This document provides details on an upcoming federal contract opportunity for construction of a new VA medical center campus in Louisville, KY. The U.S. Army Corps of Engineers Louisville District plans to issue a request for proposal for construction services over $500 million to replace aging facilities at the Robley Rex VAMC. The project scope includes a new 104 bed hospital, parking structure for 2,600 cars, campus infrastructure, central utility plant, laundry facility, roadways, and landscaping. Optional line items include additional parking, a maintenance building, fencing, and a photovoltaic system. The contract duration is 1,554 calendar days from notice to proceed. The solicitation is anticipated for release on December 3, 2020 and will utilize a best value evaluation considering past performance, management, schedule, small business participation, and price factors. The point of contact for questions is the listed contracting specialist.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2'- 0"
4'-0" 1'-6" 1'-6"
1'- 0"
M
IN
.5'- 0"
M
AX
3'- 0"
M
IN
#6@12" CONT, EF
#6@12"
DOWELS X
#6@12" DOWELS X
4" DIA. PERFORATED
DRAIN PIPE, AASHTO
M252, TYPE M; SEE
GRADING PLANS FOR
CONNECTIONS TO
STORM SYSTEM
#6@12" CONT, T&B
#6@12" X
#6@12" X
TOP OF WALL (TOW) ELEVATION
FINISH GRADE (FG)
ELEVATION
TOP OF FOOTING
(TOF) SEE PLAN &
ELEVATION
FG EL
TYPE II GEOTEXTILE
WRAP 1:2 (H:V)
DRAINAGE FILL
DAMPROOFING
1'-0"
UNDISTURBED
EARTH
3" C
OV
ER
DAMPROOFING
4"
M
IN
FILL
TOPSOIL
2" R TYP.
LIGHTLY SANDBLAST
ALL EXPOSED WALL
SURFACES 1
1'- 6"
4'-6" 1'-6" 1'-0"
1'- 0"
M
IN
3'- 6"
M
AX
2'- 6"
M
IN
FG EL
#4@12" CONT, EF
#4@12" O.C.
#4@12"
DOWELS X
#4@12"O.C.
3" C
OV
ER
TOP OF WALL (TOW) ELEVATION
FINISH GRADE (FG)
ELEVATION
4" DIA. PERFORATED DRAIN PIPE,
AASHTO M252, TYPE M; SEE
GRADING PLANS FOR CONNECTIONS
TO STORM SYSTEM
DRAINAGE FILL
DAMPROOFING
#4@12" CONT, T&B
TOP OF FOOTING
(TOF) SEE PLAN &
ELEVATION
UNDISTURBED EARTH
TYPE II GEOTEXTILE
WRAP 1:2 (H:V)
4" M
IN
DAMPROOFING
FILL
TOPSOIL
2" R TYP.
LIGHTLY SANDBLAST
ALL EXPOSED WALL
SURFACES 1
1'- 6"
3'-6" 1'-6"
(1'-0" FOR WALL 7)
1'-0"
1'- 0"
M
IN
2'- 6"
M
AX
2'- 6"
M
IN
FG EL
#4@12" CONT, EF
#4@12"
DOWELS X
#4@12"
DOWELS X
#4@12" CONT, T&B
#4@12" X
TOP OF WALL (TOW) ELEVATION
FINISH GRADE (FG)
ELEVATION
DRAINAGE FILL
DAMPROOFING
TOP OF FOOTING
(TOF) SEE PLAN &
ELEVATION
UNDISTURBED EARTH
4" DIA. PERFORATED DRAIN PIPE,
AASHTO M252, TYPE M; SEE
GRADING PLANS FOR CONNECTIONS
TO STORM SYSTEM
3" C
OV
ER
TYPE II GEOTEXTILE WRAP 1:2 (H:V)
DAMPROOFING
4" M
IN
FILL
TOPSOIL
2" R TYP.
LIGHTLY SANDBLAST
ALL EXPOSED WALL
SURFACES
CENTRAL UTILITY PLANT
NORTH PARKING STRUCTURE
2" DIA x 18" LONG EPOXY COATED
DOWEL @ 12" O.C. CENTERED IN
CONCRETE POUR, GREASE END IN
SLEEVE
CONCRETE WALL
SLEEVE
2" SEALED EXPANSION JOINT
6"
TOP OF WALL - ELEVATION
VARIES
1'- 6"
2" DIA x 18" LONG EPOXY COATED
DOWEL @ 12" O.C. CENTERED IN
CONCRETE POUR, GREASE END IN
SLEEVE
CONCRETE WALL
SLEEVE
2"SEALED EXPANSION JOINT
4"
WALL REINFORCING
4"
3" 3"
NEW PLACEMENTPREVIOUS PLACEMENT
NOTES:
1. DO NOT LAP REINF AT WCJ.
2. IF TREATED AS WCLJ STOP/CUT ALTERNATE HORIZ REINF AT EF.
3. IF TREATED AS WCLJ, BOND BREAKER NOT REQUIRED.
W
AL
L T
HK
PLAN / SECTION
CL WCLJ
NOTES:
1. DO NOT LAP REINF AT WCLJ.
2. STOP/CUT ALTERNATE HORIZ REINF AT WCJ EF.
W
AL
L T
HK
TH
K/
G
RO
OV
E (T
YP
2" GROOVE (TYP)
SEALANT JOINT
PROVIDE 6" WIDE CONT
PVC WATER STOP
VERT REINF
HORIZ REINF, SEE NOTE 2
CONT KEYWAY
SURFACE TREATED W/BOND BEAKER
(CURING COMPOUND, ASPHALTIC
EMULSION OR FORM OIL), SEE NOTE 3
RETAINING SIDE
EXPOSED SIDE
RETAINING SIDE
EXPOSED SIDE
2.00' 2.00'
TH
K/
G
RO
OV
E (T
YP
2" GROOVE (TYP)
2.00' 2.00'
CONTROL GROOVE
HORIZ REINF, SEE NOTES 1 AND 2
VERT REINF
SEALANT JOINT
PLAN / SECTION
ELEVATION / SECTION
PLAN / SECTION
t h r e e q u a r t e r s i n c h o n e f o o t o n e i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t
EM RA, JY, SH
URS | SMITHGROUP JOINT VENTURE
T 313.983.3600 F 313.983.3636
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320
TRUE NORTH
PROJECT NORTH
97 8654321 o n e s i x t e e n t h i n c h o n e f o o t o n e t h i r t y s e c o n d t h i n c h o n e f o o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
www.urscorp.com | www.smithgroupjjr.com
CONSTRUCTION DOCUMENTS
20NOV2020
USACE P2 No. 453413
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION OrientationSeal
20NOV2020
PHA CERTIFIED FINAL 20NOV2020
Mark
CS505
CONCRETE RETAINING
WALLS
CONCRETE RETAINING WALL, 5 FT MAX3 SECTION 1/2" = 1'-0"
CONCRETE RETAINING WALL, 3.5 FT MAX4 SECTION 1/2" = 1'-0"
CONCRETE RETAINING WALL, 2.5 FT MAX5 SECTION 1/2" = 1'-0"
NOTES:
1. REFER TO WALL ENLARGEMENT PLANS AND ELEVATIONS ON SHEETS CS511 TO CS514.
2. REFER TO WALL ELEVATIONS ON SHEETS CS511 TO CS514 FOR SECTION LOCATIONS.
3. PROPOSED GRADES SHOWN ON SHEETS CS511 TO CS514 ARE FINAL, PHASE B, GRADES.
CONSTRUCT AND REFER TO MASS GRADING PLANS, SHEETS CG104 TO CG106 FOR PHASE A
GRADES.
4. REFER TO SHEET CS101 FOR GEOTEXTILE MATERIALS AND APPLICATION TABLE.
WALL 5 OVERALL PLAN10 PLAN 1" = 30'
PROPERTY LINE
PROPOSED RETAINING WALL
DETAILS 1, 2 AND 6 NOT USED
DOWELLED EXPANSION JOINT AT WALL7 ELEVATION / SECTION, PLAN / SECTION 1" = 1'-0"
VERTICAL CONSTRUCTION JOINT (WCJ) AT WALL8 PLAN / SECTION 1" = 1'-0"
VERTICAL CONTROL JOINT (WCLJ) AT WALL9 PLAN / SECTION 1" = 1'-0"
10FEB2021AMENDMENT 0007 1
CERTIFIED FINAL
W
2Q R
R
_P ha se A-t h r e e q u a r t e r s i n c h o n e f o o t o n e i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t
EM RA, JY, SH
URS | SMITHGROUP JOINT VENTURE
T 313.983.3600 F 313.983.3636
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320
TRUE NORTH
PROJECT NORTH
97 8654321 o n e s i x t e e n t h i n c h o n e f o o t o n e t h i r t y s e c o n d t h i n c h o n e f o o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
www.urscorp.com | www.smithgroupjjr.com
CONSTRUCTION DOCUMENTS
20NOV2020
USACE P2 No. 453413
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION OrientationSeal
20NOV2020
PHA CERTIFIED FINAL 20NOV2020
Mark
CU234
UNDERGROUND STORAGE - TANK 4
UNDERGROUND DETENTION - TANK 4 DIAGRAMMATIC LAYOUT1 N.T.S.
TANK 4 - TYPICAL CONSTRUCTION SECTION2 N.T.S.
TANK 4 - SYSTEM UNIT LAYOUT PLAN3 N.T.S.
TANK 4 - BASE SLAB LAYOUT PLAN4 N.T.S.
LINE EXCAVATION WITH
TYPE III GEOTEXTILE
LINE EXCAVATION WITH
TYPE III GEOTEXTILE
BASIS OF DESIGN PRODUCT
REFER TO NOTES 7 AND 8 ON SHEET CU120
AMENDMENT 0007 1 10FEB2021
CERTIFIED FINAL
W
2Q R
R
_P ha se A-
2-YEAR ORIFICE ELEVATION
STRUCTURE OCS-301
RIM
INLET IE
OUTLET IE
2-YEAR
10-YEAR
100-YEAR
ORIFICE INFO.
588.50
585.50
SIZE (IN)
6.0
NUMBER
FLOW
FLOW
6.00'
DIAMETER
2.0 0'
SU
MP
FLOWFLOW
BAFFLE WALL
BAFFLE WALL
ORIFICE HOLES IN BAFFLE WALL
SEE CHART FOR NUMBER
SIZE AND ELEVATION
1.00'
12" C TO C HOLE
SPACING, TYP.
