OPEN OFFICE AREA

VAULT

VAULT

VAULT

INFO ASSURANCE OFFICE

OPEN OFFICE AREA

VAULT

VAULT

VAULT

INFO ASSURANCE OFFICE

10x16

Ø

12Ø

12Ø

Ø

Ø

Ø

ELEC PANEL BP (208V/120V)

ELEC PANEL Q (208V/120V)

ELEC PANEL "RP" (208V/120V)

CRAC AC UNIT

RS & RL

AC PUMPED CONDENSATE

SA DUCT

AC-258-1

AC-258-2

RS & RL

CU-258-1

CU-258-2

SA

RA

1" CD

CONCRETE PAD - EXTEND 4"

BEYOND EQUIPMENT ALL SIDES

COMMUNICATIONS BOX

A S

P H

A L

T

S

L O

P E

D

D

O W

N

CONCRETE PAD

AC-279-1

30x10 SA HIGH

30x14 RA LOW

28x8 SA HIGH

28x14 RA LOW

SHEET METAL

ENCLOSURE

CONCRETE EQUIPMENT

PAD (EXTEND 4" BEYOND

EQUIPMENT, ALL SIDES)

EMCS GATEWAY IN CABINET

MECHANICAL ROOM 107

SERVER ROOM 108

MECHANICAL ROOM 107

SERVER ROOM 108

18x18

18x18

8Ø

M

Ø

MAIN ELECTRICAL

DISTRIBUTION

PANEL "M"

ELECTRICAL

PANEL "A"

2" G

2" CW BELOW SLAB

3/4" UP TO DOMESTIC

WATER HEATER

GAS METER/HOUSE

REGULATOR

2" DOMESTIC

WATER SERVICE

G

W

METER VAULT

PROFESSIONAL SEAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-3

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

TRUE

NORTH

WPL REP DLH WPL

M-102

HVAC PART PLANS

FAC#210, 258, 279

1/4"=1'-0"

1/4" = 1'-0" M-102

B

BLDG 258 - VAULTS 129, 130 & 131

1/4" = 1'-0"

M-102

C

BLDG 279 - BARRIER SHED

1/4" = 1'-0"

M-102

A

BLDG 210 - PART PLAN

KEY NOTES:

PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.

PROVIDE WATER METER & INTEGRATE WITH BASE EMS.

PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.

RE-INSTALL AND/OR REPLACE ACOUSTICAL CEILING TILES & GRID.

RE-INSTALL LIGHT FIXTURES.

SPILL CONDENSATE DRAIN TO GRADE.

CONDENSATE DRAIN PIPING, SPILL TO GRADE.

2. EXISTING CRAC UNIT SHALL NOT BE REMOVED UNTIL NEW CEILING CRAC UNIT

IS INSTALLED AND FULLY FUNCTIONING. REFER TO DEMOLITION DRAWINGS.

GENERAL NOTES:

BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR FLOWS TO VALUES

MEASURED PRIOR TO DEMOLITION OF THE EXISTING UNITS.

1.

OFFICE

102D

OFFICE

102C

OFFICE

OFFICE

102B

OFFICE

102A

CLASSROOM

MEN

MEN

MECHANICAL

PAINT SHOP

BAY "A1"

BAY "A1"

BAY "B"

AC-310-1

RS & RL

AC-310-2 ON ROOF

AC-310-3 ON ROOF

CU-310-1

PREFAB PAD

EX CU

EMCS GATEWAY

IN CABINET

AC-310-2/

AC-310-3

ROOF CURB

EX ROOFING

EX INSULATION

EX BAR JOISTS

22x10 SR

(ONE ON EACH SIDE

OF SA PLENUM)

24x30 SA PLENUM

22x28 SA

18x30 RA PLENUM

18x30 RAG

CONDENSATE DRAIN

PIPING - EXTEND TO

NEAREST ROOF DRAIN

PROFESSIONAL SEAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-3

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

TRUE

NORTH

WPL REP DLH WPL

M-103

HVAC PART PLANS

FAC#310

1/8"=1'-0"

1/8" = 1'-0" M-103

A

BLDG 310 - PART PLAN

KEY NOTES:

PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.

