McEntire_JNGB_Repair_HVAC_-_100__Drawings_Part9.pdf
PDF 705 KB Posted
- Attached to
- Repair HVAC Base Wide
- Solicitation number
- W912QG-19-B-5001
About this file
Drawings Part 9/9
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL ROOM
MECHANICAL ROOM
S
EXISTING GATEWAY
ATC PANEL
S
M
PP-2
PP-4
EXISTING PANEL 'PP1'
277/480 TO REMAIN
EXISTING PANEL 'PP'
TO REMAIN
AC-1147-1
CU-1147-1
CKT. PP-2 20A FUSES
3#12 & 1#12G-3/4"
CKT. PP-4
3#10 & 1#10G-3/4"
20A FUSES
JB
JB FOR GATEWAY (50W)
FROM EXISTING CKT. PP1-21
WOMEN'S TOILET
MEN'S TOILET
OFFICE 1
CORR
WOMEN'S TOILET
MEN'S TOILET
OFFICE 1
CORR
AC-1163-1
AC-1163-2
CATWALK
A-35,37
15A FUSES
A-36,38
15A FUSES
DIS OPERATIONS
CLASS "A" VAULT
DIS OPERATIONS
CLASS "A" VAULT
CU-1163-1
CU-1163-2
A-39,41
2#6 & 1#10G-3/4"C
60A FUSES
A-40,42
2#6 & 1#10G-3/4"C
60A FUSES
MECHANICAL ROOM
MAIN ELECTRICAL
DISTRIBUTION PANEL
"MP" (208V/120V, 800 A)
ELECTRICAL PANEL "L"
MECHANICAL ROOM
MECHANICAL ROOM
XFMR
ELECTRICAL PANEL "DCA"
ELECTRICAL PANEL "LA"
ELECTRICAL PANEL "MPH"
(480V/277V, 250A MAIN)
ELECTRICAL
EXISTING PANEL 'A'
TO REMAIN 250A MCB
PANEL RS
PROFESSIONAL SEAL
DATE:
SC No.:
NAME OF REGISTERED PROFESSIONAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
BA C D E F G H
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-2
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
TRUE
NORTH
2/6/19
21049
WPL
E-106
1/4"=1'-0"
1/4" = 1'-0" E-106
A
BLDG 1147 - MECHANICAL ROOM 112
1/4" = 1'-0" E-106
B
BLDG 1163 - ATTIC PARTIAL PLAN
1/4" = 1'-0"
E-106
C
BLDG 1163 - CONDENSING UNIT AREA
KEY NOTES:
PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.
NEW 2P-60A. FUSED SAFETY SWITCH, NEMA 3R ENCLOSURE.
NEW 2P-30A. FUSED SAFETY SWITCH, NEMA 1 ENCLOSURE.
NEW 3P-30A. 600V. FUSED SAFETY SWITCH, NEMA 3R ENCLOSURE.
NEW 3P-30A. 600V. FUSED SAFETY SWITCH, NEMA 1 ENCLOSURE.
1/4" = 1'-0"
E-106
D
BLDG 1053 - MECHANICAL ROOM
1/4" = 1'-0"
BLDG 1057 - MECHANICAL ROOM 107
E-106
E
JF AR PLT
ELECTRICAL PARTIAL PLANS
BLDGS. 1147, 1163, 1053 & 1057
1/4" = 1'-0" E-106
F
BLDG 1163 - ELECTRICAL ROOM 108
E-106 - ELECTRICAL PARTIAL PLANS BLDGS. 1147, 1163, 1053 & 1057
File details come from the government source that posted it.