VTANG_B385_B3_Vol3_Nov2017.pdf

PDF 2 MB Posted

Attached to
F-35 ALTER AIRCRAFT SHELTER B385, FUEL CELL
Solicitation number
W912LN-18-B-5001
Issued by

About this file

Volume 3 of 3

View the file

Other files

File Type Posted
3._Bid_Abstract_-_B385_-_Updated.xlsx XLSX spreadsheet
OF_1419A_-_02.pdf PDF
OF_1419A_-_01.pdf PDF
OF_1419_W912LN-18-B-5001_B385_-_UPDATE.pdf PDF
OF_1419_W912LN-18-B-5001_B385.pdf PDF
ATTENDANCE_ROSTER_B385_BID_OPENING.pdf PDF
OF_1419A_-_01.pdf PDF
OF_1419A_-_02.pdf PDF
W912LN-18-B-5001_Amendment_0005_Q&As.pdf PDF
2005 B385 HEF FA A2.pdf PDF
2005 B385 HEF FA FP3.pdf PDF
2005 B385 HEF Gen info FA sys.pdf PDF
Q&A_-_Alter_B385_as_of_15_June_2018_FINAL.pdf PDF
B385_RFI_58_Attachment.zip ZIP file
2005 B385 HEF FA panel elev 2.pdf PDF
2005 B385 HEF FA panel elev.pdf PDF
2005 B385 HEF FA FP1.pdf PDF
2005 B385 HEF FA dev details.pdf PDF
2005 B385 HEF A1.pdf PDF
2005 B385 HEF FA A3.pdf PDF
2005 B385 HEF Floor plan.pdf PDF
2005 B385 HEF FA riser diag.pdf PDF
2005 B385 HEF Simplex set.pdf PDF
2005 B385 HEF FA info charts.pdf PDF
2005 B385 HEF FA FP2.pdf PDF
2005 B385 HEF COVER.pdf PDF
2005 B385 HEF FA dev details2.pdf PDF
2005 B385 HEF FA C1.pdf PDF
B385_Amendment_0004_Drawings.pdf PDF
W912LN-18-B-5001_Amendment_0004.pdf PDF
Q&A_-_Alter_B385_as_of_13_June_2018.pdf PDF
B385_Spec_01_33_29_Amendment_0004.pdf PDF
W912LN-18-B-5001_Amendment_0003.pdf PDF
Q&A_-_Alter_B385_as_of_5_June_2018.pdf PDF
Q&A_-_Alter_B385_as_of_29_May_2018.pdf PDF
W912LN-18-B-5001_Amendment_0002.pdf PDF
Updated_Drawings_Amendment_0002_22MAY2018.pdf PDF
Q&A_-_Alter_B385_as_of_18_May_2018.pdf PDF
B385_Prebid_Attendance_Roster.pdf PDF
B385_Pre_Bid_Site_Visit_10_May_2018.pdf PDF
W912LN-18-B-5001_Amendment_0001.pdf PDF
VTANG_B385_B3_Vol2_Nov2017.pdf PDF
VTANG_B385_B3_Vol1_Nov2017.pdf PDF
W912LN-18-B-5001_Alter_B385.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F-35 Phase 2 Bldg. 385 Vermont Air National Guard Base, VT

Vermont Air National Guard

CRUZ152806

Type B-3 Submittal

Specifications

Specifications Volume 3

20 November 2017

W9133L-15-D-0003 Delivery Order ZT01

PN 92654

This page was intentionally left blank for duplex printing.

F-35 Phase 2 Bldg 385 CURZ 152812

PROJECT TABLE OF CONTENTS Page 1

PROJECT TABLE OF CONTENTS

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

00 22 13.00 20 SUPPLEMENTARY INSTRUCTIONS TO OFFERORS

DIVISION 01 - GENERAL REQUIREMENTS

01 00 00 SPECIAL CONTRACT REQUIREMENTS

01 11 00 SUMMARY OF WORK

01 30 00 ADMINISTRATIVE REQUIREMENTS

01 33 00 SUBMITTAL PROCEDURES

01 42 00 SOURCES FOR REFERENCE PUBLICATIONS

01 45 00.00 10 QUALITY CONTROL

01 78 00 CLOSEOUT SUBMITTALS

01 78 23 OPERATION AND MAINTENANCE DATA

DIVISION 02 - EXISTING CONDITIONS

02 41 00 DEMOLITION

02 82 13.00 10 ASBESTOS ABATEMENT

02 83 13.00 20 LEAD IN CONSTRUCTION

DIVISION 03 - CONCRETE

03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE

FORMING

03 15 00.00 10 CONCRETE ACCESSORIES

03 20 00.00 10 CONCRETE REINFORCING

03 30 00.00 10 CAST-IN-PLACE CONCRETE

03 35 00.00 10 CONCRETE FINISHING

03 35 43 POLISHED CONCRETE FINISHING

03 39 00.00 10 CONCRETE CURING

DIVISION 04 - MASONRY

04 20 00 MASONRY

DIVISION 05 - METALS

05 05 23.16 STRUCTURAL WELDING

05 12 00 STRUCTURAL STEEL

05 30 00 STEEL DECKS

05 40 00 COLD-FORMED METAL FRAMING

05 50 13 MISCELLANEOUS METAL FABRICATIONS

PROJECT TABLE OF CONTENTS Page 2

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS

06 61 16 SOLID POLYMER (SOLID SURFACING) FABRICATIONS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 11 13 BITUMINOUS DAMPPROOFING

07 21 13 BOARD AND BLOCK INSULATION

07 21 16 MINERAL FIBER BLANKET INSULATION

07 21 19 SPRAYED POLYURETHANE FOAM INSULATION

07 22 00 ROOF AND DECK INSULATION

07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIER

07 42 13 METAL WALL PANELS

07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING

07 60 00 FLASHING AND SHEET METAL

07 72 00 ROOF ACCESSORIES

07 72 13 PREFABRICATED ROOF CURBS

07 81 00 SPRAY-APPLIED FIREPROOFING

07 84 00 FIRESTOPPING

07 92 00 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 STEEL DOORS AND FRAMES