PROVIDE WATER METER & INTEGRATE WITH BASE EMS.

PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.

RE-INSTALL AND/OR REPLACE ACOUSTICAL CEILING TILES & GRID.

RE-INSTALL LIGHT FIXTURES.

REPAIR ROOFING AND FLASH AT EQUIPMENT ROOF CURB.

PROVIDE CONDENSATE DRAIN PIPING CONNECTION TO AC UNIT

AND CONNECT TO EXISTING CONDENSATE DRAIN PIPING.

1/4" = 1'-0"

M-103

B

ROOF SECTION - AC-310-2/AC-310-3

GENERAL NOTES:

BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR FLOWS TO VALUES

MEASURED PRIOR TO DEMOLITION OF THE EXISTING UNITS.

EXISTING ROOF IS UNDER WARRANTY. REMOVE, MODIFY AND REPAIR

ROOFING AS REQUIRED BY ROOF MANUFACTURER.

ROOF CURBS SHALL BE NEW UNLESS OTHERWISE INDICATED.

1.

2.

3.

BREAK ROOM

MAIN ELEC PANEL

120V/240V, 200 A MAIN

EMCS GATEWAY IN CABINET

VAULT AREA

ELEC SWITCHGEAR

(480V/277V, 600 A RATING,

800 A MAIN)

MECHANICAL ROOM 112MECHANICAL ROOM 112

CHWR

CHWS

C H

W R

C H

W S

3/4"

1-1/2"

2-1/2"

HWS

HWR

CHWS

CHWR

2-1/2"

B-1

B-2

HWP-1

HWP-2

UH

FCU-1

CHP-1

CHP-2

CHP-3

UH

M

EX GAS

METER

EX CONC. PAD

TO REMAIN

EX CONC. PAD

TO REMAIN

CH-878-1

CH-878-2

2-1/2" CHWS & CHWR

2-1/2" CHWS

& CHWR

NORMAL ELECTRICAL ROOM

MAIN SWITCHGEAR

PROFESSIONAL SEAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-3

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

TRUE

NORTH

1/4" = 1'-0"

M-104

C

BLDG 878 - PART PLAN

WPL REP DLH WPL

M-104

HVAC PART PLANS

FAC#666, 858, 878

1/4"=1'-0"

1/4" = 1'-0"

M-104

A

BLDG 666 - BREAK ROOM

1/4" = 1'-0"

M-104

B

BLDG 858 - VAULT AREA

KEY NOTES:

PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.

PROVIDE WATER METER & INTEGRATE WITH BASE EMS.

PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.

RE-INSTALL AND/OR REPLACE CEILING TILES & GRID. RE-INSTALL

LIGHT FIXTURES.

REPAIR AND/OR REPLACE GYPSUM BOARD CEILING.

REPAIR ROOFING AND FLASH AT EQUIPMENT ROOF CURB.

1/4" = 1'-0" M-104

D

BLDG 878 - ELECTRICAL ROOM 110

GENERAL NOTES:

EACH EXISTING CHILLER SHALL BE REPLACED ONE AT A TIME. THE FIRST

CHILLER SHALL BE REMOVED, REPLACED AND FULLY OPERATIONAL PRIOR

TO REMOVAL OF THE SECOND CHILLER. THE CHILLER REPLACEMENT WORK

SHALL BE PERFORMED BETWEEN NOVEMBER 1 AND FEBRUARY 28.

1.

PALLET STORAGE

OFFICE

CORRIDOR

TOOL STORAGE

MECH/ELEC

CONCRETE APRON

PALLET STORAGE

OFFICE

CORRIDOR

TOOL STORAGE

MECH/ELEC

CONCRETE APRON

x

Ø

10Ø

Ø x x x

Ø

Ø

20x18

20x18

1"

G

ELECTRICAL XFMR

MAIN ELECTRICAL

DISTRBUTION PANEL

3/4" G

EX CONCRETE PAD

RS & RL

CU-958-2

AC-958-2

RS & RL

CU-958-1

AC-958-1

x

4"COMBUSTION

AIR INTAKE

4" FLUE

4" FLUE

4Ø

4" COMBUSTION

AIR INTAKE

RE-USE EXISTING

6" PVC CONDUIT

UNDERGROUND

EX CONCRETE PAD

20x18

EMCS GATEWAY

IN CABINET

MECHANICAL ROOM 187

MECHANICAL ROOM 187

3"

