PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
WPL REP DLH WPL
G-001
COVER SHEET
No Scale
McEntire JNGB
Eastover, South Carolina
REPAIR HVAC SYSTEMS BASE WIDE
B-3 FINAL SUBMITTAL
FEBRUARY 06, 2019
PSTE152605
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
WPL REP DLH WPL
G-002
DRAWING INDEX AND MAPS
No Scale
LOCATION MAP
SITE MAP A
SHEET NO. SHEET TITLE
G-001
COVER SHEET
G-002
HVAC DEMOLITION PART PLANS
FAC#157, 200, 243, 279
MD-102
M-405
HVAC CONTROLS & SCHEMATICS
M-406
HVAC CONTROLS & SCHEMATICS
M-001
HVAC SYMBOLS LEGEND
AND GENERAL NOTES
DRAWING INDEX AND MAPS
M-005
OVERALL BUILDING PLANS
FAC#1057, 1060, 1147, 1163
M-004
OVERALL BUILDING PLANS
FAC#878, 984, 958, 1053
M-003
OVERALL BUILDING PLANS
FAC#258, 279, 310, 666, 858
M-002
OVERALL BUILDING PLANS
FAC#157, 200, 210, 243
HVAC DEMOLITION PART PLANS FAC#258
MD-103
HVAC DEMOLITION PART PLANS FAC#310
MD-104
HVAC DEMOLITION PART PLANS FAC#878
MD-105
HVAC DEMOLITION PART PLANS
FAC#958, 984, 1060
MD-106
HVAC DEMOLITION PART PLANS
FAC#1147, 1163
M-101
HVAC PART PLANS FAC#157, 200, 243
M-102
HVAC PART PLANS FAC#210, 258, 279
M-103
HVAC PART PLANS FAC#310
M-104
HVAC PART PLANS FAC#666, 858, 878
M-105
HVAC PART PLANS FAC#958, 984, 1060
M-106
HVAC PART PLANS FAC#1053, 1057, 1163
MD-101
GENERAL
MECHANICAL
SHEET TITLE
ELECTRICAL
SHEET NO.
DRAWING INDEX
E-001
ELECTRICAL LEGEND & GENERAL NOTES
ED-101
ED-102
ED-103
ED-104
ED-105
ED-106
E-101
E-102
E-103
E-104
E-105
E-106
SITE MAP C
SITE MAP B SITE MAP D
PROJECT LOCATION
M-403
HVAC CONTROLS & SCHEMATICS
M-404
HVAC CONTROLS & SCHEMATICS
M-400
INSTRUMENTATION AND CONTROLS LEGEND
M-402
HVAC CONTROLS POINT LIST
M-641
HVAC SCHEDULES
M-642
HVAC SCHEDULES
M-501
HVAC DETAILS
M-502
HVAC DETAILS
M-407
HVAC CONTROLS & SCHEMATICS
S-001
GENERAL NOTES,
ABBREVIATIONS & SYMBOLS
STRUCTURAL
S-101
BUILDING 1163 CATWALK OVERALL PLAN
S-201
BUILDING 1163 CATWALK
PLANS AND DETAILS
S-202
BUILDING 1163 CATWALK
PLANS AND DETAILS
E-002
ELECTRICAL MECHANICAL
EQUIPMENT SCHEDULE
M-401
HVAC CONTROLS POINT LIST
ELECTRICAL DEMOLITION PART PLANS
FAC#157, 200, 279
ELECTRICAL DEMOLITION PART PLANS FAC#258
ELECTRICAL DEMOLITION PART PLANS FAC#310
ELECTRICAL DEMOLITION PART PLANS FAC#878
ELECTRICAL DEMOLITION PART PLANS
FAC#958, 984, 1060
ELECTRICAL DEMOLITION PART PLANS
FAC#1147, 1163
ELECTRICAL PART PLANS FAC#157, 200, 243, 279
ELECTRICAL PART PLANS FAC#210, 258
ELECTRICAL PART PLANS FAC#310
ELECTRICAL PART PLANS FAC#666, 858, 878
ELECTRICAL PART PLANS FAC#958, 984, 1060
ELECTRICAL DEMOLITION PART PLANS
FAC#1053, 1057, 1147, 1163
SECTION / DETAIL
MARK
VARIES
SEE PLAN
ELEVATION MARK
RECESS IN
SLAB
N
NORTH ARROW
TYPICAL
OPENING
MOMENT
CONNECTION
FTG. OR PILE CAP MARK
T/ FTG. OR PILE CAP EL.
(WIDTH x DEPTH)
TYPICAL BEAM
DIMENSIONS
SPAN DIRECTION
PLAN / DETAIL
MARK
METAL DECK
SPAN
DIRECTION
METAL DECK
SPAN DIRECTION
W/ CONC.
TOPPING
STRUCTURAL SYMBOLS
STRUCTURAL GENERAL NOTES
GENERAL STRUCTURAL CRITERIA
1. STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE ONCE IN
SERVICE. NO CONSIDERATION FOR STABILITY AND SHORING IS ASSUMED
BY THE ENGINEER DURING THE BUILDING PROCESS. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO INSURE THE STABILITY AND SAFETY
OF THE STRUCTURE AND ITS COMPONENTS BY DETERMINING AND
IMPLEMENTING ERECTION PROCEDURES AND SEQUENCE OF
CONSTRUCTION. THIS INCLUDES TEMPORARY BRACING AND SHORING AS
WELL AS SOIL STABILIZATION AND PROTECTIVE MEASURES FOR
ADJACENT EXISTING CONSTRUCTION.
2. STRUCTURAL DRAWINGS AND SPECIFICATIONS SHALL BE UTILIZED
CONCURRENTLY WITH ARCHITECTURAL, SITE, AND ENGINEERING
DRAWINGS OF OTHER DISCIPLINES TO CONSULT INFORMATION NOT
EXPLICITLY INDICATED ON STRUCTURAL DRAWINGS.