08 14 00 WOOD DOORS

08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 81 17 FIRE-RATED GLASS

08 91 00 METAL WALL LOUVERS

PROJECT TABLE OF CONTENTS Page 3

DIVISION 09 - FINISHES

09 06 90 SCHEDULES FOR PAINTING AND COATING

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 51 00 ACOUSTICAL CEILINGS

09 65 00 RESILIENT FLOORING

09 67 23 RESINOUS COATING SYSTEMS

09 67 23.16 FUEL RESISTIVE RESINOUS FLOORING, 5-COAT SYSTEM

09 68 00 CARPETING

09 90 00 PAINTS AND COATINGS

DIVISION 10 - SPECIALTIES

10 11 00 VISUAL DISPLAY UNITS

10 14 00.10 EXTERIOR SIGNAGE

10 14 00.20 INTERIOR SIGNAGE

10 21 13 TOILET COMPARTMENTS

10 26 00 WALL AND DOOR PROTECTION

10 28 13 TOILET ACCESSORIES

10 51 13 METAL LOCKERS

DIVISION 11 - EQUIPMENT

11 01 50 RIGID RAIL FALL PROTECTION SYSTEMS

DIVISION 12 - FURNISHINGS

12 21 00 WINDOW BLINDS

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

DIVISION 13 - SPECIAL CONSTRUCTION

13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT

13 48 00.00 10 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT

DIVISION 21 - FIRE SUPPRESSION

21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

21 13 18.00 10 PREACTION SPRINKLER SYSTEMS, FIRE PROTECTION

21 13 25.00 10 HIGH EXPANSION FOAM (HI EX. HEF) FIRE PROTECTION SYSTEM

DIVISION 22 - PLUMBING

22 00 00 PLUMBING, GENERAL PURPOSE

PROJECT TABLE OF CONTENTS Page 4

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST

SYSTEMS

23 00 99 AIRCRAFT, PRECONITIONED AIR UNITS, PIPING, AND

ACCESSORIES

23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS

23 05 48.00 40 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND

EQUIPMENT

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS

23 11 25 FACILITY GAS PIPING

23 21 13.00 20 LOW TEMPERATURE WATER (LTW) HEATING SYSTEM

23 23 00 REFRIGERANT PIPING

23 52 00 HEATING BOILERS

23 81 00.00 20 UNITARY AIR CONDITIONING EQUIPMENT

23 81 23.00 20 COMPUTER ROOM AIR CONDITIONING UNITS

DIVISION 25 - INTEGRATED AUTOMATION

25 10 10 AUTOMATIC TEMPERATURE CONTROLS

25 10 10.10 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS**

DIVISION 26 - ELECTRICAL

26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS

26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT

26 12 19.10 THREE-PHASE PAD-MOUNTED TRANSFORMERS

26 20 00 INTERIOR DISTRIBUTION SYSTEM

26 24 13 SWITCHBOARDS

26 35 44.00 20 270VDC SOLID STATE GROUND POWER UNIT FOR F-35

AIRCRAFT

26 36 23.00 20 MANUAL TRANSFER SWITCHES

26 41 00 LIGHTNING PROTECTION SYSTEM

26 51 00 INTERIOR LIGHTING

26 56 00 EXTERIOR LIGHTING

PROJECT TABLE OF CONTENTS Page 5

DIVISION 27 - COMMUNICATIONS

27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM

27 51 16 RADIO AND PUBLIC ADDRESS SYSTEMS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM

DIVISION 31 - EARTHWORK

31 00 00 EARTHWORK

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 01 19 FIELD-MOLDED SEALANTS FOR SEALING JOINTS IN RIGID

PAVEMENTS

32 05 33 LANDSCAPE ESTABLISHMENT

32 11 16 BASE COURSE FOR RIGID PAVING

32 11 23 GRADED-CRUSHED AGGREGATE BASE COURSE

32 12 10 BITUMINOUS TACK AND PRIME COATS

32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS

32 13 11 CONCRETE PAVEMENT FOR AIRFIELDS AND OTHER HEAVY-DUTY

PAVEMENTS

32 16 13 CONCRETE SIDEWALKS

32 17 23 PAVEMENT MARKINGS

32 31 13 BARRIER GATE OPERATOR

32 92 23 SODDING

DIVISION 33 - UTILITIES

33 11 00 WATER UTILITY DISTRIBUTION PIPING

33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

-- End of Project Table of Contents --

This page was intentionally left blank for duplex printing.

F- 35 Phase 2 Bl dg 385 CURZ 152812 Ver mont Ai r Nat i onal Guar d Base, VT

SECTI ON 25 10 10

AUTOMATI C TEMPERATURE CONTROLS

12/16

PART 1 GENERAL

1. 1 AUTOMATI C TEMPERATURE CONTROL SYSTEM

Al l Aut omat i c Temper at ur e Cont r ol s ( ATC) wor k shal l be i n keepi ng wi t h cur r ent VTANG r equi r ement s and pr act i ces, i ncl udi ng submi t t al s, pr ogr ammi ng r esponsi bi l i t i es, equi pment , cont r ol l er s, wi r i ng met hods, sequences of oper at i on, i nput / out put poi nt s and Owner i nst r uct i on.

The i nt ent i s t hat a pr oven i nst al l er and of f i c i al r epr esent at i ve of Schnei der El ect r i c I / A Ser i es wi l l pr ovi de al l mat er i al and l abor r equi r ed t o compl et e and per f ect DDC cont r ol s sequences f or al l syst ems as i ndi cat ed and/ or r equi r ed i n t hi s Sect i on. The BAS shal l be i nst al l ed t o i nc l ude al l wi r i ng, pi pi ng, i nst al l at i on super vi s i on, cal i br at i on, adj ust ment s and checkout necessar y f or a compl et e and f ul l y oper at i onal syst em t o ser ve t he building.

The i nst al l er shal l be an of f i c i al r epr esent at i ve of Schnei der El ect r i c I / A Ser i es i n t he Bur l i ngt on, VT r egi on.

New BAS wor k shal l be an ext ensi on of t he exi st i ng VTANG BAS t hat ser ves t he exi st i ng bui l di ngs at t he s i t e. Al l r ead/ wr i t e/ al ar m poi nt s speci f i ed her ei n shal l be accessi bl e and execut abl e f r om t he s i t e' s exi st i ng VTANG BAS. Thi s Cont r act or shal l be f ul l y r esponsi bl e f or coor di nat i on of al l det ai l s necessar y f or est abl i shi ng t he i nt egr at i on bet ween t he new and est abl i shed BAS on base. New gr aphi cal i nt er f ace " scr eens" shal l be pr ovi ded, as necessar y, f or al l new wor k.

Thi s mat er i al and l abor speci f i ed i n t hi s Speci f i cat i on Sect i on shal l be pr ovi ded by a s i ngl e Ti er 1 l evel Subcont r act or and shal l wor k di r ect l y f or t he Gener al Cont r act or .

Cont r ol s Cont r act or shal l pr ovi de var i abl e f r equency dr i ves ( VFD) compl yi ng wi t h Sect i on 25 10 10. 10 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS.

Sequence Check - Al l cont r ol sequences of oper at i on shal l be i ndependent l y ver i f i ed by t he Commi ssi oni ng Agent . Not e: Shoul d syst ems be f ound i ncompl et e or not per f or mi ng per Speci f i cat i on, t hi s Tr ade shal l cor r ect def i c i enci es and t he Commi ssi oni ng Agent shal l r echeck unt i l al l sequences have been ver i f i ed.

I n cooper at i on wi t h t he Cont r ol Tr ade, t he Mechani cal Tr ade shal l :

a. I nst al l aut omat i c val ves and separ abl e wel l s suppl i ed by t he Cont r ol Trade.

b. Pr ovi de on magnet i c st ar t er s f ur ni shed, al l necessar y st ep- down t r ansf or mer s and auxi l i ar y cont act s wi t h but t ons and swi t ches i n r equi r ed conf i gur at i ons.

c. I nst al l al l aut omat i c damper s.

d. Pr ovi de necessar y bl ank- of f pl at es ( saf i ng) r equi r ed t o i nst al l damper s

92654Bldg385 SECTI ON 25 10 10 Page 1 t hat ar e smal l er t han duct s i ze.

e. Assembl e mul t i pl e sect i on damper s wi t h r equi r ed i nt er connect i ng l i nkages and ext end r equi r ed number of shaf t s t hr ough duct f or ext er nal mount i ng of damper mot or s.

f . Pr ovi de necessar y sheet met al baf f l e pl at es t o el i mi nat e st r at i f i cat i on and pr ovi de ai r vol umes speci f i ed. Locat e baf f l es by exper i ment at i on and af f i x and seal per manent l y i n pl ace onl y af t er st r at i f i cat i on pr obl em has been el i mi nat ed.

g. Pr ovi de access door s or ot her appr oved means of access t hr ough duct s f or ser vi ce of cont r ol equi pment .

h. I nst al l new wat er met er s.

1. 2 ELECTRI C WI RI NG

Al l el ect r i c wi r i ng and wi r i ng connect i ons r equi r ed f or t he i nst al l at i on of t he cont r ol syst em, as her ei n speci f i ed, shal l be pr ovi ded by t he Cont r ol Tr ade unl ess speci f i cal l y shown on t he El ect r i cal Dr awi ngs or cal l ed f or i n t he El ect r i cal Speci f i cat i ons.

The cont r ol syst em shal l be i nst al l ed and wi r ed by f act or y t r ai ned and cer t i f i ed t echni c i ans i n accor dance wi t h al l per t i nent codes, par t i cul ar l y t he N. E. C. Al l l ow vol t age communi cat i on wi r i ng r un i n ar eas or spaces suscept i bl e t o damage, i . e. , boi l er r oom and mechani cal r ooms shal l be pr ot ect ed wi t hi n EMT. Al l ot her may be pl enum r at ed cabl e secur ed t o st r uct ur e wi t hi n wal l s or cei l i ng space r un as hi gh as possi bl e i n a wor kmanl i ke manner and i nst al l ed t o el i mi nat e r i sk of acci dent al pul l or cut t i ng by ot her Tr ades.