1-1/2"

2"

2"

4"

CWR

CWS

2"

4"

1"

4'

4"

C W

R

H W

R

1"

3/4"

3/4"

2"

1-1/4"

4"

3"

3"

2-1/2"

3"

1"

3"

2"

2"

3"

2-1/2"

3"

G

HWS

HWR

HWS

2"

C W

S

C W

R

H W

S

MAIN ELEC DISTRIBUTION

PANEL (480V/277V, 800 A MAIN)

DOMESTIC HOT WATER

STORAGE TANK

DOMESTIC

WATER HEATER

AHU

AHU

AHU

HWP

HWP

CHP

CHP

HWR

EX BAS CABINET

EX BTU METER

6Ø COMBUSTION

AIR INTAKE

1" G

1" G

3" HWR

3" HWS

6Ø FLUE UP

THRU ROOF

B-984-1

B-984-2

CONCRETE PAD - EXTEND 4"

BEYOND EQUIPMENT ALL SIDES

6Ø FLUE UP

THRU ROOF

MECHANICAL ROOM

RESTROOM

CONCRETE APRON

MECHANICAL ROOM

RESTROOM

CONCRETE APRON

6x6

1/2" G

12Ø RA

Ø

S

A

RS & RL

12Ø SA

DUCTWORK

12Ø RA DUCTWORK

1" CD

AC-1060-1

1" CD DRAIN

CU-1060-1

EX CONCRETE PAD

EMCS GATEWAY IN CABINET

MECHANICAL ROOM 187

HWP

HWS

HWR

B-984-1

G

C W

S

C W

R

B-984-2

CONCRETE

EQUIPMENT PAD

1'-0"

2'-11" 1'-8"

1'-0" 1'-8"

2'-2" 2'-0"

20x20 COLLAR

C

C

RA, RL &

CD CONN.

4" FLUE

4" INTAKE VENT

1-3/4" G

PLAN VIEW

1/4"=1'-0"

SECTION VIEW

1/4"=1'-0"

C

C

1'-2"

4" FLUE TO ROOF

4" INTAKE VENT TO

EXTERIOR WALL

1-3/4" G

RA, RL &

CD CONN.

AUXILLARY

DRAIN PAN

FILTER/RA PLENUM

FURNACE

SECTION

DX COOLING

COIL PLENUM

x

AC-958-1

20x18

DX COIL

(2 UNITS)

PLENUM

PROFESSIONAL SEAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-3

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

TRUE

NORTH

WPL REP DLH WPL

M-105

HVAC PART PLANS

FAC#958, 984, 1060

1/4"=1'-0"

1/4" = 1'-0"

BLDG 984 - PART PLAN

1/4" = 1'-0"

BLDG 958 - PART PLAN

M-105

A

M-105

B

1/4" = 1'-0"

BLDG 1060 - PART PLAN

M-105

C

KEY NOTES:

PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.

PROVIDE WATER METER & INTEGRATE WITH BASE EMS.

PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.

RE-INSTALL AND/OR REPLACE CEILING TILES & GRID. RE-INSTALL LIGHT FIXTURES.

REPAIR AND/OR REPLACE GYPSUM BOARD CEILING.

REPAIR ROOFING AND FLASH AT EQUIPMENT ROOF CURB.

CONNECT TO EX 6Ø FLUE BELOW ROOF.

RE-WIRE AND RE-INSTALL EX HEATING WATER SYSTEM BTU METER HWS TEMPERATURE

SENSOR, HWR TEMPERATURE SENSOR AND FLOW METER FOR RE-USE.

PROVIDE CONDENSATE DRAIN PIPING CONNECTION TO AC UNIT AND CONNECT TO

EXISTING CONDENSATE DRAIN PIPING.

PROVIDE AC UNIT CONDENSATE DRAIN PIPING AND EXTEND TO NEAREST FLOOR DRAIN.

