W912QR21R0023_CID-0000.pdf

PDF 9 MB Posted

Attached to
Hydrant Fuel Replacement at Niagara ARS, Niagara Falls Federal contract opportunity
Solicitation number
W912QR21R0023
Issued by
Department of the Army Corps of Engineers Engineering District Louisville

About this file

This federal contract opportunity is a solicitation for fuel hydrant repair located at Niagara Falls Air Reserve Station in New York. The project cost is estimated between $10-25 million. It is a full and open procurement requiring a 10% price evaluation for HUBZone small businesses. The NAICS code is 237120 and size determination is $39.5 million. No contract award will be made until funds are appropriated. Offerors must comply with System for Award Management requirements. Technical inquiries should be submitted through Bidder Inquiry on ProjNet, the project management website.

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation For Replacement Fuel Bulk Storage Facility Hydrant Repair Niagara Falls ARS, NY

P2: 488039, 488040, 488041

Design Bid Build

CID Binder (FF&E and SID) Corrected Final Design Submittal

21 May 2021

W912QR21R0023

ARIMS: 200A

Disposition: Maintain for 15yrs after construction

W912QR21R0023-0000

CID BINDER (FF&E AND SID)

CORRECTED FINAL DESIGN SUBMITTAL

1. POINTS OF CONTACT

2. DESIGN NARRATIVE

3. FURNITURE FLOOR PLANS

IFB101 – FURNITURE PLAN

4. ROOM CONTENTS LIST

5. ITEM INSTALLATION LIST

6. ITEMIZED COST ESTIMATE

7. SPECIFICATION LIST BY TAG

8. MANUFACTURER’S POC LIST

9. MANUFACTURER’S RESOURCE LIST

10. FURNITURE PROCUREMENT SHEETS

11. DRAWINGS

12. FURNITURE FINISH COLOR BOARDS

13. INTERIOR FINISH COLOR BOARDS

TABLE OF CONTENTS

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

POND PROJECT NUMBER: 1210132

W912QR21R0023-0000

MaioccoC Text Box

1. POINTS OF CONTACT

2. DESIGN NARRATIVE

3. FURNITURE FLOOR PLANS

IFB101 –FURNITURE PLAN

4. ROOM CONTENTS LIST

5. ITEM INSTALLATION LIST

6. SPECIFICATION LIST BY TAG

7. MANUFACTURER’S POC LIST

8. MANUFACTURER’S RESOURCE LIST

9. FURNITURE PROCUREMENT SHEETS

10. DRAWINGS

11. FURNITURE FINISH COLOR BOARDS

12. INTERIOR FINISH COLOR BOARDS

POINTS OF CONTACT

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

POND PROJECT NUMBER: 1210132

Ver. OCT 2019

Attachment 3: Contact Information

Name: Bruce E. Ealey, P.E. Name: Caprt. Audrey Griffith Position: Senior Project Engineer Position: Project Manager Organization: CELRL-ED-M-R Organization: CELRL-PM-AFR Mailing Address:

600 Martin Luther King Place ED-M-R (Ealey), Room 414 Louisville, KY 40202

Mailing Address:

600 Martin Luther King Place

PM-R-AF

Louisville, KY 40202

Office Phone: 502-315-6404 Office Phone: 502-315-6836 E-Mail: Bruce.e.ealey@usace.army.mil E-Mail: Audrey.s.griffith@usace.army.mil

Name: Wil Jones Name: Alex McCoy Position: Program Manager Position: Construction COR Organization: AFRC Organization: LRL-CD-R Mailing Address:

255 Richard Ray Boulevard Robins AFB, GA 31098-1637

Mailing Address:

600 Martin Luther King Place Louisville, KY 40202

Office Phone: 478-327-1024 Office Phone: 502-315-6129 E-Mail: Wilson.jones.2@us.af.mil E-Mail: Alex.s.mccoy@usace.army.mil

Name: Andy Salisbury Name: Joseph Salvatore/Jeremy Pagoada Position: Project Manager Position: Project Engineer Organization: BCE- Niagara ARS Organization: USACE- New York Ditrict Mailing Address:

2405 Franklin Drive Niagara Falls ARS, NY 14304

Mailing Address:

USACE

c/o B914 AG NFIAP Bldg 700 Niagara Falls, NY 14304-5000

Office Phone: 716-236-3122 Office Phone: 716-236-2048 E-Mail: Andrew.salisbury.1@us.af.mil E-Mail: Joseph.a.salvatore@usace.army.mil

Name: Greg Etter

Name:

Position: Program Manager Position:

Organization: USACE-Omaha District Organization:

Mailing Address:

1616 Capitol Avenue Omaha, NE 68102

Mailing Address:

Office Phone: 402-995-2180 Office Phone:

E-Mail: Gregory.m.etter@usace.army.mil E-Mail:

Name: Name:

Position: Position:

Organization: Organization:

Mailing Address:

Mailing Address:

Office Phone: Office Phone:

E-Mail: E-Mail:

DESIGN NARRATIVE

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

Replacement Fuel Bulk Storage Facility – Hydrant Repair Corrected Final Design Analysis

(P2#: 488039, 488040, 488041, and 495422)

Niagara Falls Air Reserve Station, New York May 10, 2021

35 | P a g e P2#: 488039, 488040, 488041, and 495422

VI. Interiors

a. Comprehensive Interior Design (CID)

The Comprehensive Interior Design (CID) is provided by the Design team and includes the Structural

Interior Design (SID) and the Furniture, Fixtures and Equipment (FF&E) Design (CFCI). The furniture design for these facilities is based on the provided scope of work and will be further defined by thorough consultation with the Users to establish requirements best suited to their needs. Selections will be made based on functionality, durability, and cost-effectiveness.

The FF&E includes the design, selection, specification, color coordination and procurement documentation of the required items necessary to meet the functional, operational, sustainability, and aesthetic needs of the facility. The FF&E package will include placement plans, ordering and finish information on all freestanding furnishings and accessories and will be coordinated with the Structural

Interior Design (SID) interior finish materials. The selection of furniture style, function and configuration will be coordinated with the CID defined requirements from the Design Team.

b. Furniture, Fixture and Equipment

The products selected for the FF&E package will coordinate with the SID material color palette.

Materials will be selected to provide the quality necessary to withstand operations. Comfortable seating that is ergonomically supportive with long-wearing upholstery will be selected for task and guest chairs. All FF&E items will be in keeping with the facility concept and specified to support the function and provide long lasting durability.

FF&E item data sheets and pricing will be provided to the base. All commercial furniture items will be purchased through USACE. Itemized pricing shall be provided.

The color palette for the furnishing will be coordinated with the surrounding interior finishes and will incorporate warm neutrals in timeless colors and patterns.

c. Finish Selections

Floor finishes: Floors in the mechanical and storage rooms shall have sealed concrete flooring. The classroom shall have LVT and the corridor shall have walk-off carpet tile. The lab will have five step epoxy resin system with integral cove base. Rubber base shall be installed throughout, with exception to lab.

Wall finishes: All wall partitions will be painted gypsum wall board. Epoxy paint to be used in the lab.

Ceiling finishes: The mechanical and storage rooms will have exposed ceilings. The classroom, lab and corridor will have 2’ x 4’ suspended acoustical panel ceiling systems.

Lab: Premium Lab quality, metal construction casework and epoxy countertops with 4” chemical and fuels-resistant backsplash shall be utilized according to UFC 4-310-03, 12 August 2020.

Interior Signage: Interior signage for all spaces shall be provided per UFC 3-120-10 Interior Design, 16

May 2018.

Color Scheme: All finishes will be selected during the design phase and coordination with existing finishes should always be considered.

FURNITURE FLOOR PLANS

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

LAB

CLASSROOM

STORAGE

MECH / ELEC

D1 D1 D1 D1

D1 D1 D1 D1 D1

T1

C1 C1

C1C1

C1

C1 C1

C1

C1C1C1

4' - 0"

3' - 10"

CLASSROOM

E105 ADMINISTRATION

E103

VESTIBULE

E101

WOMEN'S

RESTROOM

E102A

WOMEN'S LOCKER

ROOM

E102

MEN'S LOCKER

ROOM

E104

MEN'S RESTROOM

E104A

JANITOR'S

E104BMECH

E107

READY ROOM

E106

Room E100

T B

W B

W B

A B B.1

W1 R1

FURNITURE LEGEND

G.F.G.I. - SEE FF&E PACKAGE

C1 - TASK CHAIR

D1 - 48" TOUCHDOWN

STATION WITH

BOX/BOX/FILE &

UNDERSURFACE POWER

T1 - 48"X120" CONFERNECE

TABLE WITH

POWER/DATA (SEATS 10)

WB - 3'X4' WHITEBOARD

TB - 3'X4' TACKBOARD

R1 - LARGE RECYCLING

WASTEBASKET

W1 - LARGE WASTEBASKET

N.I.C.