3. CONTRACTOR SHALL VERIFY DIMENSIONS AND SITE CONDITIONS PRIOR
TO PROCEEDING WITH PROCUREMENT OF MATERIALS AND LABOR,
FABRICATION, AND CONSTRUCTION WORK. WHERE DISCREPANCIES
EXIST, NOTIFY ARCHITECT / ENGINEER OF SUCH DISCREPANCIES IN
WRITING VIA A REQUEST FOR INFORMATION / INTERPRETATION (RFI)
BEFORE PROCEEDING WITH THE WORK IN THE AFFECTED AREA IN
QUESTION.
4. NO STRUCTURAL MEMBER OR COMPONENT SHALL BE CUT, NOTCHED, OR
OTHERWISE ALTERED UNLESS APPROVED IN WRITING BY STRUCTURAL
ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL
COSTS INCURRED BY STRUCTURAL ENGINEER FOR REVIEW OF SUCH
DEVIATIONS AND IMPLEMENTATION OF APPROPRIATE SOLUTIONS.
5. PRIOR TO COMMENCING WORK, THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR REVIEWING AND COORDINATING WITH THE SUB-
CONTRACTORS WORK INDICATED ON STRUCTURAL DRAWINGS WITH
ARCHITECTURE, SITE WORK, DELEGATED COMPONENTS, AND THE WORK
OF OTHER ENGINEERING DISCIPLINES.
6. THE STRUCTURAL DRAWINGS AND SPECIFICATIONS ARE
REPRESENTATIVE OF THE FINISHED STRUCTURE. THE STRUCTURAL
ENGINEER SHALL NOT BE IN RESPONSIBLE CHARGE AND CONTROL OF
CONSTRUCTION MEANS, METHODS, PROCEDURES AND CONSTRUCTION
TECHNIQUES, AND JOBSITE SAFETY. THIS SHALL BE THE RESPONSIBILITY
OF THE CONTRACTOR.
7. THE STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS HAVING
CONTROL, CHARGE, AND RESPONSIBILITY FOR THE ACTS AND OMISSIONS
AND FOR FAILURE OF THE CONTRACTOR, SUB-CONTRACTOR, AND OTHER
PERSONS PERFORMING THE WORK TO CARRY OUT SUCH WORK IN
ACCORDANCE WITH THE STRUCTURAL DRAWINGS AND COLLECTIVE
CONTRACT DOCUMENTS.
8. THE USE OF REPRODUCTIONS OF THESE STRUCTURAL DRAWINGS AND
SPECIFICATIONS AND USE OF ELECTRONIC FILES AND MODELS BY ANY
CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR OR MATERIAL
SUPPLIER IN LIEU OF PREPARATION OF SHOP DRAWINGS IS PROHIBITED
UNLESS PRIOR WRITTEN APPROVAL IS OBTAINED FROM THE
STRUCTURAL ENGINEER.
9. IN THE EVENT THERE IS CONFLICTING INFORMATION BETWEEN THE
DRAWINGS, SPECIFICATIONS AND LOCAL CODE APPLICATIONS OR ANY
OTHER CONTROLLING AUTHORITY, THE MOST STRINGENT CONDITION
SHALL APPLY.
SUBSTITUTIONS
1. CHANGES AND/OR SUBSTITUTIONS BY THE CONTRACTOR TO THE
STRUCTURAL PLANS, DETAILS, MATERIALS, AND OTHER INFORMATION
IN THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL.
2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO SUBMIT TO THE
STRUCTURAL ENGINEER THE APPROPRIATE DOCUMENTATION AND
INFORMATION FOR REVIEW INCLUDING BUT NOT LIMITED TO PRODUCT
APPROVALS, SKETCHES, SIGNED AND SEALED CALCULATIONS AS
APPLICABLE, AND SPECIFIC PRODUCT MATERIAL INFORMATION AS IT
COMPARES TO THE PRODUCTS / MATERIALS SPECIFIED ON THE
STRUCTURAL DRAWINGS.
3. THE INCORPORATION OF CHANGES AND/OR SUBSTITUTIONS
INCLUDING BUT NOT LIMITED TO REVIEW, RE-DESIGN, RE-ANALYSIS,
AND RE-DRAFTING INTO THE STRUCTURAL DRAWINGS IS CONSIDERED
AND ADDITIONAL SERVICE FOR THE STRUCTURAL ENGINEER.
4. UNLESS OTHERWISE AGREED UPON BETWEEN THE CONTRACTOR AND
OWNER, THE CONTRACTOR SHALL PROVIDE AN APPLICABLE CREDIT TO
THE OWNER WHERE PROPOSED SUBSTITUTED MATERIALS AND LABOR
ARE A REDUCTION IN COST TO THE ORIGINALLY SPECIFIED ITEM.
DESIGN CRITERIA
1. STRUCTURAL WORK SHALL BE IN ACCORDANCE WITH: AISC 14TH EDITION
STEEL CONSTRUCTION MANUAL AMERICAN WELDING STANDARD (AWS) D1.1
AND THE INTERNATIONAL BUILDING CODE 2018 AS ADOPTED AND
SUPPLEMENTED BY LOCAL REGULATIONS AND ASCE 7-16.
2. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR DIMENSIONS AND
ELEVATIONS NOT INDICATED ON STRUCTURAL DRAWINGS. NOTIFY
ARCHITECT / ENGINEER OF DISCREPANCIES PRIOR TO EXECUTION OF WORK.
3. COORDINATE SIZES AND LOCATIONS OF OPENINGS IN FLOORS, WALLS AND
ROOFS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND
SITE REQUIREMENTS.
4. NO PROVISIONS HAVE BEEN MADE FOR FUTURE VERTICAL AND/OR
HORIZONTAL ADDITIONS, MODIFICATIONS, AND/OR EXPANSIONS EXCEPT AS
SHOWN ON THE STRUCTURAL DRAWINGS.
5. STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR THE DESIGN OF
CATWALK SYSTEMS, HANDRAILS, CURTAIN WALL / WINDOW WALL SYSTEMS,
COLD-FORMED STEEL FRAMING, OR OTHER SYSTEMS DELEGATED OR NOT
SHOWN IN THE STRUCTURAL DRAWINGS. SUCH SYSTEMS SHALL BE
DESIGNED, FURNISHED, AND INSTALLED BY OTHER PORTIONS OF THE
CONTRACT DOCUMENTS.