1/4" = 1'-0"

BLDG 984 - SECTION

M-105

B1

GENERAL NOTES:

EACH EXISTING BOILER SHALL BE REPLACED ONE AT A TIME. THE FIRST

BOILER SHALL BE REMOVED, REPLACED AND FULLY OPERATIONAL

PRIOR TO REMOVAL OF THE SECOND BOILER. THE BOILER REPLACEMENT

WORK SHALL BE PERFORMED BETWEEN APRIL 1 AND JUNE 30.

1.

1/4" = 1'-0"

AC-958-2 DETAIL

M-105

A2

1/4" = 1'-0"

BLDG 958 - SECTION

M-105

A1

BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR FLOWS TO VALUES

MEASURED PRIOR TO DEMOLITION OF THE EXISTING UNITS.

2.

MECHANICAL ROOM

MECHANICAL ROOM

18x16 x x x

SD

S

ATC PANEL

S

SD

x

18x16

M

10x10

DOMESTIC

WATER

HEATER

EX CONCRETE

PAD

RS & RL

18x16 RA

18x16 SA

AC-1147-1

CU-1147-1

CONCRETE PAD - EXTREND 4"

BEYOND EQUIPMENT ALL SIDE

EMCS GATEWAY

IN CABINET

OFFICE 1

CORR

MEN'S TOILET

WOMEN'S TOILET

CLASS "A" VAULT

DIS OPERATIONS

OFFICE 1

CORR

MEN'S TOILET

WOMEN'S TOILET

CLASS "A" VAULT

DIS OPERATIONS

RS & RL

RS & RL

AC-1163-1

AC-1163-2

3'-0" W x 6'-0" H

1 HOUR FIRE RATED ACCESS DOOR

36" WIDE CATWALK

CU-1163-1

CU-1163-2

CONCRETE PAD - EXTREND 4"

BEYOND EQUIPMENT ALL SIDE

EX CONCRETE PAD

ABI #1

EX CONDENSING UNIT

MECHANICAL ROOM

MAIN ELECTRICAL

DISTRIBUTION PANEL

"MP" (208V/120V, 800 A)

ELECTRICAL PANEL "L"

EMCS GATEWAY IN CABINET

MECHANICAL ROOM

MECHANICAL ROOM

CU

WALL MOUNTED

EXHAUST FAN

20x12

AC UNIT

XFMR

ELECTRICAL PANEL "DCA"

ELECTRICAL PANEL "LA"

ELECTRICAL PANEL "MPH"

(480V/277V, 250A MAIN)

2'-6"

3'-0"

M

SA

RA

EX 16x8

ELECTRIC HEATING

COIL CONTROL BOX

CONTROL BOX

FILTER

AC-1147-1

FLOOR

OA LOUVER

WALL

EX CONC. PAD

18"H x 44"W PLENUM

ELECTRICAL

EMCS GATEWAY

IN CABINET

PROFESSIONAL SEAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-3

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

TRUE

NORTH

WPL REP DLH WPL

M-106

HVAC PART PLANS

FAC#1053, 1057, 1163

1/4"=1'-0"

1/4" = 1'-0"

M-106

A

BLDG 1147 - MECHANICAL ROOM 112

1/4" = 1'-0"

M-106

BLDG 1163 - ATTIC PART PLAN

KEY NOTES:

PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.

PROVIDE WATER METER & INTEGRATE WITH BASE EMS.

PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.

RE-INSTALL AND/OR REPLACE CEILING TILES & GRID. RE-INSTALL

LIGHT FIXTURES.

PROVIDE CONDENSATE DRAIN PIPING CONNECTION TO AC UNIT

AND CONNECT TO EXISTING CONDENSATE DRAIN PIPING.

PROVIDE AC UNIT CONDENSATE DRAIN PIPING AND EXTEND TO

NEAREST FLOOR DRAIN.

1/4" = 1'-0" M-106

D

BLDG 1053 - MECHANICAL ROOM

1/4" = 1'-0"

BLDG 1057 - MECHANICAL ROOM 107

M-106

E

1/4" = 1'-0" M-106

A1

AC-1147-1 DETAIL

B

GENERAL NOTES:

BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR

FLOWS TO VALUES MEASURED PRIOR TO DEMOLITION

OF THE EXISTING UNITS.

