OPEN OFFICE AREA
VAULT
VAULT
VAULT
INFO ASSURANCE OFFICE
OPEN OFFICE AREA
VAULT
VAULT
VAULT
INFO ASSURANCE OFFICE
10x16
Ø
12Ø
12Ø
Ø
Ø
Ø
ELEC PANEL BP (208V/120V)
ELEC PANEL Q (208V/120V)
ELEC PANEL "RP" (208V/120V)
CRAC AC UNIT
RS & RL
AC PUMPED CONDENSATE
SA DUCT
AC-258-1
AC-258-2
RS & RL
CU-258-1
CU-258-2
SA
RA
1" CD
CONCRETE PAD - EXTEND 4"
BEYOND EQUIPMENT ALL SIDES
COMMUNICATIONS BOX
A S
P H
A L
T
S
L O
P E
D
D
O W
N
CONCRETE PAD
AC-279-1
30x10 SA HIGH
30x14 RA LOW
28x8 SA HIGH
28x14 RA LOW
SHEET METAL
ENCLOSURE
CONCRETE EQUIPMENT
PAD (EXTEND 4" BEYOND
EQUIPMENT, ALL SIDES)
EMCS GATEWAY IN CABINET
MECHANICAL ROOM 107
SERVER ROOM 108
MECHANICAL ROOM 107
SERVER ROOM 108
18x18
18x18
8Ø
M
Ø
MAIN ELECTRICAL
DISTRIBUTION
PANEL "M"
ELECTRICAL
PANEL "A"
2" G
2" CW BELOW SLAB
3/4" UP TO DOMESTIC
WATER HEATER
GAS METER/HOUSE
REGULATOR
2" DOMESTIC
WATER SERVICE
G
W
METER VAULT
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
TRUE
NORTH
WPL REP DLH WPL
M-102
HVAC PART PLANS
FAC#210, 258, 279
1/4"=1'-0"
1/4" = 1'-0" M-102
B
BLDG 258 - VAULTS 129, 130 & 131
1/4" = 1'-0"
M-102
C
BLDG 279 - BARRIER SHED
1/4" = 1'-0"
M-102
A
BLDG 210 - PART PLAN
KEY NOTES:
PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.
PROVIDE WATER METER & INTEGRATE WITH BASE EMS.
PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.
RE-INSTALL AND/OR REPLACE ACOUSTICAL CEILING TILES & GRID.
RE-INSTALL LIGHT FIXTURES.
SPILL CONDENSATE DRAIN TO GRADE.
CONDENSATE DRAIN PIPING, SPILL TO GRADE.
2. EXISTING CRAC UNIT SHALL NOT BE REMOVED UNTIL NEW CEILING CRAC UNIT
IS INSTALLED AND FULLY FUNCTIONING. REFER TO DEMOLITION DRAWINGS.
GENERAL NOTES:
BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR FLOWS TO VALUES
MEASURED PRIOR TO DEMOLITION OF THE EXISTING UNITS.
1.
OFFICE
102D
OFFICE
102C
OFFICE
OFFICE
102B
OFFICE
102A
CLASSROOM
MEN
MEN
MECHANICAL
PAINT SHOP
BAY "A1"
BAY "A1"
BAY "B"
AC-310-1
RS & RL
AC-310-2 ON ROOF
AC-310-3 ON ROOF
CU-310-1
PREFAB PAD
EX CU
EMCS GATEWAY
IN CABINET
AC-310-2/
AC-310-3
ROOF CURB
EX ROOFING
EX INSULATION
EX BAR JOISTS
22x10 SR
(ONE ON EACH SIDE
OF SA PLENUM)
24x30 SA PLENUM
22x28 SA
18x30 RA PLENUM
18x30 RAG
CONDENSATE DRAIN
PIPING - EXTEND TO
NEAREST ROOF DRAIN
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
TRUE
NORTH
WPL REP DLH WPL
M-103
HVAC PART PLANS
FAC#310
1/8"=1'-0"
1/8" = 1'-0" M-103
A
BLDG 310 - PART PLAN
KEY NOTES:
PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.
PROVIDE WATER METER & INTEGRATE WITH BASE EMS.
PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.