PLAN OF STRUCTURE
SECTION A-A SECTION B-B
NOTES:
MANHOLE AND OUTLET STRUCTURES TO BE PRECAST
CONCRETE STRUCTURES WITH INTEGRAL BOTTOM.
STRUCTURES TO BE PER ASTM C-478.
A A
B B
25-YEAR ORIFICE ELEVATION
PIPE INLET
100-YEAR STORM ELEVATION/OVERFLOW (TOP OF BAFFLE)
FRAME AND GRATE
(ABOVE)
FINISH GRADE
MANHOLE FRAME AND GRATE
ECCENTRIC CONE SECTION
MANHOLE STEPS
STRUCTURE
RIM
INLET IE
OUTLET IE
2-YEAR
10-YEAR
100-YEAR
ORIFICE INFO.
SIZE (IN)NUMBER
OCS-302
592.60
588.50 NA
T/BAFFLE NA
T/BAFFLE
100-YEAR ORIFICE ELEVATION
10-YEAR ORIFICE ELEVATION
25-YEAR - --
25-YEAR
STRUCTURE
RIM
INLET IE
OUTLET IE
2-YEAR
10-YEAR
100-YEAR
ORIFICE INFO.
SIZE (IN)NUMBER
OCS-303
585.75
T/BAFFLE NA
25-YEAR
STRUCTURE OCS-304
RIM
INLET IE
OUTLET IE
2-YEAR
10-YEAR
100-YEAR
ORIFICE INFO.
587.88
SIZE (IN)NUMBER
STRUCTURE
RIM
INLET IE
OUTLET IE
2-YEAR
10-YEAR
100-YEAR
ORIFICE INFO.
SIZE (IN)NUMBER
OCS-305
593.93
NA
T/BAFFLE NA
T/BAFFLE
25-YEAR
25-YEAR
STRUCTURE
RIM
INLET IE
OUTLET IE
2-YEAR
10-YEAR
100-YEAR
ORIFICE INFO.
SIZE (IN)NUMBER
OCS-307
586.27
T/BAFFLE NA
25-YEAR
587.00 588.57
5.5 6.0
589.99
589.26 6.05
582.3
2.0
584.80
582.65
582.50 584.97
3.0 4.0
582.65
587.62
586.20 5.04
574.91 577.99 579.43
3.6 6.0
581.89 NA
5.54
574.84 574.44
564.11
564.17 567.75
2.9 5.7
563.60
572.63
569.70 6.05
BASIN A
BASIN B
BASIN C
TANK 3
TANK 1
TANK 4
NOTES:
1. BASIS OF DESIGN LAG PUMPS TO BE FLYGT NP3202 LT3~616, 480V, 3-PHASE, 45 HP
PUMPS. PUMPS TO BE COMPLETE REMOVABLE PACKAGE INCLUDING LIFTING RAILS
AND ALL LEVEL CONTROLS, VALVES AND APPURTENANCES NECESSARY.
2. BASIS OF DESIGN LEAD (SUMP) PUMP TO BE BARNES 4SEV7544DS, 480V, 3 PHASE,
7.5 HP., 1750 RPM, PROVIDE PUMP CONTROLLER TO SET PUMP CYCLE FOR
EQUIVALENT DISCHARGE RATE OF 2,500 GALLONS PER HOUR (312 GPM) . PROVIDE
CHECK VALVES IN RISERS. CONNECT PUMP DISCHARGE PIPING TO ADJACENT LAG
PUMP 12" DISCHARGE PIPE. PUMP TO BE INSTALLED AS A REMOVABLE PACKAGE
INCLUDING LIFTING CHAINS. PROVIDE ALL LEVEL CONTROLS, VALVES AND
APPURTENANCES NECESSARY.
3. WET WELL TO BE 18'-10" x 13'-8" CONCRETE STRUCTURE. PROVIDE ROCK ANCHORS
AND 8" MINIMUM THICK CONCRETE LEVELING MAT ON TOP OF EXISTING ROCK
SURFACE. ROCK ANCHORS TO BE DESIGNED BY CONTRACTOR TO RESIST 100,000
LBS OF TOTAL UPLIFT.
4. APPLY TWO COATS OF MASTIC WATERPROOFING TO ENTIRE EXTERIOR SURFACE
OF WET WELL. PROVIDE CONCRETE TOP SECTION WITH CUSTOM PUMP ACCESS
HATCH FOR EACH PUMP CAPABLE OF AASHTO HS-20 LOADING. COORDINATE
ACCESS HATCH SIZE WITH PUMP MINIMUM CLEAR OPENING AND PUMP LIFTING
RAIL REQUIREMENTS. PROVIDE MANHOLE STEPS.
5. PROVIDE AND INSTALL ALL PIPING, APPURTENANCES AND SUPPORTS REQUIRED
TO CONNECT PUMPS TO 18" DISCHARGE PIPE. CHECK VALVES ARE REQUIRED IN
ALL PUMP DISCHARGE PIPING. PIPE MATERIALS TO MEET PUMP MANUFACTURER'S
RECOMMENDATIONS. PIPING SHOWN IS SCHEMATIC AND MAY BE MODIFIED TO
MEET PUMP MANUFACTURER'S REQUIREMENTS. INSTALL UNIONS OR OTHER
APPROVED QUICK DISCONNECT METHOD FOR EASY PUMP REMOVAL
6. PROVIDE AND INSTALL PUMP CONTROLLER AND ALL WIRING, BREAKERS,
DISCONNECTS, CONDUIT AND CONDUCTORS REQUIRED TO OPERATE THE PUMPS.
LOCATE PUMP CONTROLLER IN SOUTH PARKING DECK. COORDINATE WITH SHEET
ES2007. ELECTRICAL CONNECTIONS TO MEET ALL APPLICABLE CODES AND
ORDINANCES.
7. INSTALL COMMUNICATIONS LINES FROM WET WELL AND PUMP CONTROLLER TO
PUMP CONTROLLER LOCATION IN SOUTH PARKING DECK. COORDINATE CABLE
REQUIREMENTS WITH CONTRACTING OFFICER.
8. PROVIDE ADEQUATE AIR RELIEF IN DISCHARGE LINE AS REQUIRED TO PREVENT
AIR LOCK
9. ALL EXTERIOR FORCE MAIN PIPING TO BE RESTRAINED JOINT DUCTILE IRON PIPING
10. PROVIDE AND INSTALL AASHTO HS-20 RATED ACCESS HATCH FOR EACH PUMP.
COORDINATE ACCESS HATCH SIZE REQUIREMENTS WITH PUMP MANUFACTURERS
REQUIREMENTS.
'-1
0"
2'- 0"
9'- 5"
2'- 0"
18" DIP
18" x 16" REDUCER
16" X 12" REDUCING WYE
12" DIP
12" x 45° BEND
12" DIP
12" DIP
16" x 12" REDUCER
12" x 12" WYE
12" x 45° BEND
12" x 45° BEND
16" X 12" REDUCING WYE
12" DIP
MODULAR ELASTOMER SEAL
AT ALL PIPE PENETRATIONS
12" DIP
2'-0" 3'-934" 3'-114"
1'-7" 8"
4'-6" 2'-0"
10'-6" 7'-2"
18" DIP
18" x 16" REDUCER
16" X 12" REDUCING WYE
16" x 12" REDUCER
12" x 12" WYE
16" X 12" REDUCING WYE
12" x 90° BEND
12" CHECK VALVE
PUMP, PUMP SEAT, MOUNTING,
AND LIFTING RAIL AND CHAIN SET
PER PUMP MANUFACTURER.
LIFTING RAIL
MODULAR ELASTOMER SEAL
AT ALL PIPE PENETRATIONS
PIPE SUPPORT
TYP
LEAD PUMP
LAG PUMP
TYPICAL 4
PLACES
BAFFLE WALL
36" RCP IN FROM
STMH-013
1'- 6"
1'- 11 2"
PUMP LEVELS:
LEAD OFF 558.89
LEAD ON 560.89
LAG 1 OFF 560.89
LAG 1 ON 564.00
LAG 2 OFF 564.00
LAG 2 ON 566.00
LAG 3 OFF 566.00
LAG 3 ON 568.88
LAG 4 OFF 568.88
LAG 4 ON 571.46
ALARM : 577.00
NOTE:
LEAD PUMP OFF WHEN
LAG PUMP(S) RUNNING
6'-9"
17'-8"
13'-8"
'-8
3 16
ROCK ANCHOR
TYP
ROCK ANCHOR
CONCRETE LEVELING MAT
1'-
1 4" 3'-
81 2" 3'-
81 2" 3'-
81 2" 3'-
81 2" 2'-
13 4"
ROCK ANCHOR
CONCRETE LEVELING MAT
#10's @ 12" VERT
LAG PUMP
TYP
6" HIGH CONCRETE
ANTI-VORTEX BAFFLE
TYP
OPENINGS
IN BAFFLE
WALL
#6's @ 12" HORIZ
#9's @ 12" TOP & BOT #6's @ 12"
#10's @ 12" EW BOT #8's @ 12" EW TOP
1'- 6"
CONNECT LEAD PUMP 4" DISCHARGE LINE TO
LAG PUMP 12" DISCHARGE LINE WITH
12" x 4" REDUCING WYE
SLOPE FLOOR TO
PUMPS
SLOPE FLOOR TO
PUMPS
BAFFLE
WALL
NOTE:
INSTALL #6, 48"x48" CORNER BARS
@ 12" O.C. HORIZ AT STRUCTURE
CORNERS
TOP OF BAFFLE WALL
9'- 71 2"
18'-10"
9'- 71 2" 6"
3'-0"
LEAD PUMP
OPNG
1'-0" 2'-812" 1'-0" 2'-812" 1'-0" 2'-812" 1'-0" 2'-812" 6"
1'- 9"
OPENINGS IN BAFFLE WALL
TYP
#6 BARS @ 12" O.C. EW
PLACE BARS 2 12" CLEAR
FROM WALL FACE OPPOSITE
36" STORM SEWER
EXTEND BARS 10" INTO
STRUCTURE SIDE WALL
TWO #6 BARS x 48" LONG
EXTEND BARS 10" INTO
STRUCTURE FLOOR
TYP BETWEEN OPENINGS
ACCESS HATCH
PLAN
SECTION ASECTION B
BAFFLE WALL ELEVATION
36" RCP
IN FROM
STMH-013
NOTE:
LEAD PUMP NOT SHOWN
W12x26, CENTERED BETWEEN PUMPS
COORDINATE MEMBER SIZE WITH MINIMUM
HATCH SIZE AND PUMP CLEARANCE
REQUIREMENTS
W12x26
W12x26
W12x26
W12x26
BEAM POCKET
FOR ROOF BEAMS
TYP
ROOF BEAM
TYP
t h r e e q u a r t e r s i n c h o n e f o o t o n e i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t
EM RA, JY, SH
URS | SMITHGROUP JOINT VENTURE
T 313.983.3600 F 313.983.3636
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320
TRUE NORTH
PROJECT NORTH
97 8654321 o n e s i x t e e n t h i n c h o n e f o o t o n e t h i r t y s e c o n d t h i n c h o n e f o o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
www.urscorp.com | www.smithgroupjjr.com
CONSTRUCTION DOCUMENTS
20NOV2020
USACE P2 No. 453413
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION OrientationSeal
20NOV2020
PHA CERTIFIED FINAL 20NOV2020
Mark
CU235
OUTLET CONTROL
STRUCTURE DETAILS
OUTLET CONTROL STRUCTURES1 N.T.S.