1.

1/4" = 1'-0"

M-106

BLDG 1163 - ELECTRIC ROOM 108 PART PLAN

C

FAN OR PUMP

AFMS-

AIR FLOW MONITORING

STATION ALONE

COOLING COIL

CC

HEATING COIL

HC

FILTER

HUMIDIFIER

SUCTION DIFFUSER

MOTOR

FREEZESTAT

OPPOSED BLADE DAMPER

W/TWO POSITION

ACTUATOR

PARALLEL BLADE DAMPER

W/TWO POSITION

ACTUATOR

SOUND ATTENUATOR

SOFTWARE INTERLOCK LOGICI

COMMUNICATION PORT

I

SELF CONTAINED THERMOSTAT

FLOW TRANSMITTER

LEVEL SWITCH

VALVE ASSOCIATED

WITH LEVEL

CONTROL

WATER FLOW SWITCH

DIFFERENTIAL PRESSURE

BYPASS VALVE

FLOW ELEMENT

PRESSURE READOUT

MOISTURE (HUMIDITY)

TRANSMITTER

STATIC PRESSURE

TRANSMITTER

(REFERENCED TO ATMOSPHERE)

DIFFERENTIAL STATIC

PRESSURE TRANSMITTER

SPEED TRANSMITTER

SPEED INDICATION

TEMPERATURE TRANSMITTER

SI

TE

TI

ST

TT

TSL

SD

ZS

FS

FE

LE

FT

LCV

MT

DPV

PDIT

PT

PI

TI TT

FE

FT

UL RATED SMOKE DAMPER

SMDHS

HOA

HAND-OFF-AUTOMATIC CONTROL

STATION HS-HAND SWITCH

IT

CURRENT TRANSMITTER

QL

DDC ANALOG INPUT

AI

DDC ANALOG OUTPUT

AO

DDC DIGITAL INPUT

DI

DDC DIGITAL OUTPUT

DO

C

SYMBOL DESCRIPTION

AUDIBLE/VISUAL

ALARM

A

A

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTIONSYMBOL DESCRIPTION

MODULATING TWO-WAY

CONTROL VALVE

MODULATING THREE-WAY

CONTROL VALVE

TWO-POSITION, TWO-WAY

CONTROL VALVE

PIPING / DUCTWORK

ELECTRIC SIGNAL

DATA LINK SIGNAL

USERS CHOICE(*)

MULTIFUNCTION(*)

UNCLASSIFIED(*)

USERS CHOICE(*)

TEMPERATURE

RADIATION

EVENT (STATUS)

DIAL VOLATILE OR GAME COMPUTER

OXYGEN

MULTIVARIABLE(*)

WEIGHT OR FORCE

CARBON MONOXIDE

VIBRATION, MECH ANALYSIS

SPEED OR FREQUENCY

QUANTITY OR EVENT(*)

PRESSURE (OR VACUUM)

POSITION, DIMENSION

MOTION / MOISTURE

( * ) WHEN USED, EXPLANATION IS SHOWN ADJACENT TO INSTRUMENT SYMBOL. SEE ABBREVIATIONS AND LETTER SYMBOLS.

EXAMPLE: PT=PRESSURE TRANSMITTER, HS=HAND SWITCH

L

M

LEVEL

N

O

R

Y

W

X

Z

T

S

U

V

Q

P

OXYGEN

USERS CHOICE (*)

RECORD OR PRINT

MULTIFUNCTION(*)

UNCLASSIFIED(*)

POINT (TEST CONNECTION)

MOMENTARY

LIGHT (PILOT)

INTEGRATE

WELL

SAFETY

INTEGRATE

LOW

USERS CHOICE(*)

RELAY OR COMPUTE(*)

DRIVER, ACTUATOR OR

UNCLASSIFIED FINAL

CONTROL ELEMENT

TRANSFORMER

MULTIFUNCTION(*)

SWITCH

VALVE

TRANSMIT

ANALYSIS

CURRENT

FLOW RATE

VOLTAGE

BURNER FLAME

PROCESS OR INITIATING VARIABLE

HAND (MANUAL)