1. 3 SERVI CE AND TRAI NI NG

The Cont r ol Tr ade shal l pr ovi de syst em st ar t - up, commi ssi oni ng and user f i el d t r ai ni ng per f or med by a cer t i f i ed ser vi ce t echni c i an who i s exper i enced i n st ar t - up, r epai r and t r ai ni ng ser vi ces. Fi el d t r ai ni ng shal l be a mi ni mum of t hr ee ( 3) days.

1. 4 DESI GN REQUI REMENTS

a. Cont r ol Syst em Dr awi ngs Ti t l e Sheet : Pr ovi de a t i t l e sheet f or t he cont r ol syst em dr awi ng set . I ncl ude t he pr oj ect t i t l e, pr oj ect l ocat i on, cont r act number , t he cont r ol s cont r act or pr epar i ng t he dr awi ngs, an i ndex of t he cont r ol dr awi ngs i n t he set , and a l egend of t he symbol s and abbr evi at i ons used t hr oughout t he cont r ol syst em drawings.

b. Li st of I / O Poi nt s: Al so known as a Poi nt Schedul e, pr ovi de f or each i nput and out put poi nt physi cal l y connect ed t o a di gi t al cont r ol l er :

Poi nt name, poi nt descr i pt i on, poi nt t ype ( Anal og Out put ( AO) , Anal og I nput ( AI ) , Bi nar y Out put ( BO) , Bi nar y I nput ( BI ) ) , poi nt sensor r ange, poi nt act uat or r ange. Typi cal schedul es f or mul t i pl e i dent i cal equi pment ar e al l owed.

c. Cont r ol Syst em Component s Li st : Pr ovi de a compl et e l i s t of cont r ol syst em component s i nst al l ed on t hi s Pr oj ect . I ncl ude f or each cont r ol l er and devi ce: Cont r ol syst em schemat i c name, cont r ol syst em schemat i c desi gnat i on, devi ce descr i pt i on, manuf act ur er , model , par t

92654Bldg385 SECTI ON 25 10 10 Page 2 number , f i r mwar e ver si on, ser i al number , and physi cal l ocat i on ( e. g. , Bui l di ng 4, r oom 112 over head) . For sensor s, i ncl ude poi nt name, sensor r ange, and oper at i ng l i mi t s. For val ves, i ncl ude body st y l e, Cv, desi gn f l ow r at e, pr essur e dr op, val ve char act er i st i c ( l i near or equal per cent age) , and pi pe connect i on s i ze. For act uat or s, i ncl ude poi nt name, spr i ng or non- spr i ng r et ur n, modul at i ng or t wo- posi t i on act i on, nor mal ( power f ai l ) posi t i on, nomi nal cont r ol s i gnal oper at i ng r ange ( 0- 10 vol t s DC or 4- 20 mi l l i amps) , and oper at i ng l i mi t s.

d. Cont r ol Syst em Schemat i cs: Pr ovi de cont r ol syst em schemat i cs. Typi cal schemat i cs f or mul t i pl e i dent i cal equi pment ar e al l owed unl ess ot her wi se r equest ed i n desi gn or cont r act cr i t er i a. I ncl ude t he following:

( 1) Locat i on of each i nput and out put devi ce.

( 2) Fl ow di agr am f or each pi ece of HVAC equi pment .

( 3) Name or symbol f or each cont r ol syst em component .

( 4) Set poi nt s, wi t h di f f er ent i al or pr opor t i onal band val ues.

( 5) Wr i t t en sequence of oper at i on f or t he HVAC equi pment .

( 6) Val ve and Damper Schedul es, wi t h nor mal ( power f ai l ) posi t i on.

1. 5 COMMUNI CATI ON ARCHI TECTURE SCHEMATI C

Pr ovi de a schemat i c showi ng t he pr oj ect ' s ent i r e communi cat i on net wor k, i ncl udi ng any devi ces i ncl udi ng r out er s and br i dges, gat eways, cont r ol l er s, and f i el d i nt er f ace devi ces. Show connect i on t o exi st i ng Base net wor k.

1. 6 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AI R MOVEMENT AND CONTROL ASSOCI ATI ON I NTERNATI ONAL ( AMCA)

AMCA 500- D ( 2012) Labor at or y Met hods of Test i ng Damper s f or Rat i ng

AMCA 511 ( 2010) Cer t i f i ed Rat i ngs Pr ogr am f or Ai r Cont r ol Devi ces

AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )

ANSI C12. 1 ( 2008) El ect r i c Met er s Code f or El ect r i c i t y Met er i ng

ASTM I NTERNATI ONAL ( ASTM)

ASTM A536 ( 1984; R 2014) St andar d Speci f i cat i on f or Duct i l e I r on Cast i ngs

AMERI CAN WATER WORKS ASSOCI ATI ON ( AWWA)

AWWA C700 ( 2015) St andar d f or Col d Wat er Met er s -

92654Bldg385 SECTI ON 25 10 10 Page 3

Di spl acement Type, Br onze Mai n Case

U. S. DEPARTMENT OF DEFENSE ( DOD)

MIL-STD-810 ( 2008; Rev G; Change 1 2014) Envi r onment al Engi neer i ng Consi der at i ons and Labor at or y Tests

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2017) Nat i onal El ect r i cal Code

NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems

NATI ONAL I NSTI TUTE OF STANDARDS AND TECHNOLOGY ( NI ST)

NI ST SP 800- 82 ( 2015; Rev 2) Gui de t o I ndust r i al Cont r ol Syst ems ( I CS) Secur i t y

UNDERWRI TERS LABORATORI ES ( UL)

UL 5085- 3 ( 2006; Repr i nt Nov 20121) Low Vol t age Tr ansf or mer s - Par t 3: Cl ass 2 and Cl ass 3 Transformers

UL 508A ( 2001; Repr i nt Feb 2010) I ndust r i al Cont r ol Panel s

UL 864 ( 2014) St andar d f or Cont r ol Uni t s and Accessor i es f or Fi r e Al ar m Syst ems

1. 7 SUBMI TTALS

Submi t det ai l ed and annot at ed manuf act ur er ' s dat a, Dr awi ngs, and Speci f i cat i on Sheet s f or each i t em l i s t ed, t hat c l ear l y show compl i ance wi t h t he Pr oj ect Speci f i cat i ons. Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on; submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

I ncl ude t he f ol l owi ng i n t he Pr oj ect ' s cont r ol syst em dr awi ng set:

Cont r ol Syst em Dr awi ngs Ti t l e Sheet ; G

Li st of I / O Poi nt s; G

Cont r ol Syst em Component s Li st ; G

Cont r ol Syst em Schemat i cs; G

92654Bldg385 SECTI ON 25 10 10 Page 4

Communi cat i on Ar chi t ect ur e Schemat i c; G

Wi r i ng Di agr ams; G

Sequences of Oper at i on; G

Damper Schedul e; G

Val ve Schedul e; G

Syst em Gr aphi cs; G

SD- 03 Pr oduct Dat a

Di r ect Di gi t al Cont r ol l er s; G

Gat eways; G

Sensor s and I nput Har dwar e; G

Val ves; G

Damper s; G

Met er s; G

SD- 06 Test Repor t s

Per f or mance Ver i f i cat i on Test i ng Repor t ; G

SD- 09 Manuf act ur er ' s Fi el d Repor t s

Pr e- PVT Checkl i s t ; G

SD- 10 Oper at i on and Mai nt enance Dat a

Compl y wi t h r equi r ement s f or dat a packages i n Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA, except as suppl ement ed and modi f i ed i n t hi s Speci f i cat i on.

