W912LN-18-B-5001_Amendment_0004.pdf

PDF 163 KB Posted

Attached to
F-35 ALTER AIRCRAFT SHELTER B385, FUEL CELL
Solicitation number
W912LN-18-B-5001
Issued by

About this file

W912LN-18-B-5001 Amendment 4 - Drawing and Specs Updates

View the file

Other files

File Type Posted
3._Bid_Abstract_-_B385_-_Updated.xlsx XLSX spreadsheet
OF_1419A_-_02.pdf PDF
OF_1419A_-_01.pdf PDF
OF_1419_W912LN-18-B-5001_B385_-_UPDATE.pdf PDF
OF_1419_W912LN-18-B-5001_B385.pdf PDF
ATTENDANCE_ROSTER_B385_BID_OPENING.pdf PDF
OF_1419A_-_01.pdf PDF
OF_1419A_-_02.pdf PDF
W912LN-18-B-5001_Amendment_0005_Q&As.pdf PDF
2005 B385 HEF FA A2.pdf PDF
2005 B385 HEF FA FP3.pdf PDF
2005 B385 HEF Gen info FA sys.pdf PDF
Q&A_-_Alter_B385_as_of_15_June_2018_FINAL.pdf PDF
B385_RFI_58_Attachment.zip ZIP file
2005 B385 HEF FA panel elev 2.pdf PDF
2005 B385 HEF FA panel elev.pdf PDF
2005 B385 HEF FA FP1.pdf PDF
2005 B385 HEF FA dev details.pdf PDF
2005 B385 HEF A1.pdf PDF
2005 B385 HEF FA A3.pdf PDF
2005 B385 HEF Floor plan.pdf PDF
2005 B385 HEF FA riser diag.pdf PDF
2005 B385 HEF Simplex set.pdf PDF
2005 B385 HEF FA info charts.pdf PDF
2005 B385 HEF FA FP2.pdf PDF
2005 B385 HEF COVER.pdf PDF
2005 B385 HEF FA dev details2.pdf PDF
2005 B385 HEF FA C1.pdf PDF
B385_Amendment_0004_Drawings.pdf PDF
Q&A_-_Alter_B385_as_of_13_June_2018.pdf PDF
B385_Spec_01_33_29_Amendment_0004.pdf PDF
W912LN-18-B-5001_Amendment_0003.pdf PDF
Q&A_-_Alter_B385_as_of_5_June_2018.pdf PDF
Q&A_-_Alter_B385_as_of_29_May_2018.pdf PDF
W912LN-18-B-5001_Amendment_0002.pdf PDF
Updated_Drawings_Amendment_0002_22MAY2018.pdf PDF
Q&A_-_Alter_B385_as_of_18_May_2018.pdf PDF
B385_Prebid_Attendance_Roster.pdf PDF
B385_Pre_Bid_Site_Visit_10_May_2018.pdf PDF
W912LN-18-B-5001_Amendment_0001.pdf PDF
VTANG_B385_B3_Vol3_Nov2017.pdf PDF
VTANG_B385_B3_Vol2_Nov2017.pdf PDF
VTANG_B385_B3_Vol1_Nov2017.pdf PDF
W912LN-18-B-5001_Alter_B385.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

1 This amendment is issued to provide updates to specifications and draw ings as detailed below .

1. CONTRACT ID CODE PAGE OF PAGES

J 1 6

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 13-Jun-2018

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912LN-18-B-5001

X 9B. DATED (SEE ITEM 11)

20-Apr-2018

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

13-Jun-2018

CODE

158 FW/MSC (F9P3MC)

VERMONT AIR NATIONAL GUARD - WAWF W912LN

45 NCO DRIVE SUITE A

SOUTH BURLINGTON VT 05403-5873

W912LN 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912LN-18-B-5001

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE

The following have been added by full text:

1. SOLICITATION SPECIFICATIONS

The following changes are made to the project solicitation specifications.

A. Specification Section 23 05 48.00 40 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND

EQUIPMENT

ADD

1.1 REFERENCES

U.S. DEPARTMENT OF DEFENSE (DOD)

UFC 3-310-04 (2013; with Change 1) Seismic Design for Buildings UFC 4-010-01 (2012; with Change 1) DoD Minimum Antiterrorism Standards for Buildings

ADD

2.5.1

d. Radiant Heaters

B. Specification Section 23 11 25 FACILITY GAS PIPING

DELETE

3.4 Cut thermoplastic and fiberglass pipe in accordance with AGA XR0603.

DELETE

3.4.1 Do not use aluminum alloy pipe in exterior locations or underground.

ADD

3.4.1 Natural gas piping in concealed spaces shall be continuous or with welded joints.

C. Specification Section 01 33 29 SUSTAINABILITY REPORTING

Section 01 33 29 added in its entirety.

D. Specification Section 08 91 00 METAL WALL LOUVERS

DELETE

2.4.1 Color shall match new windows.

ADD

2.4.1 Color as indicated on drawings.

DELETE

2.4.1.1 , color shall match new windows.

ADD

2.4.1.1 , color as indicated on drawings.

2. SOLICITATION DRAWINGS

Changes are made to the attached solicitation drawings. A summary of changes made to each drawing is listed below.

Drawing GC-102 Added concrete joints to Building 385 to reflect changes to site plan.

Drawing GC-104 Removed notes regarding existing storm sewer elevations.

Added existing underground utilities.

Drawing B-100 Added pavement marking from site plan.

Removed concrete removal/replacement limit.

Drawing CD-101 Added pavement marking removal.

Added asphalt pavement demolition dimension.

