Hydrant Fuel Replacement at Niagara ARS, Niagara Falls
Solicitation number
W912QR21R0023
Issued by

About this file

This document provides details for a federal construction solicitation for fuel hydrant repair at Niagara Falls Air Reserve Station in New York. The solicitation seeks bids for construction services to replace an existing bulk fuel storage facility and repair hydrants, with an estimated cost between $10 million and $25 million. The North American Industry Classification System code for this project is 237120. The size determination for applicable small business categories is $39.5 million. The solicitation will utilize the HUBZone 10% price evaluation preference and is a full and open competition with no contract award until appropriated funds are available. The Department of the Army Corps of Engineers Engineering District Louisville is the issuing agency. Technical inquiries should be submitted through the Bidder Inquiry function on ProjNet, with no contract award date provided.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 5

A

B

C

D

SHEET ID

R E

P L

A C

E M

E N

T

F

U E

L

B

U L

K

S

T O

R A

G E

F

C

I L

I T

Y

H Y

D R

A N

T

R

E P

A I R

N I A

G A

R

L

L S

S

U S

A

R M

Y

C

O R

P

O

E

N G

I N

E E

R S

L O

U I S

V I L

D

I S

T R

I C

T

L O

U I S

V I L L E

K

E N

T U

C K

Y

S I Z

E

F I

N

M

E

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

C T

P R

O J E

U M

B E

R

D A

T E

D E

S C

R I P

T I O

N M

A R

K

I S

S U

E

D

A T

E

A

J U

A N

S I

D

C M

A I O

C C

O

F I L

E

P

A T

H

X

F

Y

C

B

M

C

A D

E

P

L O

T T

Y

W

A T

S O

N

C

A R

L

T

E

CERTIFIED FINAL DESIGN SUBMITTAL

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER

OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

R

K W

N

E

S

U I T

E

P E

A C

H T

R E

E

C

O R

N E

R S

G

A

P H

O N

E

F A

X

P O

J

US Army Corps of Engineers ®

Louisville Distrct

A M

E N

D M

E N

T

#4/0 BARE COPPER GROUND CONDUCTOR

#1/0 BARE COPPER GROUND CONDUCTOR UNLESS INDICATED OTHERWISE

LIGHTNING PROTECTION AIR TERMINAL

EARTH GROUND ELECTRODE

CR

TDR

MC

MOTOR STARTER COIL

TIME DELAY RELAY COIL

CONTROL RELAY COIL

MOTOR RATED DISCONNECT SWITCH WITH THERMAL OVERLOADS, SINGLE OR DOUBLE POLE

AS REQUIRED, MT ON UNIT UNLESS INDICATED OTHERWISE

GFI = GROUND FAULT INTERRUPTER; WP = WEATHER PROOF;

EXP = EXPLOSION PROOF; P = RUN PILOT LIGHT

JUNCTION BOX; BOX NUMBER ADJACENTJ

EQUIPMENT AS INDICATED

M

S

MOTOR, HP AS INDICATED

CONTROL STATION, TYPE AS INDICATED: S/S = START/STOP, PRL = PUMP RUN LIGHT

SUBSCRIPTS

LEGEND:

MCC MOTOR CONTROL CENTER

VA VOLT AMPERES

WATTS OR WIDTH OR WIRE

WATTHOUR DEMAND METER

WEATHER PROOF

XFMR

Z

W

WHDM

WP

TRANSFORMER

IMPEDANCE

PVC POLYVINYL CHLORIDE

SURGE ARRESTOR

UNDERWRITER'S LABORATORIES

SINGLE POLE DOUBLE THROW

SINGLE POLE SINGLE THROWSPST

TW PR

UL

V

TWISTED PAIR

VOLTS

SA

SPEC

SPDT

SHLD

R

SPECIFICATIONS

SHIELDED

RADIUS

POUNDS PER SQUARE INCH

NORMALLY CLOSED

MOUNT OR MOUNTED

MAIN LUGS ONLY

MANUFACTURERS ASSOCIATION

NATIONAL ELECTRICAL

NATIONAL FIRE PROTECTION ASSOCIATION

NATIONAL ELECTRICAL SAFETY CODE

NORMALLY OPEN TIMED CLOSED

NESC

PH

PSI

PNL

NOTC

P

NFPA

NTS

PHASE

PANELBOARD

NOT TO SCALE

POLES

NC

NEMA

N

MT OR MTD

MLO

NEUTRAL

MAIN CIRCUIT BREAKER

KILOVOLT - AMPERES

KW

KVA

MCB OR MB

KILOWATTS

ABBREVIATIONS:

ABOVE FINISHED FLOOR

ALTERNATING CURRENT

ABOVE FINISHED GRADE

AMPERES INTERRUPTING CAPACITY

AUTOMATIC TANK GAUGING

AIR HANDLING UNIT

CIRCUIT BREAKER

AIC

CKT

COM

ATG

BLDG

CB

C

CIRCUIT

COMMON

CONDUIT

BUILDING

AC

AFF

AL

AFG

AHU

A OR AMP

ALUMINUM

AMPERES

RACEWAY EXPOSED

RACEWAY CONCEALED BELOW SLAB/GRADE

CONDUIT AND CONDUCTOR TAG;

HANDHOLE, DESIGNATION AS INDICATED

ELECTRICAL CONNECTION

TRANSFORMER

DISCONNECT SWITCH

THERMAL OVERLOAD RELAY CONTACT

CIRCUIT BREAKER

HH-1

O.L.

3-POSITION SELECTOR SWITCH

OVERLOAD HEATER

PILOT LIGHT (G=GREEN, R=RED, A=AMBER)

OR

OFF

oox

AUTO

xoo

R

HAND

PAD MOUNTED TRANSFORMERPMT

CP

CT

CATHODIC PROTECTION

CURRENT TRANSFORMER

DEPTH

EMERGENCY FUEL SHUT OFF

EMERGENCY

DC

D

DISC

DPST

EC

EFSO

E

ESO

DPDT

EXISTING

ELECTRICAL

FUEL PUMP

FLOW SWITCH

FUELS CONTROL CENTER

FIBER OPTIC

EXIST OR EX.

EXP

EUH

ELEC

FS

FP

FCC

FO

EXPLOSION PROOF

DIRECT CURRENT

EMPTY CONDUIT

DISCONNECT SWITCH

EMERGENCY SHUT OFF

ELECTRIC UNIT HEATER

DOUBLE POLE DOUBLE THROW

DOUBLE POLE SINGLE THROW

GROUND

HEIGHT

FWE

G OR GND

FVNR

H OR HT

GFCI

HP

HID

HORSEPOWER

FURNISHED WITH EQUIPMENT

HIGH INTENSITY DISCHARGE

GROUND-FAULT-INTERRUPTER

FULL VOLTAGE NON-REVERSING

FTP FUEL TRANSFER PUMP

CU COPPER OR CONDENSING UNIT

CONTROLCNTL

C1D1 CLASS 1, DIVISION 1

HTR HEATER

PWR POWER

TWISTED SHIELDED PAIRTSP

NATIONAL ELECTRICAL CODENEC

MTR MOTOR

TYP TYPICAL

GROUND ROD 3/4" X 10'-0" COPPERCLAD, 12" BELOW FINISHED GRADE.

