleaned at completion of sign installation in accordance with the manufacturer's approved instructions and the requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA, Package 1. Submit six copies of maintenance instructions listing routine procedures, repairs, and guides.
-- End of Section --
SECTION 10 14 00.20 Page 6
SECTION 10 26 00
WALL AND DOOR PROTECTION
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D256 (2010; R 2018) Standard Test Methods for Determining the Izod Pendulum Impact Resistance of Plastics
ASTM D543 (2014) Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents
ASTM D635 (2018) Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position
ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM G21 (2015) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J1545 (2005; R 2014) Instrumental Color Difference Measurement for Exterior Finishes, Textiles and Colored Trim
SECTION 10 26 00 Page 1
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
SD-02 Shop Drawings
Corner Guards ; G
SD-03 Product Data
Corner Guards ; G
SD-06 Test Reports
Corner Guards
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and trademarks intact. Keep materials dry, protected from weather and damage, and stored under cover.
Materials must be stored at approximately 70 degrees F for at least 48 hours prior to installation.
1.4 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
To the maximum extent possible, corner guards, door and door frame protectors, wall guards (bumper guards), wall panels and wall covering must be the standard products of a single manufacturer and must be furnished as detailed. Drawings show general configuration of products required, and items differing in minor details from those shown will be acceptable.
2.1.1 Resilient Material
Provide resilient material consisting of high impact resistant extruded acrylic vinyl, polyvinyl chloride, or injection molded thermal plastic conforming to the following:
2.1.1.1 Minimum Impact Resistance
Minimum impact resistance must be 18 ft-lbs/sq. inch when tested in accordance with ASTM D256, (Izod impact, ft-lbs per sq inch notched).
SECTION 10 26 00 Page 2
2.1.1.2 Fire Rating
Fire rating must be Class 1 when tested in accordance with ASTM E84, having a maximum flame spread of 25 and a smoke developed rating of 450 or less. Material must be rated self extinguishing when tested in accordance with ASTM D635. Material must be labeled and tested by an approved nationally known testing laboratory. Resilient material used for protection on fire rated doors and frames must be listed by the testing laboratory performing the tests. Resilient material installed on fire rated wood/steel door and frame assemblies must have been tested on similar type assemblies. Test results of material tested on any other combination of door/frame assembly will not be acceptable.
2.1.1.3 Integral Color
Colored components must have integral color and must be matched in accordance with SAE J1545 to within plus or minus 1.0 on the CIE-LCH scales.
2.1.1.4 Chemical and Stain Resistance
Materials must be resistant to chemicals and stains reagents in accordance with ASTM D543.
2.1.1.5 Fungal and Bacterial Resistance
Materials must be resistant to fungi and bacteria in accordance with ASTM G21, as applicable.
2.2 CORNER GUARDS
2.2.1 Resilient Corner Guards
Corner guard units must be surface mounted type, radius formed to profile shown. Corner guards must be 4 feet high. Mounting hardware, cushions, and base plates must be furnished. Assembly must consist of a snap-on corner guard formed from high impact resistant resilient material, mounted on a continuous aluminum retainer. Extruded aluminum retainer must conform to ASTM B221, alloy 6063, temper T5 or T6. Flush mounted type guards must act as a stop for adjacent wall finish material. Factory fabricated end closure caps must be furnished for top and bottom of surface mounted corner guards. Flush mounted corner guards installed in fire rated wall must maintain the rating of the wall. Insulating materials that are an integral part of the corner guard system must be provided by the manufacturer of the corner guard system. Exposed metal portions of fire rated assemblies must have a paintable surface.
2.3 ADHESIVES
Adhesive for resilient material must be in accordance with manufacturers recommendations. Provide sealants and non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) the VOC content requirements of SCAQMD Rule 1168 , or VOC content requirements of GS-36.
SECTION 10 26 00 Page 3
2.4 COLOR
Color must be as indicated. Color listed is not intended to limit the selection of equal colors from other manufacturers.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install items that show visual evidence of biological growth.