TRU

E N

PLAN

NORTH

1 2 3

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IA

T

IO

N

N O

P R

O J E

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

4 5

US Army Corps of Engineers ® Louisville Distrct

C M

A

IO

C C

O

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

P N

O A

N D

A D

IS

K S

H E

L L

K S

H E

L L

/7

/2

:1

:5

A M

C U s e rs \s h e llk

\D o c u m e n ts \1

N

F A

R S

A

R C

H v

S h e llK

.r v t

IFB101

CORRECTED FINAL DESIGN SUBMITTAL

F U

R N

IT

U

R E

P L A

N

R E

P L A

C E

M E

N T

F U

E L B

U L K

S T

O R

A G

E F

A C

IL

IT

Y H

Y D

R A

N T

R E

P A

IR

N

IA

G

A R

A F

A L L S

A R

S

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

-0

J O

B N

O

M

A Y

W Q

R -1

-D

-0

W Q

R -2

-F

-0

SCALE: 1/4" = 1'-0"A1

FURNITURE PLAN

SCALE: = 1'-0"

0 4 84

1/4"

ROOM CONTENTS LIST

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

ROOM CONTENTS LIST

DATE:

5/10/2021

CODE

102 - CLASSROOM

C1

D1

T1

WB

TB

W1

R1 Recyling Wastebasker 1

48" TouchDown Station 9

48"x120" Conference Table 1

Whiteboard 2

Tackboard 1

Wastebasket 1

QTY

Task Chair 11

FF&E ITEM

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

Corrected Final

Design

ITEM INSTALLATION LIST

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

ITEM INSTALLATION LIST

5/10/2021

CODE

C H A I R S:

C1

D E S K S:

D1

T A B L E S:

T1

M I S C:

R1

W1

WB

TB

Corrected Final

Design

FF&E ITEM

Tackboard 1

White Board 2

Recycling Wastebasket 1

Wastebasket 1

48"x120" Conference Table 1

QTY

11Task Chair

48" TouchDown Station 9

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

SPECIFICATION LIST BY TAG

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

SPECIFICATION LIST BY TAG

5/10/2021

CODE

C H A I R S:

C1

D E S K S:

D1

T A B L E S:

T1

M I S C:

R1

W1

WB

TB

Corrected Final

Design

Recycling Wastebasket

White Board

Tackboard

Wastebasket

FF&E ITEM

Task Chair

48"x120" Conference Table

48" TouchDown Station

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

MANUFACTURER’S POC LIST

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

MANUFACTURER'S POINTS OF CONTACT LIST

5/10/2021

TITLE: Kimball INT.

COMPANY NAME Kimball Contact: Karen Kontoulas

COMPANY ADDRESS 1600 Royal Street Tele: 336-918-2026

CITY, STATE, ZIP Jasper, IN 47546 Email: Karen.Kontoulas@kimball.com

TITLE: Alle

COMPANY NAME Alle Contact: Cole

COMPANY ADDRESS 27 Ruskin Rd Tele: 716-446-5538

CITY, STATE, ZIP Amherst, NY Email: cole@alleofficesolutions.com

TITLE: Claridge

COMPANY NAME Claridge Contact: OED

COMPANY ADDRESS

601 Highway 62-65

South Tele: 770-984-9047

CITY, STATE, ZIP

Harrison, AR 72602-

0910 Email: michelle@oedreps.com

POINTS OF CONTACT

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

Corrected Final

Design

MANUFACTURER’S RESOURCE LIST

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

MANUFACTURER'S RESOURCE LIST

5/10/2021

KIMBALL

CONTRACT SUMMARY

ALLE

CONTRACT SUMMARY

Claridge

CONTRACT SUMMARY

Corrected Final

Design

Business Size: SMALL

DUNS Number: 006338099

NAICS: 337214

MANUFACTURER

Contract Number: GS-28F-0042U

Contract Period: PRESENT-2.11.21

Business Size: OTHER

MANUFACTURER

Contract Period: PRESENT- 9.30.21

Business Size: SMALL

Contract Number: GS-07F-0026T

DUNS Number: 620726955

NAICS: 325998

NAICS: 337214

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

MANUFACTURER'S LIST

MANUFACTURER

Contract Number: GS-03F-059DA

DUNS Number: 6365803

FURNITURE PROCUREMENT SHEETS

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

Design Phase

5/10/2021

FF&E ITEM: Task Chair ITEM CODE: C1

MANUFACTURER:

GSA Contract #:

Expiration Date:

PRODUCT NAME: PHOTO(S) / FINISHES:

MODEL NO.(S):

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

DEPARTMENT

Classroom

Joya

QTY.

Mesh back task chair, upholstered seat, 5 prong base in black plastic, black casters, adjustable lumbar support, black arm pads, 4-way adjustable arms, full synchro-tilt 4 position lock with seat slider.

K56TMBU

OVERALL H: 39 1/4"-43 1/4"

OVERALL W: 26 1/4"

OVERALL D: 23"

Seat H: 18 1/2"-22 1/2"

Seat D: 17 3/4"

LIMITED LIFETIME

SEAT: SEDONA c: MESA

MESH: JOYA MESH c: BLACK

FRAME: BLACK

ROOM NO.

02.11.21

GS-03F-059DA

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

Kimball

Corrected Final

Design

SEATBACK FRAME

5/10/2021

FF&E ITEM: 48" TouchDown Station ITEM CODE: D1

MANUFACTURER:

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

102 Classroom 9

ROOM NO. DEPARTMENT QTY.

Corrected Final

Design

SEE BOM

02.11.21

LAMINATE: MIDTOWN WALNUT

METAL: CINDER

MAIN DESK: 30" X 66"

LIMITED LIFETIME

48" Straight laminate worksurface with laminate end and modesty panel, mini-tap power unit with two recpeltacles mounted under worksurface edge and 15" undersurface metal BBF.

• Work surfaces must offer grommet wire manager on all work surfaces for managing cables within

UNDER SURFACE STORAGE:

•Drawer fronts must be field removable

• Full length pulls

• Full drawer extensions are required for file drawers with all bearing glides

• Plastic sleeve break-away keys should be specified

• Each pedestal to have pencil tray included

• All undersurface storage has 1-1/2" glides to provide 1-1/4" adjustment to handle uneven floors

**IMAGE FOR REFERENCE ONLY**

EXACT FINISHES NOT SHOWN

Kimball

GS-03F-059DA

Footprint

New Tank, Offload, and Building Addition

LAMINATE METAL

48"

Bill of Material

Date 4/14/2021 Page 3 / 4

# Part Number Options Description Preview Package Count TAG1 Qty

48" TD

1 12S2415PUBBFM FOOTPRINT, 24DX15WX27H, STOR, PEDESTAL, BBF,

FLAT PROFILE, PAINT

48" TD 1

E EXTENDED

KRB RANDOM CORE INCL,NOT INSTALLED

STD STANDARD GROUP 1,NON-METALLIC

462 CINDER

2 ABEPS FOOTPRINT, GUSSET BRACKET FOR END PANEL 48" TD 1

3 FEP2327L FOOTPRINT, 23WX27H, FREESTANDING, END

PANEL, LAMINATE

48" TD 1

462 CINDER

~ Undefined ~ Undefined

0000000923 FINISH TOP EDGE

Y YES

0000000948 DELETE VEIN LINE

Y YES

4 FMP4824L FOOTPRINT, 48WX24H, MODESTY FINISH PANEL,

LAMINATE

48" TD 1

462 CINDER

~ Undefined ~ Undefined

0000000923 FINISH TOP EDGE

Y YES

0000000948 DELETE VEIN LINE

Y YES

5 SS2448WSSL2 FOOTPRINT, 24DX48W, SURF, 1 3/16T, STR,

LAMINATE, DOUBLE RIM PF

48" TD 1

P 1/8" MOLDED VIN

STD STANDARD GROUP 1

MW MIDTOWN

MW MIDTOWN

~ Undefined ~ Undefined ~ Undefined ~ Undefined

6 KCE0303MTPPUSMB ELECTRICAL, MINITAP, POWER CENTER, BLACK 48" TD 1

*BOM QUANTITY PER 1

TOUCHDOWN STATION

5/10/2021

FF&E ITEM: 48"x120" Conference Table ITEM CODE: T1

MANUFACTURER:

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

Niagara Falls, NY

Solicitation:

ROOM NO. DEPARTMENT QTY.

LAMINATE: MIDTOWN WALNUT

METAL: CINDER

Classroom 1102

Corrected Final

Design

74K3030SQ2L, 74K3228TBX

48" X 120" X 29" H

Kimball

GS-03F-059DA

Dock

02.11.21

48" X 120" Rectangular, laminate top with Y Blade base, softened vinyl rim profile, (2) E2X power/data modules in left and right of surface(includes 2 sides with 3 power outlets on each, VGA DB15HD female with 120" cable, USB 2-port simplex charger, one 3.5mm stereo jack, 1 HDMI coupler, 1 open port), wire management in bases and under table top.