CARBON DIOXIDE

TIME OR SCHEDULE

DENSITY (S.G.)/DEWPOINT

B

A

I

J

K

POWER

E

G

F

H

GAUGE

C

D

READOUT OR PASSIVE FUNCTION

USERS CHOICE(*)

SENSOR (PRIMARY ELEMENT)

ALARM

MODIFIER

INDICATE

SCAN

RATE OF CHANGE

GLASS

RATIO

DIFFERENTIAL

FIRST LETTER(S)

MODIFIER

SUCCEEDING LETTERS

OUTPUT FUNCTION

CONTROL STATION

GATE

CONTROL

DAMPER

HIGH

USERS CHOICE(*)

AFMS-

AIR FLOW MONITORING STATION

WITH INTEGRAL AUTOMATIC

MODULATING DAMPER

OPPOSED BLADE DAMPER

W/MODULATING

ACTUATOR

PARALLEL BLADE DAMPER

W/MODULATING

ACTUATOR

THREE WAY AUTOMATIC

CONTROL VALVE W /

TWO POSITION

ACTUATOR

CURRENT SWITCH

CS

M

THE POSITION OF ANOTHER

DEVICE (E.G. DAMPER

TEMPERATURE ELEMENT (RTD,

THERMISTOR, BIMETAL, ETC)

TEMPERATURE READOUT

(BIMETALLIC OR MERCURY IN

GLASS THERMOMETER)

SWITCH ASSOCIATED WITH THE

POSITION OF A VALVE OR DAMPER.

SWITCH IS ACTIVATED BY END

SWITCH).

LOW TEMPERATURE SWITCH WITH

MANUAL RESET

DUCT SMOKE DETECTOR WITH

REMOTE LIGHT, AUXILIARY CONTACTS

AND MANUAL RESET

FLOW ELEMENT WITH FLOW

TRANSMITTER

PILOT LIGHT INDICATING STATUS

HARDWIRED INTERLOCK

RELAY

LOGIC

16. THERMOSTATS - PROVIDE SPACE MOUNTED THERMOSTATS WITH +/-2°F ADJUSTMENT CAPABILITIES.

15. SENSOR ALARMS - HIGH AND LOW LIMIT SHALL BE PROGRAMMED INTO ALL HUMIDITY, PRESSURE

AND TEMPERATURE SENSORS. IF ALARM LEVELS ARE EXCEEDED AN ALARM SHALL BE GENERATED

AND LOGGED BY THE DDC SYSTEM AT THE EXISTING REMOTE WORKSTATION. TEMPERATURE

SENSORS ON AHUs AND WATER SYSTEMS THAT OPERATE AT DIFFERENT RANGES DEPENDING UPON

HEATING OR COOLING MODE SHALL HAVE SEPARATE ALARM LIMITS FOR HEATING AND COOLING

MODES.

14. ALL SAFETY DEVICES SUCH AS FREEZESTATS, SMOKE DETECTION, AND HIGH STATIC PRESSURE

SWITCHES SHALL BE MANUAL RESET AND SHALL PERFORM ALL ASSOCIATED SHUTDOWN/FAILSAFE

ACTIONS VIA HARDWIRING. SOFTWARE SHALL NOT BE USED TO EXCLUSIVELY PERFORM ANY

SHUTDOWN/FAILSAFE ACTIONS FROM SAFETY DEVICES. FOR EXAMPLE, FREEZESTATS SHALL SHUT

OFF FAN, FULLY OPEN COIL VALVE, AND CLOSE OUTSIDE AIR DAMPER VIA HARDWIRING WITHOUT

RELYING ON ANY SOFTWARE FUNCTIONS. SOFTWARE SHUTDOWN/FAILSAFE SHALL BE PROVIDED AS

A REDUNDANT BACKUP TO THE REQUIRED HARDWIRED SHUTDOWNS.

13. IF ANY DDC CONTROLLER OR EQUIPMENT MANUFACTURER'S CONTROL PANEL LOSES

COMMUNICATION WITH THE BAS NETWORK, AN ALARM SHALL BE INITIATED AT THE BAS INDICATING

THE LOCATION OF THE FAULT.