Di r ect Di gi t al Cont r ol ( DDC) Syst em, Dat a Package 4; G

Cont r ol s Syst em Oper at or s Manual s, Dat a Package 4; G

VFD Ser vi ce Manual s, Dat a Package 4; G

SD- 11 Cl oseout Submi t t al s

Tr ai ni ng Document at i on; G

1. 8 PROJECT SEQUENCE

The cont r ol syst em wor k f or t hi s Pr oj ect shal l pr oceed i n t he f ol l owi ng order:

a. Submi t and r ecei ve appr oval on t he Shop Dr awi ngs, and Pr oduct Dat a speci f i ed under t he Par agr aph " Submi t t al s" .

b. Per f or m t he cont r ol syst em i nst al l at i on wor k, i ncl udi ng al l f i el d

92654Bldg385 SECTI ON 25 10 10 Page 5 check- out s and t uni ng.

c. Pr ovi de suppor t t o TAB per sonnel as speci f i ed under t he Par agr aph " Test And Bal ance Suppor t " .

d. Submi t and r ecei ve appr oval of t he Cont r ol s Syst em Oper at or s Manual speci f i ed under t he Par agr aph " Cont r ol s Syst em Oper at or s Manual s" .

e. Submi t and r ecei ve appr oval of t he Per f or mance Ver i f i cat i on Test i ng Pl an and t he Pr e- PVT Checkl i st speci f i ed under t he Par agr aph " Per f or mance Ver i f i cat i on Test i ng" .

f . Per f or m t he Per f or mance Ver i f i cat i on Test i ng.

g. Submi t and r ecei ve appr oval on t he PVT Repor t .

h. Submi t and r ecei ve appr oval on t he Tr ai ni ng Document at i on. Submi t at l east 30 days bef or e t r ai ni ng.

i . Del i ver t he f i nal Cont r ol s Syst em Oper at or s Manual s.

j . Conduct t he on- si t e/ hands- on t r ai ni ng.

k. Submi t and r ecei ve appr oval of Cl oseout Submi t t al s.

1. 9 ABBREVI ATI ONS

a. DDC = Di r ect Di gi t al Cont r ol .

b. CTI = Cont r ol Technol ogi es, I nc.

c. GCM = Gl obal Cont r ol Modul e.

d. BMMS = Base Mast er Moni t or i ng Syst em.

e. ACV = Aut omat i c Cont r ol Val ve.

f . ACD = Aut omat i c Cont r ol Damper .

g. ERU = Ener gy Recover y Uni t .

PART 2 PRODUCTS

Aut omat i c t emper at ur e cont r ol f i el d moni t or i ng and cont r ol syst em usi ng f i el d pr ogr ammabl e mi cr o- pr ocessor based uni t s. Syst em shal l be an ext ensi on of t he exi st i ng base BAS syst em.

Pr ovi de di st r i but ed syst em of f ul l y i nt el l i gent , s t and- al one cont r ol l er s, oper at i ng i n a mul t i - t aski ng, mul t i - user envi r onment on t oken passi ng net wor k, wi t h cent r al and r emot e har dwar e, sof t war e, and i nt er connect i ng wi r e and condui t .

I ncl ude comput er sof t war e, oper at or i nput / out put devi ces, cont r ol uni t s, l ocal ar ea net wor ks ( LAN) , sensor s, cont r ol devi ces, act uat or s.

Pr ovi de cont r ol syst ems consi st i ng of t her most at s, cont r ol val ves, damper s and oper at or s, i ndi cat i ng devi ces, i nt er f ace equi pment and ot her appar at us and accessor i es r equi r ed t o oper at e mechani cal syst ems, and t o per f or m f unct i ons speci f i ed.

92654Bldg385 SECTI ON 25 10 10 Page 6

I ncl ude i nst al l at i on and cal i br at i on, super vi s i on, adj ust ment s, and f i ne t uni ng necessar y f or compl et e and f ul l y oper at i onal syst em.

2. 1 DI RECT DI GI TAL CONTROL ( DDC) SYSTEM

DDC cont r ol l er s shal l be used t o manage t he f ol l owi ng syst ems and f unct i ons:

a. Occupi ed/ unoccupi ed schedul es.

b. New ENCs as r equi r ed f or bui l di ng cont r ol and BMMS i nt er f ace.

c. Pumps cont r ol and moni t or i ng t hr ough t he BMMS.

d. I nt egr at i on of al l LonWor ks net wor k var i abl es f r om Var i abl e Fr equency Dr i ves v i a manuf act ur er - pr ovi ded LonWor ks car ds. ( For moni t or i ng onl y) .

e. HVAC syst ems cont r ol and moni t or i ng t hr ough t he BMMS.

f . Boi l er syst em cont r ol s and moni t or i ng t hr ough t he BMMS.

g. Exhaust f ans cont r ol and moni t or i ng t hr ough t he BMMS.

h. HVAC equi pment cont r ol and moni t or i ng t hr ough t he BMMS.

i . I ndi v i dual r ooms cont r ol and moni t or i ng t hr ough t he BMMS.

The DDC syst em shal l be compr i sed of f ul l y pr ogr ammabl e cont r ol l er s t hat have t he abi l i t y t o empl oy cust om bl ock pr ogr ams and r un i n a st andal one mode. Syst em bl ock pr ogr ammi ng l anguage shal l pr ovi de t he oper at or wi t h 100 per cent f l ex i bi l i t y f or cr eat i on of new and uni que cont r ol st r at egi es.

The DDC syst em shal l cont r ol al l pi eces of mechani cal equi pment not ed her ei naf t er and on t he Dr awi ngs, i ncl udi ng t hose t hat ar e appl i cat i on speci f i c . Thr ough t he f r ont end comput er or a not ebook comput er i nt er f ace, i t shal l be possi bl e f or cont r ol pr ogr ams t o be downl oaded t o al l devi ces r equi r i ng a gi ven sequence of oper at i on. The DDC syst em shal l of f er f ul l pr ogr ammabi l i t y f or easy cr eat i on and modi f i cat i on of cust om cont r ol st r at egi es, and easy dupl i cat i on of cont r ol l er dat abases f or mechani cal equi pment cont ai ni ng s i mi l ar or i dent i cal cont r ol st r at egi es.

DDC modul ar har dwar e, al ong wi t h net wor ki ng capabi l i t i es, shal l al l ow easy syst em expansi on as needs of t he f aci l i t y change i n t he f ut ur e. Al l pr ogr ammabl e cont r ol l er s shal l be LON based ( as appl i cabl e) t o st or e appl i cat i on cont r ol pr ogr ams and al l ow modi f i cat i on of exi st i ng cont r ol sequences or cr eat i on of new ones.

Syst em ar chi t ect ur e shal l per mi t pr ogr ammer i nt er f ace f r om anywher e wi t hi n t he BMMS net wor k and al l ow web based cont r ol st r at egi es t o be easi l y performed.

New BMMS gr aphi cs shal l i ncl ude al l VTANG " St andar d" gr aphi c di spl ays.

2. 2 CYBER SECURI TY REQUI REMENTS FOR DEPARTMENT OF DEFENSE FACI LI TI ES

Depl oyed syst em must sat i sf y syst em r equi r ement s t o meet DI ARMF ( U. S.

Depar t ment of Def ense I nf or mat i on Assur ance Ri sk Management Fr amewor k) compl i ance. Onl y except i on i s i f syst em i s empl oyi ng a PEMS syst em such as descr i bed i n subsect i on bel ow.

92654Bldg385 SECTI ON 25 10 10 Page 7

The syst em shal l have t he capabi l i t y t o pr ovi de a web- based AFDD ( aut omat ed f aul t det ect i on and di agnost i c) syst em. The AFDD syst em shal l be abl e t o i nt er f ace di r ect l y wi t h t he Pr oj ect BAS and ener gy/ per f or mance met er i ng syst em t o pr ovi de i nf or mat i on on HVAC syst ems t hat ar e bei ng cont r ol l ed.

Successf ul compl i ance t est i ng shal l be compl et ed i n accor dance wi t h t he following:

a. DoDI 8510. 01, Ri sk Management Fr amewor k ( RMF) f or DoD I nf or mat i on Technol ogy ( I T) ( May 24, 2016) .

b. DoDI 8500. 01 Cyber secur i t y ( Mar ch 14, 2014) .

c. Nat i onal I nst i t ut e of St andar ds and Technol ogy ( NI ST) gui del i nes:

(1) NI ST SP 800- 53.

(2) NI ST SP 800- 53a.

(3) NI ST SP 800- 82.

(4) NI ST SP 800- 37.