6. REFERENCED DATUM FOR THE PROJECT SHALL BE TAKEN AS 0'-0"
ESTABLISHED FROM SLAB ON GRADE FINISH FLOOR. VERIFY ACTUAL
ELEVATIONS WITH CIVIL DRAWINGS.
GRAVITY LOADS
LIVE LOAD REDUCTION ON SUPPORTING ELEMENTS SHALL BE
IN ACCORDANCE WITH THE BUILDING CODE. UNIFORMED DEAD
LOAD IS ADDITIVE TO ACTUAL STRUCTURAL WEIGHTS.
LOCATION
SELF WT.
UNIFORM
DEAD LOAD
(PSF)
SELF WT.
CONC.
DEAD LOAD
(LBS)
UNIFORM
LIVE LOAD
CATWALK --- --- 40 PSF
CONC.
LIVE LOAD
(LBS)
GUARDRAIL --- 50 PLF 200 TOP RAIL
150 MID RAIL
DESIGN LOADING
INTERIOR WIND PRESSURE
WIND LOADS
PER IBC 1607.14
9 PSF (UNFACTORED)
SUBSTITUTIONS FOR SPECIALTY ENGINEERED COMPONENTS AND
SYSTEMS
1. COMPONENTS AND SYSTEMS DELEGATED TO A SPECIALTY ENGINEER
SHALL CONFORM TO THE DESIGNER OF RECORD’S DESIGN INTENT
AND SHALL NOT DEVIATE IN REQUIRMENTS WITHOUT PRIOR WRITTEN
ACCEPTANCE FROM THE DESIGNER OF RECORD.
2. THE DESIGNER OF RECORD SHALL BE COMPENSATED FOR AND
ALLOWED THIRTY CALENDAR DAYS TO APPROPRIATELY REVIEW AND
RESEARCH PROPOSED SUBSTITUTIONS PRIOR TO ISSUING APPROVAL
OR DENIAL.
3. THE CONTRACTOR SHALL BEAR THE ADDITIONAL COSTS RELATED TO
THE PROPOSED SUBSITUTION INCLUDING BUT NOT LIMITED TO
DESIGNER OF RECORD’S REVIEW TIME, COST OF SPECIALTY
ENGINEERING, COST OF DIRECT AND INDIRECT IMPACT TO OTHER
PORTIONS OF THE WORK INCLUDING RE-ENGINEERING COSTS, AND
COSTS ASSOCIATED WITH TIME AND/OR SCHEDULE DELAYS
INCURRED ON THE PROJECT.
4. OWNER’S APPROVAL OF SUBSTITUTIONS NOT APPROVED BY THE
DESIGNER OF RECORD SHALL RELIEVE THE DESIGNER OF RECORD
OF RESPONSIBILITY FOR SAID PORTION OF THE WORK AND OTHER
AREAS IMPACTED AS A RESULT OF THE UNAPPROVED SUBSTITUTION.
5. FOR UNAPPROVED SUBSTITUTIONS, IT IS THE CONTRACTOR’S
RESPONSIBILITY FOR NOTIFYING THE SPECIALTY ENGINEER THAT
THEY ARE THE DESIGNER OF RECORD FOR SUCH PORTIONS OF THE
WORK AND FOR COMPENSATING THE ENGINEER FOR SUCH
SERVICES.
6. THE DESIGNER OF RECORD FOR AN UNAPPROVED SUBSTITUTION
SHALL DEVELOP INDEPENDENT DESIGN CRITERIA FOR SUCH PROTION
OF THE WORK, SHALL NOT RELY ON PREVIOUSLY DEVELOPED AND
SUBMITTED CRITERIA, AND SHALL CREATE AN INDEPENDENT SET OF
DRAWINGS, SPECIFICATIONS, AND CALCULATIONS FOR SAID WORK.
SHOP DRAWING SUBMITTALS
1. SHOP DRAWING SUBMITTALS ARE REQUIRED FOR ALL STRUCTURAL
FRAMING, ELEMENTS, COMPONENTS, AND SYSTEMS INDICATED ON
THE STRUCTURAL DRAWINGS. SHOP DRAWING SUBMITTALS INCLUDE
BUT ARE NOT LIMITED TO THE FOLLOWING:
A. STRUCTURAL STEEL SUBMITTALS (*)
B. STRUCTURAL STEEL CONNECTIONS NOT DETAILED
OTHERWISE ON THESE DRAWINGS (*)
SHOP DRAWING SUBMITTALS FOR ITEMS NOT LISTED ABOVE SHALL BE
SUBMITTED FOR REVIEW UPON REQUEST BY THE STRUCTURAL
ENGINEER, OR AS INDICATED IN THE SPECIFICATIONS.
ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF THE
PROJECT.
ITEMS MARKED (#) SHALL BE SUBMITTED FOR ENGINEERS RECORD
ONLY.
2. SHOP DRAWINGS SHALL BE REVIEWED BY THE STRUCTURAL
ENGINEER FOR COMPLIANCE WITH DESIGN INTENT AND FOR
GENERAL CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
CORRECTIONS OR COMMENTS MADE ON THE SHOP DRAWINGS SHALL
NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE
STRUCTURAL DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR CONFORMING AND CORRELATING
QUANTITIES, DIMENSIONS, ELEVATIONS, AND LENGTHS, FOR
SELECTING FABRICATION PROCESSES, FOR SELECTING METHODS OF
CONSTRUCTION, FOR COORDINATING SUB TRADES AND FOR
PERFORMING WORK IN A SAFE MANNER.
3. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR AND
MARKED "APPROVED" PRIOR TO SUBMITTING THE DRAWINGS TO THE
ARCHITECT ENGINEER FOR REVIEW. SHOP DRAWINGS SHALL BE
MARKED WITH A REVIEW STAMP FROM THE CONTRACTOR INDICATING
REVIEW DISPOSITION AND SHALL BE DATED AND INITIALED. SHOP
DRAWINGS THAT HAVE NOT BEEN REVIEWED, STAMPED, DATED AND
INITIALED WILL BE CONSIDERED NOT REVIEWED BY THE CONTRACTOR
AND SHALL BE RETURNED NOT REVIEWED AND UNCHECKED BY THE
STRUCTURAL ENGINEER.
4. STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR DELAYS
CAUSED DUE TO THE REJECTION OF INCOMPLETE SUBMITTALS,
SUBMITTALS RETURNED DUE TO THE CONTRACTOR'S FAILURE TO
REVIEW DOCUMENTS PRIOR TO RECEIPT BY THE STRUCTURAL
ENGINEER, AND FOR THE ADDITIONAL TIME REQUIRED BY THE
CONTRACTOR'S SUB TRADES TO REVISE AND RE-SUBMIT THE
DRAWINGS AND FOR THE STRUCTURAL ENGINEER TO PERFORM
ADDITIONAL REVIEWS OF NON-CONFORMING SUBMITTALS.
5. UPON RECEIPT OF SHOP DRAWING SUBMITTALS FROM THE
CONTRACTOR THAT HAVE BEEN REVIEWED, STAMPED, DATED, AND
INITIALED BY THE CONTRACTOR, THE ENGINEER SHALL BEGIN
REVIEW OF THE RECEIVED SUBMITTALS. THE CONTRACTOR SHALL
ALLOW FOURTEEN (14) WORKING DAYS FOR SUBMITTAL REVIEW BY
THE STRUCTURAL ENGINEER FROM RECEIPT OF SHOP DRAWINGS.
THE CONTRACTOR SHALL FURTHER ALLOW TEN (10) WORKING DAYS
FROM RECEIPT OF SHOP DRAWING RE-SUBMITTALS FOR REVIEW BY
THE STRUCTURAL ENGINEER.
6. THE STRUCTURAL ENGINEER'S OBLIGATIONS TO REVIEW SHOP
DRAWINGS AND OTHER SUBMITTALS AND TO RETURN THEM IN A
TIMELY MANNER ARE CONDITIONED UPON THE PRIOR REVIEW AND
APPROVAL OF THE SHOP DRAWINGS OR SUBMITTALS BY THE
CONTRACTOR AS REQUIRED IN THE CONSTRUCTION CONTRACT AND
THE CONTRACTOR'S SUBMITTAL OF THE SHOP DRAWINGS AND OTHER
SUBMITTALS IN ACCORDANCE WITH A WRITTEN SCHEDULE
DISTRIBUTED IN ADVANCE TO THE ENGINEER IDENTIFYING THE DATES
FOR THE SUBMITTAL OF THE VARIOUS SHOP DRAWINGS AND
SUBMITTALS.
7. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR
MATERIALS THAT ARE FABRICATED, DELIVERED, AND INSTALLED AT
THE SITE WITHOUT A SET OF SHOP SUBMITTALS THAT HAVE BEEN
REVIEWED AND APPROVED BY THE STRUCTURAL ENGINEER. COSTS
ASSOCIATED WITH THE REMOVAL OF UNAPPROVED MATERIALS AND
THE DELAYS ASSOCIATED WITH THE REPAIR, RECONFIGURATION,
AND/OR REMOVAL OF SUCH MATERIALS SHALL NOT BE THE
RESPONSIBILITY OF THE STRUCTURAL ENGINEER.
8. SHOP DRAWINGS REVIEWED BY THE STRUCTURAL ENGINEER AND
RETURNED WITH A MARK OF 'REJECTED' OR 'REVISE AND RESUBMIT'
SHALL BE RE-SUBMITTED FOR REVIEW BY THE STRUCTURAL
ENGINEER. REVISIONS MADE TO SHOP DRAWINGS SHALL BE CLEARLY
MARKED AND THE PURPOSE FOR THE RE-SUBMISSION SHALL BE
CLEARLY NOTED ON THE SHOP DRAWING TRANSMITTAL. REVISIONS
SHALL BE ASSIGNED A SEQUENTIAL REVISION NUMBER.
9. THE CONTRACT DOCUMENTS SHALL GOVERN OVER THE SHOP
DRAWINGS UNLESS OTHERWISE SPECIFIED IN WRITING BY THE
ENGINEER.
SPECIALITY ENGINEER REQUIREMENTS AND SUBMITTALS
1. THE TERM "DELEGATE ENGINEER" SHALL REFER TO A REGISTERED
PROFESSIONAL ENGINEER RETAINED BY THE CONTRACTOR TO
PROVIDE DESIGN AND FABRICATION SUBMITTALS AND CALCULATIONS
FOR THE COMPONENTS DELEGATED BY THE STRUCTURAL ENGINEER
OF RECORD HEREIN.
2. WHERE NOTED ON THIS SET OF CONSTRUCTION DOCUMENTS AND AS
INDICATED BELOW, THE CONTRACTOR SHALL ENGAGE THE SERVICES
OF A DELEGATED ENGINEER TO PROVIDE SPECIALTY ENGINEERING
SERVICES FOR STRUCTURAL COMPONENTS THESE COMPONENTS
SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
A. STRUCTURAL STEEL CONNECTIONS NOT DETAILED OTHERWISE ON
THESE DRAWINGS
B. STEEL CATWALK SYSTEMS
3. THE DELEGATE ENGINEER FOR EACH COMPONENT SHALL BE A
REGISTERED PROFESSIONAL ENGINEER CURRENT AND IN GOOD
STANDING WITH THE STATE OF THE PROJECT WITH A MINIMUM OF FIVE
(5) YEARS OF EXPERIENCE IN DESIGN FOR EACH SPECIFIC
COMPONENT.
4. THE DELEGATE ENGINEER SHALL BE THE ENGINEER OF RECORD FOR
THE AFOREMENTIONED COMPONENTS AND SHALL SUBMIT SIGNED AND
SEALED CALCULATIONS AND DRAWINGS FOR REVIEW BY THE
STRUCTURAL ENGINEER.
5. CALCULATIONS AND DRAWINGS SUBMITTED BY THE DELEGATE
ENGINEER FOR REVIEW BY THE ENGINEER SHALL INCLUDE CLEARLY
DEFINED DESIGN CRITERIA, DESIGN PROCEDURES, STRUCTURAL LOADS,
CODE COMPLIANCE, REQUIRED DETAILS, AND LAYOUTS. DOCUMENTS
SHALL BE IN CONFORMANCE WITH PARAGRAPH 5 OF THIS SECTION.