SOUTH PUMP STATION - PS-6022 N.T.S.
MAXIMUM ALLOWABLE DISCHARGE RATES (CFS)
2-YEAR 10-YEAR 25-YEAR 100-YEAR
TANK-1 (OCS-305) 3.39 7.22 9.50 12.93
TANK-3 (OCS-304) 2.41 9.90 15.14 23.58
TANK-4 (OCS-307) 1.69 6.94 10.62 16.54
UNDERGROUND DETENTION SYSTEM BASIS OF DESIGN:
1. BASIS OF DESIGN MANUFACTURER FOR UNDERGROUND DETENTION SYSTEM IS STORMTRAP PRECAST
CONCRETE DETENTION UNITS.
2. CONTRACTOR MAY MAY ELECT TO USE SUBSTITUTE UNDERGROUND DETENTION SYSTEM MEETING THE
FOLLOWING REQUIREMENTS.
3. SUBSTITUTE UNDERGROUND DETENTION SYSTEM MUST BE DESIGNED BY A LICENSED PROFESSIONAL
ENGINEER REGISTERED IN THE STATE OF KENTUCKY
4. SUBSTITUTE SYSTEM MUST BE WATER TIGHT.
5. SUBSTITUTE SYSTEM MAY NOT USE AN OPEN BOTTOM / AGGREGATE BASE DESIGN.
6. UNDERGROUND PIPE SIZE OR VAULT HEIGHT SHALL NOT BE LESS THAN 36-INCHES.
7. UNDERGROUND DETENTION SYSTEM SHALL HAVE A MINIMUM OF TWO ACCESS-WAYS FOR MAINTENANCE
AND INSPECTION OF THE ENTIRE DETENTION SYSTEM.
8. UNDERGROUND DETENTION SYSTEMS SHALL DISCHARGE THROUGH A MULTI-STAGE CONTROLLED
OUTLET. DISCHARGE RATES MAY NOT EXCEED THE PRE-CONSTRUCTION DISCHARGE RATES FOR THEIR
TRIBUTARY AREAS. MAXIMUM DISCHARGE RATES ARE AS LISTED IN THE TABLE BELOW:
9. DESIGN, LAYOUT, SHOP DRAWINGS AND CALCULATIONS MUST BE PROVIDED TO THE CONTRACTING
OFFICER FOR RECORD KEEPING PURPOSES.
14. THE CONFIGURATION OF A SUBSTITUTE UNDERGROUND DETENTION SYSTEM MAY NOT INTERFERE WITH
OR IMPACT DESIGN AND INSTALLATION OF OTHER SITE SYSTEMS.
15. DESIGN OF SUBSTITUTE SYSTEM IS CONSIDERED PART OF THE CONTRACTOR'S BIDDING PROCESS.
DESIGN FEES ASSOCIATED WITH THE CONTRACTOR'S PREPARATION OF SUBSTITUTE SYSTEM WILL NOT
BE REIMBURSED.
PREFABRICATED WATER QUALITY UNITS BASIS OF DESIGN:
1. BASIS OF DESIGN MANUFACTURER FOR UNDERGROUND DETENTION SYSTEM IS STORMTRAP PRECAST
CONCRETE WATER QUALITY UNITS.
2. CONTRACTOR MAY MAY ELECT TO USE SUBSTITUTE MANUFACTURER FOR PREFABRICATED WATER
QUALITY UNITS.
3. PREFABRICATED UNITS MUST BE 'OFF-LINE' DESIGN
4. SUBSTITUTE UNITS MUST MEET THE CURRENT 80-PERCENT TOTAL SUSPENDED SOLIDS REMOVAL
CRITERIA CONTAINED IN CHAPTER 18 OF THE LATEST MSD DESIGN MANUAL. AND CURRENT CITY OF
LOUISVILLE / MSD GREEN INFRASTRUCTURE ORDINANCE AND DESIGN REQUIREMENTS.
5. CONTRACTOR MAY USE MANUFACTURER AND UNITS PRE-APPROVED BY MSD. CONTACT MSD FOR
CURRENT LIST OF MANUFACTURERS AND MODELS.
6. PREFABRICATED UNITS MUST BE CAPABLE OF TREATING THE FLOW RATES LISTED BELOW, RATES ARE CALCULATED USING THE RAINFALL INTENSITY OF 2.82 INCHES/HOUR RAINFALL INTENSITY PER CHAPTER
18 OF 2015 EDITION OF THE MSD DESIGN MANUAL.
7. DESIGN, LAYOUT, AND SHOP DRAWINGS MUST BE PROVIDED TO THE CONTRACTING OFFICER FOR
RECORD KEEPING PURPOSES.
8. THE CONFIGURATION OF A SUBSTITUTE UNDERGROUND DETENTION SYSTEM MAY NOT INTERFERE WITH
OR IMPACT DESIGN AND INSTALLATION OF OTHER SITE SYSTEMS.
9. ANY DESIGN ASSOCIATED WITH SUBSTITUTE PREFABRICATED WATER QUALITY UNITS IS CONSIDERED PART OF THE CONTRACTOR'S BIDDING PROCESS. DESIGN FEES ASSOCIATED WITH THE CONTRACTOR'S
PREPARATION OF SUBSTITUTE SYSTEM WILL NOT BE REIMBURSED.
WATER QUALITY TREATMENT RATES (CFS)
STRUCTURE UPSTREAM
STRUCTURE
DOWNSTREAM
STRUCTURE TREATMENT RATE
WQ-501-4 STMH-051 TANK 1 7.88
WQ-503-6 CB-213 TANK 3 23.47
WQ-503-7 CB-215 TANK 3 0.48
WQ-504-8 STMH-011 TANK 4 3.21
WQ-504-9 STMH-019 TANK 4 15.89
PUMP STATION BASIS OF DESIGN:
1. BASIS OF DESIGN MANUFACTURER FOR STORMWATER PUMPS ARE AS LISTED IN NOTES 1 AND 2 ABOVE DETAIL.
2. CONTRACTOR MAY ELECT TO USE SUBSTITUTE PUMP MODELS / MANUFACTURER MEETING THE FOLLOWING REQUIREMENTS.
3. LAG PUMPS MUST BE CAPABLE OF PUMPING THE COMBINED OUTFLOWS FROM SURFACE DETENTION BASIN C, AND UNDERGROUND DETENTION TANKS 3 AND 4 FOR THE 2, 10, 25 AND 100-YEAR RAINFALL
EVENTS.
4. LAG PUMPS MUST BE CAPABLE OF PUMPING A MINIMUM OF 4,000 GPM INDIVIDUALLY WITH A COMBINED MINIMUM PUMPING CAPACITY OF 15,000 GPM WITH A VERTICAL LIFT OF 27-FEET, WITH TOTAL
DYNAMIC HEAD OF 36.5-FEET.
5. LAG PUMPS SHALL NOT RUN AT WATER LEVELS IN THE WET WELL THAT ARE BELOW THOSE INDUCED BY RAIN EVENTS LESS THAN THE 2-YEAR EVENT.
6. LEAD PUMP SHALL BE CAPABLE OF PUMPING 350 GPM AT 27-FEET OF VERTICAL LIFT.
7. LEAD PUMP SHALL RUN AT WATER LEVELS IN THE WET WELL THAT ARE BELOW THOSE INDUCED BY THE 2-YEAR RAIN EVENT.
8. WET WELL DESIGN SHOWN ABOVE IS TAILORED TO SPECIFIC BASIS OF DESIGN PUMP MODELS MANUFACTURED BY FLYGT AND BARNES. CONTRACTOR SHALL PROVIDE WET WELL DESIGN TAILORED TO
SUBSTITUTE PUMP MODEL'S AND MANUFACTURER'S REQUIREMENTS .
9. CONTRACTOR'S SUBSTITUTE PUMP STATION MUST BE PROVIDED AS A COMPLETE, OPERABLE PACKAGE. ALL PUMPS, PUMP CONTROLS, LIFTING RAILS, LIFTING CHAINS, ACCESS HATCHES, PIPING, VALVES, FITTINGS AND APPURTENANCES MUST BE INCLUDED.
10. CONTRACTOR SHALL COORDINATE POWER REQUIREMENTS FOR SUBSTITUTE PUMP STATION WITH THOSE SHOWN IN THE CONTRACT DOCUMENTS. REVISIONS OR MODIFICATIONS TO THE POWER AND OR
CONTROLLER REQUIREMENTS WILL BE INCLUDED WITH THE CONTRACTOR'S PRICE FOR THE SUBSTITUTED PUMP STATION
11. CONTRACTOR SHALL DESIGN WET WELL ASSOCIATED WITH SUBSTITUTE PUMP STATION FOR AASHTO HS-20 LOADING.
12. CONTRACTOR SHALL DESIGN WET WELL ASSOCIATED WITH SUBSTITUTE PUMP STATION TO RESIST BUOYANCY INDUCED BY GROUND WATER LEVELS TO THE TOP OF THE WET WELL.