Tool s used f or compl i ance t est i ng must be appr oved by t he DoD, Def ense I nf or mat i on Syst ems Agency ( DI SA) and NI ST. Gui del i nes r equi r ed f or successf ul compl i ance and shal l i ncl ude:

a. Nessus vul ner abi l i t y scanner ;

b. NMap por t scanner ;

c. Assur ed Compl i ance Assessment Sol ut i ons ( ACAS) ;

d. Secur i t y Cont ent Aut omat i on Pr ot ocol ( SCAP) ;

e. Manual Secur i t y Techni cal I mpl ement at i on Gui de ( STI G) .

Pr oduct t est r esul t s must successf ul l y show:

a. The pr oduct meet s or exceeds t he RMF st andar d.

b. The pr oduct does not have any Hi gh or Medi um cat egor y vul ner abi l i t i es.

c. The pr oduct i s expect ed t o meet or exceed any r i sk assessment and obt ai n a f ul l aut hor i zat i on t o oper at e ( ATO) .

2. 3 CONTROLLERS

2. 3. 1 Bui l di ng Cont r ol l er s

Bui l di ng shal l have a mi ni mum of ( 1) ASP whi ch aggr egat es bui l di ng dat a bef or e sendi ng t o t he base Ent er pr i se Ser ver . The ASP shal l al so hol d any gl obal l ogi c i nf or mat i on r equi r ed f or bui l di ng oper at i on. Al l pl ant l evel cont r ol shal l be pr ogr ammed wi t h Wor k Pl ace Tech Tool .

Manage gl obal st r at egi es by one or mor e, i ndependent , st andal one, mi cr opr ocessor based cont r ol l er s. Pr ovi de suf f i c i ent memor y t o suppor t cont r ol l er ' s oper at i ng syst em, dat abase, and pr ogr ammi ng r equi r ement s.

92654Bldg385 SECTI ON 25 10 10 Page 8

Shar e dat a bet ween net wor ked cont r ol l er s and ut i l i ze r eal - t i me cl ock f or scheduling.

Cont r ol l er oper at i ng syst em manages i nput and out put communi cat i on s i gnal s al l owi ng di st r i but ed cont r ol l er s t o shar e r eal and v i r t ual obj ect i nf or mat i on and al l owi ng f or cent r al moni t or i ng and al ar ms. Syst em shal l cont i nuousl y check pr ocessor st at us and memor y c i r cui t s f or abnor mal oper at i on. Cont r ol l er t o assume pr edet er mi ned f ai l ur e mode and gener at e al ar m not i f i cat i on upon det ect i on of abnor mal oper at i on. Communi cat i on wi t h ot her net wor k devi ces t o be based on assi gned pr ot ocol .

Al l f i el d bus cont r ol l er s shal l be LonWor ks MNL or Bacnet MNB ser i es cont r ol l er s f or poi nt count under 20. Fi el d equi pment r equi r i ng mor e t han 20 I / O shal l ut i l i z i ng t he BacNet I P AnnexJ MNB- 1000 cont r ol l er wi t h expandabl e I / O. BacNet MSTP bus shal l never be used f or mul t i - vendor syst ems and each MSTP br anch shal l not cont ai n mor e t han 20 devi ces. Al l t hi r d par t y pr oduct shal l be LonWor ks FT- 10. Pr ovi de wi t h ser vi ce communi cat i on por t f or connect i on t o a por t abl e oper at or ' s t er mi nal or hand hel d devi ce wi t h compat i bl e pr ot ocol .

Cont r ol l er s shal l be mount ed wi t hi n dust pr oof encl osur es and r at ed f or oper at i on at 32 t o 120 degr ees F.

Make al l wi r i ng connect i ons t o f i el d r emovabl e, modul ar t er mi nal st r i ps, or t o a t er mi nat i on car d connect ed by a r i bbon cabl e. Pr ovi de wi t h di agnost i c LEDs f or power , communi cat i on, and pr ocessor . I n t he event of a power l oss, mai nt ai n al l BI OS and pr ogr ammi ng i nf or mat i on f or a mi ni mum of 72 hours.

Cont r ol l er s shal l per f or m or der l y shut down bel ow 80 per cent of nomi nal vol t age. Cont r ol l er oper at i on shal l be pr ot ect ed agai nst el ect r i cal noi se of 5 t o 120 Hz and f r om keyed r adi os up t o 5 W. at 3 f eet .

2. 3. 2 Appl i cat i on Speci f i c Cont r ol l er s

Not f ul l y user pr ogr ammabl e, mi cr opr ocessor based cont r ol l er s dedi cat ed t o cont r ol speci f i c equi pment . Cust omi zed f or oper at i on wi t hi n t he conf i nes of equi pment ser ved. Communi cat i on wi t h ot her net wor k devi ces t o be based on assi gned pr ot ocol .

Cont r ol l er t o r esi de on a LonWor ks net wor k usi ng MS/ TP Dat a Li nk/ Physi cal l ayer pr ot ocol . Pr ovi de wi t h ser vi ce communi cat i on por t f or connect i on t o a por t abl e oper at or ' s t er mi nal or hand hel d devi ce wi t h compat i bl e pr ot ocol .

Cont r ol l er s shal l be mount ed wi t hi n dust pr oof encl osur es and r at ed f or oper at i on at 32 t o 120 degr ees F.

Make al l wi r i ng connect i ons t o f i el d r emovabl e, modul ar t er mi nal st r i ps, or t o a t er mi nat i on car d connect ed by a r i bbon cabl e. Pr ovi de wi t h di agnost i c LEDs f or power , communi cat i on, and pr ocessor . I n t he event of a power l oss, mai nt ai n al l BI OS and pr ogr ammi ng i nf or mat i on f or a mi ni mum of 72 hours.

Cont r ol l er s shal l per f or m or der l y shut down bel ow 80 per cent of nomi nal vol t age. Cont r ol l er oper at i on shal l be pr ot ect ed agai nst el ect r i cal noi se of 5 t o 120 Hz and f r om keyed r adi os up t o 5 W. at 3 f eet .

92654Bldg385 SECTI ON 25 10 10 Page 9

2. 3. 3 I nput / Out put I nt er f ace

Har dwi r ed i nput s and out put s t i e i nt o t he DDC syst em t hr ough bui l di ng, cust om appl i cat i on, or appl i cat i on speci f i c cont r ol l er s.

Al l I nput / Out put Poi nt s shal l pr ot ect cont r ol l er f r om damage r esul t i ng f r om any poi nt shor t - c i r cui t i ng or gr oundi ng and f r om vol t age up t o 24 vol t s of any dur at i on. Pr ovi de uni ver sal t ype f or bui l di ng and cust om appl i cat i on cont r ol l er s wher e i nput or out put i s sof t war e desi gnat ed as ei t her bi nar y or anal og t ype wi t h appr opr i at e pr oper t i es.

Bi nar y I nput s al l ow moni t or i ng of On/ Of f s i gnal s f r om r emot e devi ces, sense dr y cont act c l osur e, or pr ovi de wet t i ng cur r ent of 12 mA mi ni mum, compat i bl e wi t h commonl y avai l abl e cont r ol devi ces and pr ot ect ed agai nst t he ef f ect s of cont act bounce and noi se.

Pul se Accumul at i on I nput Obj ect s: Conf or m t o al l r equi r ement s of bi nar y i nput obj ect s and accept up t o 10 pul ses per second.

Anal og I nput s shal l be compat i bl e wi t h and f i el d conf i gur abl e t o commonl y avai l abl e sensi ng devi ces. Al l ow f or moni t or i ng of l ow vol t age 0 t o 10 VDC, 4 t o 20 mA cur r ent , or r esi st ance si gnal s ( t her mi st or , RTD) .

Bi nar y Out put s shal l be used f or On/ Of f oper at i on or a pul sed l ow- vol t age si gnal f or pul se wi dt h modul at i on cont r ol ; out put s pr ovi ded wi t h t hr ee posi t i on ( On/ Of f / Aut o) over r i de swi t ches; st at us l i ght s f or bui l di ng and cust om appl i cat i on cont r ol l er s t o be sel ect abl e f or nor mal l y open or nor mal l y c l osed oper at i on.