6. THE DELEGATE ENGINEER SHALL ALSO BE RESPONSIBLE FOR
GENERATING ERECTION DRAWINGS AND FABRICATION PROCEDURES
FOR THE SPECIALTY ENGINEERED COMPONENTS.
7. REVIEW OF CALCULATIONS AND DRAWINGS SUBMITTED BY THE
DELEGATE ENGINEER TO THE STRUCTURAL ENGINEER SHALL BE LIMITED
TO THE VERIFICATION THAT THE DELEGATE ENGINEER HAS UTILIZED THE
DESIGN CRITERIA SPECIFIED AND HAS UNDERSTOOD THE INTENT OF THE
DESIGN. THE STRUCTURAL ENGINEER WILL NOT MAKE A DETAILED
CHECK OF THE CALCULATIONS AND DESIGN PROCESSES UTILIZED BY
THE DELEGATE ENGINEER. THE DELEGATE ENGINEER SHALL BE
RESPONSIBLE FOR THE STRUCTURAL INTEGRITY OF THE SPECIALTY
COMPONENTS.
8. REFER TO SHOP DRAWING SUBMITTAL SECTION FOR ADDITIONAL
INFORMATION REGARDING SUBMITTAL PROCEDURES AND
REQUIREMENTS.
9. SPECIALITY ENGINEER TO COORDINATE WITH THE ORIGINAL BUILDING
DESIGNER TO CONFIRM THE ADEQUACY OF THE EXISTING STRUCTURE
TO CARRY THE CATWALK AND ADDITIONAL FRAMING LOADS.
OPERATION AND MAINTENANCE
1. STRUCTURES REQUIRE PERIODIC MAINTENANCE TO EXCEED LIFE SPAN
AND TO ENSURE STRUCTURAL INTEGRITY FROM EXPOSURE TO THE
ENVIRONMENT. A PLANNED PROGRAM OF MAINTENANCE SHALL BE
ESTABLISHED BY THE OWNER.
2. THIS PROGRAM SHALL INCLUDE ITEMS SUCH AS, BUT NOT LIMITED TO,
PAINTING OF STRUCTURAL STEEL, PROTECTIVE COATINGS FOR CONCRETE,
SEALANTS, CAULKED JOINTS, EXPANSION JOINTS, CONTROL JOINTS,
SPALLS AND CRACKS IN CONCRETE, AND PRESSURE WASHING OF
EXPOSED STRUCTURAL ELEMENTS EXPOSED TO SALT ENVIRONMENT OR
OTHER HARSH CHEMICALS.
REQUIRED STRUCTURAL INSPECTIONS
1. INSPECTIONS BY THE BUILDING OFFICIAL.
A. FRAMING INSPECTION SHALL BE MADE AFTER ALL ROUGH
MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS IN
PLACE, BUT PRIOR TO FIREPROOFING OR WALL COVERING IS
INSTALLED.
2. IN ACCORDANCE WITH THE REQUIREMENTS OF THE BUILDING CODE, THE
OWNER WILL PROVIDE QUALIFIED PERSONNEL TO PERFORM THE
FOLLOWING SPECIAL INSPECTIONS AND REPORT THE FINDINGS TO THE
ENGINEER. THIS DOES NOT RELIEVE THE CONTRACTOR OF ANY
RESPONSIBILITY TO PERFORM THE WORK IN ACCORDANCE WITH THE
DESIGN DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE INSPECTOR 24
HOURS IN ADVANCE OF ALL INSPECTIONS.
A. FRAMING INSPECTIONS DURING THE ERECTION OF ALL STEEL
FRAMING MEMBERS. INSPECTIONS OF ALL DECKING PLACEMENT
AND ATTACHMENTS.
B. HIGH-STRENGTH BOLTS SHALL BE INSPECTED DURING
INSTALLATION AND TIGHTENED IN ACCORDANCE WITH THE CODE.
C. SPRAY-APPLIED FIREPROOFING INSPECTIONS SHALL BE MADE IN
ACCORDANCE WITH THE CODE.
D. ALL WELDS TO BE INSPECTED BY A CERTIFIED WELDING
INSPECTOR AT OWNERS EXPENSE.
MISCELLANEOUS
1. THE CONTRACTOR SHALL PROVIDE THE FOLLOWING SERVICES AS PART
OF THE CONSTRUCTION SCOPE OF WORK:
A. VERIFICATION OF ALL DIMENSIONS, ELEVATIONS, AND OPENING
SIZES, PRIOR TO STARTING WORK.
B. REVIEW AND APPROVE ALL SHOP DRAWINGS PRIOR TO SUBMITTAL,
NOTING CHANGES MADE WHICH DO NOT COMPLY WITH DESIGN
DRAWINGS.
C. PROVIDE TEMPORARY BRACING AND SHORING AS NEEDED TO
PREVENT EXCESSIVE DEFLECTIONS AND DAMAGE DURING
CONSTRUCTION. DESIGN OF TEMPORARY BRACING AND SHORING
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
EXISTING STRUCTURE
1. INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE
DRAWINGS WAS TAKEN FROM A PARTIAL SET OF THE FOLLOWING:
PREPARED BY: CURT DAVIS & ASSOCIATES, ARCHITECTS
ENTITLED: EAGLE VISION FACILITY: McENTIRE AIR NATIONAL GUARD
STATION
DATE: 8/18/03
AND BY A PARTIAL SET OF THE FOLLOWING:
PREPARED BY: BUTLER MANUFACTURING COMPANY
ENTITLED: SC AIR NG, RICHLAND, SC
DATE: 7/11/03
2. WORK SHOWN ON THESE DRAWINGS ASSUMES THAT THE ORIGINAL
CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE
INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO)
DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC.
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO
NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR
CONFLICTS.
3 DESIGNER OF EXISTING STRUCTURE TO PROVIDE CONFIRMATION
THAT EXISTING STRUCTURE CAN CARRY LOADS IMPOSED BY THE
CATWALK.
STRUCTURAL STEEL FRAMING
1. STRUCT STEEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
BUILDING CODE AND AISC SPECIFICATIONS FOURTEENTH EDITION.