LIMITED LIFETIME

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

LAMINATE METAL

120"

Bill of Material

Date 4/14/2021 Page 4 / 4

# Part Number Options Description Preview Package Count TAG1 Qty

48x120 conference

1 KCE820ELPDCPC ELEC, M2X,

POWER/DATA/USB/HDMI/VGA, POWDER

COAT, SILVER

48x120 conference 2

2 74K279828CFYL DOCK, TABLE BASE, Y, BLADE, PAINT 48x120 conference 1

462 CINDER

462 CINDER

3 74K48120RTLL DOCK, TABLE TOP, RECTANGULAR,

LAMINATE(TFL) 48X120

48x120 conference 1

P 1/8" MOLDED VIN

C2LR_CUTOUT C2,LEFT & RIGHT,CUTOUT ONLY

MW MIDTOWN

MW MIDTOWN

0000008461 MODIFIED DEPTH

X NO MODIFIED DEPTH (STANDARD)

0000008466 MODIFIED WIDTH

X NO MODIFIED WIDTH (STANDARD)

5/10/2021

FF&E ITEM: Recycling Wastebasket ITEM CODE: R1

MANUFACTURER:

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

RCS Berch Series XL

RCSB935

09.30.21

9 1/2" X 18 1/4" X 35 1/2" H

LID: PLATINUM

WASTEBASKET: PEBBLE BLOCK GLOSS

Powder-coated steel 17 gallon body recycling waste receptacle with internal liner, outer label reading "Recyclables", integrated bag arms, adjustable glides, Comingle lid opening, Fire-safe steel with over 30% recycled material content, ADA Compliant.

LIMITED

Corrected Final

Design

ROOM NO. DEPARTMENT QTY.

102 Classroom 1

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

Alle

GS-07F-0026T

LID WASTEBASKET

5/10/2021

FF&E ITEM: Wastebasket ITEM CODE: W1

MANUFACTURER:

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

RCS Berch Series XL

RCSB935

09.30.21

9 1/2" X 18 1/4" X 35 1/2" H

LID: PLATINUM

WASTEBASKET: PEBBLE BLOCK GLOSS

Powder-coated steel 17 gallon body waste receptacle with internal liner, outer label reading "Trash", integrated bag arms, adjustable glides, 15" x 6" lid opening, Fire-safe steel with over 30% recycled material content, ADA Compliant.

LIMITED

Corrected Final

Design

ROOM NO. DEPARTMENT QTY.

102 Classroom 1

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

Alle

GS-07F-0026T

LID WASTEBASKET

5/10/2021

FF&E ITEM: White Board ITEM CODE: WB

MANUFACTURER:

Expiration Date: 09.02.2023

PRODUCT NAME: 800 Series Markerboard PHOTO(S) / FINISHES:

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

800 Series Markerboards - Aluminum Frame - LCS porcelain enamel steel dryerase writing surface markerboards have satin anodize frame, angle clip hangers. White furnished if color not specified. Full length marker tray and map rail with 2 map hooks. Adhesive recommended.

1 YEAR

CLARIDGE

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

Corrected Final

Design

814L

102 Classroom 2

3'X4'

ANODIZED ALUMINUM FRAME

ROOM NO. DEPARTMENT QTY.

GS-28F-0042U

5/10/2021

FF&E ITEM: Tackboard ITEM CODE: TB

MANUFACTURER:

Expiration Date: 09.02.2023

PRODUCT NAME: 800 Series Tackboard PHOTO(S) / FINISHES:

ITEM DESCRIPTION:

WARRANTY:

DIMENSIONS:

FINISHES:

LOCATION OF ITEM / QUANTITY BY ROOM:

UNIT PRICE EXT PRICE

TOTAL QUANTITY: TOTAL PRICE -$

SPECIAL INSTRUCTIONS:

*Provide Room # on Carton(s)

800 Series Tackboards - Aluminum Frame - Guilford of Maine FR701

Fabric tackboards have satin anodize frame with angle clip hangers.

Adhesive recommended.

1 YEAR

New Tank, Offload, and Building Addition

Niagara Falls Air Reserve Station

Niagara Falls, NY

Solicitation:

CLARIDGE

GS-28F-0042U

840D

Corrected Final

Design

3'X4'

ANODIZED ALUMINUM FRAME

FABRIC: CEMENT MIX

ROOM NO. DEPARTMENT QTY.

102 Classroom 1

FABRIC

DRAWINGS

CORRECTED FINAL DESIGN SUBMITTAL

1301 Gervais St Suite 1300, Columbia SC 292015/6/2021

NFARS

NIAGARA FALLS AIR RESERVE STATION, NY

Contract #W912QR-18-D-0011

FY 2021

GENERAL ARCHITECTURE NOTES:

1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF

WORK. THE DRAWINGS ARE NOT INTENDED TO

INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE

FULL PERFORMANCE AND COMPLETION OF THE

REQUIREMENTS OF THE CONTRACT DOCUMENTS.

2. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN

ONE PORTION OF THE CONTRACT DOCUMENTS SHALL

NOT BE CONSTRUED TO EXCLUDE OTHER ITEMS

NECESSARY OR IMPLIED THEREFROM.

3. THE CONTRACTOR IS RESPONSIBLE FOR THE

COORDINATION OF ALL PARTS OF THE WORK SO THAT

NO WORK SHALL BE LEFT IN AN UNFINISHED OR

INCOMPLETE CONDITION.

4. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY

AND MANUFACTURER'S PUBLISHED STANDARDS FOR

QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL

AS, ALL REQUIREMENTS IN THESE DRAWINGS AND

SPECIFICATIONS. ANY CONFLICTING REQUIREMENTS

OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT

TO THE CONTRACTING OFFICER'S REPRESENTATIVE'S

ATTENTION PRIOR TO PROCEEDING WITH THE WORK.

5. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-

PLACE, AND NEW WORK.

6. ALL WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF

THE CONSTRUCTION SCOPE OF WORK AGREEMENT.

7. THE CONTRACTOR SHALL PAY FOR AND COORDINATE

THE REMOVAL AND LEGAL DISPOSAL OF MATERIALS

AND RUBBISH.

8. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL

DIMENSIONS AND SHALL VERIFY ALL NEW AND

EXISTING CONDITIONS, SHOWN ON THESE DRAWINGS.

THE CONTRACTOR SHALL NOTIFY THE CONTRACTING

OFFICER'S REPRESENTATIVE IN WRITING OF ANY

DIFFERING CONDITIONS BEFORE COMMENCEMENT OF

WORK.

9. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN,

LARGE SCALE DETAILS GOVERN OVER SMALL SCALE

DETAILS. THE CONTRACTOR SHALL NOTIFY THE

CONTRACTING OFFICER'S REPRESENTATIVE IN

WRITING OF ANY DIFFERING CONDITIONS BEFORE

COMMENCEMENT OF WORK.

10. UNLESS NOTED OTHERWISE, ALL GYPSUM BOARD

SURFACES ARE TO RECEIVE ONE PRIMER COAT AND

TWO COATS OF PAINT.

11. DIMENSIONS NOTED AS 'HOLD' SHALL NOT VARY BY

MORE THAN 1/8" FROM SIDE TO SIDE OR FROM FRONT

TO BACK, FINISHED SURFACE TO FINISHED SURFACE.

12. NFPA 241, STANDARD FOR SAFEGUARDING

CONSTRUCTION, AND ALTERATION OPERATIONS SHALL

BE APPLIED.

13. WALL AND/OR CEILING ASSEMBLIES THAT ARE

IDENTIFIED WITH A FIRE RESISTIVE RATING SHALL BE

CONSTRUCTED AS DETAILED HEREIN.

14. DIMENSIONS SHOWN ARE TO FACE OF STUD OR CMU

(U.N.O.).

15. PROVIDE EXPANSION AND CONTROL JOINTS IN ALL

WORK AS PER PRODUCT MANUFACTURER'S

STANDARDS.

16. THE CONTRACTOR SHALL PERFORM ALL WORK IN

ACCORDANCE WITH ALL APPLICABLE CODES,

ORDINANCES AND REGULATORY AGENCIES AND SHALL

OBTAIN NECESSARY BUILDING AND FIRE PERMITS

FROM ALL AUTHORITIES HAVING JURISDICTION.

17. ALL INTERIOR FINISH MATERIALS SHALL COMPLY WITH

THE REQUIREMENTS OF ALL APPLICABLE CODES,

ORDINANCES AND REGULATORY AGENCIES.

18. ALL DISSIMILAR METALS SHALL BE ISOLATED FROM

EACH OTHER TO AVOID GALVANIC CORROSION.