-- End of Section --
SECTION 10 26 00 Page 4
SECTION 10 44 16
FIRE EXTINGUISHERS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 1 (2021) Fire Code
NFPA 10 (2018; ERTA 1-2 2018) Standard for Portable Fire Extinguishers
NFPA 101 (2021) Life Safety Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.157 (2003) Portable Fire Extinguishers
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00.00 06 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Fire Extinguishers ; G
Accessories ; G
Cabinets ; G
Wall Brackets ; G
Schedule ; G
SD-03 Product Data
Fire Extinguishers ; G
Accessories ; G
Cabinets ; G
Wall Brackets ; G
Replacement Parts List ; G
SECTION 10 44 16 Page 1
SD-04 Samples
Equipment Samples ; G
SD-07 Certificates
Fire Extinguishers Certifications ; G
Manufacturer's Warranty with Inspection Tag ; G
1.3 DELIVERY, STORAGE, AND HANDLING
Protect materials from weather, soil, and damage during delivery, storage, and construction.
Deliver materials in their original packages, containers, or bundles bearing the brand name and the name and type of the material.
1.3.1 Samples
Provide the following equipment samples : One of each type of fire extinguisher being installed; one full-sized sample of each type of cabinet being installed; three samples of wall brackets and accessories of each type being used.
Use approved samples for installation, with proper identification and storage.
1.4 WARRANTY
Guarantee that Fire Extinguishers are free of defects in materials, fabrication, finish, and installation and that they will remain so for a period of not less than 10 years after completion.
Submit the manufacturer's warranty with inspection tag .
1.5 PROJECT SCHEDULE
For fire extinguishers. Coordinate final fire extinguisher schedule with fire protection cabinet schedule to ensure proper fit and function. Use same designations indicated on Drawings.
PART 2 PRODUCTS
Submit fabrication drawings consisting of fabrication and assembly details performed in the factory and product data for the following items: Fire Extinguishers; Accessories , cabinets , Wall Brackets.
2.1 SYSTEM DESCRIPTION
2.1.1 Types
Submit fire extinguishers certifications showing compliance with local codes and regulations.
Provide fire extinguishers conforming to NFPA 10 . Provide quantity and placement in compliance with the applicable sections of NFPA 1, NFPA 101 and 29 CFR 1910.157 .
SECTION 10 44 16 Page 2
2.1.2 Material
Provide corrosion-resistant steel extinguisher shell.
2.1.3 Size
30 pounds extinguishers.
2.1.4 Accessories
Forged brass valve
Fusible plug
Safety release
Antifreeze
Pressure gage
2.2 EQUIPMENT
2.2.1 Cabinets
2.2.1.1 Material
Provide corrosion-resistant steel cabinets.
2.2.1.2 Type
Provide recessed type cabinets.
Provide semi-recessed cabinet for a 4 inch wall.
Provide recessed bubble type cabinets.
2.2.1.3 Size
Dimension cabinets to accommodate the specified fire extinguishers.
2.2.2 Wall Brackets
Provide wall-hook fire extinguisher wall brackets.
Provide wall bracket and accessories as approved.
2.2.2.1 Identification
Provide lettering complying with authorities having jurisdiction for letter style, size, spacing, and location. Locate as indicated by the drawings.
Identify bracket-mounted fire extinguishers with the words "FIRE EXTINGUISHER" in red letter decals applied to mounting surface.
Orientation: Vertical.
SECTION 10 44 16 Page 3
PART 3 EXECUTION
3.1 INSTALLATION
Install Fire Extinguishers where indicated on the drawings. Verify exact locations prior to installation.
Provide extinguishers which are fully charged and ready for operation upon installation. Provide extinguishers complete with Manufacturer's Warranty with Inspection Tag attached.
Install fire extinguishers in locations indicated and in compliance with requirements of authorities having jurisdiction.
Comply with the manufacturer's recommendations for all installations.
3.2 PROTECTION
3.2.1 Repairing
Remove and replace damaged and unacceptable portions of completed work with new work at no additional cost to the Government.
Submit replacement parts list indicating specified items replacement part, replacement cost, and name, address and contact for replacement parts distributor.
3.2.2 Cleaning
Clean all surfaces of the work, and adjacent surfaces which are soiled as a result of the work. Remove from the site all construction equipment, tools, surplus materials and rubbish resulting from the work.
-- End of Section --
SECTION 10 44 16 Page 4
SECTION 10 73 00
PRE-MANUFACTURED ALUMINUM CANOPIES
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes: Design, fabrication, and installation of welded extruded aluminum walkway cover systems.