2. STRUCT STEEL SHALL MEET THE FOLLOWING REQUIREMENTS UNO ON
THE DWGS:
TYPE ASTM GRADE
WIDE-FLANGE TYPE SHAPES (W, S & M) A992 50
ANGLES, CHANNELS AND PLATES A36 -----
PIPE A53 B TYPE E
STRUCT TUBING A500 C
ANCHOR BOLTS A1554 W/S1 -----
STRUCT BOLTS A325N -----
ERECTION BOLTS A307 -----
3. ALL CONNECTIONS NOT DETAILED OR OTHERWISE NOTED SHALL BE
DESIGNED BY THE FABRICATOR OR SPECIALTY ENGINEER. SHOP DWGS
AND CONNECTION CALCULATIONS SHALL BE SUBMITTED BEARING THE
SEAL OF AN ENGINEER REGISTERED IN THE STATE WHERE THE
PROJECT IS LOCATED.
A. BEAM SHEAR CONNECTIONS SHALL BE STANDARD AISC
CONNECTIONS, AND SHALL BE DESIGNED PER SCHED.
DESIGN SHALL BE BASED ON BEARING TYPE BOLTED
CONNECTIONS WITH BOLTS "SNUG TIGHT" PER AISC. WELDED
TYPE CONNECTIONS SHALL BE APPROVED FOR USE PRIOR TO
SUBMITTAL OF SHOP DWGS.
B. ALL MOMENT CONNECTIONS ON THE DWGS SHALL
DEVELOP THE FULL MOMENT CAPACITY OF THE CONNECTED
MEMBERS. MOMENT CONNECTIONS SHALL BE WELDED TYPE.
BOLTED MOMENT CONNECTIONS USING FRICTION TYPE
PRETENSIONED BOLTS SHALL BE APPROVED FOR USE PRIOR
TO SUBMITTAL OF SHOP DWGS. DIRECT TENSION
INDICATOR (DTI) WASHERS SHALL BE USED TO INSURE
PROPER TENSIONING.
C. ALL WELDING SHALL BE IN ACCORDANCE WITH LATEST AWS
D1.1. AND USE E70XX ELECTRODES. ALL WELD SHALL BE
TOUCHED UP WITH ZINC-RICH PROTECTIVE PAINT FOR
CORROSION RESISTANCE.
PROFESSIONAL SEAL
In c h e s
/2
/4
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.comCopyright © Atkins Limited (2016)
+1 407 647 7275 +1 407 806 4500
Tel:
Fax:
482 South Keller Road Orlando
FL 32810
BA C D E F G H
Client Project Number PSTE152605
GENERAL NOTES, ABBREVIATIONS
& SYMBOLS
McEntire JNGB Repair
EB
2/05/2019
CS JI JI
TYPE B-3
South Carolina Air National Guard 169th Civil Engineer Squadron, McEntire JNGB
S-001
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MPH MILES PER HOUR
NIC NOT IN CONTRACT
NO NUMBER
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTERS
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
PAF POWDER ACTIVATED FASTENERS
PAR PARALLEL
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FEET
PCI PRECAST CONCRETE INSTITUTE
PCL PRECAST/PRESTRESSED CONCRETE LINTEL
PEMB PRE ENGINEERED METAL BUILDING
PEN PENETRATION
PJF PREMOLDED BITUMINOUS JOINT FILLER
PL PROPERTY LINE, PLATE
PLF POUNDS PER LINEAR FOOT
PLY PLYWOOD
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCING
REQD REQUIRED
RTU ROOF TOP UNIT
RW RETAINING WALL
SBP SOIL BEARING PLATE
SCHED SCHEDULE
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SOG SLAB ON GRADE
Sp SECTION MODULES
SPC SPACE/SPACES
SPCG SPACING
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL
SYM SYMMETRICAL
SYP SOUTHERN YELLOW PINE WOOD
T&B TOP AND BOTTOM
T/, TO TOP OF
TB TIE BEAM
TDS TURN DOWN SLAB
TEMP TEMPERATURE
TENS TENSION
THD THREAD/THREADED
THK THICK
TOL TOLERANCE
TS TUBE STEEL/THICKENED SLAB
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE (ALSO UON)
VERT VERTICAL
VOL VOLUME
VWP VERIFY WITH PROCESS
W WIDE FLANGE
W/ WITH
WD WOOD
WF WALL FOOTING
WH WEEP HOLE
WO, W/O WITHOUT
WP WORKING POINT, WATERPROOF
WS WELDED STUD
WT WEIGHT, STRUCTURAL TEE SECTION
WWF WELDED WIRE FABRIC
Ø DIAMETER
# POUNDS
& AND
+/- PLUS OR MINUS
@ AT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLTS
ABBREV ABBREVIATION
ACI AMERICAN CONCRETE INSTITUTE
ADD ADDITIVE
ADDL ADDITIONAL
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALT ALTERNATE/ALTERNATIVE
ALUM, AL ALUMINUM
ARCH ARCHITECTURE/ARCHITECTURAL
ASPH ASPHALT
ASTM AMERICAN SOCIETY OF TESTING MATERIALS
AWS AMERICAN WELDING SOCIETY
B/, BO BOTTOM OF
BFF BELOW FINISH FLOOR
BIT BITUMINOUS, BITUMASTIC
BLDG BUILDING
BLK BLOCK
BM BENCH MARK
BM BEAM
BOT BOTTOM
BP BASE PLATE/BEARING PLATE
BRG BEARING
BTWN BETWEEN
BU BUILT-UP
C CHANNEL
CB CONCRETE BEAM
CC CONCRETE COLUMN
CF CUBIC FEET (FOOT)
CI CAST-IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLR CLEAR/CLEARANCE
CM CONCRETE MASONRY
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO COMPANY
COL COLUMN
CONC CONCRETE
CONN CONTINUOUS
CONST CONSTRUCTION
COORD COORDINATE
CS CAST-STEEL
CSJ CONSTRUCTION JOINT
CTR CENTER
CTRD CENTERED
CV CUBIC YARD
DBA DEFORMEDABLE BAR ANCHOR(WELDABLE
REBARS)
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIST DISTANCE
DN DOWN
DR DRAIN
DWG DRAWING
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION, ELEVATOR
ELEC ELECTRIC/ELECTRICAL
ENGR ENGINEER
EQ SP EQUAL SPACED
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FF FLR FINISHED FLOOR
FIN FINISH
FIN GR FINISH GRADE
FOW EXTERIOR FACE OF WALL (REVEAL SIDE)
FP FULL PENETRATION WELD
FS FAR SIDE
FT FEET/FOOT
FTG FOOTING
GA GAGE/GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GRID LINE
GS GALVANIZED STEEL
GSN GENERAL STRUCTURAL NOTES
HCS HOLLOW CORE SLAB
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSB HIGH STRENGTH BOLT (A-325)
HT HEIGHT
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INT INTERIOR
INV INVERT
Ip MOMENT OF INERTIA
JST JOIST
JT JOINT
K 1,000 POUNDS (KIP)
KWY KEYWAY
L ANGLE
LDG LANDING
LG L LONG ANGLE
LGTH LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT WT LIGHT WEIGHT
MATL MATERIAL
MAX MAXIMUM
MB MASONRY BEAM, MACHINE BOLT
MECH MECHANICAL
MEP, M/E/P MECHANICAL,ELECTRICAL,PLUMBING
MET METAL
MFR MANUFACTURE/MANUFACTURER
MID MIDDLE
STRUCTURAL ABBREVIATIONS
NOTE: ABBREVIATIONS MAY BE SHOWN WITH OR
WITHOUT PERIODS (IE, AWS OR A.W.S.)