RE-INSTALL AND/OR REPLACE ACOUSTICAL CEILING TILES & GRID.
RE-INSTALL LIGHT FIXTURES.
REPAIR ROOFING AND FLASH AT EQUIPMENT ROOF CURB.
PROVIDE CONDENSATE DRAIN PIPING CONNECTION TO AC UNIT
AND CONNECT TO EXISTING CONDENSATE DRAIN PIPING.
1/4" = 1'-0"
M-103
B
ROOF SECTION - AC-310-2/AC-310-3
GENERAL NOTES:
BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR FLOWS TO VALUES
MEASURED PRIOR TO DEMOLITION OF THE EXISTING UNITS.
EXISTING ROOF IS UNDER WARRANTY. REMOVE, MODIFY AND REPAIR
ROOFING AS REQUIRED BY ROOF MANUFACTURER.
ROOF CURBS SHALL BE NEW UNLESS OTHERWISE INDICATED.
1.
2.
3.
BREAK ROOM
MAIN ELEC PANEL
120V/240V, 200 A MAIN
EMCS GATEWAY IN CABINET
VAULT AREA
ELEC SWITCHGEAR
(480V/277V, 600 A RATING,
800 A MAIN)
MECHANICAL ROOM 112MECHANICAL ROOM 112
CHWR
CHWS
C H
W R
C H
W S
3/4"
1-1/2"
2-1/2"
HWS
HWR
CHWS
CHWR
2-1/2"
B-1
B-2
HWP-1
HWP-2
UH
FCU-1
CHP-1
CHP-2
CHP-3
UH
M
EX GAS
METER
EX CONC. PAD
TO REMAIN
EX CONC. PAD
TO REMAIN
CH-878-1
CH-878-2
2-1/2" CHWS & CHWR
2-1/2" CHWS
& CHWR
NORMAL ELECTRICAL ROOM
MAIN SWITCHGEAR
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
TRUE
NORTH
1/4" = 1'-0"
M-104
C
BLDG 878 - PART PLAN
WPL REP DLH WPL
M-104
HVAC PART PLANS
FAC#666, 858, 878
1/4"=1'-0"
1/4" = 1'-0"
M-104
A
BLDG 666 - BREAK ROOM
1/4" = 1'-0"
M-104
B
BLDG 858 - VAULT AREA
KEY NOTES:
PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.
PROVIDE WATER METER & INTEGRATE WITH BASE EMS.
PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.
RE-INSTALL AND/OR REPLACE CEILING TILES & GRID. RE-INSTALL
LIGHT FIXTURES.
REPAIR AND/OR REPLACE GYPSUM BOARD CEILING.
REPAIR ROOFING AND FLASH AT EQUIPMENT ROOF CURB.
1/4" = 1'-0" M-104
D
BLDG 878 - ELECTRICAL ROOM 110
GENERAL NOTES:
EACH EXISTING CHILLER SHALL BE REPLACED ONE AT A TIME. THE FIRST
CHILLER SHALL BE REMOVED, REPLACED AND FULLY OPERATIONAL PRIOR
TO REMOVAL OF THE SECOND CHILLER. THE CHILLER REPLACEMENT WORK
SHALL BE PERFORMED BETWEEN NOVEMBER 1 AND FEBRUARY 28.
1.