B. Products Furnished but not Installed Under this Section: Column sleeves (Styrofoam blockouts) or anchor bolts.
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2603 (2002) Voluntary Specification, Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2010; Change 2010; Change 2011; Errata 2011; Change 2011) Minimum Design Loads for Buildings and Other Structures
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
ASTM INTERNATIONAL (ASTM)
ASTM B209 (2010) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2012) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B221 (2013) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
AMERICAN WELDING SOCIETY (AWS)
ANSI/ AWS D1.2 (2008) Structural Welding Code - Aluminum
1.3 SYSTEM DESCRIPTION
A. Design Requirements:
1. Design Walkways in accordance with The Aluminum Design Manual 2000.
2. Comply with the wind requirements of ASCE 7.
3. Provide an all welded extruded aluminum system complete with
SECTION 10 73 00 Page 1 internal drainage. Non- welded systems are not acceptable.
4. Provide expansion joints to accommodate temperature changes of 120 degrees F. Provide expansion joints with no metal to metal contact.
B. Performance Requirements:
1. Grout: Compressive strength of 2000 psi, minimum.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section
01 33 00.00 06 SUBMITTAL PROCEDURES:
SD-03 Product Data ; G
Manufacturer's product information, specifications, and installation instructions for walkway cover components and accessories.
SD-04 Samples
1. Selection: Manufacturer's full range of colors for the finishes selected.
2. Verification: 3-inch square samples of each finish selected on the substrate specified.
SD-05 Design Data
Design calculations bearing the seal of a Registered Professional Engineer, licensed in the state where the project is located.
Design calculations shall state that the walkway cover system design complies with the wind requirements of ASCE 7, the stability criteria of applicable building code, and all other governing criteria.
SD-06 Test Reports
Include plan dimensions, elevations, and details.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications: At least ten years experience in the design, fabrication, and erection of extruded aluminum walkway cover systems.
B. Installer Qualifications: Have walkway covers installed by manufacturer, third party installation is not acceptable.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. The design is based on Super Lumideck by: Mapes Architectural Canopies Inc.
1. Comparable products not limited to the following manufacturers also will be acceptable:
a. Dittmer Architectural Aluminum.
b. E.L. Burns Company.
SECTION 10 73 00 Page 2
c. Peachtree Protective Covers Inc.
2.2 MATERIALS
A. Aluminum Members: Extruded aluminum, ASTM B221, 6063 alloy, T6 temper.
B. Fasteners: Aluminum, 1808 stainless steel, or 300 series stainless steel.
C. Decking-interlocking roll-form 2 1/2 W style pan (0.840" aluminum).
D. Hanger rods and attachment hardware: powder coated.
E. Fascia shall be standard 8" extruded J style.
F. Gaskets: Dry seal santoprene pressure type.
G. Aluminum Flashing: ASTM B209, Type 3003 H14, 0.040 inch, minimum.
2.3 FABRICATION
A. General:
1. Shop Assembly: Assemble components in ship to greatest extent possible to minimize field assembly.
2. Welding: In accordance with ANSI/AWS D1.2 .
3. Bent Construction: Factory weld beams with neatly mitered corners to form one-piece rigid bents. Make welds smooth and uniform using an inert gas shielded arc. Perform suitable edge preparation to assure 100% penetration. Grind welds only where interfering with adjoining structure to allow for flush connection. Field welding is not permitted. Rigid mechanical joints may be used only if fully welded bents cannot be shipped on local, state, or federal highways without a special permit from the department of transportation.
4. Deck Construction: Fabricate from extruded modules that interlock in a self-flashing manner. Positively fasten interlocking joints at 8 inches on center creating a momolithic structural unit capable of developing the full strength of the sections. The fastenings must have minimum shear strength of 350 pounds each. Assemble deck with sufficient camber to offset dead load deflection.
B. Beams: Provide open-top tubular extrusion, top edges thickened for strength and designed to receive deck members in self-flashing manner.
Provide structural ties in tops of all beams.
C. Deck: Extruded self-flashing sections interlocking into a composite unit. Provide welded plate closures at deck ends.
E. Fascia: Manufacturer's standard shape. Provide fascia splices where continuous runs of fascia are jointed. Locate splices to be in line with bents and fasten in place on hidden or non-vertical surfaces.
F. Factory Finishing: Finish designations prefixed by AA comply with system established by the AAMA for designating aluminum finishes.
1. Baked-Enamel Finish: AA-C12C42R1x (Chemical Finish: cleaned with inhibited chemicals; Chemical Finish: acid-chromate-fluoride-phosphate conversion coating; Organic Coating: Thermosetting, modified-acrylic enamel primer/topcoat system, except with a minimum dry film thickness of 1.5 mils (0.04 mm), medium gloss), complying with AAMA 2603. Apply baked enamel complying with paint manufacturer's specifications for cleaning, conversion coating, and painting.