LIGHTNING PROTECTION CONDUCTOR

MOTOR OPERATED VALVEMOV

O/WS OIL/WATER SEPARATOR

LSH LEVEL SWITCH HIGH

LSHH LEVEL SWITCH HIGH-HIGH

LSL LEVEL SWITCH LOW

LSLL LEVEL SWITCH LOW-LOW

FUSE

E/G ENGINE/GENERATOR

SOLENOID

TELEPHONE TERMINAL BOARDTTB

KEYED HAND-AUTO SELECTOR SWITCH AND RUN LIGHT

HA

S

NORMALLY CLOSED TIMED OPENNCTO

HANDHOLEHH

NORMALLY OPENNO

3-POLE DISCONNECT SWITCH, (DISCONNECT SIZE/POLES/NEMA ENCLOSURE)

20/3/7

J

J OR JB JUNCTION BOX

KCM KILO CIRCULAR MILS

OTT OVER TEMP THERMOSTAT

FLEXIBLE METAL CONDUIT (SEE SPECIFICATION

FOR AREAS REQUIRING LIQUIDTIGHT)

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION

INST INSTANTANEOUS

SURGE PROTECTIVE DEVICESPD

PROGRAMMABLE LOGIC CONTROLLERPLC

LP

G

G4

XX

ZZ

GROUND TEST WELL

RGS RIGID GALVANIZED STEEL

C1D2 CLASS 1, DIVISION 2

INSTRUMENT TAG AS FOLLOWS:

XX-INDICATES TYPE

ATG=AUTOMATIC TANK GAUGE

FSL=FLOW SWITCH

LD=LEAK DETECTOR

ZS=LIMIT SWITCH

LSH=HIGH LEVEL SWITCH

LSHH=HIGH HIGH LEVEL SWITCH

LSL=LOW LEVEL SWITCH

LSLL=LOW LOW LEVEL SWITCH

LT=LEVEL TRANSMITTER

SV=SOLENOID VALVE

DPS= DIFFERENTIAL PRESSURE SENSOR

PIT = PRESSURE INDICATING TRANSMITTER

PS = PRESSURE SENSOR

ZZ-INDICATES NUMBER CORRESPONDING TO I/O DIAGRAMS

GENERAL NOTES:

1. ALL NEW WORK IS INDICATED IN A BOLD LINESTYLE AND/OR IS LABELED AS SUCH ON PLANS OR

DETAILS THAT SHOWS NEW WORK TO BE PERFORMED TO, IN, OR AROUND EXISTING EQUIPMENT

AND INFRASTRUCTURE.

2. PROJECT DESIGN AND EXECUTION SHALL CONFORM TO THE LATEST VERSIONS OF:

(A) NEC (NATIONAL ELECTRICAL CODE)

(B) NESC (NATIONAL ELECTRICAL SAFETY CODE)

(C) APPLICABLE LOCAL, STATE AND FEDERAL CODES

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH ALL OTHER TRADES BEFORE ANY

INSTALLATION IS MADE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SPACE

REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE AND CORRECT ROUGH-IN LOCATIONS

OF ELECTRICAL CONNECTIONS.

4. DRAWINGS ARE IN GENERAL DIAGRAMMATIC IN NATURE. FIELD ADJUST CONDUIT AND TRAY

ROUTING BASED ON COORDINATION WITH OTHER NEW AND EXISTING UTILITIES AND EQUIPMENT.

NOT ALL COMPONENTS, CONDUITS, AND EQUIPMENT ARE SHOWN IN ALL VIEWS. THE

CONTRACTOR SHALL MAKE USE OF THE ENTIRE SET OF DRAWINGS, REQUIREMENTS, AND

SPECIFICATIONS IN ORDER TO INCLUDE ALL COMPONENTS NECESSARY TO CONSTRUCT A FULLY

OPERATIONAL SYSTEM.

5. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS.

6. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED,

PUBLISHED LITERATURE.

7. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR

REPLACEMENT.

8. ALL CONDUCTORS AND CABLES SHALL BE COPPER. REFER TO SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS FOR CONDUCTORS AND CABLES.

9. PROVIDE THE NECESSARY COMPONENTS TO ALLOW THE TERMINATION OF CONDUCTORS WHICH

HAVE BEEN OVERSIZED DUE TO VOLTAGE DROP ON STANDARD LUGS, CONNECTIONS, AND

TERMINATIONS. TRIMMING OF WIRES AT TERMINATIONS SHALL NOT BE PERMITTED.