PALLET STORAGE
OFFICE
CORRIDOR
TOOL STORAGE
MECH/ELEC
CONCRETE APRON
PALLET STORAGE
OFFICE
CORRIDOR
TOOL STORAGE
MECH/ELEC
CONCRETE APRON
x
Ø
10Ø
Ø x x x
Ø
Ø
20x18
20x18
1"
G
ELECTRICAL XFMR
MAIN ELECTRICAL
DISTRBUTION PANEL
3/4" G
EX CONCRETE PAD
RS & RL
CU-958-2
AC-958-2
RS & RL
CU-958-1
AC-958-1
x
4"COMBUSTION
AIR INTAKE
4" FLUE
4" FLUE
4Ø
4" COMBUSTION
AIR INTAKE
RE-USE EXISTING
6" PVC CONDUIT
UNDERGROUND
EX CONCRETE PAD
20x18
EMCS GATEWAY
IN CABINET
MECHANICAL ROOM 187
MECHANICAL ROOM 187
3"
1-1/2"
2"
2"
4"
CWR
CWS
2"
4"
1"
4'
4"
C W
R
H W
R
1"
3/4"
3/4"
2"
1-1/4"
4"
3"
3"
2-1/2"
3"
1"
3"
2"
2"
3"
2-1/2"
3"
G
HWS
HWR
HWS
2"
C W
S
C W
R
H W
S
MAIN ELEC DISTRIBUTION
PANEL (480V/277V, 800 A MAIN)
DOMESTIC HOT WATER
STORAGE TANK
DOMESTIC
WATER HEATER
AHU
AHU
AHU
HWP
HWP
CHP
CHP
HWR
EX BAS CABINET
EX BTU METER
6Ø COMBUSTION
AIR INTAKE
1" G
1" G
3" HWR
3" HWS
6Ø FLUE UP
THRU ROOF
B-984-1
B-984-2
CONCRETE PAD - EXTEND 4"
BEYOND EQUIPMENT ALL SIDES
6Ø FLUE UP
THRU ROOF
MECHANICAL ROOM
RESTROOM
CONCRETE APRON
MECHANICAL ROOM
RESTROOM
CONCRETE APRON
6x6
1/2" G
12Ø RA
Ø
S
A
RS & RL
12Ø SA
DUCTWORK
12Ø RA DUCTWORK
1" CD
AC-1060-1
1" CD DRAIN
CU-1060-1
EX CONCRETE PAD
EMCS GATEWAY IN CABINET
MECHANICAL ROOM 187
HWP
HWS
HWR
B-984-1
G
C W
S
C W
R
B-984-2
CONCRETE
EQUIPMENT PAD
1'-0"
2'-11" 1'-8"
1'-0" 1'-8"
2'-2" 2'-0"
20x20 COLLAR
C
C
RA, RL &
CD CONN.
4" FLUE
4" INTAKE VENT
1-3/4" G
PLAN VIEW
1/4"=1'-0"
SECTION VIEW
1/4"=1'-0"
C
C
1'-2"
4" FLUE TO ROOF
4" INTAKE VENT TO
EXTERIOR WALL
1-3/4" G
RA, RL &
CD CONN.
AUXILLARY
DRAIN PAN
FILTER/RA PLENUM
FURNACE
SECTION
DX COOLING
COIL PLENUM
x
AC-958-1
20x18
DX COIL
(2 UNITS)
PLENUM
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
TRUE
NORTH
WPL REP DLH WPL
M-105
HVAC PART PLANS
FAC#958, 984, 1060
1/4"=1'-0"
1/4" = 1'-0"
BLDG 984 - PART PLAN
1/4" = 1'-0"
BLDG 958 - PART PLAN
M-105
A
M-105
B
1/4" = 1'-0"
BLDG 1060 - PART PLAN
M-105
C
KEY NOTES:
PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.
PROVIDE WATER METER & INTEGRATE WITH BASE EMS.
PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.
RE-INSTALL AND/OR REPLACE CEILING TILES & GRID. RE-INSTALL LIGHT FIXTURES.
REPAIR AND/OR REPLACE GYPSUM BOARD CEILING.
REPAIR ROOFING AND FLASH AT EQUIPMENT ROOF CURB.
CONNECT TO EX 6Ø FLUE BELOW ROOF.
RE-WIRE AND RE-INSTALL EX HEATING WATER SYSTEM BTU METER HWS TEMPERATURE
SENSOR, HWR TEMPERATURE SENSOR AND FLOW METER FOR RE-USE.
PROVIDE CONDENSATE DRAIN PIPING CONNECTION TO AC UNIT AND CONNECT TO
EXISTING CONDENSATE DRAIN PIPING.
PROVIDE AC UNIT CONDENSATE DRAIN PIPING AND EXTEND TO NEAREST FLOOR DRAIN.