13. DESIGN, LAYOUT, AND SHOP DRAWINGS MUST BE PROVIDED TO THE CONTRACTING OFFICER FOR RECORD KEEPING PURPOSES.
14. SUBSTITUTE PUMP STATION MUST BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF KENTUCKY.
15. THE CONFIGURATION OF A SUBSTITUTE PUMP STATION MAY NOT INTERFERE WITH OR IMPACT DESIGN AND INSTALLATION OF OTHER SITE SYSTEMS.
16. DESIGN OF SUBSTITUTE PUMP STATION IS CONSIDERED PART OF THE CONTRACTOR'S BIDDING PROCESS. DESIGN FEES ASSOCIATED WITH THE CONTRACTOR'S PREPARATION OF SUBSTITUTE PUMP
STATION WILL NOT BE REIMBURSED.
AMENDMENT 0007 1 10FEB2021
CERTIFIED FINAL
W
2Q R
R
_P ha se A-
CU237D
C7
TYP
8' - 6" 7' - 8" 7' - 8" 7' - 8" 7' - 8" 7' - 8" 7' - 8" 8' - 6"
4' - 0"5' - 3"2' - 6"5' - 2"2' - 6"5' - 2"2' - 6"5' - 2"2' - 6"5' - 2"2' - 6"5' - 2"2' - 6"5' - 2"2' - 6"5' - 3"4' - 0"
5' - 0" 7' - 3" 3' - 0" 12' - 9" 3' - 0" 12' - 9" 3' - 0" 7' - 3" 5' - 0"
CU237C
B6
TYP
CU237B
C7
TYP
CU237B
B7
TYP
TOC
548.30
CONCRETE PAVING
ELEVATION
SEE CIVIL
PROVIDE CONCRETE TOPPING TO ACHIEVE SLOPE
AS SHOWN IN THE MAT SLAB GRADING PLAN
SEE GENERAL NOTES AND CONCRETE SPEC FOR
SURFACE PREP
TOP OF ROCK
SEE CIVIL
PERIMETER DRAIN
BEHIND WALL
SEE CIVIL DRAWINGS
COMPACTED
GRANULAR BACKFILL
TO FOLLOW SLOPE
GRANULAR BACKFILL TO MEET
REQUIREMENTS OF THE
GEOTECHNICAL REPORT
TO BE APPROVED BY GEOTECHNICAL
ENGINEER OR THIRD PARY INSPECTOR
PRIO TO PLACEMENT
BOTTOM OF CONCRETE ELEVATION
583.10
PAVEMENT
#10 @ 6" O.C BOTH SIDES
#7 @ 6" O.C BOTH SIDES
4' - 0"
#7 @ 12" O.C T&B
#5 @ 12" O.C T&B
#8 CORNER BAR TO MATCH
VERTICAL REINFORCEMENT
IN WALL
TOC
548.30
PROVIDE CONCRETE TOPPING TO ACHIEVE SLOPE
AS SHOWN IN THE MAT SLAB GRADING PLAN
SEE GENERAL NOTES AND CONCRETE SPEC FOR
SURFACE PREP
TOP OF ROCK
SEE CIVIL
PERIMETER DRAIN
BEHIND WALL
SEE CIVIL DRAWINGS
COMPACTED
GRANULAR BACKFILL
TO FOLLOW SLOPE
COMPACTED GANULAR BACKFILL TO
MEET REQUIREMENTS OF THE
GEOTECHNICAL REPORT
TO BE APPROVED BY GEOTECHNICAL
ENGINEER OR THIRD PARTY
INSPECTOR PRIOR TO PLACEMENT
CU237B
B7
TYP
CU237C
B6
TYP
CU237D
C7
TYP
BOTTOM OF CONCRETE ELEVATION
583.10
CONCRETE PAVING
ELEVATION
SEE CIVIL
PAVEMENT
548.90
548.90
SEE MAT SLAB PLAN
S E
E M
A T
S
LA
B P
LA
N
548.45
548.74
548.30
OUTLET INVERT
P lo t D at e th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
CONSTRUCTION DOCUMENTS -
URS | SMITHGROUP JOINT VENTURE
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
T 313.983.3600
F 313.983.3636 www.urscorp.com | www.smithgroupjjr.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321 o n e s ix te e n th in c h o n e fo o t o n e th ir ty s e c o n d th in c h o n e fo o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
SHEET INDEX ID:
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION
OrientationSeal
CERTIFIED FINAL
Mark 20NOV2020
2/ 8/
:4
0:
P M
10FEB2021
CU237D
SANITARY TANK ELEVATION VIEW
ANDREA
REYNOLDS
KYLE
GERARD
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
603-320
SITE STRUCTURES.SANITARY TANK-CU237D-STRUCTURAL
SCALE: 1/4" = 1'-0"
C1
SANITARY TANK ELEVATION VIEW
SCALE: 1" = 1'-0"
C7
TYPICAL CONNECTION BETWEEN SLAB AND SANITARY WALL
ROUGHN SURFACE TO 1/4" AMPLITUDE
SCALE: 1/4" = 1'-0"
F1
SANITARY TANK ELEVATION VIEW
SCALE: 1/2" = 1'-0"
E7
MAT SLAB GRADING PLAN
PHA CERTIFIED FINAL 20NOV2020
AMENDMENT 0007 1 10FEB2021
W
2Q R
R
_P ha se A-
PARKING GARAGE FRAMING AND DURABILITY CRITERIA
1. FRAMING SYSTEM SHALL UTILIZE PRECAST-PRESTRESSED DOUBLE TEES, PRE-TOPPED, AS INDICATED IN DRAWINGS. FIELD TOPPING SHALL BE PLACED TO CREATE FLUSH SURFACE BETWEEN ADJOINING DOUBLE TEES, TO PROVIDE FIELD CONNECTIONS TO SUPPORTING MEMBERS, AND TO CREATE DRAINAGE CONTOURS ADJACENT TO WALLS AND FOR DIRECTION OF SURFACE FLOW TOWARDS DRAINS. SEE
PLANS FOR DRAINAGE CONTOUR INTENT.
2. BASED UPON DRAINAGE PROFILE, MANY OF THE PRECAST DOUBLE TEE MEMBERS WILL REQUIRE "SECONDARY DRAINAGE WARPING" DURING MANUFACTURE TO ACHIEVE PROFILE FOR CROSS-SLOPE WITHIN THE PRE-TOPPED CONFIGURATION.
3. GARAGE CLEARANCES SHALL MAINTAIN 8'-4" IN ALL AREAS, INCLUDING AT TRANSITION POINTS FOR RAMPS WITH DRAINAGE CONTOURS.
THE INTENT IS TO ALIGN DRAINAGE CONTOUR ELEMENTS SUCH THAT THE PLAN POSITION MATCHES FLOOR-TO-FLOOR WITHOUT
REDUCTION OF CLEARANCE.
4. DOUBLE-TEE FLANGE CONNECTIONS SHALL UTILIZE STAINLESS STEEL. DOUBLE-TEE FLANGE-TO-FLANGE CONNECTIONS AT 6’- 0” SPACING, OR LESS. FIRST FLANGE CONNECTIONS LESS THAN OR EQUAL TO 2’- 0” FROM THE ENDS OF DOUBLE- TEES.
5. THREADED CONNECTERS SHALL BE ELECTROPLATED (MINIMUM COATING). HOT-DIPPED GALVANIZING FOR ALL OTHER CONNECTORS AND PLATES. SCOURING AND PAINTING WITH A LIQUID GALVANIZING COATING SHALL BE APPLIED TO ALL HOT-DIPPED GALVANIZED PLATE
WELDS.
6. EPOXY COATING SHALL BE APPLIED TO THE ENDS OF PRE-STRESSING STRANDS IN ALL HORIZONTAL FRAMING MEMBERS (BEAMS, TEES
AND SLABS). COATING SHALL EXTEND A MINIMUM 1’-6” INTO CAST MEMBER.
7. EPOXY COATING SHALL BE APPLIED TO ALL TOPPING STEEL REINFORCING BARS AND STEEL WIRE REINFORCEMENT.
8. PROVIDE TWO INCHES MINIMUM CONCRETE COVER FOR LONGITUDINAL STEEL REINFORCING BARS AT ALL HORIZONTAL FRAMING
MEMBERS. PROVIDE 1-1/2 INCHES MINIMUM CONCRETE COVER FOR BEAM STIRRUPS.
9. PROVIDE TWO INCHES OF CONCRETE COVER AT ALL COLUMNS AND SHEAR WALL LONGITUDINAL STEEL REINFORCING BARS. PROVIDE
1-1/2 INCHES MINIMUM CONCRETE COVER FOR COLUMN AND PIER TIES.
10. MINIMUM CONCRETE PROPERTIES FOR PRECAST ELEMENTS SHALL BE AS FOLLOWS:
• MINIMUM COMPRESSIVE STRENGTH = 5000psi AT 28 DAYS FOR ALL GARAGE COMPONENTS
• MINIMUM COMPRESSIVE STRENGTH = 6000psi AT 28 DAYS FOR ALL MEMBERS WITH DIRECT EXPOSURE TO VEHICLE TRAFFIC, UNLESS SEPARATE SURFACE POTECTION SYSTEM IS PROVIDED.
• MAXIMUM WATER-TO-CEMENT RATIO = 0.38
11. MINIMUM CONCRETE PROPERTIES FOR FIELD-CAST ELEMENTS AND TOPPING INFILL SHALL BE AS FOLLOWS:
• MINIMUM COMPRESSIVE STRENGTH = 5500psi AT 28 DAYS
• MAXIMUM WATER-TO-CEMENT RATIO = 0.40
• SEE PROJECT SPECIFICATIONS FOR CORROSION INHIBITING ADMIXTURE.