G. Hanger Assemblies: Provide extruded aluminum hanger rods in manufacturer's standard shapes and sized to meet the loads seen by canopy.
SECTION 10 73 00 Page 3
PART 3 EXECUTION
3.1 EXAMINATION
A. Verification of Conditions: Verify that all concrete, masonry, and roofing work in the vicinity is complete and cleaned.
3.2 ERECTION
A. Erect protective cover true to line, level, and plumb.
B. Provide hairline miters and fitted joints.
3.3 CLEANING
A. Clean all protective cover components promptly after installation.
3.4 PROTECTION
A. Protect materials during and after installation.
-- End of Section --
SECTION 10 73 00 Page 4
SECTION 11 53 00
LABORATORY EQUIPMENT AND FUMEHOODS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)
ACGIH-2097 (2013) Industrial Ventilation: A Manual of Recommended Practice (Metric)
ASTM INTERNATIONAL (ASTM)
ASTM A1008/A1008M (2020) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM C1048 (2018) Standard Specification for Heat-Strengthened and Fully Tempered Flat Glass
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 45 (2019) Standard on Fire Protection for Laboratories Using Chemicals
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
1.2 RELATED WORK SPECIFIED IN OTHER SECTIONS
Provide final utility connections and utility service to equipment including waste, under Sections 22 00 00 PLUMBING SYSTEMS and 26 20 00
INTERIOR DISTRIBUTION SYSTEM.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00.00 06 SUBMITTAL
PROCEDURES:
SECTION 11 53 00 Page 1
SD-02 Shop Drawings
Laboratory equipment and fume hood layout ; G
Laboratory equipment and hood schedules
SD-03 Product Data
Fumehood assembly ; G
Base Cabinet ; G
SD-04 Samples
Exterior hood paint ; G
SD-06 Test Reports
Fumehood test ; G
SD-08 Manufacturer's Instructions
Fumehood assembly
SD-10 Operation and Maintenance Data
Fumehood assembly , Data Package 2; G
Submit in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
1.4 SUBMITTAL REQUIREMENTS
1.4.1 Hood Paint
Submit color chips of exterior hood paint . Submit at least five colors which are standard with the manufacturer.
1.4.2 Drawing Requirements
Show pertinent installation layout . Indicate details of construction and rough-in requirements.
1.4.3 Schedule
Include each type of equipment and hood and submit in equipment submittal .
1.4.4 Tests
Submit fumehood test reports required by ACGIH-2097 .
PART 2 PRODUCTS
2.1 MATERIALS, COMPONENTS, AND SPECIAL DESIGN REQUIREMENTS
2.1.1 Aluminum Alloy
ASTM B221 equivalent in ultimate tensile, yield, and shear strengths to Alloy 6063-T5 or 6063-T6.
SECTION 11 53 00 Page 2
2.1.2 Carbon Steel
ASTM A1008/A1008M , cold rolled sheets, commercial bright finish.
2.1.3 Stainless Steel
No 4 satin finish including welds and fabricated surfaces. Provide Type 302, 304, or 316 alloy unless otherwise specified. Provide minimum thickness of U.S. Standard 16 gage , except 14 gage for working surface.
2.1.4 Safety Glass
ASTM C1048, fully tempered "FT," clear.
2.1.5 Fumehood Design
Design, calculate face velocities, and test fume hoods in accordance with ACGIH-2097 , Laboratory fume hoods, auxiliary systems, and associated equipment shall meet the requirements of NFPA 70 and NFPA 45 .
2.1.6 Hood Static Pressure Loss
With the sash in full-open position the static pressure loss through the fumehood shall not exceed 1/2 inch water gage when operating at 75 feet per minute (fpm) , 7/8 inch water gage at 100 fpm , 1.125 inch water gage at 125 fpm . For hoods equipped with bypass, the static pressure loss and exhaust volume shall remain relatively constant (within 5 percent) regardless of sash position.
2.1.7 Electrical Devices
Prewired at the factory to a common, integral junction box to provide easy exterior connection and disconnection.
2.2 UNITS
2.2.1 Unit
2.2.1.1 Base Cabinet Portion of Assembly
Base Cabinet shall be same width as laboratory fume hood and conform to the National Fire Protection Association (NFPA) 30 Flamable and Combustible Liquids Code Specifications .