1/4" = 1'-0"
BLDG 984 - SECTION
M-105
B1
GENERAL NOTES:
EACH EXISTING BOILER SHALL BE REPLACED ONE AT A TIME. THE FIRST
BOILER SHALL BE REMOVED, REPLACED AND FULLY OPERATIONAL
PRIOR TO REMOVAL OF THE SECOND BOILER. THE BOILER REPLACEMENT
WORK SHALL BE PERFORMED BETWEEN APRIL 1 AND JUNE 30.
1.
1/4" = 1'-0"
AC-958-2 DETAIL
M-105
A2
1/4" = 1'-0"
BLDG 958 - SECTION
M-105
A1
BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR FLOWS TO VALUES
MEASURED PRIOR TO DEMOLITION OF THE EXISTING UNITS.
2.
MECHANICAL ROOM
MECHANICAL ROOM
18x16 x x x
SD
S
ATC PANEL
S
SD
x
18x16
M
10x10
DOMESTIC
WATER
HEATER
EX CONCRETE
PAD
RS & RL
18x16 RA
18x16 SA
AC-1147-1
CU-1147-1
CONCRETE PAD - EXTREND 4"
BEYOND EQUIPMENT ALL SIDE
EMCS GATEWAY
IN CABINET
OFFICE 1
CORR
MEN'S TOILET
WOMEN'S TOILET
CLASS "A" VAULT
DIS OPERATIONS
OFFICE 1
CORR
MEN'S TOILET
WOMEN'S TOILET
CLASS "A" VAULT
DIS OPERATIONS
RS & RL
RS & RL
AC-1163-1
AC-1163-2
3'-0" W x 6'-0" H
1 HOUR FIRE RATED ACCESS DOOR
36" WIDE CATWALK
CU-1163-1
CU-1163-2
CONCRETE PAD - EXTREND 4"
BEYOND EQUIPMENT ALL SIDE
EX CONCRETE PAD
ABI #1
EX CONDENSING UNIT
MECHANICAL ROOM
MAIN ELECTRICAL
DISTRIBUTION PANEL
"MP" (208V/120V, 800 A)
ELECTRICAL PANEL "L"
EMCS GATEWAY IN CABINET
MECHANICAL ROOM
MECHANICAL ROOM
CU
WALL MOUNTED
EXHAUST FAN
20x12
AC UNIT
XFMR
ELECTRICAL PANEL "DCA"
ELECTRICAL PANEL "LA"
ELECTRICAL PANEL "MPH"
(480V/277V, 250A MAIN)
2'-6"
3'-0"
M
SA
RA
EX 16x8
ELECTRIC HEATING
COIL CONTROL BOX
CONTROL BOX
FILTER
AC-1147-1
FLOOR
OA LOUVER
WALL
EX CONC. PAD
18"H x 44"W PLENUM
ELECTRICAL
EMCS GATEWAY
IN CABINET
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
TRUE
NORTH
WPL REP DLH WPL
M-106
HVAC PART PLANS
FAC#1053, 1057, 1163
1/4"=1'-0"
1/4" = 1'-0"
M-106
A
BLDG 1147 - MECHANICAL ROOM 112
1/4" = 1'-0"
M-106
BLDG 1163 - ATTIC PART PLAN
KEY NOTES:
PROVIDE ELECTRIC METER & INTEGRATE WITH BASE EMS.
PROVIDE WATER METER & INTEGRATE WITH BASE EMS.
PROVIDE NATURAL GAS METER & INTEGRATE WITH BASE EMS.
RE-INSTALL AND/OR REPLACE CEILING TILES & GRID. RE-INSTALL
LIGHT FIXTURES.
PROVIDE CONDENSATE DRAIN PIPING CONNECTION TO AC UNIT
AND CONNECT TO EXISTING CONDENSATE DRAIN PIPING.
PROVIDE AC UNIT CONDENSATE DRAIN PIPING AND EXTEND TO
NEAREST FLOOR DRAIN.
1/4" = 1'-0" M-106
D
BLDG 1053 - MECHANICAL ROOM
1/4" = 1'-0"
BLDG 1057 - MECHANICAL ROOM 107
M-106
E
1/4" = 1'-0" M-106
A1
AC-1147-1 DETAIL
B
GENERAL NOTES:
BALANCE AC UNIT SUPPLY, RETURN AND OUTSIDE AIR
FLOWS TO VALUES MEASURED PRIOR TO DEMOLITION
OF THE EXISTING UNITS.