Added general demolition notes and utility demolition notes.

Updated legend.

Removed concrete pavement demolition in front of hangar doors.

Drawing CS-101 Added pavement marking to match architectural plans.

Added pavement marking for fire department building connection along with associated notes and dimensions.

Removed concrete replacement and jointing along with associated northings and eastings.

Added a note about door track remaining.

Updated legend.

Drawing CS-110 Added pavement marking from site plan.

Removed concrete removal/replacement limit.

Updated standoff distance note.

Updated drawing name.

Updated legend to reflect note.

Drawing CS-500 Updated note for bollard (detail A3).

Drawing CS-501 Removed concrete paving details to match changes in site plan.

Drawing CG-101 Added spot elevations where site will be graded to match the existing elevations.

Added slopes to grading plan.

Added pavement marking from site plan.

Removed spot elevations for concrete pavement to match changes to the site plan.

Drawing CU-101 Added pavement marking from site plan.

Removed concrete removal/replacement limit.

Drawing FA001 Revised heat detector symbol in legend to include zones.

Added General Note 13.

Drawing FA101 Added heat detector locations, which include two zones.

Drawing FX001 Added Fire Suppression General Note 13.

Drawing S-001 (B385) Added general note regarding the addition of new structure where existing architectural/mechanical/electric/fire protections systems are to remain.

Drawing S-100 (B385) Added note to call out NAVD 88 Elevation that corresponds to 100’-0”.

Drawing S-110 (B385) Added note to call out NAVD 88 Elevation that corresponds to 100’-0”.

Drawing S-120 (B385) Added note to call out NAVD 88 Elevation that corresponds to 100’-0”.

Drawing AG002 (B385) Corrected scale at detail B2 Standard ABA Mounting Heights

Drawing A-001(B385) Added dimensions at detail B1 Striping Plan

Drawing A-201 (B385) Added note for building number and signage tag at Elevations C1 & D3

Drawing A-501 (B385) Removed metal stud bracing note at Partition Type S1 Detail.

Updated reference for Partition Type S2- Head Detail Added General Note #10 for partitions extending to deck

Drawing A-511 (B385) Added interior partition details E1 & C5

Drawing A-611 (B385) Removed single general sheet scale and added scale at each detail on sheet.

Drawing A-721 (B385) Added exterior signage tags

Drawing A-741 (B385) Added scales for all details Added signage exterior building type detail H Updated signage information on Detail B1 for exterior building entrance sign Updated schedule to include sign tags S126 and S127

Drawing P-001 Added clarification for ball valves at each fixture.

Added clarification on contractor requirements to coordinate existing plumbing systems conflicts with new structural elements being installed during construction.

Drawing P-102 Adjusted location of pipe sizes for better clarity. Corrected size of compressed air piping near column line F from ½” to ¾”.

Drawing P-304 Moved location of emergency eyewash/shower, hose station, and compressed air drop.

Drawing P-403 Added clarification for sloping flue.

Drawing P-404 Moved location of emergency eyewash/shower, hose station, and compressed air drop.

Drawing P-502 Corrected scale on detail B2.

Drawing P-902 Revised piping for emergency eyewash/shower, hose station to match changes on P-404.

Drawing M-001 Added clarification on contractor requirements to coordinate existing systems conflicts with new structural elements being installed during construction.

Drawing M-101 Corrected range of flexible exhaust duct required.

Drawing M-102 Changed description for graphic user interface in keyed note 11.

Drawing M-201 Added note to provide drain on boiler vent per manufacturer’s instructions.

Drawing M-301 Corrected flue vent piping from DOAS units.

Added exhaust register tag.

Added Keyed note 2 indicating location of airflow measuring station.

Drawing M-401 Added clarification for sloping flue.

Drawing M-404 Renumbered Keyed Notes.

Removed requirement for Humidity control and Fuel Cell process modes switches and replaced with graphic user interface station.

Drawing M-603 Corrected name of ‘Gas Fired Duct Furnace’ schedule to match up with specification language.

Clarified Gas Fired Duct Furnaces to have stainless steel heat exchangers, burners, and drip pans.

Drawing M-701 Added pulse accumulator clarifications to water meter and gas meter description.

Drawing M-704 Revised Buttons and graphic user display.

Removed requirements for Fuel Maintenance, Humidity, and Fuel Maintenance Humidity modes to time out.

Drawing M-706 Fixed wording for SA-P alarm.

Drawing M-717 Revisions to schematic diagram, sequences for DOAS-104.

Drawing M-718 Revisions to points for DOAS-104 reflecting the changes to M-717.

New Drawing M-719 Added details for graphic user interface displays.

Drawing E-001 Added arc flash notes to general notes.

Drawing E-101 Added circuit for heat trace control panel.

Added UH-104.

Updated circuit number for EF-101.

Relocated generator cannon plug.

Added receptacles for air pear fan connections.

Added standard duplex receptacle to Janitor’s Closet 120.

Drawing E-401 Updated circuit number for fire alarm panels located in Electrical room 105.

Added keyed notes clarifying 270V converter cable length and installation requirements.

Added keyed note requiring receptacle to be weatherproof and GFCI.

Drawing E-601 Added keyed note clarifying conductor and conduit requirements for generator cannon plug connection.

Added clarification on site transformer dual rating requirements.

Updated total load of main switchboard MSB.

Drawing E-602 Update panelboard schedule.

Drawing EG101 Updated grounding plan.

Added touch plate and ground bar to hangar bay.

Drawing EG501 Updated hangar bay grounding receptacle detail to hook type.

(End of Summary of Changes)

File details come from the government source that posted it.