19. NOTES APPEAR ON VARIOUS SHEETS FOR DIFFERENT

SYSTEMS AND MATERIALS. SHEETS ARE TO BE

REVIEWED AND NOTES ON INDIVIDUAL SHEETS SHALL

BE APPLIED TO RELATED DRAWINGS AND DETAILS.

20. A FINISH INDICATION ON A WALL SHALL MEAN THE

ENTIRE LENGTH AND HEIGHT OF WALL IS TO BE

FINISHED OR FIRE-RATED AS INDICATED.

21. WHEN NON-DIMENSIONED PARTITIONS APPEAR IN

CONJUNCTION WITH DOOR OPENINGS, THE DOOR

WIDTH AND THE DOOR FRAME DETAILS DETERMINE

THE LOCATION OF ADJACENT WALLS AND FRAMES.

22. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO

THOSE DETAILED. WHERE SPECIFIC DIMENSIONS,

DETAILS OR DESIGN INTENT CANNOT BE DETERMINED,

CONSULT THE CONTRACTING OFFICER'S

REPRESENTATIVE BEFORE PROCEEDING WITH THE

WORK.

23. THE CONTRACTOR SHALL COORDINATE ALL

MECHANICAL AND ELECTRICAL FLOOR AND WALL

SLEEVES INCLUDING CONDUITS WITH ALL

MECHANICAL, ELECTRICAL, PLUMBING, FIRE

PROTECTION, STRUCTURAL AND ARCHITECTURAL

DRAWINGS.

24. PROVIDE ACCESS PANELS AS REQUIRED BY

APPLICABLE CODES AND AS REQUIRED FOR

MECHANICAL EQUIPMENT AND PLUMBING WORK. ALL

ACCESS PANELS SHALL BE CONCEALED AND

LOCATIONS SHALL BE REVIEWED WITH THE

ARCHITECT PRIOR TO PROCEEDING.

25. ALL PIPE DUCTS AND BUS DUCTS THAT PENETRATE

FLOOR SLABS OR WALL PARTITIONS SHALL BE

INSTALLED IN A MANNER THAT WILL PRESERVE THE

MOISTURE RESISTIVENESS, FIRE RATING, AND

STRUCTURAL INTEGRITY OF THE BUILDING.

26. DO NOT CUT INTO, REMOVE OR ALTER ANY

STRUCTURAL MEMBER OR PORTION OF THE FLOOR

SYSTEM UNLESS IT IS SPECIFICALLY NOTED OR

SHOWN ON THE STRUCTURAL DRAWINGS.

27. INTERIOR PARTITION MOVEMENT CONTROL:

A. VERTICAL CONTROL JOINTS FOR ANY WALL LENGTH

ARE TO OCCUR AT NOT MORE THAN 30'-0" O.C. IN

THE HORIZONTAL DIRECTION, UNLESS NOTED

OTHERWISE.

B. PROVISIONS SHALL BE MADE IN THE DESIGN,

FABRICATION, AND INSTALLATION OF INTERIOR

PARTITIONS FOR TYPICAL FLOOR DEFLECTIONS OF

THE STRUCTURE UNDER SUPERIMPOSED LOADS AS

FOLLOWS:

a. TYPICAL ROOF/FLOOR MEMBERS: SPAN/360

BUT NOT LESS THAN 1/2”.

28. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO

PROVIDE ADEQUATE PROTECTION FOR PERSONS AND

PROPERTY AT ALL TIMES, AND EXECUTE THE WORK IN

SUCH A MANNER TO AVOID ANY HAZARD TO PERSONS

AND PROPERTY AS NECESSARY.

29. THE CONTRACTOR SHALL COORDINATE THE PHASING

OF THE WORK TO BE PERFORMED IN OR ABOUT

EXISTING FACILITIES, IF APPLICABLE, WITH THE

CONTRACTING OFFICER'S REPRESENTATIVE PRIOR TO

START OF SUCH WORK.

ARCHITECTURAL ABBREVIATIONS:

A.F. ACCESS FLOORING

A.F.F. ABOVE FINISHED FLOOR

ACC. DR. ACCESS DOOR / PANEL

ADAAG AMERICAN WITH DISABILITIES

ACCESSIBILITY GUIDELINES

ADJ. ADJUST/ ADJUSTABLE

ACOUST. ACOUSTICAL

A.B. ANCHOR BOLT

ACT ACOUSTICAL CEILING TILE

ANOD. ANODIZED

A.C. AIR CONDITIONING

AL / ALUM. ALUMINUM

APP. APPROVED

APPROX. APPROXIMATE

ARCH. ARCHITECTURAL

AT / FP ANTI TERRORISM / FORCE PROTECTION

AVG. AVERAGE

A.W.I. ARCHITECTURAL WOODWORK INSTITUTE

B.H.M.I. BUILDER'S HARDWARE MANUFACTURER'S

ASSOCIATION, INC.

BM. BEAM

BLKG. BLOCKING

BD. BOARD

BTM. BOTTOM

BLDG. BUILDING

B.U.R. BUILT-UP ROOFING

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CFMF COLD FORMED METAL FRAMING