1.
1/4" = 1'-0"
M-106
BLDG 1163 - ELECTRIC ROOM 108 PART PLAN
C
FAN OR PUMP
AFMS-
AIR FLOW MONITORING
STATION ALONE
COOLING COIL
CC
HEATING COIL
HC
FILTER
HUMIDIFIER
SUCTION DIFFUSER
MOTOR
FREEZESTAT
OPPOSED BLADE DAMPER
W/TWO POSITION
ACTUATOR
PARALLEL BLADE DAMPER
W/TWO POSITION
ACTUATOR
SOUND ATTENUATOR
SOFTWARE INTERLOCK LOGICI
COMMUNICATION PORT
I
SELF CONTAINED THERMOSTAT
FLOW TRANSMITTER
LEVEL SWITCH
VALVE ASSOCIATED
WITH LEVEL
CONTROL
WATER FLOW SWITCH
DIFFERENTIAL PRESSURE
BYPASS VALVE
FLOW ELEMENT
PRESSURE READOUT
MOISTURE (HUMIDITY)
TRANSMITTER
STATIC PRESSURE
TRANSMITTER
(REFERENCED TO ATMOSPHERE)
DIFFERENTIAL STATIC
PRESSURE TRANSMITTER
SPEED TRANSMITTER
SPEED INDICATION
TEMPERATURE TRANSMITTER
SI
TE
TI
ST
TT
TSL
SD
ZS
FS
FE
LE
FT
LCV
MT
DPV
PDIT
PT
PI
TI TT
FE
FT
UL RATED SMOKE DAMPER
SMDHS
HOA
HAND-OFF-AUTOMATIC CONTROL
STATION HS-HAND SWITCH
IT
CURRENT TRANSMITTER
QL
DDC ANALOG INPUT
AI
DDC ANALOG OUTPUT
AO
DDC DIGITAL INPUT
DI
DDC DIGITAL OUTPUT
DO
C
SYMBOL DESCRIPTION
AUDIBLE/VISUAL
ALARM
A
A
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTIONSYMBOL DESCRIPTION
MODULATING TWO-WAY
CONTROL VALVE
MODULATING THREE-WAY
CONTROL VALVE
TWO-POSITION, TWO-WAY
CONTROL VALVE
PIPING / DUCTWORK
ELECTRIC SIGNAL
DATA LINK SIGNAL
USERS CHOICE(*)
MULTIFUNCTION(*)
UNCLASSIFIED(*)
USERS CHOICE(*)
TEMPERATURE
RADIATION
EVENT (STATUS)
DIAL VOLATILE OR GAME COMPUTER
OXYGEN
MULTIVARIABLE(*)
WEIGHT OR FORCE
CARBON MONOXIDE
VIBRATION, MECH ANALYSIS
SPEED OR FREQUENCY
QUANTITY OR EVENT(*)
PRESSURE (OR VACUUM)
POSITION, DIMENSION
MOTION / MOISTURE
( * ) WHEN USED, EXPLANATION IS SHOWN ADJACENT TO INSTRUMENT SYMBOL. SEE ABBREVIATIONS AND LETTER SYMBOLS.