Anal og Out put s shal l be f or moni t or i ng s i gnal pr ovi des a 0 t o 10 VDC or a 4 t o 20 mA out put s i gnal f or end devi ce cont r ol . Pr ovi de st at us l i ght s and t wo posi t i on ( AUTO/ MANUAL) swi t ch f or bui l di ng and cust om appl i cat i on cont r ol l er s wi t h manual l y adj ust abl e pot ent i omet er f or manual over r i de on bui l di ng and cust om appl i cat i on cont r ol l er s. Dr i f t t o not exceed 0. 4 per cent of r ange per year .

Tr i St at e Out put s shal l coor di nat e t wo bi nar y out put s t o cont r ol t hr ee poi nt , f l oat i ng t ype, el ect r oni c act uat or s wi t hout f eedback. Cont r ol al gor i t hms r un t he zone act uat or t o one end of i t s st r oke once ever y 24 hour s f or ver i f i cat i on of oper at or t r acki ng. Li mi t t he use of t hr ee poi nt , f l oat i ng devi ces t o t he f ol l owi ng zone and t er mi nal uni t cont r ol applications:

a. Radi at i on.

Syst em si ze t o be expandabl e t o t wi ce t he number of i nput out put obj ect s r equi r ed by pr ovi di ng addi t i onal cont r ol l er s, i ncl udi ng associ at ed devi ces and wi r i ng.

Har dwar e addi t i ons or sof t war e r evi s i ons f or t he i nst al l ed oper at or i nt er f aces ar e not t o be r equi r ed f or f ut ur e, syst em expansi ons.

2. 4 POWER SUPPLI ES AND LI NE FI LTERI NG

2. 4. 1 Power Suppl i es

Pr ovi de UL l i s t ed cont r ol t r ansf or mer s wi t h Cl ass 2 cur r ent l i mi t i ng t ype or over - cur r ent pr ot ect i on i n bot h pr i mar y and secondar y c i r cui t s f or Cl ass 2 ser vi ce as r equi r ed by t he NEC.

92654Bldg385 SECTI ON 25 10 10 Page 10

Li mi t connect ed l oads t o 80 per cent of r at ed capaci t y, mat ch DC power suppl y t o cur r ent out put and vol t age r equi r ement s. Uni t t o be f ul l wave r ect i f i er t ype wi t h out put r i ppl e of 5. 0 mV maxi mum peak t o peak.

Regul at i on t o be 1 per cent combi ned l i ne and l oad wi t h 100 mi cr osecond r esponse t i me f or 50 per cent l oad changes. Pr ovi de over - vol t age and over - cur r ent pr ot ect i on t o wi t hst and a 150 per cent cur r ent over l oad f or 3 seconds mi ni mum wi t hout t r i p- out or f ai l ur e.

Pr ovi de f or ambi ent condi t i ons of 32 t o 120 degr ees F. EM/ RF meet s FCC Cl ass B and VDE 0871 f or Cl ass B and MIL-STD-810 f or shock and v i br at i on.

Li ne vol t age uni t s UL r ecogni zed and CSA appr oved.

2. 4. 2 Power Li ne Fi l t er i ng

Pr ovi de ext er nal or i nt er nal t r ansi ent vol t age and sur ge suppr essi on component f or al l wor kst at i ons and cont r ol l er s. Mi ni mum sur ge pr ot ect i on attributes:

a. Di el ect r i c st r engt h of 1000 vol t s mi ni mum.

b. Response t i me of 10 nanoseconds or l ess.

c. Tr ansver se mode noi se at t enuat i on of 65 dB or gr eat er .

d. Common mode noi se at t enuat i on of 150 dB or gr eat er at 40 t o 100 Hz.

2. 5 LOCAL AREA NETWORK ( LAN)

Pr ovi de communi cat i on bet ween cont r ol uni t s over l ocal ar ea net wor k ( CE VLAN) . Net wor k por t s shal l be pr ovi ded by base comm uni t s.

2. 6 CONTROLLER SOFTWARE

2. 6. 1 Appl i cat i ons

Al l appl i cat i ons r esi de and oper at e i n t he syst em cont r ol l er s and edi t i ng of al l appl i cat i ons occur s at t he oper at or wor kst at i on.

2. 6. 2 Syst em Secur i t y

a. User access secur ed v i a user passwor ds and user names.

b. Passwor ds r est r i c t user t o t he obj ect s, appl i cat i ons, and syst em f unct i ons as assi gned by t he syst em manager .

c. User Log On/ Log Of f at t empt s ar e r ecor ded.

d. Aut omat i c Log Of f occur s f ol l owi ng t he l ast keyst r oke af t er a user def i ned del ay t i me.

2. 6. 3 Obj ect or Obj ect Gr oup Schedul i ng

Weekl y schedul es based on separ at e, dai l y schedul es shal l i ncl ude st ar t , st op, opt i mal st op, and ni ght economi zer . 10 event s maxi mum per schedul e.

St ar t / st op t i mes adj ust abl e f or each gr oup obj ect .

Except i on schedul es shal l be based on any day of t he year , def i ned up t o one year i n advance. Aut omat i cal l y di scar ded and r epl aced wi t h st andar d

92654Bldg385 SECTI ON 25 10 10 Page 11 schedul e f or t hat day of t he week upon execut i on.

Hol i day or speci al schedul es shal l have capabi l i t y t o def i ne up t o 99 schedul es r epeat ed annual l y. Lengt h of each per i od i s oper at or def i ned.

2. 6. 4 Equi pment Coor di nat i on

Pr ovi de st andar d appl i cat i on f or equi pment coor di nat i on and gr oupi ng based on f unct i on and l ocat i on t o be used f or schedul i ng and ot her appl i cat i ons.

2. 6. 5 Al ar ms

a. Bi nar y obj ect i s set t o al ar m based on t he oper at or speci f i ed st at e.

b. Anal og obj ect t o have hi gh/ l ow al ar m l i mi t s.

c. Al l al ar mi ng i s capabl e of bei ng aut omat i cal l y and manual l y di sabl ed.

d. Oper at or det er mi nes act i on t o be t aken f or al ar m event . Al ar ms t o be r out ed t o appr opr i at e wor kst at i on.

e. Al ar m Repor t i ng Opt i ons:

( 1) St ar t pr ogr ams.

( 2) Pr i nt .

( 3) Logged.

( 4) Cust om messagi ng.

( 5) Gr aphi cal di spl ays.

2. 6. 5. 1 Mai nt enance Management

Syst em moni t or s equi pment st at us and gener at es mai nt enance messages based upon user - desi gnat ed r un- t i me l i mi t s.

2. 6. 5. 2 Sequenci ng

Appl i cat i on sof t war e based upon speci f i ed sequences of oper at i on on t he Drawings.

2. 6. 5. 3 PI D Cont r ol Char act er i s t i cs

Di r ect or r ever se act i on, ant i - wi ndup, cal cul at ed, t i me- var yi ng, anal og val ue, posi t i ons an out put or st ages a ser i es of out put s. User sel ect abl e cont r ol l ed var i abl e, set - poi nt , and PED gai ns.

2. 6. 5. 4 St agger ed St ar t Appl i cat i on

Pr event s al l cont r ol l ed equi pment f r om si mul t aneousl y r est ar t i ng af t er power out age. Or der of equi pment st ar t up i s user sel ect abl e.

2. 6. 5. 5 Ener gy Cal cul at i ons

Accumul at ed i nst ant aneous power or f l ow r at es ar e conver t ed t o ener gy use dat a. Al gor i t hm cal cul at es a r ol l i ng aver age and al l ows wi ndow of t i me t o be user speci f i ed i n mi nut e i nt er val s. Al gor i t hm cal cul at es a f i xed wi ndow

92654Bldg385 SECTI ON 25 10 10 Page 12 aver age wi t h a di gi t al i nput s i gnal f r om a ut i l i t y met er def i ni ng t he st ar t of t he wi ndow per i od t hat i n t ur n synchr oni zes t he f i xed- wi ndow aver age wi t h t hat used by t he power company.

2. 6. 5. 6 Ant i - Shor t Cycl i ng

Al l bi nar y out put obj ect s pr ot ect ed f r om shor t - cycl i ng. Al l ows mi ni mum on- t i me and of f - t i me t o be sel ect ed.