CH. CHANNEL

CPT CARPET

CLG. CEILING

CLG. HT. CEILING HEIGHT

CTR. CENTER

C CENTER LINE

C. TO C. CENTER TO CENTER

CT CERAMIC TILE

CLR CLEAR

CO CLEANOUT

CLOS. CLOSET

COL. COLUMN

CONC. CONCRETE

CORR. CORRIDOR

COTR CONTRACTING OFFICER'S TECHNICAL

REPRESENTATIVE

CMU CONCRETE MASONRY UNIT

CONF. CONFERENCE

CONST. CONSTRUCTION

CONT. CONTINUOUS

CONTR. CONTRACTOR

CJ CONTROL JOINT

CY CUBIC YARD

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DISP DISPENSER

DR DOOR

DN DOWN

DS DOWNSPOUT

DESC. DESCRIPTION

DWG DRAWING

L

EA EACH

ELEC ELECTRICAL OR ELECTRIC

EL. ELEVATION

EWC ELECTRIC WATER COOLER

ERD EMERGENCY ROOF DRAIN

EP EPOXY PAINT

ENGR ENGINEER

EOS EDGE OF SLAB

EQUIP EQUIPMENT

EQ EQUAL

EXIST EXISTING

EXP EXPANSION / EXPOSED

EJ (EXP. JT.) EXPANSION JOINT

EXP ST EXPOSED TO STRUCTURE

EXT EXTERIOR

ETD ESTIMATED TRAVEL DISTANCE

FAC FACTORY

FDC FIRE DEPARTMENT CONNECTION

FT FEET

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FIN. FINISH

F.P. FLAT PAINT

FF FINISHED FLOOR

FLR FLOOR

FD FLOOR DRAIN

FLUOR FLUORESCENT

F/O FACE OF

F.O.G. FACE OF GIRT

FTG. FOOTING

FDN. FOUNDATION

FV FIELD VERIFY

GA. GAGE OR GAUGE

GALV. GALVANIZED

G.B.F. GYPSUM BOARD FURRING

GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED

G.L. GIRT LINE

G.P. GLOSSY PAINT

GL. GLASS

GOVT. GOVERNMENT

GYP. GYPSUM

GYP. (GWB) GYPSUM BOARD

HKS HOOKS

HR. HANDRAIL

HDW. HARDWARE

HGT. HEIGHT

H. HIGH

H.P. HIGH POINT

H.M. HOLLOW METAL

HORIZ. HORIZONTAL

HB HOSE BIBB

H.V.A.C. HEATING VENTILATION & AIR CONDITIONING

IN. INCH

I.D. INSIDE DIAMETER

INSUL. INSULATION

INT. INTERIOR

JAN. JANITOR

J.C. JANITOR'S CLOSET

JT. JOINT

JST. JOIST

K.P. KICK PLATE

LAM. LAMINATE

LDG. LANDING

LAV. LAVATORY

L.H. LEFT HAND

LHR LEFT HAND REVERSE

LT. LIGHT

LTG. LIGHTING

LONG. LONGITUDINAL

LVR. LOUVER

L.P. LOW POINT

MAS. MASONRY

M.O. MASONRY OPENING

MGR. MANAGER

MANUF. MANUFACTURER

MATL MATERIAL

MAX. MAXIMUM

MECH. MECHANICAL

MTL. METAL

M.W.P. METAL WALL PANEL

MIN. MINIMUM

MISC. MISCELLANEOUS

N.I.C. NOT IN CONTRACT

NO. (#) NUMBER

NTS NOT TO SCALE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

O.C. ON CENTER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFGI OWNER FURNISHED GOVERNMENT INSTALLED

O.H. OPPOSITE HAND

OPNG. OPENING

O.W. OPEN WEB

OPP. OPPOSITE

O.D. OUTSIDE DIAMETER

OSHA OCCUPATIONAL SAFETY AND HEALTH ACT

OVHD OVERHEAD

PDU POWER DISTRIBUTION UNIT

PT PAINT

PR. PAIR

PNL. PANEL

PART. PARTITION

PLAS. PLASTER OR PLASTIC

PL PLATE

PLYWD. PLYWOOD

LBS. OR # POUNDS

PSF POUNDS / SQUARE FOOT

PSI POUNDS / SQUARE INCH

P.M.J.F. PRE-MOLDED JOINT FILLER

PRE-FAB. PREFABRICATED

Q.T. QUARRY TILE

RAF RAISED ACCESS FLOOR

RECEP. RECEPTIONIST

REF. REFERENCE

REINF. REINFORCEMENT

REQ'D. REQUIRED

REV. REVISIONS / REVISED

R.D. ROOF DRAIN

R.D. RIGHT HAND

RH RIGHT HAND REVERSE

RM. ROOM

R.O. ROUGH OPENING

RB RUBBER BASE

SC SEALED CONCRETE

SCW SOLID CORE WOOD

SCHED. SCHEDULE

SECT . SECTION

S.G.P. SEMI-GLOSS PAINT

SSK SERVICE SINK

SHT. MET. SHEET METAL

SIM. SIMILAR

STC SOUND TRANSMISSION CLASS

SPEC(S) SPECIFICATION

SFRM SPRAYED FIRE RESISTIVE MATERIAL

SQ. SQUARE

ST. STAIN

S.S. STAINLESS STEEL

STD. STANDARD

STL. STEEL

STOR. STORAGE

STRUCT. STRUCTURAL

SUSP. SUSPENDED

TOIL. / TLT TOILET

TEL. TELEPHONE

THK. THICK

T'HOLD THRESHOLD

TG TEMPERED GLASS

T/ TOP OF

TOB TOP OF BEAM

TOC TOP OF CONCRETE

T/C TOP OF CURB

TOS TOP OF STEEL

T/W TOP OF WALL

TU TOUCH-UP

TYP. TYPICAL

U.L. UNDERWRITERS LABORATORIES

UNFIN UNFINISHED

U.N.O. UNLESS NOTED OTHERWISE

VERT. VERTICAL

VEST. VESTIBULE

VCT VINYL COMPOSITION TILE

VCB VINYL COVE BASE

V.T.R. VENT THRU ROOF

W. WIDTH

W/ WITH

W.C. WATER CLOSET

WCO WALL CLEAN OUT

WD. WOOD

WDW. WINDOW

W.M.P. WIRE MESH PARTITION

W/O WITHOUT

W.R.G.B. WATER RESISTANT GYPSUM BOARD

W.S. WEATHERSTRIPPING

W.R.O. WINDOW ROUGH OPENING

YD. YARD

1 2 3

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IA

T

IO

N

N O

P R

O J E

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

4 5

US Army Corps of Engineers ® Louisville Distrct

C M

A

IO

C

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

P N

O A

N D

K K

O T

E L L O

S

D G

R A

H A

M

R J E

N N

IN

G

S

/7

/2

:4

:5

P M

C U s e rs \G ra h a m

D \D o c u m e n ts \1

N

F A

R S

A

R C

H v g ra h a m d

P H

B .r v t

AB001

CORRECTED FINAL DESIGN SUBMITTAL

G E

N E

R A

L N

O T

E S

A N

D A

B B

R E

V

IA

T

IO

N S

R E

P L A

C E

M E

N T

F U

E L B

U L K

S T

O R

A G

E F

A C

IL

IT

Y H

Y D

R A

N T

R E

P A

IR

N

IA

G

A R

A F

A L L S

A R

S

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

-0

J O

B N

O

M

A Y

W Q

R -1

-D

-0

W Q

R -2

-F

-0

SYMBOLS:

VIEW TITLES:

PLAN SYMBOLS:

SECTION NUMBER

DWG. NO. WHERE

SECTION IS DRAWN

WALL SECTION MARK

SECTION NUMBER

DWG. NO. WHERE

SECTION IS DRAWN

BUILDING SECTION MARK

ELEVATION

NUMBER (TYP.)

DWG. NO. WHERE

ELEVATION IS DRAWN

INTERIOR ELEVATION MARK

DWG. NO. WHERE

DETAIL IS DRAWN

CALLOUT HEAD

DETAIL NUMBER (TYP.)

AREA COVERED BY

DETAIL

DOOR TAG WINDOW &

LOUVER TAG

ROOM TAG PARTITION TYPE KEYNOTE

TAG

CEILING TAG

(HEIGHT)

CEILING TAG

(TYPE & HEIGHT)

CEILING HGT.

CEILING TYPE

SUBSCRIPT

TYPE (AS REQ)

PARTITION TYPE

EQUIPMENT

TAG

DETAIL IDENTIFIER (MODULE LETTER AND NUMBER)

NORTH ARROW

FLOOR PLANS, ELEVATIONS, SECTIONS AND DETAIL VIEWS TITLE

A-101

SIM

A-101

ROOM NAME

A101 12'-0" A.F.F. 1t 12'-0"A1-X 1i

A1

ELEVATIONS, DETAILS & CALLOUTS

SCALE: 1/8" = 1'-0"

A-101

EXTERIOR ELEVATION MARK

ELEVATION

NUMBER (TYP.)

DWG. NO. WHERE

ELEVATION IS DRAWN

REVISION

TAG

A-101

A-101

A-101

1 TRU

E N

PLAN

NORTH

MATERIALS

COMPACTED EARTH

CERAMIC TILE

TERRAZZO

GYPSUM BOARD

INSULATION RIGID

INSULATION BATT

ACOUSTICAL TILE

PLASTER/MET LATH

PLASTER/ROCK LATH

PLYWOOD

GLASS

WOOD-FINISH

WOOD-BLOCKING (DISCONTINUOUS)

WOOD-FRAMING (CONTINUOUS)

METAL-SMALL SCALE

METAL-LARGE SCALE

BRICK

EXTERIOR INSULATION FINISH SYSTEM

CONCRETE BLOCK(CMU)

CONCRETE

SAND / MORTAR

ROCKFILL

ROCK

SHEET NAMING CONVENTION

A-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

1 2 3

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IA

T

IO

N

N O

P R

O J E

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

4 5

US Army Corps of Engineers ® Louisville Distrct

C M

A

IO

C

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

P N

O A

N D

K K

O T

E L L O

S

D G

R A

H A

M

R J E

N N

IN

G

S

/7

/2

:4

:5

P M

C U s e rs \G ra h a m

D \D o c u m e n ts \1

N

F A

R S

A

R C

H v g ra h a m d

P H

B .r v t

AB002

CORRECTED FINAL DESIGN SUBMITTAL

S Y

M B

O L S

A N

D M

A T

E R

IA

L S

R E

P L A

C E

M E

N T

F U

E L B

U L K

S T

O R

A G

E F

A C

IL

IT

Y H

Y D

R A

N T

R E

P A

IR

N

IA

G

A R

A F

A L L S

A R

S

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

-0

J O

B N

O

M

A Y

W Q

R -1

-D

-0

W Q

R -2

-F

-0

CONT. 2" WIDE x 22 GA.

METAL STRAP FOR

TOP ATTACHMENT OF

GYPSUM BOARD.

CONT. 22 GA. 3" DEEP LEG

DEFLECTION TRACK

ATTACH TO DECK AT 12"

O.C. MAX.

CONT. 2" WIDE x 22 GA. METAL

STRAP FOR TOP

ATTACHMENT OF GYPSUM

BOARD.

WHERE GYP. BD. IS

CONCURRENT WITH DECK

FLUTE RECESS EXTENT UP

INTO RECESS AS SHOWN.

DO NOT ATTACH

GYPSUM BOARD OR

STUDS TO

DEFLECTION TRACK IN

THIS AREA.

SEAL ONE SIDE OF PARTITION

AGAINST PASSAGE OF SMOKE

WHEN PARTITION IS ALIGNED AT DECK

FLUTE RECESS - PROVIDE A 6" x 10" x 22 GA

MTL. PLATE AT DECK FLUTE RECESS THAT

IS CONTIGUOUS WITH PARTITION - ATTACH

MTL. PLATE TO DECK WITH POWER DRIVEN

FASTENERS AT SAME SPACING REQUIRED

FOR PARTITION TOP TRACK.

DO NOT ATTACH GWB OR STUDS

TO DEFLECTION TRACK IN THIS

AREA

FLUTED STEEL DECK / CONCRETE FLOOR OR ROOF

PERPENDICULAR OR DIAGONAL TO FLUTES

RATED OR SMOKE RESISTANT

FLUTED STEEL DECK / CONCRETE FLOOR OR ROOF

PARALLEL TO FLUTES

RATED OR SMOKE RESISTANT

EXTEND AT MINIMUM ONE

LAYER UP INTO FLUTE

RECESS AND SEAL.

/4

CONT. 22 GA 3" DEEP

LEG DEFLECTION TRACK

ATTACHED TO DECK AT

12" O.C. MAX.