JOHN AZIZ ILTER OKLAHOMA P.E. NO 22929 DATE: 2/6/2019
CORR
MEN'S TOILET
WOMEN'S TOILET
S-201
S-201
(F
IE
L D
V E
R
IF
Y
/4
(F
IE
L D
V E
R
IF
Y
/4
(FIELD VERIFY)
9' - 8"
HVAC UNIT
HVAC UNIT
NEW DOOR
OPENING BY
OTHERS
NOTES:
1. FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS.
2. CATWALK AND GUARDRAIL TO BE PRE-MANUFACTURED AND OSHA COMPLIANT.
NEW
PREFABRICATED
CATWALK, ABI #1
N13
N15
N24
N23
N18
N17
N21
N14
N16
N22
N20
N19
UNFACTORED DEAD LOAD REACTION TABLE
Fx Fy Fz
FORCES (KIPS) MOMENTS (KIP*FT)
Mx My Mz
0.00 0.22 0.00 0.00 0.00 0.01
0.00 0.28 -0.01 -0.03 0.00 0.00
0.00 0.22 0.00 0.00 0.00 0.01
0.00 0.24 0.00 -0.01 0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.01
0.00
0.18
0.17
0.35
0.34
0.40
0.39
0.18
0.18
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.01
0.00
0.00
-0.01
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.01
0.01
0.06
0.06
NODE
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
UNFACTORED INTERNAL WIND DOWN REACTION TABLE
NODE
FORCES (KIPS) MOMENTS (KIP*FT)
0.00 0.04 0.00 0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00 0.00
0.00 0.03 0.00 0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.01
0.08
0.10
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.04
0.08
0.10
0.02
0.04
0.02
Fx Fy Fz Mx My Mz
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
UNFACTORED INTERNAL WIND LOAD X REACTION TABLE
NODE
FORCES (KIPS) MOMENTS (KIP*FT)
-0.01 0.00 0.00 0.00 0.00
-0.02 0.00 -0.04
0.00 0.00 0.00
0.00 0.00
0.01
-0.18
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.02
0.00 0.00
0.00
0.00
0.00
-0.14
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.14
0.01
-0.19
0.19
0.00
-0.02
0.19
0.00
0.00
-0.02
-0.02
-0.03
-0.02
-0.03
-0.02
-0.03
-0.02
-0.03
-0.03
-0.03
Fx Fy Fz Mx My Mz
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
UNFACTORED INTERNAL WIND LOAD Z REACTION TABLE
NODE
FORCES (KIPS) MOMENTS (KIP*FT)
0.06 -0.04 0.15 -0.01
0.23
0.06
0.15
0.15 0.01
0.05
-0.20 0.07
0.04
0.04
-0.22
0.22
-0.26
0.30
0.60
-0.30
-0.55
0.01
0.02
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.06
0.03
-0.05
-0.07
-0.04
-0.02
-0.04
-0.04
-0.02
-0.02
-0.02
-0.02
-0.02
-0.02
0.15
0.06
0.04
0.06
0.06
0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
0.01
-0.01
-0.01
0.02
-0.02
-0.02
0.01
-0.01
-0.01
0.01
Fx Fy Fz Mx My Mz
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
UNFACTORED INTERNAL WIND UP REACTION TABLE
NODE
FORCES (KIPS) MOMENTS (KIP*FT)
0.00 -0.04 0.00 0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00 0.00
0.00 -0.03 0.00 0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.01
-0.08
-0.10
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.02
0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.04
-0.08
-0.10
-0.02
-0.04
-0.02
Fx Fy Fz Mx My Mz
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
UNFACTORED LIVE LOAD CONCENTRATED REACTION TABLE
NODE
FORCES (KIPS) MOMENTS (KIP*FT)
0.00 0.05 0.00 0.00 0.00 0.00
0.00 0.07 0.00 0.00
0.00 0.00 0.00 0.00
0.00 0.06 0.00 0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.13
0.12
0.13
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.03
0.00 0.00
0.00
0.00
0.00
0.00
0.05
0.02
0.13
0.00
0.00
0.00
0.00
0.00
Fx Fy Fz Mx My Mz
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
UNFACTORED LIVE LOAD UNIFORM REACTION TABLE
NODE
FORCES (KIPS) MOMENTS (KIP*FT)
0.00 0.18 0.00 0.00 0.00 0.01
0.00 0.16 0.00 0.00
0.00 0.18 0.00 0.00 0.00 0.01
0.00 0.14 0.00 0.00 0.00
0.00
0.00
0.00
0.00
0.00
0.00
-0.01
0.00
0.07
0.38
0.37
0.46
0.45
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.07
0.07
0.07
0.00 0.00
0.00
0.00
0.00
Fx Fy Fz Mx My Mz
N13
N14
N15
N16
N17
N18
N19
N20
N21
N22
N23
N24
X
Z
Y
PROFESSIONAL SEAL
In c h e s
/2
/4
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.comCopyright © Atkins Limited (2016)
+1 407 647 7275 +1 407 806 4500
Tel:
Fax:
482 South Keller Road Orlando
FL 32810
BA C D E F G H
Client Project Number PSTE152605
BUILDING 1163 CATWALK OVERALL
PLAN
McEntire JNGB Repair
EB
2/05/2019
CS JI JI
TYPE B-3
South Carolina Air National Guard 169th Civil Engineer Squadron, McEntire JNGB
S-101
SCALE: 1/4" = 1'-0"1
BUILDING 1163 - FIRST FLOOR CEILING PART PLAN
SCALE:2
3D VIEW
NOTE:
THESE REACTIONS ARE A MINIMUM AND MAY INCREASE DEPENDING
ON THE FRAMING DESIGNED BY THE CATWALK MANUFACTURER.