2. 6. 5. 7 On- Of f Cont r ol wi t h Di f f er ent i al

Al gor i t hm al l ows bi nar y out put t o be cycl ed based on a cont r ol l ed var i abl e and set - poi nt . Al gor i t hm t o be di r ect - act i ng or r ever se- act i ng i ncor por at i ng an adj ust abl e di f f er ent i al .

2. 6. 5. 8 Run- Ti me Tot al i zat i on

Tot al i ze r un- t i mes f or al l bi nar y i nput obj ect s. Pr ovi des oper at or wi t h capabi l i t y t o assi gn hi gh r un- t i me al ar m.

2. 7 WEATHERSHI ELDS

Pr ovi de weat her shi el ds const r uct ed of gal vani zed st eel pai nt ed whi t e, unpai nt ed al umi num, al umi num pai nt ed whi t e, or whi t e PVC.

2. 8 CONTROL PANELS

Uni t i zed cabi net t ype f or each syst em under aut omat i c cont r ol wi t h r el ays and cont r ol s mount ed i n cabi net and t emper at ur e i ndi cat or s, pr essur e gauges, pi l ot l i ght s, push but t ons and swi t ches f l ush on cabi net panel f ace. NEMA 250, gener al pur pose ut i l i t y encl osur es wi t h enamel ed f i ni shed f ace panel . Pr ovi de common keyi ng f or al l panel s.

2. 9 TOUCHSCREEN DI SPLAY

Wi descr een f l at panel LCD or LED t ouchscr een moni t or s i zed as i ndi cat ed on t he dr awi ngs but no l ess t han 24 i nch nomi nal wi t h mi ni mum r esol ut i ons of 1920 or 1080 pi xel s and mi ni mum r ef r esh r at e of 70Hz.

2. 10 WI RE AND CABLE

Pr ovi de wi r e and cabl e meet i ng t he r equi r ement s of NFPA 70 and NFPA 90A i n addi t i on t o t he r equi r ement s of t hi s Speci f i cat i on and r ef er enced Specifications.

2. 10. 1 Ter mi nal Bl ocks

For t er mi nal bl ocks whi ch ar e not i nt egr al t o ot her equi pment , pr ovi de t er mi nal bl ocks whi ch ar e i nsul at ed, modul ar , f eed- t hr ough, c l amp st y l e wi t h r ecessed capt i ve scr ew- t ype c l ampi ng mechani sm, sui t abl e f or DI N r ai l mount i ng, and whi ch have encl osed si des or end pl at es and par t i t i on pl at es f or separ at i on.

2. 10. 2 Cont r ol Wi r i ng f or Bi nar y Si gnal s

For Cont r ol Wi r i ng f or Bi nar y Si gnal s, pr ovi de 18 AWG copper or t hi cker wi r e r at ed f or 300- vol t ser vi ce.

92654Bldg385 SECTI ON 25 10 10 Page 13

2. 10. 3 Cont r ol Wi r i ng f or Anal og Si gnal s

For Cont r ol Wi r i ng f or Anal og Si gnal s, pr ovi de 18 AWG or t hi cker , copper , s i ngl e- or mul t i pl e- t wi st ed wi r e meet i ng t he f ol l owi ng r equi r ement s:

a. Mi ni mum 2 i nch l ay of t wi st .

b. 100 per cent shi el ded pai r s.

c. At l east 300- vol t i nsul at i on.

d. Each pai r has a 20 AWG t i nned- copper dr ai n wi r e and i ndi v i dual over al l pai r i nsul at i on.

e. Cabl es have an over al l al umi num- pol yest er or t i nned- copper cabl e- shi el d t ape, over al l 20 AWG t i nned- copper cabl e dr ai n wi r e, and over al l cabl e insulation.

2. 10. 4 Power Wi r i ng f or Cont r ol Devi ces

For 24- vol t c i r cui t s, pr ovi de i nsul at ed copper 18 AWG or t hi cker wi r e r at ed f or 300 VAC ser v i ce. For 120- vol t c i r cui t s, pr ovi de 14 AWG or t hi cker st r anded copper wi r e r at ed f or 600- vol t ser vi ce.

2. 10. 5 Tr ansf or mer s

Provide UL 5085- 3 appr oved t r ansf or mer s. Sel ect t r ansf or mer s s i zed so t hat t he connect ed l oad i s no gr eat er t han 80 per cent of t he t r ansf or mer r at ed capacity.

2. 11 AUTOMATI C CONTROL VALVES

Pr ovi de val ves wi t h st ai nl ess- st eel st ems and st uf f i ng boxes wi t h ext ended necks t o c l ear t he pi pi ng i nsul at i on. Pr ovi de val ves wi t h bodi es meet i ng 125 psi g pr essur e r at i ngs. Pr ovi de val ves r at ed f or modul at i ng or t wo- posi t i on ser vi ce as i ndi cat ed, whi ch c l ose agai nst a di f f er ent i al pr essur e i ndi cat ed as t he Cl ose- Of f pr essur e and whi ch ar e Nor mal l y- Open, Nor mal l y- Cl osed, or Fai l - I n- Last - Posi t i on as i ndi cat ed.

2. 11. 1 Val ve Type

Use bal l val ves except t hat but t er f l y val ves may be used f or s i zes 4 i nch and l ar ger .

2. 11. 2 Val ve Fl ow Coef f i c i ent and Fl ow Char act er i st i c

2. 11. 2. 1 Two- Way Modul at i ng Val ves

Pr ovi de t he val ve coef f i c i ent ( Cv) i ndi cat ed. Pr ovi de equal - per cent age f l ow char act er i s t i c f or l i qui d ser vi ce except f or but t er f l y val ves.

2. 11. 2. 2 Thr ee- Way Modul at i ng Val ves

Pr ovi de t he val ve coef f i c i ent ( Cv) i ndi cat ed. Pr ovi de l i near f l ow char act er i st i c wi t h const ant t ot al f l ow t hr oughout f ul l pl ug t r avel .

2. 11. 3 Two- Posi t i on Val ves

Use f ul l l i ne s i ze f ul l por t val ves wi t h maxi mum avai l abl e ( Cv) .

92654Bldg385 SECTI ON 25 10 10 Page 14

2. 11. 4 Bal l Val ves

Li qui d Ser vi ce Not Exceedi ng 150 Degr ees F.

a. Val ve body and connect i ons:

( 1) Val ves 1- 1/ 2 i nches and smal l er : Bodi es of br onze, wi t h t hr eaded or uni on ends

( 2) Val ves f r om 2 i nches t o 3 i nches i ncl usi ve: Bodi es of br onze, or i r on. 2 i nch val ves wi t h t hr eaded connect i ons; val ves f r om 2- 1/ 2 t o 3 i nches wi t h f l anged connect i ons.

b. Bal l : St ai nl ess st eel .

c. Seal s: Rei nf or ced Tef l on seal s and EPDM O- r i ngs.

d. St em: St ai nl ess st eel , bl ow- out pr oof .

2. 11. 5 But t er f l y Val ves

Pr ovi de but t er f l y val ves whi ch ar e t hr eaded l ug t ype sui t abl e f or dead- end ser vi ce and modul at i on t o t he f ul l y- c l osed posi t i on, wi t h car bon- st eel bodi es or wi t h duct i l e i r on bodi es i n accor dance wi t h ASTM A536. Pr ovi de but t er f l y val ves wi t h non- cor r osi ve di scs, st ai nl ess st eel shaf t s suppor t ed by bear i ngs, and EPDM seat s sui t abl e f or t emper at ur es f r om - 20 t o +250 degr ees F. Pr ovi de val ves wi t h r at ed Cv of t he Cv at 70 per cent ( 60 degr ees) open posi t i on.

2. 11. 6 Duct - Coi l and Ter mi nal - Uni t - Coi l Val ves

For duct or t er mi nal - uni t coi l s pr ovi de cont r ol val ves wi t h ei t her scr ew t ype or sol der - t ype ends.