12. ALL CONCRETE FOR PIT STRUCTURES AND RETAINING WALLS SHALL INCLUDE AN INTEGRAL WATER-REPELLANT ADMIXTURE.
P lo t D at e:
th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
CONSTRUCTION DOCUMENTS -
URS | SMITHGROUP JOINT VENTURE
500 WEST JEFFERSON ST.
Suite 1600
LOUISVILLE, KY 40202
T 313.983.3600 F 313.983.3636 www.urscorp.com | www.smithgroupjjr.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
B
A
C
D
E
F
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
TRUE NORTH
PROJECT NORTH
97 8654321 o n e s ix te e n th in c h o n e fo o t o n e th ir ty s e c o n d th in c h o n e fo o t
PROJECT # 14576907/22200.000
OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT - CENTRAL REGION
3001 GREEN BAY ROAD
BUILDING 48
NORTH CHICAGO, IL 60064
T 224.610.3492
U.S. DEPARTMENT OF VETERANS AFFAIRS
SHEET INDEX ID:
NON-SPRINKLERED
USACE LOUISVILLE DISTRICT
600 DR. MARTIN LUTHER KING PLACE
LOUISVILLE, KY 40202
PHONE: 502-315-6766
FAX: 502-315-6195
CONTRACTING DIVISION
OrientationSeal
CERTIFIED FINAL
Mark
2/ 9/
:1
8:
P M
10FEB2021
SF003F
SOUTH PARKING STRUCTURAL
GENERAL NOTES
EJM SAH
Louisville, Kentucky
REPLACEMENT VA MEDICAL CENTER
VA Project No. 603-320 USACE P2 No. 453413
601.07.1.S0-SF003F-STRUCTURAL
20NOV2020
8. NO LOADS SHALL BE HUNG FROM STEEL ROOF DECK.
7. STEEL DECK CROSS SECTIONS ARE ONLY REPRESENTED DIAGRAMMATICALLY ON THE DRAWINGS.
S= 0.247 IN3/FT S= 0.240 IN3/FT
I= 0.212 IN4/FT I= 0.195 IN4/FT
1.5" DEEP ROOF DECK - TYPE B (20 GAGE) 1.5" DEEP STEEL COMPOSITE FLOOR DECK
6. THE DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
5. FOR CONCRETE FILLED FLOOR DECK, DECK SHALL BE PUDDLE WELDED (5/8" DIAMETER MINIMUM) TO THE SUPPORTS AT 12" CENTERS MAXIMUM WI...
4. UNLESS NOTED OTHERWISE, ROOF DECK SHALL BE PUDDLE WELDED (5/8" DIAMETER MINIMUM) TO THE SUPPORTS AT 12" CENTERS MAXIMUM WITH THE FIRST AND LAST RIBS OF EACH SHEET WELDED TO THE SUPPORTS. AT BRACED FRAMES, MOMENT FRAMES, BUILDING PERIMETER AND HIGH AND LOW ROOF STEP ELEVATIONS, PROVIDE PUDDLE WELDS AT 6" ON CENTER MAXIMUM. SPACE WELDS AT 6" CENTERS IN THE CORNER AND PERIMETER AREAS BASED ON ROOF AREA DEFINITIONS OF FM LOSS PREVENTION DATA SHEET 1-28. SIDE LAPS SHALL BE SCREWED WITH #10 SELF-TAPPING SCREWS AT 36" ON CENTER. MECHANICAL FASTENING WITH HILTI X-HSN 24 AND HILTI X-ENP 19 FASTENERS IN LIEU OF WELDING
PERMITTED WITH PRIOR APPROVAL FROM RESIDENT ENGINEER.
3. ROOF DECK SHALL BE GALVANIZED (G-90), UNLESS NOTED OTHERWISE.
2. DECK SHALL INCLUDE ALL MISCELLANEOUS CLOSURE PIECES, METAL SCREEDS, ROOF CURBS, DRAIN SUMP PANS, REINFORCING AROUND OPENINGS, ETC. REQUIRED TO MAKE A COMPLETE JOB. MISCELLANEOUS ITEMS SHALL BE GALVANIZED AND SHALL BE NO THINNER THAN 18 GAGE.
1. STEEL DECK FABRICATION AND ERECTION SHALL CONFORM TO THE LATEST STEEL DECK INSTITUTE SPECIFICATIONS.
STEEL DECK
HEAVIER GAGE STUDS OR TIGHTER SPACING MAY BE REQUIRED AT CORNERS, LONGER SPANS, WALL OPENINGS, ETC. CRITERIA LISTED ABOVE IS
A MINIMUM REQUIREMENT.
NOTE:
(600S162-43)
Sx-x = 0.77 IN3
Ix-x = 2.32 IN4
DEPTH = 6"
GAGE = 18 SEE STRUCTURAL DESIGN LOAD SECTION OF THE GENERAL NOTES FOR CRITERIA
EXTERIOR WALLS WIND LOADING
MINIMUM DESIGN REQUIREMENTS AND SECTION PROPERTIES (MAXIMUM SPACING = 16" ON CENTER)
- CANTILEVER/200 FOR CANTILEVERS, BUT NO GREATER THAN 3/8" AT ANY WINDOW CONDITION
- SPAN/400 FOR SIMPLE SPANS
- CFS BACKING UP METAL PANEL OR OTHER DUCTILE FACADE MATERIALS
- CANTILEVER/300 FOR CANTILEVERS
- SPAN/600 FOR SIMPLE SPANS
- CFS BACKING UP BRICK
10. DEFLECTION CRITERIA FOR CFS FACADE BACKUP, UNDER THE 10-YEAR WIND AS DEFINED BY ASCE-7 ARE AS FOLLOWS:
9. WINDOW AND DOOR HEADS SHALL BE FRAMED WITH JOIST SECTIONS SUFFICIENT TO CARRY THE WEIGHT OF THE WALL ABOVE AND TRANSFER WINDOW AND WALL LATERAL FORCES TO THE JAMBS. JAMB SECTIONS SHALL CONSIST OF HEAVIER GAGE STUDS, MULTIPLE STUDS OR BOTH AS
REQUIRED TO PROVIDE LATERAL SUPPORT FOR WINDOW AND DOOR OPENINGS.
8. PROVIDE AND COORDINATE VERTICAL SLIP CONNECTIONS TO STRUCTURAL STEEL MEMBERS WHERE REQUIRED.
7. PROVIDE CONNECTIONS, BRACES, BRIDGING AND RUNNER TRACKS (MINIMUM 16 GAGE, BUT NOT LESS THAN GAGE OF SUPPORTED STUD) TO DEVELOP THE FULL CAPACITY OF THE MEMBERS. PROVIDE CLIPS, CONNECTIONS, STRAPPING FOR TEMPORARY LATERAL BRACING AND ALL
ITEMS NECESSARY FOR COMPLETE INSTALLATION.
6. COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL LIGHT GAGE FRAMING LOCATIONS AND REQUIREMENTS. COORDINATE
LOCATIONS AND DESIGN FOR ALL WALL HUNG EQUIPMENT.
5. TEMPORARY BRACING SHALL BE PROVIDED UNTIL ERECTION IS COMPLETED. WALL STUD BRIDGING SHALL BE INSTALLED IN A MANNER AS TO PREVENT ROTATION AND ALSO IN A MANNER TO PROVIDE RESISTANCE TO BOTH MINOR AXIS BENDING AND ROTATION. BRIDGING ROWS SHALL BE
EQUALLY SPACED AT 4'-0" ON CENTER MAXIMUM, UNLESS APPROVED OTHERWISE.
4. HANDLING AND LIFTING OF PREFABRICATED PANELS SHALL BE DONE IN SUCH A MANNER AS TO NOT CAUSE DISTORTION IN ANY MEMBER.
TRACKS SHALL BE SECURELY ANCHORED TO THE SUPPORTING STRUCTURE. STUDS SHALL BE PLUMBED, ALIGNED AND SECURELY ATTACHED TO THE FLANGES OR WEBS OF BOTH UPPER AND LOWER TRACKS. JACK STUDS OR CRIPPLES SHALL BE INSTALLED BELOW WINDOW SILLS AND ABOVE WINDOW AND DOOR HEADS, AT FREE-STANDING RAILS AND ELSEWHERE TO FURNISH SUPPORT AND SHALL BE SECURELY ATTACHED TO
SUPPORTING MEMBERS.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE FINAL DESIGN AND PERFORMANCE OF ALL COLD-FORMED LIGHT GAGE STEEL FRAMING. ALL SIZES, GAGES AND DESIGN REQUIREMENTS SHOWN ON THESE DRAWINGS ARE TO BE CONSIDERED MINIMUM REQUIREMENTS AND NOT FINAL REQUIREMENTS. PRIOR TO FABRICATION OF FRAMING, THE CONTRACTOR SHALL SUBMIT FABRICATION AND ERECTION DRAWINGS TO THE A/E FOR APPROVAL. COMPLETE CALCULATIONS SHALL BE SUBMITTED WITH THE FABRICATION DRAWINGS FOR ALL METAL STUD FRAMING. THE CALCULATIONS SHALL BE SIGNED AND SEALED BY AN ENGINEER REGISTERED IN THE STATE OF KENTUCKY.
2. STRUCTURAL STUDS, JOISTS, BRIDGING AND ACCESSORIES SHALL HAVE A MINIMUM YIELD STRENGTH OF 50000 PSI FOR 16 GAGE AND THICKER MATERIALS AND 33000 PSI FOR MATERIALS THINNER THAN 16 GAGE. ALL COLD-FORMED STEEL FRAMING ASSOCIATED WITH THE PARKING
GARAGE STRUCTURE SHALL BE HOT-DIP GALVANIZED TO A MINIMUM G90 THICKNESS.
1. DETAILING AND FABRICATION OF ALL COLD-FORMED STRUCTURAL MEMBERS SHALL CONFORM TO THE AISI SPECIFICATIONS FOR THE DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS, LATEST EDITION.
COLD-FORMED LIGHT GAGE STEEL FRAMING
7. ALL GALVANIZING SHALL BE REPAIRED IN ACCORDANCE WITH ASTM A780.
6. ALL GRATING SHALL BE GALVANIZED ACCORDING TO ASTM A123 GRADE 100. ALL GALVANIZING SHALL BE PERFORMED AFTER FABRICATION AND
THE GRATING SHALL BE STRAIGHTENED IF DISTORTED DURING THE PROCESS.
5. ALL CUT-OUTS AND NOTCHES SHALL BE SHOP FABRICATED.
4. ALL GRATING SHALL BE CONNECTED TO SUPPORTING STEEL BY WELDING EVERY 5TH BEARING BAR WITH 1/8" X 1" LONG FILLET WELD TO EACH SUPPORT OR BY MECHANICAL FASTENERS INSTALLED PER MANUFACTURER'S RECOMMENDATIONS. WHERE GRATING IS REMOVABLE, CONNECT
WITH STANDARD BOLTED FASTENER EVERY 5TH BEARING BAR TO EACH SUPPORT.