2.2.2 Fumehood Assembly , Constant Volume
Constant volume, bypass air configuration, enclosed unit mounted on base cabinet; exterior dimensions maximum 72 inches wide (across face) by 38 inches deep (front to back) by 60 inches high ; interior working area at least 60 inches wide 24 inches deep by 47 inches high . Hood shall modulate dampers for bypass via internal controls to maintain velocity across sash opening .
2.2.2.1 Upper Cabinet Portion of Assembly
Carbon steel, modified to have recessed apron to contain electrical convenience outlets.
SECTION 11 53 00 Page 3
2.2.2.2 Hood Interior, Including Working Surface
Type 304 stainless steel, with interior vertical joints and intersections of vertical surface with working surface having an approximate 3/4 inch radius. Provide working surface with a raised rim around all sides to prevent spillage from running out face of hood.
2.2.2.3 Sash
Safety glass, 7/32 inch minimum thickness, counterbalanced, vertical sliding type, Type 304 stainless steel frame.
2.2.2.4 Baffle
Adjustable, with moving parts resistant to corrosion, removable for cleaning.
2.2.2.5 Lighting Fixtures
Explosion proof, fluorescent, with cool white lamps and switch, providing 75 foot candles on working area. Locate switch for fixture on exterior of hood frame, or in recess of base cabinet. Provide sealed safety glass window barrier between interior working and fixture spaces, and access for tube replacement exterior to hood interior working area.
2.2.2.6 Service Fixtures
Provide remote controls for piped services and locate on hood exterior frame. Provide serrated supply ends with nozzles arranged close to sash, precluding the need of reaching to interior back of hood to make connections to outlets. Base metal of fixtures shall be brass. Protect metal fixtures inside hood with chemical resistant coating of clear plastic over polished chrome plate.
a. Vacuum: Provide fixtures for each service, each fitting with remote controlled valve and supply end (inside hood) consisting of a serrated hose nozzle and escutcheon trim. Provide vacuum at 30 inches of HG.
2.2.2.7 Blower Switch
Double-pole, 208-volt, 60-Hz, with pilot light. Locate switch in hood frame or in recess of base cabinet.
2.2.2.8 Duct Stub
Collar size suitable for ductwork indicated. Finish of areas that may come in direct contact with fumes shall be same material and finish as hood interior.
2.2.3 Biological Safety Cabinet
2.2.3.1 Light Fixture
LED, prewired, with cool white, with switch hood-mounted exterior to working area.
2.2.3.2 Service Fittings
Locate remote controls for piped services on hood exterior; provide
SECTION 11 53 00 Page 4 serrated supply end. Base metal of fixtures shall be brass. Protect metal fixtures inside hood with chemical resistant coating of clear plastic over polished chrome plate.
a. Vacuum at 30 inches HG.
2.2.3.3 Viewing Panel
Safety glass, 7/32 inch minimum thickness.
2.2.3.4 Duct Stub
Collar size suitable for ductwork indicated. Finish of areas that may come in direct contact with fumes to be same as to hood interior.
2.2.3.5 Warning System
Ensure detection and alarm for insufficient air velocities caused by failure of exhaust system or by dirty filters.
PART 3 EXECUTION
3.1 INSTALLATION
Install units at locations indicated. Conform to installation provisions of and utility installation provisions of Section 23 11 20 FACILITY GAS PIPING; Section 22 00 00 PLUMBING SYSTEMS; and the ACGIH-2097 including provision for an adequate supply of tempered make-up air to meet the air flow requirements of fume hood(s). Provide interlocks for controls and alarms to maintain the required air balance between hood interiors and the room.
3.2 FIELD QUALITY CONTROL
3.2.1 Inspection
Examine each unit for visual defects, operation and conformance to specifications.
3.2.2 Tests
Test each unit to ensure that the equipment is operational and conforms to specification requirements. Field tests for fume hood operation and performance shall meet the requirements of ACGIH-2097 .