2. 11. 7 Aut omat i c Fl ow Cont r ol Val ves

Val ve shal l aut omat i cal l y mai nt ai n t he const ant f l ow i ndi cat ed on t he desi gn dr awi ngs. Val ve shal l modul at e by sensi ng t he pr essur e di f f er ent i al acr oss t he val ve body. Val ve shal l be sel ect ed f or t he f l ow r equi r ed and pr ovi ded wi t h a per manent namepl at e or t ag car r y i ng a per manent r ecor d of t he f act or y- det er mi ned f l ow r at e and f l ow cont r ol pr essur e l evel s. Pr ovi de val ve t hat cont r ol s t he f l ow wi t hi n 5 per cent of t he t ag r at i ng. Val ve mat er i al s shal l be t he same as speci f i ed f or t he bal l or pl ug val ves.

Pr ovi de val ve t hat ar e el ect r i c t ype as i ndi cat ed. Val ve shal l be capabl e of posi t i ve shut of f agai nst t he syst em pump head, val ve bodi es shal l be pr ovi ded wi t h t apped openi ngs and pi pe ext ensi ons wi t h shut of f val ves out s i de of pi pe i nsul at i on. The pi pe ext ensi ons shal l be pr ovi ded wi t h qui ck connect i ng hose f i t t i ngs sui t abl e f or t he oper at i ng pr essur e specified.

2. 12 DAMPERS

2. 12. 1 Damper Assembl y

Pr ovi de s i ngl e damper sect i ons wi t h bl ades no l onger t han 48 i nches and whi ch ar e no hi gher t han 72 i nches and damper bl ade wi dt h of 8 i nches or l ess. When l ar ger s i zes ar e r equi r ed, combi ne damper sect i ons. Pr ovi de

92654Bldg385 SECTI ON 25 10 10 Page 15 damper s made of st eel , or ot her mat er i al s wher e i ndi cat ed and wi t h assembl y f r ames const r uct ed of 0. 07 i nch mi ni mum t hi ckness gal vani zed st eel channel s wi t h mi t er ed and wel ded cor ner s. St eel channel f r ames const r uct ed of 0. 06 i nch mi ni mum t hi ckness ar e accept abl e pr ovi ded t he cor ner s ar e r ei nf or ced.

a. Fl at bl ades must be made r i gi d by f ol di ng t he edges. Bl ade- oper at i ng l i nkages must be wi t hi n t he f r ame so t hat bl ade- connect i ng devi ces wi t hi n t he same damper sect i on must not be l ocat ed di r ect l y i n t he ai r stream.

b. Damper axl es must be 1/ 2 i nch mi ni mum, pl at ed st eel r ods suppor t ed i n t he damper f r ame by st ai nl ess st eel or br onze bear i ngs. Bl ades mount ed ver t i cal l y must be suppor t ed by t hr ust bear i ngs.

c. Pr ovi de damper s whi ch do not exceed a pr essur e dr op t hr ough t he damper of 0. 04 i nches wat er gauge at 1000 f t / mi n i n t he wi de- open posi t i on.

Pr ovi de damper s wi t h f r ames not l ess t han 2 i nch i n wi dt h. Pr ovi de damper s whi ch have been t est ed i n accor dance wi t h AMCA 500- D.

2. 12. 2 Oper at i ng Li nkages

For oper at i ng l i nks ext er nal t o damper s, such as cr ank ar ms, connect i ng r ods, and l i ne shaf t i ng f or t r ansmi t t i ng mot i on f r om damper act uat or s t o damper s, pr ovi de l i nks abl e t o wi t hst and a l oad equal t o at l east 300 per cent of t he maxi mum r equi r ed damper - oper at i ng f or ce wi t hout def or mi ng.

Rod l engt hs must be adj ust abl e. Li nks must be br ass, br onze, z i nc- coat ed st eel , or st ai nl ess st eel . Wor ki ng par t s of j oi nt s and cl evi ses must be br ass, br onze, or st ai nl ess st eel . Adj ust ment s of cr ank ar ms must cont r ol t he open and cl osed posi t i ons of damper s.

2. 12. 3 Damper Types

2. 12. 3. 1 Fl ow Cont r ol Damper s

Pr ovi de par al l el - bl ade or opposed bl ade t ype damper s f or out s i de ai r , r et ur n ai r , r el i ef ai r , and exhaust damper s. Bl ades must have i nt er l ocki ng edges. The channel f r ames of t he damper s must be pr ovi ded wi t h j amb seal s t o mi ni mi ze ai r l eakage. Unl ess ot her wi se i ndi cat ed, damper s must meet AMCA 511 Cl ass 1A r equi r ement s ( 3 cf m per sq. f oot of damper f ace ar ea at

1. 0 i nches wat er gage st at i c pr essur e) . Out si de ai r damper seal s must be sui t abl e f or an oper at i ng t emper at ur e r ange of - 40 t o +167 degr ees F.

Damper s must be r at ed at not l ess t han 2000 f t / mi n ai r vel oci t y.

2. 13 ACTUATORS

Pr ovi de di r ect - dr i ve el ect r i c act uat or s f or al l cont r ol appl i cat i ons, except wher e i ndi cat ed ot her wi se. Al l act uat or s shal l i ncl ude a f eedback l oop f or det ect i ng act uat or f aul t s. The act uat or shal l r epor t act ual posi t i on back t o t he cont r ol syst em. Bi nar y act uat or s shal l pr ovi de open/ cl osed st at us, at a mi ni mum. Modul at i ng act uat or s and pr ocess shal l pr ovi de posi t i on f eedback expr essed ( di r ect l y or t hr ough span conver si on) as per cent open/ cl osed. Act uat or st at us shal l be der i ved f r om act uat or posi t i on; however , ef f ect may be used i n cases wher e di r ect f eedback i s not practical.

Use ai r f l ow sensor s as a f eedback l oop f or damper act uat or s. Use di f f er ent i al t emper at ur e as a f eedback mechani sm f or coi l val ve act uat i on.

92654Bldg385 SECTI ON 25 10 10 Page 16

2. 13. 1 El ect r i c Act uat or s

Each act uat or shal l del i ver t he t or que r equi r ed f or cont i nuous uni f or m mot i on and shal l have i nt er nal end swi t ches t o l i mi t t he t r avel , or be capabl e of wi t hst andi ng cont i nuous st al l i ng wi t hout damage. Act uat or s shal l f unct i on pr oper l y wi t hi n 85 t o 110 per cent of r at ed l i ne vol t age.

Pr ovi de act uat or s wi t h har dened st eel r unni ng shaf t s and gear s of s t eel or copper al l oy. Fi ber or r ei nf or ced nyl on gear s may be used f or t or ques l ess t han 16 i nch- pounds. Pr ovi de t wo- posi t i on act uat or s of s i ngl e di r ect i on, spr i ng r et ur n, or r ever si ng t ype. Pr ovi de modul at i ng act uat or s capabl e of st oppi ng at any poi nt i n t he cycl e, and st ar t i ng i n ei t her di r ect i on f r om any poi nt . Act uat or s shal l be equi pped wi t h a swi t ch f or r ever si ng di r ect i on, and a but t on t o di sengage t he c l ut ch t o al l ow manual adj ust ment s. Pr ovi de t he act uat or wi t h a hand cr ank f or manual adj ust ment s, as appl i cabl e. Ther mal t ype act uat or s may onl y be used on t er mi nal f an coi l uni t s, convect or s, and uni t heat er s. Spr i ng r et ur n act uat or s shal l be pr ovi ded on al l cont r ol damper s and al l cont r ol val ves except t er mi nal f an coi l uni t s, convect or s, and uni t heat er s; unl ess i ndi cat ed ot her wi se. Each act uat or shal l have di st i nct mar ki ngs i ndi cat i ng t he f ul l - open and f ul l - c l osed posi t i on, and t he poi nt s i n- bet ween.

2. 14 SENSORS

Unl ess ot her wi se speci f i ed, pr ovi de sensor s and i nst r ument at i on whi ch i ncor por at e an i nt egr al t r ansmi t t er . Sensor s and i nst r ument at i on, i ncl udi ng t hei r t r ansmi t t er s, must meet t he speci f i ed accur acy and dr i f t r equi r ement s at t he i nput of t he connect ed…