McEntire_JNGB_Repair_HVAC_-_100__Drawings_Part9.pdf

PDF 705 KB Posted

Attached to
Repair HVAC Base Wide
Solicitation number
W912QG-19-B-5001
Issued by

About this file

Drawings Part 9/9

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL ROOM

MECHANICAL ROOM

S

EXISTING GATEWAY

ATC PANEL

S

M

PP-2

PP-4

EXISTING PANEL 'PP1'

277/480 TO REMAIN

EXISTING PANEL 'PP'

TO REMAIN

AC-1147-1

CU-1147-1

CKT. PP-2 20A FUSES

3#12 & 1#12G-3/4"

CKT. PP-4

3#10 & 1#10G-3/4"

20A FUSES

JB

JB FOR GATEWAY (50W)

FROM EXISTING CKT. PP1-21

WOMEN'S TOILET

MEN'S TOILET

OFFICE 1

CORR

WOMEN'S TOILET

MEN'S TOILET

OFFICE 1

CORR

AC-1163-1

AC-1163-2

CATWALK

A-35,37

15A FUSES

A-36,38

15A FUSES

DIS OPERATIONS

CLASS "A" VAULT

DIS OPERATIONS

CLASS "A" VAULT

CU-1163-1

CU-1163-2

A-39,41

2#6 & 1#10G-3/4"C

60A FUSES

A-40,42

2#6 & 1#10G-3/4"C

60A FUSES

MECHANICAL ROOM

MAIN ELECTRICAL

DISTRIBUTION PANEL

"MP" (208V/120V, 800 A)

ELECTRICAL PANEL "L"

MECHANICAL ROOM

MECHANICAL ROOM

XFMR

ELECTRICAL PANEL "DCA"

ELECTRICAL PANEL "LA"

ELECTRICAL PANEL "MPH"

(480V/277V, 250A MAIN)

ELECTRICAL

EXISTING PANEL 'A'

TO REMAIN 250A MCB

PANEL RS

PROFESSIONAL SEAL

DATE:

SC No.:

NAME OF REGISTERED PROFESSIONAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

BA C D E F G H

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-2

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

TRUE

NORTH

2/6/19

21049

WPL

E-106

1/4"=1'-0"

1/4" = 1'-0" E-106

A

BLDG 1147 - MECHANICAL ROOM 112

1/4" = 1'-0" E-106

B

BLDG 1163 - ATTIC PARTIAL PLAN

1/4" = 1'-0"

E-106

C

BLDG 1163 - CONDENSING UNIT AREA

KEY NOTES:

PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.

NEW 2P-60A. FUSED SAFETY SWITCH, NEMA 3R ENCLOSURE.

NEW 2P-30A. FUSED SAFETY SWITCH, NEMA 1 ENCLOSURE.

NEW 3P-30A. 600V. FUSED SAFETY SWITCH, NEMA 3R ENCLOSURE.

NEW 3P-30A. 600V. FUSED SAFETY SWITCH, NEMA 1 ENCLOSURE.

1/4" = 1'-0"

E-106

D

BLDG 1053 - MECHANICAL ROOM

1/4" = 1'-0"

BLDG 1057 - MECHANICAL ROOM 107

E-106

E

JF AR PLT

ELECTRICAL PARTIAL PLANS

BLDGS. 1147, 1163, 1053 & 1057

1/4" = 1'-0" E-106

F

BLDG 1163 - ELECTRICAL ROOM 108

E-106 - ELECTRICAL PARTIAL PLANS BLDGS. 1147, 1163, 1053 & 1057

File details come from the government source that posted it.