EXAMPLE: PT=PRESSURE TRANSMITTER, HS=HAND SWITCH
L
M
LEVEL
N
O
R
Y
W
X
Z
T
S
U
V
Q
P
OXYGEN
USERS CHOICE (*)
RECORD OR PRINT
MULTIFUNCTION(*)
UNCLASSIFIED(*)
POINT (TEST CONNECTION)
MOMENTARY
LIGHT (PILOT)
INTEGRATE
WELL
SAFETY
INTEGRATE
LOW
USERS CHOICE(*)
RELAY OR COMPUTE(*)
DRIVER, ACTUATOR OR
UNCLASSIFIED FINAL
CONTROL ELEMENT
TRANSFORMER
MULTIFUNCTION(*)
SWITCH
VALVE
TRANSMIT
ANALYSIS
CURRENT
FLOW RATE
VOLTAGE
BURNER FLAME
PROCESS OR INITIATING VARIABLE
HAND (MANUAL)
CARBON DIOXIDE
TIME OR SCHEDULE
DENSITY (S.G.)/DEWPOINT
B
A
I
J
K
POWER
E
G
F
H
GAUGE
C
D
READOUT OR PASSIVE FUNCTION
USERS CHOICE(*)
SENSOR (PRIMARY ELEMENT)
ALARM
MODIFIER
INDICATE
SCAN
RATE OF CHANGE
GLASS
RATIO
DIFFERENTIAL
FIRST LETTER(S)
MODIFIER
SUCCEEDING LETTERS
OUTPUT FUNCTION
CONTROL STATION
GATE
CONTROL
DAMPER
HIGH
USERS CHOICE(*)
AFMS-
AIR FLOW MONITORING STATION
WITH INTEGRAL AUTOMATIC
MODULATING DAMPER
OPPOSED BLADE DAMPER
W/MODULATING
ACTUATOR
PARALLEL BLADE DAMPER
W/MODULATING
ACTUATOR
THREE WAY AUTOMATIC
CONTROL VALVE W /
TWO POSITION
ACTUATOR
CURRENT SWITCH
CS
M
THE POSITION OF ANOTHER
DEVICE (E.G. DAMPER
TEMPERATURE ELEMENT (RTD,
THERMISTOR, BIMETAL, ETC)
TEMPERATURE READOUT
(BIMETALLIC OR MERCURY IN
GLASS THERMOMETER)
SWITCH ASSOCIATED WITH THE
POSITION OF A VALVE OR DAMPER.
SWITCH IS ACTIVATED BY END
SWITCH).
LOW TEMPERATURE SWITCH WITH
MANUAL RESET
DUCT SMOKE DETECTOR WITH
REMOTE LIGHT, AUXILIARY CONTACTS
AND MANUAL RESET
FLOW ELEMENT WITH FLOW
TRANSMITTER
PILOT LIGHT INDICATING STATUS
HARDWIRED INTERLOCK
RELAY
LOGIC
16. THERMOSTATS - PROVIDE SPACE MOUNTED THERMOSTATS WITH +/-2°F ADJUSTMENT CAPABILITIES.
15. SENSOR ALARMS - HIGH AND LOW LIMIT SHALL BE PROGRAMMED INTO ALL HUMIDITY, PRESSURE
AND TEMPERATURE SENSORS. IF ALARM LEVELS ARE EXCEEDED AN ALARM SHALL BE GENERATED
AND LOGGED BY THE DDC SYSTEM AT THE EXISTING REMOTE WORKSTATION. TEMPERATURE
SENSORS ON AHUs AND WATER SYSTEMS THAT OPERATE AT DIFFERENT RANGES DEPENDING UPON
HEATING OR COOLING MODE SHALL HAVE SEPARATE ALARM LIMITS FOR HEATING AND COOLING
MODES.
14. ALL SAFETY DEVICES SUCH AS FREEZESTATS, SMOKE DETECTION, AND HIGH STATIC PRESSURE
SWITCHES SHALL BE MANUAL RESET AND SHALL PERFORM ALL ASSOCIATED SHUTDOWN/FAILSAFE
ACTIONS VIA HARDWIRING. SOFTWARE SHALL NOT BE USED TO EXCLUSIVELY PERFORM ANY
SHUTDOWN/FAILSAFE ACTIONS FROM SAFETY DEVICES. FOR EXAMPLE, FREEZESTATS SHALL SHUT
OFF FAN, FULLY OPEN COIL VALVE, AND CLOSE OUTSIDE AIR DAMPER VIA HARDWIRING WITHOUT
RELYING ON ANY SOFTWARE FUNCTIONS. SOFTWARE SHUTDOWN/FAILSAFE SHALL BE PROVIDED AS
A REDUNDANT BACKUP TO THE REQUIRED HARDWIRED SHUTDOWNS.
13. IF ANY DDC CONTROLLER OR EQUIPMENT MANUFACTURER'S CONTROL PANEL LOSES
COMMUNICATION WITH THE BAS NETWORK, AN ALARM SHALL BE INITIATED AT THE BAS INDICATING
THE LOCATION OF THE FAULT.