AC-1163-1
AC-1163-2
AC-1163-1
AC-1163-2
TYP
TYP
W6X8.5W6X8.5
STEEL GRATING
CL
E Q
E Q
CATWALK HANGER
RAILING, TYP
NOTES:
1. CONNECTIONS DESIGNED BY CATWALK MANUFACTER.
2. ATTACH METAL BAR GRATING PER MANUFACTURE'S
DETAILS.
3. ENSURE HANGER AND W-BEAM FRAMING SIZES ALLOW FOR
REQUIRED WELDING CLEARANCE BETWEEN HANGER AND
BEAM CONNECTION
STL PL
STIFFENER
T/STEEL
S-201
13' - 4 1/4" 3' - 0"
NOTES:
1. NOTCH GRATING AS REQUIRED AROUND POSTS AND HANGERS.
MIN 3/4"x3/16" STEEL WELDED BAR
GRATING. ATTACH PER
MANUFACTURER'S INSTRUCTIONS
ANGLE BRACES
AS NEEDED, TYP
S-201
6' - 8 1/8" 6' - 8 1/8" 2' - 9"
/8
/8
EQ EQ EQ EQ
HVAC UNIT
HVAC UNIT
DIAGONAL BRACING
AS NEEDED, TYP
NOTES:
1. COMPLY WITH OSHA REGULATIONS FOR CATWALK AND GUARDRAIL DESIGN.
CATWALK AND GUARDRAIL TO BE DESIGNED BY SPECIALTY ENGINEER.
2. FIELD VERIFY ALL DIMENSIONS.
3. CATWALK DESIGNER TO PROVIDE SIGNED AND SEALED CALCULATIONS FOR
REVIEW.
6" DEEP WIDE FLANGE FRAMING, MIN, TYP
3" MIN SQUARE HSS
VERT SUPPORT, TYP
Pip e1
-1 /2
STD
Pip e1
-1 /2
STD
Pip e1
-1 /2
STD
Pip e1
-1 /2
STD
L3X3X1/2 L3X3X1/2 L3X3X1/2 L3X3X1/2
PROFESSIONAL SEAL
In c h e s
/2
/4
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.comCopyright © Atkins Limited (2016)
+1 407 647 7275 +1 407 806 4500
Tel:
Fax:
482 South Keller Road Orlando
FL 32810
BA C D E F G H
Client Project Number PSTE152605
BUILDING 1163 CATWALK PLANS
AND DETAILS
McEntire JNGB Repair
EB
2/05/2019
CS JI JI
TYPE B-3
South Carolina Air National Guard 169th Civil Engineer Squadron, McEntire JNGB
S-201
SCALE: 1 1/2" = 1'-0"3
ABI #1 CATWALK HANGER BASE CONNECTION
SCALE: 3/4" = 1'-0"2
ABI #1 CATWALK GRATING PLAN
SCALE: 3/4" = 1'-0"1
ABI #1CATWALK FRAMING PLAN
NOTES:
1. PROVIDE ADDITIONAL ROOF FRAMING AS NECESSARY.
2. FIELD VERIFY ALL DIMENSIONS.
3. COORDINATE ADDITIONAL FRAMING AND CATWALK PLACEMENT WITH BUTLER
MANUFACTURING COMPANY AND MECHANICAL. SPECIALITY ENGINEER FOR
CATWALK TO BE RESPONSIBLE FOR ADDITIONAL FRAMING DESIGN.
PROPOSED LOCATIONS OF
STEEL COLUMNS HUNG
FROM EXISTING TAPERED
FRAME AND PURLINS, TYPEXIST PURLIN, TYP
EXIST TAPERED FRAME
PROPOSED CATWALK
PLATFORM BELOW
PROPOSED ADDITIONAL
FRAMING SUPPORTS
BETWEEN PURLINS, TYP
S-202
TYP
HSS CATWALK
HANGER
EXIST ROOF
EXIST STEEL FRAME
OR ADDITIONAL
FRAMING SUPPORT
BRACING
3 SIDES
A
SECTION A-A
A
1/4" STEEL
STIFFENER
PL, TYP
1/4" STEEL
STIFFENER
PL
PROFESSIONAL SEAL
In c h e s
/2
/4
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.comCopyright © Atkins Limited (2016)
+1 407 647 7275 +1 407 806 4500
Tel:
Fax:
482 South Keller Road Orlando
FL 32810
BA C D E F G H
Client Project Number PSTE152605
BUILDING 1163 CATWALK PLANS
AND DETAILS
McEntire JNGB Repair
EB
2/05/2019
CS JI JI
TYPE B-3
South Carolina Air National Guard 169th Civil Engineer Squadron, McEntire JNGB
S-202
SCALE: 3/4" = 1'-0"1
ABI #1 CATWALK ROOF FRAMING PLAN
SCALE: 1 1/2" = 1'-0"2
ABI #1 CATWALK HANGER TOP CONNECTION
| G-001 - COVER SHEET |
| G-002 - DRAWING INDEX AND MAPS |
| S-001 - GENERAL NOTES, ABBREVIATIONS & SYMBOLS |
| S-101 - BUILDING 1163 CATWALK OVERALL PLAN |
| S-201 - BUILDING 1163 CATWALK PLANS AND DETAILS |
| S-202 - BUILDING 1163 CATWALK PLANS AND DETAILS |