INTERIOR PARTITION GENERAL NOTES

PARTITION TYPE NOMENCLATURE

1S6AS1

PARTITION TYPE MODIFIER

(WHERE APPLICABLE)

SOUND ATTENUATION BLANKETS (SAB)

(WHERE APPLICABLE)

PARTITION HEAD CONDITION

PARTITION STRUCTURE SIZE

(SEE STUD OR CMU WIDTH SCHEDULE)

PARTITION TYPE

PARTITION RATING (WHERE APPLICABLE)

PARTITION TYPES

M CONCRETE MASONRY UNIT PARTITION

G METAL STUD PARTITION

S SHAFTWALL PARTITION

F METAL FURRING PARTITION

PARTITION STRUCTURE WIDTH DESIGNATOR

# METAL STUD WOOD STUD CMU

0 * 0-7/8" -- --

1 *1-1/2" -- --

2 2-1/2" * 1-1/2"

3 3-5/8" --

4 4"

6 6"

8 8"

10 10"

12 12"

2-1/2"

3-1/2"

5-1/2"

7-1/4"

9-1/4"

11-1/4"

3-5/8"

5-5/8"

7-5/8"

11-5/8"

PARTITION HEAD CONDITION DESIGNATOR

A

PARTITION TO BOTTOM OF STRUCTURAL ROOF

OR FLOOR DECK ABOVE

B

PARTITION TO 6" ABOVE CEILING - BRACE WALL

AS NEEDED

C PARTITION TO BOTTOM OF CEILING ABOVE

D PARTIAL HEIGHT PARTITION - SEE PLAN FOR HEIGHT

PARTITION TYPE MODIFIER

* FURRING MEMBER

1. PARTITION TYPES DESCRIBE GENERAL REQUIREMENTS

FOR PARTITIONS. REFER TO THE MANUFACTURER'S

SPECIFICATIONS AND REQUIREMENTS OF APPLICABLE

TESTING AGENCIES FOR SPECIFICS OF PARTITION

CONSTRUCTION.

2. REFER TO "PARTITION TYPE NOMENCLATURE" FOR

SYMBOLS USED TO IDENTIFY ADDITIONAL REQUIREMENTS

AND MODIFIERS TO BASIC PARTITION TYPES.

3. "LINE OF STRUCTURE" INDICATED FOR EACH PARTITION IS

DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT

CONSTRUCTION CONDITIONS OR GEOMETRY.

4. TYPICAL FLOOR PLAN DIMENSIONS OF PARTITIONS ARE

TO FACE OF STUD OR CMU UNLESS NOTED OTHERWISE.

5. WHERE A CLEAR OPENING DIMENSION IS INDICATED, THE

DIMENSION IS MEASURED FACE-TO-FACE BETWEEN

FINISHED SURFACES.

6. REFER TO SPECIFICATIONS FOR MINIMUM STUD DESIGN

CRITERIA, MAXIMUM SPACING AND ALLOWABLE LIMITING

HEIGHTS DEFLECTION CRITERIA FOR GYPSUM BOARD.

7. METAL STUD GAUGE (IF NOTED) AND UL TEST NUMBERS

WILL VARY DEPENDING ON THE MANUFACTURER OF

COMPONENTS ACTUALLY USED.

8. REFER TO FLOOR PLANS FOR FIRE PROTECTION

RATINGS.

9. ALL RATED PARTITIONS SHALL BE LABELED ABOVE

CEILING WITH LABELS PER AHJ AS REQUIRED. IBC

CHAPTER 7 AT MINIMUM.

10. PENETRATIONS IN RATED PARTITIONS AND CONNECTIONS

OF THE PARTITIONS TO OTHER PORTIONS OF THE WORK

TO BE IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDED DETAILS AND IN COMPLIANCE WITH

APPLICABLE TESTING AGENCY REQUIREMENTS.

11. INSTALLATION OF GYPSUM BOARD, BACKER BOARD AND

BASE BOARD TO CONFORM TO REQUIREMENTS FOR FIRE

RATINGS AND ACOUSTICAL RATINGS.

12. PROVIDE WATER RESISTANT TYPE GYPSUM BOARD AT

AREAS THAT ARE NOTED IN ROOM FINISH SCHEDULE TO

RECEIVE CERAMIC OR PORCELAIN TILE FINISH.

13. INSTALL BLOCKING OR BACKER MATERIAL FOR

ATTACHMENT / MOUNTING OF WALL HUNG ITEMS OR

EQUIPMENT DESCRIBED IN THE DOCUMENTS. ALL

BLOCKING TO BE FIRE RETARDANT TREATED.

14. PARTITIONS THAT ARE REQUIRED TO EXTEND TO THE

DECK ABOVE ARE TO HAVE THE GYPSUM BOARD CUT TO

FIT WITHIN A 1/4" MAXIMUM TOLERANCE TO THE SHAPE OF

THE DECK ABOVE. GYPSUM BOARD SHALL BE

CONTINUOUSLY SEALED FOR THE FULL DEPTH OF THE

GYPSUM BOARD WITH FLEXIBLE SEALANT.

15. PROVIDE METAL STRAPPING @ 24" VERT. TO HOLD BATT

INSULATION FOR AREAS WITHOUT GYPSUM WALLBOARD.

16. GYPSUM BOARD IS TO BE CUT SO THAT THE CLEARANCE

BETWEEN METALLIC ELECTRICAL OUTLET BOXES AND

THE GYPSUM BOARD DOES NOT EXCEED 1/8".

17. THE BOTTOM OF THE GYPSUM BOARD AT INTERIOR

PARTITIONS IS TO BE 1/4" MINIMUM AND 1/2" MAXIMUM

ABOVE THE FLOOR STRUCTURE AND IS TO BE SEALED

FOR THE FULL DEPTH OF THE GYPSUM BOARD WITH

FLEXIBLE SEALANT.

18. REFER TO INTERIOR FINISH SCHEDULE FOR WALL

FINISHES.

19. REFER TO PARTITION TYPE MODIFIERS FOR STC RATED

PARTITIONS

W WOOD STUD PARTITION

RESILIENT CHANNEL AND SOUND BATT

MINIMUM STC RATING - 50

SOUND BATT

MINIMUM STC RATING - 42

2" Z-GIRT AND 1/2" ABUSE-RESISTANT GYPSUM BOARD

WIDTH

CAULKLINE OF FLOOR

STRUCTURE

CAULK

REFER TO PARTITION

HEAD DETAILS FOR

RATED OR NON- RATED

CONDITIONS

LINE OF CEILING

LINE OF

FLOOR/ROOF

STRUCTURE

P L

A N

CMU

CMU

CMU

REFER TO CMU

SCHEDULE BELOW FOR

CMU WIDTH

B A

S E

LINE OF CEILING

CMU

LINE OF CEILING

CMU

CAULK

LINE OF CEILING ABOVE

CMU

. REFER TO PLANS

FOR PARTITION

HEIGHT AND CAP

FINISH DETAILS

CMU BOND BEAM

H E

A D

D E

S

IG

N A

T

IO

N S

T Y

P E

A T

Y P

E B

T Y

P E

C T

Y P

E D

CAULKLINE OF FLOOR

STRUCTURE

METAL RUNNER

GYPSUM BOARD,

EACH SIDE

CAULK

METAL RUNNER

REFER TO PARTITION HEAD

CONNECTION DETAILS FOR

RATED CONDITIONS

REFER TO METAL STUD

SCHEDULE BELOW FOR

PARTITION WIDTH

LINE OF CEILING

LINE OF FLOOR/ROOF

STRUCTURE

ADDITIONAL LAYERS

GYPSUM BOARD (EACH

SIDE) FOR FIRE RATING

PER SCHEDULE BELOW

P L

A N

WIDTH

METAL RUNNER

LINE OF CEILING

B A

S E

METAL RUNNER

LINE OF CEILING

LINE OF CEILING ABOVE

METAL RUNNER

REFER TO PLANS FOR

PARTITION HEIGHT AND

CAP FINISH DETAILS

H E

A D

D E

S

IG

N A

T

IO

N S

T Y

P E

A T

Y P

E B

T Y

P E

C T

Y P

E D

CAULKLINE OF FLOOR

STRUCTURE

METAL RUNNER

GYPSUM BOARD

CAULK

METAL RUNNER

REFER TO PARTITION

HEAD DETAILS FOR

RATED OR NON-

RATED CONDITIONS

REFER TO FURRING STUD

SCHEDULE BELOW FOR

PARTITION WIDTH

WIDTH

LINE OF CEILING

LINE OF FLOOR/ROOF

STRUCTURE

P L

A N

LINE OF STRUCTURE

OR OTHER WALL

CONSTRUCTION

PROVIDING BACK-UP

FOR STUD BRACING

BRACE EACH STUD AT

4'-0" O.C. VERTICALLY

BRACE EACH STUD

AT 4'-0" O.C.