10. ALL CONTROL PANELS, CUSTOM OR STANDARD, SHALL BE SHOP FABRICATED AND ASSEMBLED.

NO FIELD ASSEMBLED PANEL WILL BE ACCEPTABLE.

11. THE PROJECT ENCOMPASSES BOTH EXISTING AND NEW COMPONENTS AND DEVICES. NEW

EQUIPMENT, CONDUITS, COMPONENTS, WIRES, CONDUCTORS, ETC ARE SHOWN IN BOLD.

EXISTING ITEMS ARE SHOWN IN GRAY OR SHADED COLOR.

12. PRIOR TO ANY CONSTRUCTION ACTIVITIES, CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS

OF ALL UNDERGROUND UTILITIES IN THE AFFECTED AREAS. MAINTAIN EXISTING UTILITIES AND

PROTECT FROM DAMAGE THROUGHOUT THE ENTIRE DURATION OF CONSTRUCTION ACTIVITIES.

13. EXISTING ELECTRICAL WORK NOT SHOWN OR SHOWN IN GRAY SHALL BE REUSED FOR THE NEW

SYSTEM AND SHALL REMAIN. SHOULD EXISTING ELECTRICAL POWER, LIGHTING, CONTROL,

INSTRUMENTATION, OR AUXILIARY CIRCUIT, FEEDER, OR EQUIPMENT BE SEVERED,

DISCONNECTED, DAMAGED, AND/OR DEMOLISHED IN THE PROCESS OF CONSTRUCTION UNLESS IT

IS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DEMOLISHED, THEN SAID CIRCUIT,

FEEDER, OR EQUIPMENT SHALL BE RESTORED TO THE ORIGINAL, FIRST CLASS CONDITION. THE

RESTORATION SHALL INCLUDE REROUTING, RELOCATION, RECONNECTION, AND/OR

REPLACEMENT. SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND SHALL BE

PERFORMED AT NO ADDITIONAL COST TO THE GOVERNMENT.

14. TEST WIRING TO VERIFY THAT NO SHORT CIRCUITS OR ACCIDENTAL GROUNDS EXIST. PERFORM

INSULATION RESISTANCE TESTS ON WIRING NO. 12 AWG AND LARGER DIAMETER USING

INSTRUMENT WHICH APPLIES VOLTAGE OF APPROXIMATELY 500 VOLTS TO PROVIDE DIRECT

READING OF RESISTANCE. MINIMUM RESISTANCE: 100,000,000 OHMS. ALL WIRING THAT FAILS THE

TEST SHALL BE REPLACED AND RETESTED. ALL TESTING SHALL BE PERFORMED ON BOTH

EXISTING AND NEW WIRING.

15. THE TERM PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK, AND IS

HEREBY DEFINED TO REQUIRE THE CONTRACTOR TO STORE, FURNISH, INSTALL, MOUNT,

CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS APPURTENANCES TO MAKE

ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THE DRAWINGS AND SPECIFICATIONS.

16. CONTRACTOR IS FREE TO USE ANY PRODUCT WHICH MEETS THE GOVERNMENT'S MINIMUM

REQUIREMENTS AND NOT IN CONFLICT WITH OTHER CONTRACT PROVISIONS. UNLESS INDICATED

OTHERWISE ON THE PLANS OR SPECIFICATIONS (E.G. SOLE SOURCE), ALL LISTED EQUIPMENT

MUST COMPLY WITH THE DOD AW 78-24-28 TYPE III STANDARDS AND UFC 3-460-01. THE ONLY

EQUIPMENT TO BE EXEMPT FROM THIS IS THE SIMPLEX FIRE ALARM PANEL, AND THE EXISTING

PCP PANEL TO BE REFURBISHED FOR THIS PROJECT.