3. ALL GRATING SHALL HAVE NON-SLIP SURFACES UNLESS NOTED OTHERWISE. ALL STAIR TREADS SHALL HAVE SOLID, NON-SLIP NOSING.
2. ALL GRATING SHALL BE BANDED ON EDGES AT CUT-OUTS.
1. ALL GRATING MATERIAL SHALL CONFORM WITH ASTM A36 OR ASTM A569.
STEEL GRATING
17. ALL EXTERIOR HSS SHALL INCLUDE MINIMUM 1/4" THICK CAP PLATE WITH SEAL WELD FOR POINTS OF TERMINATION AND/OR CONNECTION TO OTHER MEMBERS. WHERE CONNECTION IS BY ABUTTING WELDED CONNECTION ("CANTILEVER BEAM" PER C5/SF553F AND DETAILS "A" AND "C" PER F1/SF553F), THE CAP PLATE MAY BE OMITTED TO FACILITATE FIELD-WELDING TO SUPPORT MEMBER.
16. UNO, ALL STEEL ASSOCIATED WITH PARKING STRUCTURESHALL BE HOT-DIPPED GALVANIZED AFTER FABRICATION. GALVANIZING SHALL BE REMOVED PER AWS D-19.0, "WELDING ZINC COATED STEEL", PRIOR TO FIELD WELDING. WELDS SHALL BE TOUCHED-UP WITH TWO COATS OF ZINC-RICH PAINT. PROVIDE VENT/DRAINAGE HOLES IN HSS MEMBERS (MINIMUM 3/4Ø, BOTTOM SIDE OF HORIZONTAL MEMBERS, WITHIN 2" OF BASE FOR VERTICAL MEMBERS) PRIOR TO GALVANIZING. FOR HORIZONTAL TUBES, LOCATE THE VENT/DRAIN HOLES IN THE BOTTOM FACE.
15. PROVIDE A NON-METALLIC, NON-SHRINK GROUT UNDER ALL COLUMN BASE PLATES AND BEAM BEARINGS.
14 COLUMN SPLICES SHALL BE DESIGNED IN ACCORDANCE WITH TABLE 14-3, 14TH EDITION OF THE AISC "STEEL CONSTRUCTION MANUAL".
13. VERIFY THE EXACT SIZE AND LOCATION OF ALL OPENINGS PRIOR TO FABRICATION OF STEEL FRAMING MEMBERS.
12. TRUSS MEMBERS AND BRACING CONNECTIONS SHALL BE DESIGNED FOR THE FORCES INDICATED ON THE DRAWINGS.
11. MOMENT CONNECTIONS INDICATED ON THE DRAWINGS SHALL BE DESIGNED FOR THE MOMENTS NOTED. IF NO DESIGN MOMENT IS INDICATED, THEN
THE FULL CAPACITY OF THE SECTION MUST BE DEVELOPED.
DESIGN FOR THE REACTION 'R' IF SHOWN ON THE DRAWINGS.
NON-COMPOSITE BEAMS SHALL BE DESIGNED TO DEVELOP 55% OF THE TOTAL LOAD CAPACITY DERIVED FROM THE MAXIMUM UNIFORM LOAD TABLES, 13TH EDITION OF THE AISC "STEEL CONSTRUCTION MANUAL", (R) (ASD OR LRFD) BASED ON NOTE #2 ABOVE.
10. UNLESS NOTED OTHERWISE, TYPICAL BEAM SHEAR CONNECTIONS SHALL BE DETAILED WITH STANDARD DOUBLE ANGLE OR SHEAR PLATE TYPE
CONNECTIONS, USING A325 BOLTS.
9. UNLESS NOTED OTHERWISE, TYPICAL BEAM SHEAR CONNECTIONS SHALL BE DETAILED WITH STANDARD DOUBLE ANGLE OR SHEAR PLATE TYPE CONNECTIONS, USING A325 BOLTS. SHEAR CONNECTORS SHALL BE DESIGNED FOR THE REACTIONS NOTED ON THE PLANS AND SHALL MEET THE MINIMUM NOMINAL AXIAL TENSILE STRENGTH REQUIREMENTS OF IBC SECTION 1615.3.2.2. IF NO REACTION IS INDICATED ON PLAN, THEN DESIGN FOR
THE SHEAR CAPACITY LISTED IN THE TYPICAL DETAILS.
8. ALL BOLTS SHALL BE TIGHTENED TO A "SNUG-TIGHT" CONDITION, UNLESS NOTED OTHERWISE. BOLTS IN MOMENT CONNECTIONS SHALL BE DESIGNED "SLIP-CRITICAL", WITH A CLASS "A" FAYING SURFACE. BOLTS IN BRACING CONNECTIONS AND COLUMN SPLICES SHALL BE FULLY
PRE-TENSIONED, BUT ARE NOT REQUIRED TO BE SLIP CRITICAL.
7. WELDING ELECTRODES SHALL BE E70 XX (LOW HYDROGEN) OR BETTER. FOR WELDING SYMBOLS WITH NO LENGTH DIMENSION GIVEN, THE WELDING SHALL BE CONTINUOUS BETWEEN ABRUPT CHANGES IN DIRECTION. WELDS NOT OTHERWISE NOTED SHALL BE 1/4" IN SIZE.
ASTM A500, GRADE C - SQUARE RECTANGULAR AND ROUND HSS FOR MEMBERS OTHER THAN VERTICAL BRACES.
ASTM A1085 (FY=50KSI) - SQUARE RECTANGULAR AND ROUND HOLLOW STRUCTURAL SECTIONS FOR VERTICAL BRACES.
ASTM A36 (FY=36 KSI) - ROLLED STEEL PLATES, CHANNELS, ANGLES, BARS AND RODS AS NOTED ON THE DRAWINGS.
ASTM A992 (FY=50 KSI) - ROLLED STEEL SHAPES UNLESS NOTED ON THE DRAWINGS.
6. STRUCTURAL STEEL:
5. BOLTS AND BOLTED CONNECTIONS SHALL CONFORM TO THE REQUIREMENTS OF THE "SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" AS APPROVED BY THE COUNCIL ON RIVETED AND BOLTED JOINTS. UNLESS NOTED OTHERWISE, USE BEARING-TYPE BOLTS WITH THREADS INCLUDED IN THE SHEAR PLANE. ANCHOR BOLTS SHALL CONFORM TO ASTM F-1554, GRADE 36, OR AS SPECIFIED ON THE DRAWINGS.
4. ALL STRUCTURAL STEEL, BOLTS, ETC. SHALL BE DOMESTICALLY PRODUCED.
3. WELDED CONNECTIONS SHALL CONFORM TO THE AMERICAN WELDING SOCIETY, AWS D1.1, LATEST EDITION.
2. THE STRUCTURE WAS DESIGNED USING LRFD APPROACH PER THE 14TH EDITION OF THE AISC "STEEL CONSTRUCTION MANUAL."
1. STRUCTURAL STEEL SHALL CONFORM TO THE AISC "SPECIFICATIONS FOR DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDINGS", LATEST EDITION, "STEEL CONSTRUCTION MANUAL - 14TH EDITION."
STRUCTURAL STEEL
3/4" DIAMETER ADHESIVE ANCHORS - 6 1/2" EMBEDMENT.
5/8" DIAMETER ADHESIVE ANCHORS - 5 1/2" EMBEDMENT.
1/2" DIAMETER ADHESIVE ANCHORS - 4 1/2" EMBEDMENT.
3/4" DIAMETER EXPANSION BOLTS - 4 3/4" EMBEDMENT.
5/8" DIAMETER EXPANSION BOLTS - 4" EMBEDMENT.
1/2" DIAMETER EXPANSION BOLTS - 3 1/4" EMBEDMENT.
7. EMBEDMENT LENGTH OF EXPANSION BOLTS OR ADHESIVE ANCHORS INTO SOLID (OR GROUTED) MASONRY OR CONCRETE SHALL BE AS
FOLLOWS UNLESS NOTED OTHERWISE:
6. ADHESIVE ANCHORS SHALL BE INSTALLED INTO DRY CONCRETE.
5. CONCRETE SHALL BE AT LEAST 21 DAYS OLD PRIOR TO ANCHOR INSTALLATION.
4. ANCHORS SHALL BE INSTALLED BY QUALIFIED PERSONNEL IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS. INSTALLATION OF ADHESIVE ANCHORS SHALL BE PERFORMED BY PERSONNEL CERTIFIED BY ACI/CRSI AS AN ADHESIVE ANCHOR INSTALLER. ALL PERSONNEL INSTALLING ADHESIVE OR MECHANICAL ANCHORS SHALL BE TRAINED BY THE ANCHOR MANUFACTURER ON PROPER INSTALLATION TECHNIQUES. TRAINING DOCUMENTATION FROM THE MANUFACTURER SHALL BE AVAILABLE UPON REQUEST.
3. MECHANICAL ANCHORS SHALL BE HILTI KWIK BOLT TZ (OR APPROVED EQUAL CONSIDERING LOAD RESISTANCE, MATERIAL PROPERTIES, CORROSION PROTECT, AND INSTALLATION REQUIREMENTS). MECHANICAL ANCHORS SHALL BE APPROVED FOR USE WITH CRACKED CONCRETE
PER AC 193. CURRENT ICC-ESR SHALL BE SUBMITTED.
2. ADHESIVE ANCHORS INTO HOLLOW MASONRY SHALL BE HILTI-HY 70 (OR APPROVED EQUAL CONSIDERING LOAD RESISTANCE, IN-SERVICE AND INSTALLATION TEMPERATURE, CREEP, MATERIAL PROPERTIES, CORROSION PROTECT, AND INSTALLATION REQUIREMENTS). ANCHOR RODS SHALL BE HILTI HAS-E ANCHOR RODS (OR APPROVED EQUAL) UNLESS NOTED OTHERWISE. CURRENT ICC-ESR SHALL BE SUBMITTED.