12. WHENEVER AN ALARM IS INITIATED, THE BAS SHALL RETAIN IN MEMORY THE READING AND
SET-POINT OF EACH ASSOCIATED DEVICE TO HELP THE OPERATOR IN ISOLATING THE CAUSE OF THE
ALARM.
11. WHENEVER A UNIT IS SHUT DOWN BECAUSE OF ONE OF IT'S SAFETIES, THE BAS SHALL RETAIN IN
MEMORY THE READING AND SET-POINT OF EACH ASSOCIATED DEVICE TO HELP THE OPERATOR IN
ISOLATING THE CAUSE OF THE SHUT DOWN.
10. PROVIDE ADEQUATE DAMPING OF ALL MODULATING CONTROL LOOPS TO PREVENT HUNTING.
MAXIMUM RESPONSE TIME SHALL BE 30 SECONDS.
9. FAIL SAFE POSITIONS INDICATED ARE POSITIONS THAT DEVICES WILL GO TO WHEN THE ASSOCIATED
EQUIPMENT IS DEENERGIZED.
8. PROVIDE COMMUNICATIONS INTERFACE (INCLUDING NECESSARY SOFTWARE) BETWEEN THE BAS
AND EACH MANUFACTURER SUPPLIED CONTROL PANEL SPECIFIED. BAS SHALL BE CAPABLE OF
READING AND DISPLAYING ALL DATA USED BY THE MANUFACTURER'S CONTROL PANEL. SOFTWARE
INTERFACE SHALL BE THROUGH BACNET COMPLIANT PROTOCOL. WHERE THE BAS IS REQUIRED
TO CONTROL THE OPERATION OF THE EQUIPMENT, PROVIDE INPUT AND OUTPUT INTERFACE AS
REQUIRED.
7. COORDINATE ALL SENSOR INSTALLATION LOCATIONS WITH HVAC CONTRACTOR AND SUBMIT
PROPOSED POSITIONS ON APPLICABLE PIPING AND DUCTWORK COORDINATION SUBMITTALS.
COORDINATE AND INSURE MANUFACTURER'S RECOMMENDED UPSTREAM AND DOWNSTREAM PIPE
OR DUCT DIAMETERS ARE PROVIDED. SPECIAL ATTENTION IS REQUIRED FOR FLOW ELEMENTS AND
TRANSMITTERS.
6. ALL EQUIPMENT CONTROLLED BY THE BAS SHALL BE CAPABLE OF MANUAL OPERATION THROUGH
HAND-OFF-AUTOMATIC (HOA) SWITCHES LOCATED IN THE MOTOR STARTERS. THE POSITIONING OF
ALL VALVES CONTROLLED BY THE BAS SHALL BE CAPABLE OF MANUAL POSITIONING (OPEN, CLOSED, MODULATED, AUTO) VIA LABELED POTENTIOMETERS AND SWITCHES PROVIDED BY THE BAS
CONTRACTOR.SAFETY DEVICES SHALL FUNCTION AND SHUT DOWN THE ASSOCIATED EQUIPMENT
WHEN THE MANUAL SWITCHES ARE IN BOTH THE HAND AND AUTO POSITIONS.
5. THE DESIGN INTENT IS FOR THE BAS TO MONITOR PRESSURES, TEMPERATURES AND FLOWS AND TO
CONTROL VALVES, VARIABLE FREQUENCY DRIVES (VFDS), AHUS, PUMPS, ETC.... MONITORED DATA
WILL BE USED TO ENERGIZE OR DE-ENERGIZE EQUIPMENT IN ACCORDANCE WITH THE SEQUENCES
OUTLINED.
4. PROVIDE MENU DRIVEN CAPABILITY TO OVERRIDE AUTOMATED START/STOP OR OPERATING MODES
FOR EACH PIECE OF EQUIPMENT (INCLUDING PUMPS, AIR HANDLING UNITS, VV BOXES, ETC...). IF A
SEQUENCE IS DISABLED BY MANUAL INPUT AND THE BAS ATTEMPTS AN AUTOMATED CHANGE IN
OPERATING MODE, AN ALARM SHALL BE INITIATED AT THE BAS STATING THAT THE SYSTEM WAS
UNABLE TO CHANGE THE MODE DUE TO USER INPUT. WHERE APPLICABLE A MANUAL INPUT
COMMAND WILL THEN BE REQUIRED FROM THE USER INSTRUCTING THE BAS TO START THE NEXT
SEQUENTIAL PIECE OF EQUIPMENT.