17. CONTRACTORS ARE FREE TO USE ANY PRODUCT WHICH MEETS THE GOVERNMENT'S MINIMUM

REQUIREMENTS AND NOT IN CONFLICT WITH OTHER CONTRACT PROVISIONS. UNLESS INDICATED

OTHERWISE ON THE PLANS OR SPECIFICATIONS (E.G. SOLE SOURCE), ALL LISTED

MANUFACTURERS ARE THE BASIS OF DESIGN. FOR THESE BASIS OF DESIGN PRODUCTS, OTHER

MANUFACTURERS MAY BE SUBSTITUTED AS LONG AS THE STANDARD OF QUALITY AND

CHARACTERISTICS OF THE SUBSTITUTED MANUFACTURER MEET OR EXCEED THE STANDARD OF

QUALITY AND CHARACTERISTICS OF THE BASIS OF DESIGN.

M

S

TIME DELAY (NC & NO)

TEMPERATURE SWITCH

SOLID STATE SOFT STARTERSSSS

BPCV BACK PRESSURE CONTROL VALVE

PCV PRESSURE CONTROL VALVE

D/FV DEFUEL/FLUSH VALVE

PCP PUMP CONTROL PANEL

HLV HIGH LEVEL VALVE

HLCV HIGH LEVEL CONTROL VALVE

I.S. INTRINSICALLY SAFE

TIME DELAY RELAYTDR

PB PULL BOX

S/S START/STOP

DM DAMPER MOTOR FOR THE LOUVER

T THERMOSTAT

HORN/STROBE

PULL BOX; BOX NUMBER ADJACENTP

BRK BREAKER

LDS LEAK DETECTION SYSTEM

COMM COMMUNICATION(S)

GROUND CABLE CONNECTION

END OF LINEEOL

PENDANT MOUNTED LIGHT FIXTURE, REFER TO FIXTURE SCHEDULE ON EP503.

FILTER SEPARATOR CONTROL VALVEFSCV

KEYED INTERLOCK

K

N.C. & N.O. FLOW SWITCH

EL EXISTING EMERGENCY LIGHT

#6/0 BARE COPPER GROUND CONDUCTOR

G6

THREE WAY SWITCH, DOUBLE POLE

S

SEE EP609, EP610, AND EP611

N.C. & N.O. CONTACT

WALL MOUNTED EXIT SIGN LIGHT FIXTURE, REFER TO FIXTURE SCHEDULE ON EP-503

LIGHT FIXTURE (WITH POLE AS INDICATED), SEE FIXTURE SCHEDULE ON EP-503.

B

W

T

GENERATORG

CT

CT COIL

CT

LIMIT SWITCH

EMERGENCY SWITCH

AUXILIARY RELAYCR

PAD MOUNTED UTILITY TRANSFORMER

CXXX

DISCONNECT SWITCH

E L

E C

T R

I C

G

E N

D

A

B B

R E

V I A

T I O

N S

A N

D

G

E N

E R

T

E S

E-001

G

S

A N

T I A

G O

V

M

A L O

Y

B

C

A R

P E

N T

E R

E d w g

A

M E

N D

M E

W

2Q R

R

-0

XXXX

X

X

X

X

X

X

X X

X X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X X

X X

X X

X X

X X

X

X

XXXX

X X

X X

X X

X X

X X

X X

X X

X

X

X X

X

X

X

X

U U

U U

S

T

1 2 3 4 5

A

B

C

D

SHEET ID

R E

P L

A C

E M

E N

T

F

U E

L

B

U L

K

S

T O

R A

G

C

I L

I T

Y

H Y

D R

A N

T

R

E P

A I R

N I A

G A

L

S

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

L O

U I S

V I L

S

T R

I C

T

L O

U I S

V I L L E

K

E N

T U

C K

Y

S I Z

E

F I

M

E

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

P R

O J E

M

B E

R

D A

T E

D E

S C

R I P

T I O

N M

A R

K

I S

S U

E

D

A T

E

A

J U

A N

S I

D

C M

A I O

C C

O

F I

T

H

X

F

Y C

M

C

A D

F

M

O

T T

M

I O

C C

O

C

H R

I S

T I

T

E

CERTIFIED FINAL DESIGN SUBMITTAL

IT IS A VIOLATION OF ARTICLE 7209.2 FOR ANY PERSON TO ALTER THIS DOCUMENT IN ANY WAY UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR LAND SURVEYOR. IF THE PLAN IS ALTERED IN ANY WAY THE ALTERING ENGINEER

OR LAND SURVEYOR SHALL SEAL THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY:" FOLLOWED BY THEIR SIGNATURE, THE DATE OF THE ALTERATION, AND A SPECIFIC DESCRIPTION OF EACH ALTERATION.