VERTICALLY

METAL RUNNER

LINE OF CEILING

METAL RUNNER

LINE OF CEILING

LINE OF CEILING ABOVE

METAL RUNNER

REFER TO PLANS FOR

PARTITION HEIGHT AND

CAP FINISH DETAILS

H E

A D

D E

S

IG

N A

T

IO

N S

T Y

P E

A T

Y P

E B

T Y

P E

C T

Y P

E D

B A

S E

RATED PARTITION HEAD CONNECTION DETAILS

PARTITION TYPE M PARTITION TYPE GPARTITION TYPE F

METAL STUD SCHEDULE

MARK

STUD

WIDTH GWB LAYERS

PARTITION

WIDTH

FIRE

RATING UL LISTING

G3B 3-5/8" (1) 5/8" 4 7/8" 0 HR N/A

1G3A 3-5/8" (1) 5/8" TYPE X 4 7/8" 1 HR U419

FURRING STUD SCHEDULE

MARK

STUD

WIDTH

GWB

LAYERS

PARTITION

WIDTH

FIRE

RATING UL LISTING

F0B 7/8" (1) 5/8" 1 1/2" 0 HR N/A

F3B 3-5/8" (1) 5/8" 4 1/4" 0 HR N/A

CMU SCHEDULE

MARK

PARTITION

WIDTH

FIRE

RATING UL LISTING

M8A 7 5/8"

M8A3 10 1/8"

1 2 3

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IA

T

IO

N

N O

P R

O J E

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

4 5

US Army Corps of Engineers ® Louisville Distrct

C M

A

IO

C

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

P N

O A

N D

K K

O T

E L L O

S

D G

R A

H A

M

R J E

N N

IN

G

S

/7

/2

:4

:0

P M

C U s e rs \G ra h a m

D \D o c u m e n ts \1

N

F A

R S

A

R C

H v g ra h a m d

P H

B .r v t

AB003

CORRECTED FINAL DESIGN SUBMITTAL

P A

R T

IT

IO

N T

Y P

E S

D

E T

A

IL

S

R E

P L A

C E

M E

N T

F U

E L B

U L K

S T

O R

A G

E F

A C

IL

IT

Y H

Y D

R A

N T

R E

P A

IR

N

IA

G

A R

A F

A L L S

A R

S

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

-0

J O

B N

O

M

A Y

W Q

R -1

-D

-0

W Q

R -2

-F

-0

DEMOLITION PLAN LEGEND

EXISTING CMU AND / OR STUD WALLS /

PARTITIONS TO BE DEMOLISHED

EXISTING CMU AND / OR STUD WALLS /

PARTITIONS TO REMAIN

EXISTING DOOR, FRAME AND

ACCESSORIES TO BE DEMOLISHED

EXISTING DOOR, FRAME, AND

ACCESSORIES TO BE DEMOLISHED

DEMOLITION PLAN SHEET NOTES:

1. ALL EXISTING CONDITIONS INDICATED ON THE DRAWINGS SHALL BE

VERIFIED BY THE CONTRACTOR. ANY DIFFERING CONDITIONS

SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING

OFFICER'S REPRESENTATIVE.

2. ALL DEMOLITION MATERIAL, EQUIPMENT AND DEBRIS SHALL BE

REMOVED FROM THE SITE AND DISPOSED OF PROPERLY.

3. THE DEMOLITION CONTRACTOR SHALL REVIEW INSTALLATION

DRAWINGS FOR NEW MATERIALS AND BE FAMILIAR WITH LIMITS OF

DEMOLITION. THE CONTRACTOR SHALL KNOW AND UNDERSTAND

NEW MATERIAL INSTALLATION IN AREAS WHERE EXISTING

MATERIALS ARE REMOVED.

4. SEE STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL

DRAWINGS FOR ADDITIONAL INFORMATION.

5. DO NOT CUT INTO, REMOVE OR ALTER ANY STRUCTURAL MEMBER

UNLESS IT IS SPECIFICALLY NOTED OR SHOWN ON THE

STRUCTURAL DRAWINGS.

6. REMOVE EXISTING FLOOR FINISHES AND WALL BASE IN ALL AREAS.

PREPARE SUBFLOOR TO RECEIVE NEW FLOOR MATERIALS AS

SCHEDULED.

7. WHILE WORK UNDER THIS CONTRACT IS IN PROCESS, PROTECT

EXISTING BUILDING, GROUNDS AND CONTENTS INCLUDING

ADJACENT AREAS FROM DAMAGE OR HARM.

8. COORDINATE DEMOLITION WORK WITH ALL OTHER ELEMENTS OF

THE WORK TO ENSURE THAT THE BUILDING ENVELOPE REMAINS

WATERTIGHT AT ALL TIMES.

9. PROVIDE TEMPORARY SHELTER OR PORTALS AT ENTRANCES AND

EXIT DOORS AS MAY BE REQUIRED FOR PROTECTION FROM

FALLING DEBRIS OR OPEN TRENCHES. TEMPORARY PORTALS AND

WALKWAYS ARE TO MEET ALL CODE REQUIREMENTS FOR WIDTH

AND WALKING SURFACE CONTINUITY.

10. THE PROJECT REQUIRES PLANNED SCHEDULING OF THE

SEQUENCE OF PHASES, APPROVALS, COORDINATION WITH THE

CONTRACTING OFFICER'S REPRESENTATIVE AND DELIVERY OF

MATERIALS IN A TIMELY FASHION ARE REQUIRED TO ENSURE THAT

AREAS TO REMAIN OPERATIONAL AND IT'S CONTENTS ARE NOT

DAMAGED OR DISTURBED IN ANY WAY. THIS INCLUDES BUT IS NOT

LIMITED TO WATER LEAKING THROUGH OPENINGS EXPOSED BY

DEMOLITION OF WINDOW, ROOF, ETC.

KEYNOTES:

(KEYNOTE NUMBERS ARE UNIFORM ACROSS ALL SHEETS

AND SOME MAY NOT BE REQUIRED ON THIS SHEET)

29' - 0"

READY ROOM

E106

CLASSROOM

E105

MECH

E107

JANITOR'S

E104B

MEN'S RESTROOM

E104A

MEN'S LOCKER

ROOM

E104

WOMEN'S LOCKER

ROOM

E102

WOMEN'S

RESTROOM

E102A

ADMINISTRATION

E103

Room E100

VESTIBULE

E101

B.1

/2

/4

/2

A2

A1

A2

A20A20

TRU

E N

PLAN

NORTH

1 2 3

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IA

T

IO

N

N O

P R

O J E

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

4 5

US Army Corps of Engineers ® Louisville Distrct

C M

A

IO

C

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

P N

O A

N D

K K

O T

E L L O

S

D G

R A

H A

M

R J E

N N

IN

G

S

/7

/2

:5

:4

P M

C U s e rs \G ra h a m

D \D o c u m e n ts \1

N

F A

R S

A

R C

H v g ra h a m d

P H

B .r v t

ABD101

CORRECTED FINAL DESIGN SUBMITTAL

A R

C H

IT

E

C T

U R

A L D

E M

O L

IT

IO

N

P L A

N

R E

P L A

C E

M E

N T

F U

E L B

U L K

S T

O R

A G

E F

A C

IL

IT

Y H

Y D

R A

N T

R E

P A

IR

N

IA

G

A R

A F

A L L S

A R

S

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

-0

J O

B N

O

M

A Y

W Q

R -1

-D

-0

W Q

R -2

-F

-0

KEY # KEYNOTE DESCRIPTION

A1 REMOVE EXISTING DOOR, DOOR FRAME, AND DOOR

HARDWARE. PREPARE OPENING FOR CASED FRAME.

A2 REMOVE EXISTING WINDOW. INFILL WALL TO ALIGN

WITH EXISTING WALL.

A20 REMOVE EXISTING CANOPY AND STRUCTURAL

SUPPORTS. WHERE CANOPIES REMOVED CLEAN

BRICK FREE OF ALL CAULK AND SEALANT. NOTIFY

DESIGNER OF ANY DAMAGE TO BRICK AND MORTAR.

FULLY REPAIR AND PATCH ALL HOLES ASSOCIATED

WITH REMOVAL OF CANOPY.

SCALE: 1/4" = 1'-0"A1

DEMOLITION PLAN

SCALE: = 1'-0"

0 4 84

1. REFER TO SHEET A-001 FOR GENERAL NOTES.

2. SEE STRUCTURAL, MECHANICAL, PLUMBING, & ELECTRICAL

DRAWINGS FOR ADDITIONAL INFORMATION.

3. REFER TO ELECTRICAL & MECHANICAL DRAWINGS FOR THE

LOCATION OF ALL ELECTRICAL & MECHANICAL INCLUDING, BUT NOT

LIMITED TO LIGHTS, DIFFUSERS, AND DUCT WORK.