1. ADHESIVE ANCHORS SHALL BE HILTI HY 200 SAFE-SET (OR APPROVED EQUAL CONSIDERING LOAD RESISTANCE, IN-SERVICE AND INSTALLATION TEMPERATURE, CREEP, MATERIAL PROPERTIES, CORROSION PROTECT, AND INSTALLATION REQUIREMENTS). ANCHOR RODS SHALL BE HILTI HIT-Z ANCHOR RODS (OR APPROVED EQUAL) UNLESS NOTED OTHERWISE. ADHESIVE ANCHORS SHALL BE APPROVED FOR USE WITH CRACKED
CONCRETE PER AC 308. CURRENT ICC-ESR SHALL BE SUBMITTED.
POST-INSTALLED ANCHORS
STRUCTURAL PRECAST CONCRETE
1. PRECAST CONCRETE WORK , INCLUDING DELEGATED DESIGN, SHALL CONFORM TO THE LATEST AMERICAN CONCRETE INSTITUTE AND THE PRESTRESSED CONCRETE INSTITUTE CODES AND STANDARDS LISTED IN THE PROJECT MANUAL, EXCEPT AS MODIFIED THEREIN. DESIGN OF PRECAST GARAGE SYSTEMS SHALL BE IN ACCORDANCE WITH ALL ASPECTS OF IBC 2012, ASCE 7-10 AND ACI 318-11. SEE NOTES FOR REQUIRED
GARAGE LOADING CRITERIA.
2. ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE IN 28 DAYS SHALL BE 5000 PSI. FOR MEMBERS WITH DIRECT EXPOSURE TO VEHICLE TRAFFIC, ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE IN 28 DAYS SHALL BE 6000 PSI, UNLESS SEPARATE SURFACE PROTECTION SYSTEMS (INTEGRAL WATERPROOFING, CORROSION INHIBITING ADMIXTURE, EPOXY COATED REINFORCING STEEL) ARE PROVIDED.
3. FIELD PLACED TOPPING SLAB OVER PRECAST MEMBERS SHALL BE CONSIDERED A “BONDED-SLAB” MATERIAL WITH SURFACES PREPARED ACCORDINGLY. TOPPING SLAB SHALL PROVIDE SIMILAR MATERIAL STRENGTH AND DURABILITY TO THE PLANT CAST MATERIALS. CURE ALL
FIELD-PLACED MATERIALS WITH “MOIST CURING” METHODS.
4. ALL CONCRETE MATERIALS USED WITHIN PARKING GARAGE SHALL BE CONSIDERED “EXPOSED TO FREEZE-THAW”, WITH AIR ENTRAINMENT OF 6% +/- 1.5%.
5. MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE AT TIME OF FORCE TRANSFER SHALL BE 3500 PSI.
6. REINFORCING BARS SHALL BE A615 GRADE, 60 KSI YIELD STRENGTH, UNLESS NOTED OTHERWISE. ALL FIELD PLACED REINFORCING STEEL SHALL BE EPOXY-COATED. WELDED WIRE FABRIC WITHIN FIELD-PLACED STRUCTURAL TOPPING SHALL BE 4x4-W4.0xW4.0 (MIN), STAINLESS STEEL.
7. PRESTRESSING WIRE SHALL CONFORM TO ASTM A-421-65, TYPE BA, "SPECIFICATIONS FOR UNCOATED STRESS RELIEVED WIRE FOR PRESTRESSED CONCRETE". PRESTRESSING STRAND SHALL CONFORM TO ASTM A-416-68, GRADE 270, "SPECIFICATIONS FOR UNCOATED STRESS RELIEVED
STRAND FOR PRESTRESSED CONCRETE", USING LOW-RELAXATION STRAND.
8. PRECAST MEMBERS SHALL BE DESIGNED BY THE MANUFACTURER FOR COMPOSITE ACTION TO SUPPORT SUPERIMPOSED LOADS AS GIVEN IN THE NOTES PLUS THE DEAD LOAD OF PRECAST AND TOPPING. UNLESS NOTED OTHERWISE, ALL PRECAST DOUBLE-TEES SHALL INCORPORATE
PLANT-CAST “PRE-TOPPED” CONSTRUCTION.
9. FIELD PLACED TOPPING SLAB OVER PRECAST MEMBERS TO BE 2" THICK REINFORCED WITH 4x4-W4.0xW4.0 (MIN) WELDED WIRE REINFORCEMENT.
SEE PLANS FOR LOCATIONS REQUIRING ADDITIONAL TOPPING TO FACILITATE SURFACE DRAINAGE.
10. BEARING PADS SHOWN ON THE DRAWINGS SHALL BE 60 DUROMETER HARDNESS NEOPRENE, UNLESS OTHERWISE NOTED.
11. THE PRECAST MANUFACTURER SHALL COORDINATE SIZE AND LOCATION OF ALL OPENINGS IN PRECAST MEMBERS WITH ALL OTHER TRADES. SEE REFERNCE DOCUMNETS FOR ANTICIPATED PENETRATIONS TO BE REQUIRED IN PHASE B. IDENTIFY LOCATIONS IN WHICH TRADES MAY CORE DRILL OPENINGS FOR VERTICAL PENETRATIONS THROUGH FLOOR SYSTEM AND HORIZONTAL PENETRATION OF WALL PANELS.
12. ALL OPENINGS LARGER THAN 10" SQUARE OR ROUND SHALL BE PROVIDED BY THE PRECAST MANUFACTURER. SMALLER OPENINGS SHALL BE FIELD-CUT OR CORED BY THE TRADES REQUIRING THE OPENINGS AFTER WRITTEN APPROVAL FROM THE PRECAST MANUFACTURER.
13. PROVIDE STAINLESS STEEL SHEAR CONNECTORS WITHIN THE FLANGES OF PRECAST TEES, RECESSED FROM TRAFFIC SURFACE OF PRETOPPED UNITS. FIELD WELD AS REQUIRED FOR FORCE TRANSFER. PROVIDE FIELD-TOPPED SLAB PLACEMENT AT RECESSED CONNECTIONS.
14. ALL JOINTS OF THE PRECAST FLOOR OR ROOF UNITS SHALL BE JOINTED TOGETHER BY WELDING OR GROUTING CONTINUOUS SHEAR KEYS.
15. SEE DRAWINGS FOR LAYOUT AND CONFIGURATION OF PROPOSED GARAGE STRUCTURAL SYSTEMS, INCLUDING BUT NOT LIMITED TO: PRETOPPED DOUBLE TEES AND SLABS, STAIR FRAMING, PRECAST BEAMS AND SPANDRELS, LOAD-BEARING WALLS AND LITE-WALLS. SUBSTANTIAL VARIATION FOR SYSTEMS SHOWN, INCLUDING TABULATED FOUNDATION REACTIONS, SHALL BE SUBMITTED TO RESIDENT ENGINEER FOR EVALUATION OF
ACCEPTABILITY PRIOR TO PROCEEDING WITH THE WORK.
16. THE PARKING GARAGE IS INTENDED TO PROVIDE A MINIMUM OVERHEAD CLEARANCE OF 8'-4", INCLUDING CLEARANCE FOR LIVE LOAD DESIGN DEFLECTION OF OVERHEAD FLOORS AND TOLERANCE FOR TOPPING INSTALLATION, ERECTION AND CAMBER. CONTRACTOR SHALL BE RESPONSIBLE FOR CHANGES IN MEMBER DEPTHS AND FIELD-PLACED DRAINAGE FILL TO MAINTAIN CLEARANCE HEIGHTS.
17. THE PARKING GARAGE IS INTENDED TO ACCOMMODATE A FUTURE HORIZONTAL EXPANSION ALONG GRID LINE SD. THE FUTURE EXPANSION WILL INCLUDE PARKING LEVELS 1 THROUGH 5, PARTIAL LEVEL 6. WIDTH OF FUTURE EXPANSION SHALL BE APPROXIMATELY 62FT. THE INTENT IS TO HAVE ADDITIONAL FUTURE DOUBLE-TEE FLOOR MEMBERS TO BEAR UPON THE SINGLE-LOADED INVERTED TEE GIRDER PROVIDED ALONG GRID SD.
THE INTENT IS TO HAVE THE CURRENT GARAGE SHEARWALLS TO PROVIDE LATERAL LOAD RESTRAINT FOR THE "EXPANDED GARAGE" CONFIGURATION. SEE SCHEDULE FOR ESTIMATED LOADING FOR COLUMNS AND ADDED LATERAL FORCES FOR GARAGE SHEARWALLS.
18. SEE DRAWINGS FOR APPLIED LOADING TO BE SUPPORTED BY PRECAST BUILDING SYSTEMS. SUPPORTED LOADING IS REPRESENTATIVE OF SYSTEMS, SUCH AS: VEHICLE BARRIER SYSTEM, ARCHITECTURAL EXTERIOR CLADDING SYSTEM, PV SUPPORT STEEL FRAMING, ELEVATOR EQUIPMENT LOADS. ALL SUCH LOADS SHALL BE COORDINATED WITH THE SYSTEMS SUPPLIED BY SUBCONTRACTORS PRIOR TO FINAL SUBMISSION OF GARAGE STRUCTURAL DESIGN AND FABRICATION OF THE WORK. VARIATION FOR SYSTEMS SHOWN, INCLUDING TABULATED FOUNDATION REACTIONS, SHALL BE SUBMITTED TO RESIDENT ENGINEER FOR EVALUATION OF ACCEPTABILITY PRIOR TO PROCEEDING WITH THE WORK.
19. IN CONJUNCTION WITH PRECAST STRUCTURAL FRAMING SHOP DRAWINGS, THE PRECAST SUBMITTALS SHALL INCLUDE A FULL SET OF SYSTEM CALCULATIONS SIGNED AND SEALED BY THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE WORK.
PARKING GARAGE FRAMING AND DURABILITY CRITERIA
PHA CERTIFIED FINAL 20NOV2020
AMENDMENT 0007 1 10FEB2021
W
2Q R
R
_P ha se A-
SD
S1 S2
24" SQ PRECAST
CONC COL
SPAN
5' - 8 1/2" 7' - 7 1/2"
9'
9'
1'
W10x33
HSS12x8x3/8
W10x33
PRECAST CONC
STAIR LANDING BY
PRECAST MFR
8" PRECAST
CONC SLAB +
2" TOPPING
HSS12x8x3/8 HSS12x8x3/8
W10x33
S2.5
(-0'-6.25")
S0.9
SC.9
SC.7
/4
/4
/4
/4
8"
11' - 10 1/2" 8' - 1" 8" 13' - 4" 8" 8' - 1" 8" 1' - 4" 1' - 3 1/2"
22' - 0" 18' - 4 1/2"
(0'-0")
4" EXP JT
E X
P J
T
(-0'-3")
FIELD-TOPPED CONCRETE
TRANSITION. SEE SECT.