12. WHENEVER AN ALARM IS INITIATED, THE BAS SHALL RETAIN IN MEMORY THE READING AND

SET-POINT OF EACH ASSOCIATED DEVICE TO HELP THE OPERATOR IN ISOLATING THE CAUSE OF THE

ALARM.

11. WHENEVER A UNIT IS SHUT DOWN BECAUSE OF ONE OF IT'S SAFETIES, THE BAS SHALL RETAIN IN

MEMORY THE READING AND SET-POINT OF EACH ASSOCIATED DEVICE TO HELP THE OPERATOR IN

ISOLATING THE CAUSE OF THE SHUT DOWN.

10. PROVIDE ADEQUATE DAMPING OF ALL MODULATING CONTROL LOOPS TO PREVENT HUNTING.

MAXIMUM RESPONSE TIME SHALL BE 30 SECONDS.

9. FAIL SAFE POSITIONS INDICATED ARE POSITIONS THAT DEVICES WILL GO TO WHEN THE ASSOCIATED

EQUIPMENT IS DEENERGIZED.

8. PROVIDE COMMUNICATIONS INTERFACE (INCLUDING NECESSARY SOFTWARE) BETWEEN THE BAS

AND EACH MANUFACTURER SUPPLIED CONTROL PANEL SPECIFIED. BAS SHALL BE CAPABLE OF

READING AND DISPLAYING ALL DATA USED BY THE MANUFACTURER'S CONTROL PANEL. SOFTWARE

INTERFACE SHALL BE THROUGH BACNET COMPLIANT PROTOCOL. WHERE THE BAS IS REQUIRED

TO CONTROL THE OPERATION OF THE EQUIPMENT, PROVIDE INPUT AND OUTPUT INTERFACE AS

REQUIRED.

7. COORDINATE ALL SENSOR INSTALLATION LOCATIONS WITH HVAC CONTRACTOR AND SUBMIT

PROPOSED POSITIONS ON APPLICABLE PIPING AND DUCTWORK COORDINATION SUBMITTALS.

COORDINATE AND INSURE MANUFACTURER'S RECOMMENDED UPSTREAM AND DOWNSTREAM PIPE

OR DUCT DIAMETERS ARE PROVIDED. SPECIAL ATTENTION IS REQUIRED FOR FLOW ELEMENTS AND

TRANSMITTERS.

6. ALL EQUIPMENT CONTROLLED BY THE BAS SHALL BE CAPABLE OF MANUAL OPERATION THROUGH

HAND-OFF-AUTOMATIC (HOA) SWITCHES LOCATED IN THE MOTOR STARTERS. THE POSITIONING OF

ALL VALVES CONTROLLED BY THE BAS SHALL BE CAPABLE OF MANUAL POSITIONING (OPEN, CLOSED, MODULATED, AUTO) VIA LABELED POTENTIOMETERS AND SWITCHES PROVIDED BY THE BAS

CONTRACTOR.SAFETY DEVICES SHALL FUNCTION AND SHUT DOWN THE ASSOCIATED EQUIPMENT

WHEN THE MANUAL SWITCHES ARE IN BOTH THE HAND AND AUTO POSITIONS.

5. THE DESIGN INTENT IS FOR THE BAS TO MONITOR PRESSURES, TEMPERATURES AND FLOWS AND TO

CONTROL VALVES, VARIABLE FREQUENCY DRIVES (VFDS), AHUS, PUMPS, ETC.... MONITORED DATA

WILL BE USED TO ENERGIZE OR DE-ENERGIZE EQUIPMENT IN ACCORDANCE WITH THE SEQUENCES

OUTLINED.

4. PROVIDE MENU DRIVEN CAPABILITY TO OVERRIDE AUTOMATED START/STOP OR OPERATING MODES

FOR EACH PIECE OF EQUIPMENT (INCLUDING PUMPS, AIR HANDLING UNITS, VV BOXES, ETC...). IF A

SEQUENCE IS DISABLED BY MANUAL INPUT AND THE BAS ATTEMPTS AN AUTOMATED CHANGE IN

OPERATING MODE, AN ALARM SHALL BE INITIATED AT THE BAS STATING THAT THE SYSTEM WAS

UNABLE TO CHANGE THE MODE DUE TO USER INPUT. WHERE APPLICABLE A MANUAL INPUT

COMMAND WILL THEN BE REQUIRED FROM THE USER INSTRUCTING THE BAS TO START THE NEXT

SEQUENTIAL PIECE OF EQUIPMENT.