4. DIMENSIONS OF EXTERIOR WALLS ARE TO FACE OF BRICK,CMU

WALLS & INTERIOR WALLS ARE TO FACE CMU OR METAL STUD.

U.N.O.

5. PARTITION TYPE INDICATED WITH . SEE SHEET AB003 FOR

PARTITION TYPES.

6. DOORS INDICATED WITH . SEE SHEET AB601 FOR DOOR

SCHEDULE, TYPES, & DETAILS.

7. WINDOWS INDICATED WITH . SEE SHEET AB602 FOR WINDOW

SCHEDULE, TYPES, & DETAILS.

8. KEYNOTES INDICATED WITH .

9. CONSTRUCTION PROFESSIONAL SHALL LOCATE BLOCKING

BLOCKING AS REQUIRED FOR WALL MOUNTED EQUIPMENT.

10. PARTITIONS SHALL BE TYPE "A" (NO SUBSCRIPT), U.N.O.

SHEET NOTES:

WALL LEGEND

EXISTING CMU AND / OR STUD WALLS /

PARTITIONS TO REMAIN

NEW CMU AND / OR STUD WALLS /

PARTITIONS

NEW 1-HOUR RATED STUD WALL /

PARTITIONS

DEPRESSED SLAB. SEE STRUCTURAL.

KEYNOTES:

(KEYNOTE NUMBERS ARE UNIFORM ACROSS ALL SHEETS

AND SOME MAY NOT BE REQUIRED ON THIS SHEET)

E X

P A

N S

IO

N

F O

O T

P R

IN

T

STORAGE

LAB

READY ROOM

E106

A B

B

A B

A

A B

C

CLASSROOM

E105

MECH

E107

JANITOR'S

E104B

MEN'S RESTROOM

E104A

MEN'S LOCKER

ROOM

E104

WOMEN'S LOCKER

ROOM

E102

WOMEN'S

RESTROOM

E102A

ADMINISTRATION

E103

G3B

F0B

F3B

AB301

AB301

B4

A5 A4

D4 C4

A

B

104 103 E107

E105 E103

E104 E102

E104B

E101B E101A

MECH / ELEC

CLASSROOM

Room E100

VESTIBULE

E101

4' - 8 5/8"

6"

/8

/4

/4

F3B

EXPANSION FOOTPRINT

25' - 0"

EXISTING FOOTPRINT

29' - 0"

M8A3

A B B.1

B1

AB301

__________ B1

AB301

6"23' - 11 5/8"

/2

/2

/2

/4

/4

1' - 10"

6' - 4"3' - 2"

8"

15' - 0"

1G3A

A1

AB301

A1

AB301

-0' - 6"

ES1

ES2

1' - 5 5/8"3' - 4"

A4A4

A4A4

A3A3

A7

A6

A5

A5

A8

A7

A11

M8A

M8A3

A16

A17

A16

A18

A18

1' - 0"

A18

A19A19

TRU

E N

PLAN

NORTH

1 2 3

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IA

T

IO

N

N O

P R

O J E

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

4 5

US Army Corps of Engineers ® Louisville Distrct

C M

A

IO

C

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

P N

O A

N D

K K

O T

E L L O

S

D G

R A

H A

M

R J E

N N

IN

G

S

/7

/2

:4

:0

P M

C U s e rs \G ra h a m

D \D o c u m e n ts \1

N

F A

R S

A

R C

H v g ra h a m d

P H

B .r v t

AB101

CORRECTED FINAL DESIGN SUBMITTAL

F L O

O R

P L A

N

R E

P L A

C E

M E

N T

F U

E L B

U L K

S T

O R

A G

E F

A C

IL

IT

Y H

Y D

R A

N T

R E

P A

IR

N

IA

G

A R

A F

A L L S

A R

S

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

-0

J O

B N

O

M

A Y

W Q

R -1

-D

-0

W Q

R -2

-F

-0

KEY # KEYNOTE DESCRIPTION

A3 DEPRESSED SLAB. SEE STRUCTURAL.

A4 FURNITURE. SEE SHEET IF101.

A5 EXPANSION JOINT. SEE C1/AB501.

A6 THRESHOLD. SEE A4/AB502 FOR TRANSITION

DETAIL.

A7 INFILL MASONRY WALL SECTIONS INDICATED WITH

BLOCKS EQUAL IN DEPTH TO THE EXISTING DEPTH

AND BRICK VENEER TO MATCH EXISTING WALL.

A8 FUME HOOD. SEE MECHANICAL.

A11 ALUMINUM PREFINISHED DOWNSPOUT 4" X 4"

A16 FLOOR DRAIN. SEE PLUMBING.

A17 EMERGENCY SHOWER / EYE WASH STATION. SEE

PLUMBING.

A18 MECHANICAL EQUIPMENT. SEE MECHANICAL.

A19 FLOOR BOXES. SEE IB-101 AND ELECTRICAL.

SCALE: 1/4" = 1'-0"A1

FLOOR PLAN

SCALE: = 1'-0"

0 4 84

SHEET NOTES:

1. ALL MATERIAL EXPOSED WITHIN A RETURN AIR CEILING PLENUM

SHALL BE NONCOMBUSTIBLE OR SHALL BE LIMITED IN

COMBUSTIBILITY AND HAVE A FLAME SPREAD INDEX OF 25 MAX.

AND A SMOKE- DEVELOPMENT INDEX OF 50 MAX., PER ASTM E84.

2. IN LATRINES, TOILETS, LOCKER ROOMS AND JANITOR CLOSETS ALL

GYPSUM BOARD CEILINGS SHALL BE WATER RESISTANT GYPSUM

BOARD.

3. ALL CEILING MOUNTED DEVICES SHALL BE CENTERED IN BOTH

DIRECTIONS IN ACOUSTICAL CEILING PANELS U.N.O. CENTER

SPRINKLER HEADS IN ACOUST. CEILING PANELS WHERE THEY

OCCUR - COORDINATE THE LOCATION OF THE SPRINKLER HEADS

WITH OTHER CEILING FIXTURES AND EQUIPMENT IN ALL CEILING.

ENSURE THAT A SYMMETRICAL AND BALANCED ARRANGEMENT IS

INSTALLED. CONTRACTING OFFICER IS TO REVIEW INSTANCE OF

NON-EQUAL SPACING PRIOR TO INSTALLATION.

4. CEILING HEIGHTS INDICATED (I.E. 9'-0") ARE RELATIVE TO THE

FINISH FLOOR ELEVATION OF THE ROOM FOR WHICH THEY ARE

INDICATED.

5. CEILING GRIDS SHALL BE ORIENTED WITHIN SPACES AS SHOWN,

U.N.O. FULL TILE (FT) WHERE INDICATED, SHALL ABUT DESIGNATED

WALL. LIMIT PARTIAL PANELS TO NO LESS THAN 6".

6. DEVICES HAVE BEEN SHOWN FOR COORDINATION PURPOSES. ALL

DEVICES MAY NOT BE SHOWN.

7. THE CONTRACTOR SHALL ENSURE THE INSTALLATION OF ALL

DEVICES INDICATED ON THE ENGR. DWG. SEE MECHANICAL,

ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS FOR

ITEMS NOT SHOWN ON REFLECTED CEILING PLANS. CONTACT THE

ARCHITECT IF ANY CONFLICTS OCCUR.

8. AT WALLS WITH SOUND ATTENUATION BLANKETS PROVIDE SOUND

ATTENUATION BLANKETS ON CEILING TO 2'-0" ON BOTH SIDES OF

WALL EXCEPT AT WALLS WITH SOUND ATTENUATION BLANKETS

EXTENDING TO STRUCTURE.

9. COORDINATE ACCESS PANELS WITH MECHANICAL BALANCING

DAMPER LOCATIONS.

S

P

CEILING MOUNTED MASS

NOTIFICATION SPEAKER, ONE

WAY TYPE

CEILING MOUNTED PUBLIC

ADDRESS SPEAKER, ONE WAY

TYPE

OCCUPANCY SENSOR

EXT. WALL MOUNTED FIXTURE

REFLECTED CEILING PLAN LEGEND

1' X 4' PENDANT LIGHT FIXTURE

OPEN TO STRUCTURE

24" X 24" MECH. EXHAUST

24" X 24" MECH. DIFFUSERS

EMERGENCY DOWNLIGHT- CENTER IN

ACOUST. CEILING PANELS, TYP., U.N.O.

WALL MOUNTED EXIT SIGN

CEILING MOUNTED EXIT SIGN

2' X 4' FLUORESCENT LIGHT FIXTURE

2' X 4' EMERGENCY LIGHT FIXTURE

A

1' X 4' EMERGENCY PENDANT LIGHT FIXTURE

2'-0" x 4'-0" ACOUSTICAL CEILING SYSTEMB

DOWNLIGHT- CENTER IN ACOUST. CEILING

PAN…

This is the start of the file's text. The full file is on GovTribe.