R

K W

N

E

S

U I T

E

P E

A C

H T

R E

E

C

O R

N E

R S

G

A

P H

O N

E

F A

X

P O

J

US Army Corps of Engineers ®

Louisville Distrct

A M

E N

D M

E N

T

SHEET NOTES:

1. SEE FM001 FOR MECHANICAL GENERAL NOTES, LEGEND,

AND ABBREVIATIONS.

2. THIS SHEET IS PART OF A MULTI-DISCIPLINE, MULTI-SHEET

SET OF CONSTRUCTION PLANS AND MUST BE READ AND

COORDINATED WITH THE FULL SET TO BEST ENSURE

PROPER INTERPRETATION.

3. ALL WORK MUST COMPLY WITH APPLICABLE FEDERAL,

STATE, AND LOCAL CODES, SPECIFICATIONS AND

REQUIREMENTS. ALL NECESSARY LICENSES AND PERMITS

MUST BE OBTAINED BY THE CONTRACTOR AT THEIR

EXPENSE.

4. INDICATES PIPING TO BE ABANDONED IN PLACE AND

SLURRY FILLED.

5. DEMOLITION WORK SHOWN IS ASSOCIATED WITH THE TANK

DEMOLITION AND ABANDONMENT OF EXISTING FUEL BULK

STORAGE TRANSFER LINE BID OPTION (CLIN 0009).

DEMOLITION WORK ASSOCIATED WITH THIS BID OPTION

SHALL NOT BEGIN UNTIL BASE BID (CLIN 0001 AND CLIN 0002)

WORK HAS BEEN COMMISSIONED AND ACCEPTED BY THE

GOVERNMENT. IF BID OPTION CLIN0008 IS EXECUTED, IT

SHALL BE COMMISSIONED AND ACCEPTED BY THE

GOVERNMENT PRIOR TO COMMENCEMENT OF THE

DEMOLITION WORK ASSOCIATED WITH THIS DRAWING.

CONTRACTOR SHALL REQUEST WRITTEN AUTHORIZATION

FROM THE CONTRACTING OFFICER REPRESENTATIVE TO

PROCEED WITH WORK ASSOCIATED WITH BID OPTION CLIN

0009.

⎔ KEYNOTES:

1. SEE CIVIL 200 SERIES DRAWINGS FOR EXISTING 6" CC / 8"

FRP TRANSFER PIPELINE ABANDONMENT AND SLURRY FILL

DETAILS.

SCALE: 1" = 30'

0 15' 30' 60' 90'

A1

EX/DEMO SITE PLAN - BULK FUEL FARM

E X

D

E M

O

S

I T

E

P

L A

N

B

U L

K

F

U E

L

F

A R

M

FM104

C B

A R

R

S R

I C

H A

R D

S

B

E

N T

R E

K I N

F M d w g

A1

FM105

EX/DEMO ENLARGED PLAN

OFFLOAD POSITIONS AND

TRANSFER PUMP HOUSE

A1

FM106

EX/DEMO ENLARGED PLAN

TANK A AND FILLSTANDS

A1

FM107

EX/DEMO ENLARGED PLAN

TANK C

TANK C

TANK A

U T

Z

IG

D R

K

I N

R

O

T R

PLAN

NORTH

A M

E N

D M

E N

T

A M

E N

D M

E N

T

W

2Q R

R

-0

E-001
XX E-001
FM104
XX FM104
XX FM104