3. ABILITY TO REVIEW ALL MEASURED DATA, CONTROL SETPOINTS AND FUNCTIONS SHALL BE

PROVIDED AT THE EXISTING REMOTE EMCS WORKSTATION.

2. UNLESS OTHERWISE SPECIFIED, ALL SET-POINTS AND TIME DELAYS SHALL BE ADJUSTABLE BY THE

OPERATOR THROUGH THE BAS AND THROUGH MENU ACCESS AT ALL DDC CONTROLLERS WITHOUT

ANY HARDWARE OR SOFTWARE REVISIONS.

1. SEQUENCES OUTLINED (UNLESS OTHERWISE SPECIFIED) SHALL BE PERFORMED BY DIRECT DIGITAL

CONTROL FIELD PANELS (DDCFPS) OR LOCALLY MOUNTED DIRECT DIGITAL UNIT CONTROLLERS.

1. ALL OPERATING SAFETIES INCLUDING FREEZE PROTECTION AND HIGH/LOW STATIC PRESSURE LIMITS SHALL BE HARDWIRED FOR

SHUTDOWN AND MONITORED BY BAS FOR ALARM.

2.

3.

4.

5.

6.

7.

UNLESS OTHERWISE NOTED, ALL CONTROLS SHALL BE DIRECT DIGITAL TYPE (DDC).

ALL SET-POINTS INDICATED IN THE SEQUENCES SHALL BE ADJUSTABLE AT THE EXISTING REMOTE WORKSTATION AND VIA A

LAPTOP COMPUTER CONNECTED TO ANY DDC CONTROLLER.

MODULATING ACTUATORS FOR ALL VALVES LARGER THAN 3" SHALL HAVE POSITIONERS.

SOFTWARE COMMUNICATION SHALL BE REQUIRED BETWEEN THE BAS AND EQUIPMENT MANUFACTURERS PACKAGED CONTROL

SYSTEMS WHERE INDICATED.

ALL DDC CONTROLLER SHALL BE CAPABLE OF INDEPENDENT OPERATION REGARDLESS OF THE STATUS OF THE BUILDING

AUTOMATION SYSTEM (BAS NETWORK).

THE CONTROLS CONTRACTOR SHALL APPLY FOR AND OBTAIN AUTHORIZATION FOR GOVERNMENT COMPUTER ACCESS. THE

CONTROLS CONTRACTOR WILL BE GIVEN ACCESS ONCE AUTHORIZED BY THE GOVERNMENT.

CONTROL SYSTEM NOTES INSTRUMENT IDENTIFICATION LETTERS SEQUENCE OF CONTROLS - GENERAL

PROFESSIONAL SEAL

I n c h e s

Rev. Date Description By Chk'd App'd

Date

DesignedScale

Drawing Title

Project Title

Drawing Status

Drawn Checked Authorized

Client

Original Size

Suitability

Drawing Number Revision www.atkinsglobal.com

Copyright © Atkins Limited (2016)

+1 703 535 3008

+1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040

Alexandria

VA 22314

Client Project Number PSTE152605

McEntire JNGB HVAC REPAIR

HVAC SYSTEMS BASE WIDE

02/06/2019

TYPE B-3

South Carolina Air National Guard

169th Civil Engineer Squadron, McEntire JNGB

WPL REP DLH WPL

M-400

INSTRUMENTATION AND

CONTROLS LEGEND

No Scale

M-102 - HVAC PART PLANS FAC#210, 258, 279
M-103 - HVAC PART PLANS FAC#310
M-104 - HVAC PART PLANS FAC#666, 858, 878
M-105 - HVAC PART PLANS FAC#958, 984, 1060
M-106 - HVAC PART PLANS FAC#1053, 1057, 1163
M-400 - INSTRUMENTATION AND CONTROLS LEGEND