3. ABILITY TO REVIEW ALL MEASURED DATA, CONTROL SETPOINTS AND FUNCTIONS SHALL BE
PROVIDED AT THE EXISTING REMOTE EMCS WORKSTATION.
2. UNLESS OTHERWISE SPECIFIED, ALL SET-POINTS AND TIME DELAYS SHALL BE ADJUSTABLE BY THE
OPERATOR THROUGH THE BAS AND THROUGH MENU ACCESS AT ALL DDC CONTROLLERS WITHOUT
ANY HARDWARE OR SOFTWARE REVISIONS.
1. SEQUENCES OUTLINED (UNLESS OTHERWISE SPECIFIED) SHALL BE PERFORMED BY DIRECT DIGITAL
CONTROL FIELD PANELS (DDCFPS) OR LOCALLY MOUNTED DIRECT DIGITAL UNIT CONTROLLERS.
1. ALL OPERATING SAFETIES INCLUDING FREEZE PROTECTION AND HIGH/LOW STATIC PRESSURE LIMITS SHALL BE HARDWIRED FOR
SHUTDOWN AND MONITORED BY BAS FOR ALARM.
2.
3.
4.
5.
6.
7.
UNLESS OTHERWISE NOTED, ALL CONTROLS SHALL BE DIRECT DIGITAL TYPE (DDC).
ALL SET-POINTS INDICATED IN THE SEQUENCES SHALL BE ADJUSTABLE AT THE EXISTING REMOTE WORKSTATION AND VIA A
LAPTOP COMPUTER CONNECTED TO ANY DDC CONTROLLER.
MODULATING ACTUATORS FOR ALL VALVES LARGER THAN 3" SHALL HAVE POSITIONERS.
SOFTWARE COMMUNICATION SHALL BE REQUIRED BETWEEN THE BAS AND EQUIPMENT MANUFACTURERS PACKAGED CONTROL
SYSTEMS WHERE INDICATED.
ALL DDC CONTROLLER SHALL BE CAPABLE OF INDEPENDENT OPERATION REGARDLESS OF THE STATUS OF THE BUILDING
AUTOMATION SYSTEM (BAS NETWORK).
THE CONTROLS CONTRACTOR SHALL APPLY FOR AND OBTAIN AUTHORIZATION FOR GOVERNMENT COMPUTER ACCESS. THE
CONTROLS CONTRACTOR WILL BE GIVEN ACCESS ONCE AUTHORIZED BY THE GOVERNMENT.
CONTROL SYSTEM NOTES INSTRUMENT IDENTIFICATION LETTERS SEQUENCE OF CONTROLS - GENERAL
PROFESSIONAL SEAL
I n c h e s
Rev. Date Description By Chk'd App'd
Date
DesignedScale
Drawing Title
Project Title
Drawing Status
Drawn Checked Authorized
Client
Original Size
Suitability
Drawing Number Revision www.atkinsglobal.com
Copyright © Atkins Limited (2016)
+1 703 535 3008
+1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040
Alexandria
VA 22314
Client Project Number PSTE152605
McEntire JNGB HVAC REPAIR
HVAC SYSTEMS BASE WIDE
02/06/2019
TYPE B-3
South Carolina Air National Guard
169th Civil Engineer Squadron, McEntire JNGB
WPL REP DLH WPL
M-400
INSTRUMENTATION AND
CONTROLS LEGEND
No Scale
| M-102 - HVAC PART PLANS FAC#210, 258, 279 |
| M-103 - HVAC PART PLANS FAC#310 |
| M-104 - HVAC PART PLANS FAC#666, 858, 878 |
| M-105 - HVAC PART PLANS FAC#958, 984, 1060 |
| M-106 - HVAC PART PLANS FAC#1053, 1057, 1163 |
| M-400 - INSTRUMENTATION AND CONTROLS LEGEND |