C1/SF532F
CONC WASH. SEE
SECT. C1/SF532F
D1
SF525F
F3
SF525F
F1
SF525F
E3
SF524F
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH ELEVATOR
LOBBY FRAMING
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH STAIR
FRAMING
HSS6x6x1/4
HSS6x6x1/4
(EL 615'-1" TO TOP)
HSS6x6x3/8
(BASE TO EL 615'-1")
H S
S x6 x3
/8
4'
0"
H S
S x6 x3
/8
4'
0"
HSS6x6x3/8
654' - 10"
HSS6x6x3/8
654' - 10"
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH STAIR
FRAMING
F5
SF525F B2
SF525F
E1
SF524F
C8
SF524F
(BASE TO TOP)
F6
SF532F
E8
SF532F
E6
SF532F
SD
S1 S2
22' - 0"
4' - 4"
PRECAST CONC
STAIR LANDING BY
PRECAST MFR
OPENING FOR ELEVATOR
CABLES AND EQUIPMENT.
COORD WITH ELEV SUPPLIER
ELEVATOR MACHINE BM
REACTIONS, TYP COORD
WITH ELEV SUPPLIER
S0.9
SC.9
SC.7
E5
SF524F
E8
SF524F
PRECAST WALL
(BELOW)
PRECAST WALL
HAUNCH (BELOW)
5" CONCRETE COMPOSITE SLAB
(3.5" OVER 1.5" METAL DECK) W/
4.5 LB/CY SYNTHETIC MACRO
REINFORCING
D5
SF525F
B1
SF526F
C3
SF526F
E8
SF525F
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH ELEVATOR
LOBBY FRAMING
/4
/4
H S
S x6 x3
/8 H
S S x6 x3 /8
HSS6x6x3/8
HSS6x6x3/8
FLOOR SLAB
(10" PRECAST + 2"
SLAB TOPPING)
INTERMEDIATE STAIR
LANDING LEVEL
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH STAIR
FRAMING
668'-4 1/2"
UPPER LANDING
663'-3 1/4" TOP
659'-8"
LOWER LANDING
W
4x
2'
/2
W14x61
( 672' - 0 1/2" )
W
4x
2'
/2
W
4x
2'
/2
W
4x
2'
/2
W
4x
2'
/2
W
4x
2'
/2
W
4x
2'
/2
W
4x
2'
/2
W14x61
( 672' - 0 1/2" )
5" CONCRETE
COMPOSITE SLAB (3.5"
OVER 1.5" METAL DECK)
W/ 4.5 LB/CY SYNTHETIC
MACRO REINFORCING
ACCESS OPENING
(4'-4"x6'-4"). PROVIDE
EDGE DETAILS TO ALLOW
INFILL (BY OTHERS) IN
PHASE B.
E3
SF524F
SEE DRAWING AT4.00F002 FOR "BASIS-
OF-DESIGN” ELEVATOR REACTIONS USED
FOR MEMBER SIZING.
SPAN
10' - 7" 8' - 1" 8" 13' - 4" 8" 8' - 1"
SEE B6/SF550F FOR
SUPPLEMENTAL FRAMING AT
FLOOR DECK OPENING (TYP).
SD
S1 S2 22' - 0"
5' - 0"
S P
A N
W
X
W
X
S0.9
SC.9
SC.7
C5
SF526F
F3
SF526F
F8
SF526F
F6
SF526F
C8
SF526F
G8
SF526F
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH STAIR
FRAMING
CURTAIN WALL. SEE ARCH.
COORD PLACEMENT AND
SUPPORT WITH ELEVATOR
LOBBY FRAMING
0'
-6
0'
-6
P R
E C
A S
T R
O O
F S
LA
B
PROVIDE ALLOWANCE FOR
FUTURE 16"x16" OPENING FOR
MECH EQUIP.
1' - 4" 2' - 6"
HSS6x6x3/8
683' - 2 1/2"
F1
SF526F
SEE QM4501F FOR
STANCHION PLACEMENT
& APPLIED LOADS
10' - 7" 7' - 3" 7' - 2 1/2" 9' - 1 1/2" 7' - 3"
EXTEND PRECAST ROOF SLAB
PLUS UPTURNED BEAM TO
CONNECT AT SUPPORTING HSS
BEAMS PLUS COLUMNS.
SA
S12S11
12' - 0"
/8
SPAN
8" PRECAST CONC WALL
BELOW
SA.1
/4
12" PRECAST
CONC WALL
8" PRECAST CONC
SPANDREL SUPPORTING
ROOF SLAB
8"
10' - 3"
1' - 0"
SA.2
S12.1
C3
SF522F
C6
SF522F
C8
SF522F
/2
/2
9' - 11" 10"
12" PRECAST WALL
8" PRECAST
CONC WALL
PROVIDE ALLOWANCE FOR
FUTURE 16"x16" OPENING FOR
MECH EQUIP.
HSS6x6x3/8
654' - 10"
3' - 8" 1' - 4"
SEE QM4501F FOR
STANCHION PLACEMENT
& APPLIED LOADS
EXTEND PRECAST ROOF SLAB
PLUS UPTURNED BEAM TO
CONNECT AT SUPPORTING HSS
BEAMS PLUS COLUMNS.
PLAN NOTES:
1. SEE PLAN SHEETS SF102F THROUGH SF106F FOR FRAMING PLANS AND FRAMING DETAILS. ALL
ELEVATOR AND STAIR CONSTRUCTION IS INTENDED TO CONSIST OF PRECAST WALL PANELS AND
PRECAST SLABS.
2. ALL SLABS SLOPE TO DRAIN, AS INDICATED ON PLANS. REFERENCE FLOOR ELEVATION VARIES, AS
FOLLOWS:
- FOR BASE OF STAIR LANDING, FLOOR
ELEVATION SHALL BE
LEVEL 2 : 609’-11” (-0’-3”)
LEVEL 3 : 621’- 1” (-0’-3”)
LEVEL 4 : 632’- 3” (-0’-3”)
LEVEL 5 : 643’- 5” (-0’-3”)
LEVEL 6 : 654’- 7” (-0’-3”)
3. TOP OF STEEL FRAMING WITHIN ELEVATOR HOISTWAY SHALL MATCH ADJACENT ELEVATOR LOBBY
TOP OF SLAB.
4. TOP OF STEEL FRAMING WITHIN STAIR SHALL MATCH ADJACENT INTERMEDIATE STAIR LANDING
ELEVATION, UNLESS INDICATED THUS (-0’-0”).
5. SEE DETAILS D1/SF522F, D5/SF522F, D6/SF522F, F1/SF522F AND F5/SF522F FOR STEEL CONNECTIONS
DETAILS HSS-TO-HSS.
6. SEE DETAIL C5/SF553F FOR STEEL CONNECTIONS TO PRECAST EMBEDDED PLATES.
- FOR BASE OF ELEVATOR LOBBY, FLOOR
ELEVATION SHALL BE
LEVEL 2 : 609’-10.5” (-0’-3.5”)
LEVEL 3 : 621’- 0.5” (-0’-3.5”)
LEVEL 4 : 632’- 2,5” (-0’-3.5”)
LEVEL 5 : 643’- 4.5” (-0’-3.5”)
LEVEL 6 : 654’- 6.5” (-0’-3.5”)
PLAN NOTES:
1. SEE PLAN SHEETS SF107F FOR FRAMING PLANS AND FRAMING DETAILS. ALL ELEVATOR AND STAIR
CONSTRUCTION IS INTENDED TO CONSIST OF PRECAST WALL PANELS AND PRECAST SLABS.
2. FLOOR ELEVATION SHALL BE: 664'-6"
3. TOP OF STEEL FRAMING WITHIN STAIR SHALL MATCH ADJACENT INTERMEDIATE STAIR LANDING
ELEVATION, UNLESS INDICATED THUS (-0’-0”).
4. SEE DETAILS D1/SF522F, D5/SF522F, D6/SF522F, F1/SF522F AND F5/SF522F FOR STEEL CONNECTIONS
DETAILS HSS-TO-HSS.
5. SEE DETAIL C5/SF553F FOR STEEL CONNECTIONS TO PRECAST EMBEDDED PLATES.
PLAN NOTES:
1. SEE PLAN SHEETS SF107F FOR FRAMING PLANS AND FRAMING DETAILS. ALL ELEVATOR AND STAIR
CONSTRUCTION IS INTENDED TO CONSIST OF PRECAST WALL PANELS AND PRECAST SLABS.
2. FLOOR ELEVATION SHALL BE: 672'-0 1/2".
3. TOP OF STEEL FRAMING WITHIN ELEVATOR HOISTWAY SHALL MATCH ADJACENT ELEVATOR LOBBY
TOP OF SLAB.
4. TOP OF STEEL FRAMING WITHIN STAIR SHALL MATCH ADJACENT INTERMEDIATE STAIR LANDING
ELEVATION, UNLESS INDICATED THUS (-0’-0”).
5. SEE DETAILS D1/SF522F, D5/SF522F, D6/SF522F, F1/SF522F AND F5/SF522F FOR STEEL CONNECTIONS
DETAILS HSS-TO-HSS.
6. SEE DETAIL C5/SF553F FOR STEEL CONNECTIONS TO PRECAST EMBEDDED PLATES.
PLAN NOTES:
1. SEE PLAN SHEETS SF107F FOR FRAMING PLANS AND FRAMING DETAILS. ALL ELEVATOR AND STAIR
CONSTRUCTION IS INTENDED TO CONSIST OF PRECAST WALL PANELS AND PRECAST SLABS.
2. FLOOR ELEVATION SHALL BE: 683'-2 1/2"
3. TOP OF STEEL FRAMING WITHIN ELEVATOR HOISTWAY SHALL MATCH ADJACENT ELEVATOR LOBBY
TOP OF SLAB.
4. TOP OF STEEL FRAMING WITHIN STAIR SHALL MATCH ADJACENT INTERMEDIATE STAIR LANDING
ELEVATION, UNLESS INDICATED THUS (-0’-0”).
5. SEE DETAILS D1/SF522F, D5/SF522F, D6/SF522F,…