During commissioning the following tests and measurements must be performed in accordance with ANSI/ASSE Z9.5:
a. Airflow visualization tests
b. Cross drafts velocity tests
c. Exhaust flow measurements
d. Face velocity tests
e. Hood static pressure measurement
f. Tracer gas testing
-- End of Section --
SECTION 11 53 00 Page 5
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 11 53 00 Page 6
SECTION 12 24 13
ROLLER WINDOW SHADES
PART 1 GENERAL
1.1 GENERAL REQUIREMENTS
Provide roller window shades, complete with necessary brackets, fittings, and hardware as indicated on drawings . Mount and operate equipment in accordance with manufacturer's instructions. Windows to receive a shade must be completely covered.
a. Submit drawings showing plans, elevations, sections, product details, installation details, operational clearances, wiring diagrams and relationship to adjacent work. Include the use of same room designations as indicated on the drawings.
b. Provide manufacturer's data composed of catalog cuts, brochures, product information, and operating and maintenance instructions on each product to be used. Include styles, profiles and features.
c. Furnish samples of each type and color of roller shade fabric and roller shade channel. Shade material shall be minimum 6 by 6 inch in size. Mark face of material to indicate interior faces.
d. Submit fire resistance data, flame spread and smoke contribution data.
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM G21 (2015) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 701 (2019) Standard Methods of Fire Tests for Flame Propagation of Textiles and Films
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
UL 325 (2017) UL Standard for Safety Door, SECTION 12 24 13 Page 1
Drapery, Gate, Louver, and Window Operators and Systems
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00.00 06 SUBMITTAL
PROCEDURES
SD-02 Shop Drawings
Installation ; G
SD-03 Product Data
Window Shades ; G Recycled Content for various fiber components ; S
SD-04 Samples
Window Shades ; G
SD-06 Test Reports
Window Shades
SD-07 Certificates
Indoor Air Quality for roller window shades ; S
SD-08 Manufacturer's Instructions
Window Shades
SD-10 Operation and Maintenance Data
Window Shades
SD-11 Closeout Submittals
Warranty ; G
1.4 CERTIFICATES
1.4.1 Indoor Air Quality Certifications
1.4.1.1 Roller Window Shades
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard), SCS Global Services Indoor Advantage Gold or provide validation by other third-party program that products meet the requirements of this paragraph. Provide current product certification documentation from certification body.
SECTION 12 24 13 Page 2
1.5 QUALITY ASSURANCE
1.5.1 Qualifications
1.5.1.1 Manufacturer's Qualifications
Obtain motor-controlled roller shades through one source from a single manufacturer with a minimum of twenty years experience and minimum of three projects of similar scope and size in manufacturing products comparable to those specified in this section.
1.5.1.2 Installer's Qualifications
Installer trained and certified by the manufacturer with a minimum of ten years experience in installing products comparable to those specified in this section.
1.5.2 Flammability Requirements
Passes in accordance with NFPA 701 small and large-scale vertical burn.
Materials tested must be identical to products proposed for use.
1.5.3 Electrical Requirements
NFPA Article 100 listed and labeled in accordance with UL 325 or other testing agency acceptable to authorities having jurisdiction, marked for intended use, and tested as a system. Individual testing of components will not be acceptable in lieu of system testing.
1.5.4 Anti-Microbial Requirements
'No Growth' per ASTM G21 results for fungi ATCC9642, ATCC 9644, ATCC9645.
1.6 DELIVERY, STORAGE, AND HANDLING
Deliver components to the jobsite in the manufacturer's original packaging with the brand or company name, item identification, and project reference clearly marked. Store components in a dry location that is adequately ventilated and free from dust, water, or other contaminants and has easy access for inspection and handling. Store materials flat in a clean dry area with temperature maintained above 50 degrees F . Do not open containers until needed for installation unless verification inspection is required.
1.7 WARRANTY
Provide 10 year minimum limited warranty.
PART 2 PRODUCTS
2.1 WINDOW SHADES
Roller tube must operate smoothly and be of sufficient diameter and thickness to prevent excessive deflection. Provide brackets that are appropriate for inside mount. The shade cloth must meet the performance described in NFPA 701 , small scale test. Treat steel features for corrosion resistance.
Provide Various Fiber Components with a minimum of 60 percent recycled
SECTION 12 24 13 Page 3 content. Provide data identifying percentage of recycled content for various fiber components .
Provide certification of indoor air quality for roller window shades .
2.1.1 Light Filtering Shades
Provide light filtering window shades to conform with the following:
a. Roller tube must be extruded aluminum or steel. Diameter, wall thickness, and material to be selected by the manufacturer to accommodate the shade size. Provide roller idler assembly of molded nylon and zinc-plated steel pin. Sliding pin must allow easy installation and removal of roller. Fabric must be connected to the roller tube with double sided adhesive specifically developed to attach coated textiles to metal to eliminate horizontal impressions in fabric or attached with a spline lock system.
b. Fascia must be L-shaped aluminum extrusion to conceal…