This document outlines a federal contract opportunity to construct a new Michigan Army National Guard Readiness Center. The solicitation number is W912JB-24-B-0001 and seeks the design and construction of up to 46,831 square feet of a new National Guard Readiness Center to support training, administrative, and logistical requirements for the Michigan Army National Guard. The project scope includes all necessary utility services, information systems, fire detection and alarm systems, roads, walls, curbs, storm drainage, parking areas, and site improvements. The new facility must meet industry standards as well as all local, state and federal building codes and Public Law 90-480. It should have a minimum 50-year life span and incorporate energy efficiencies, building envelope standards, and integrated building systems per DoD and ASA(IE&E) policies. Access for individuals with disabilities and DoD antiterrorism standards are also requirements.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. CONTRACTOR SHALL VERIFY FUSE/BREAKER SIZE AND CABLING REQUIREMENTS WITH FINAL APPROVED
VENDOR DRAWINGS.
2. ALL WIRES SHALL BE COPPER THWN OR AS OTHERWISE NOTED ON THESE PLANS.
3. EQUIPMENT INSIDE ELECTRICAL ROOMS TO COMPLY WITH NEC 110.26.
4. PROVIDE PERMANENT PLAQUE FOR EACH SERVICE LOCATION AS PER NEC 230.2.
5. PROVIDE CABLE SUPPORT IN ALL VERTICAL RACEWAYS AS PER NEC TABLE 300.19(A).
6. ALL ELECTRICAL EQUIPMENT WILL BE LABELED TO INDICATE POTENTIAL ELECTRIC ARC FLASH HAZARDS IN
FULL COMPLIANCE WITH NEC 110.16.
7. DESIGN BASIS IS SQUARE D I-LINE PANELS, QED-2 AND BREAKERS.
8. ALL ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE CONNECTED TO GROUND.
GENERAL SHEET NOTES:
480V, 3 PHASE, 4 WIRE + GROUND BUS42KAIC
MDP
ELECTRICAL ROOM 132
1600A
1000AT
1200AF
1000 kVA 8320V-480Y
600AT
800AF
SPD
30AT
90AF
100AT
150AF
LSIG
60AT
150AF
BAS
400AT
400AF
EXISTING DEAD FRONT SWITCH
ENCLOSURE 25KV RATED, 200A, WITH 4
INTERFACE POINTS PER PHASE.
1 SET OF 15kV INSULATED EPR
133% (3) 1/C #2 (AL) IN 5" CONDUIT
4" C
3 SETS OF
(4) 600 KCMIL (AL)
800 A
277/480V, 3-PHASE, 4 WIRE(22,000 AIC)
DP1
3 1/2" C
2 SETS OF
(4) 350 KCMIL
(1) #1
800AF
600AT
SPD
EM BAS
RP1
480V- 120/208V
#4
T-RP1
45 kVA
1" C
(3) #6
(1) #10
2" C
(4) #1/0
(1) #6
LP1
1 1/2" C
(4) #2
(1) #8
100AT
150AF
125AT
150AF
EM
SPD
RP2
480V- 120/208V
#2
T-RP2
75 kVA
2" C
(3) #1
(1) #6
3" C
(4) 250 KCMIL
(1) #4
LP2
1 1/2" C
(4) #2
(1) #8
EM BAS
SPD
SPD
30AT
150AF
EM
BAS
EMBAS
SPD
5 BAS
EM
SPD
NET2
BAS
SPD
EM BAS
LP3
SPD
EM BAS
RP3
480V- 120/208V
#2
T-110-01 75 kVA
2" C
(3) #1
(1) #6
4" C
(4) 500 KCMIL
(1) #3TRAINING
BAY
(OPTION #3)
1/
4" C
(4
(1
3" C
(4) 250 KCMIL
(1) #4
SPARESPARE
150AF SPACESPACE
100 A 90 A
RTU-SE
125AT
150AF
SPARESPARE
100AF
40AT
SPARE
150AF SPACESPACE
SPD
EM BAS
K
480V- 120/208V
#2
T-K 75 kVA
2" C
(3) #1
(1) #6
3" C
(4) 250 KCMIL
(1) #4
125AT
150AF
KITCHEN
(OPTION #4)
110AT
150AF
RTU-NE
100AT
150AF
RTU-NW
100AF
20AT
HWP-2
HP
FIRE PUMP
HP
480V, 3PH, 60HZ
1 1/2" C
(4) #2 (AL)
M
1 1/4" C
(3) #3
(1) #8
1 1/4" C
(3) #3
(1) #8
100 A 90 A
100 A 70 A
1" C
(3) #6
(1) #10
3/4" C
(3) #12
(1) #12
ATS-FP
200 A
G 150KW
480V, 3PH, 60HZ
175AT
225AF
80AT
100AF
100AT
100AF
NATURAL GAS EMERGENCY GENERATOR,
LEVEL 1, TYPE 10.
SPD
EM BAS
LSH1
SPD
EM BAS
LSL1
480V- 120/208V
#6
T-LSL1
30 kVA
1" C
(3) #6
(1) #10
1 1/2" C
(4) #2
(1) #8
SPD
EM BAS
LSL2
1 1/4" C
(4) #4
(1) #8
SPD
EM BAS
LSH2
SPD
EM BAS
NEH1
SPD
EM BAS
NEL1
480V- 120/208V
#6
T-NEL1
30 kVA
1" C
(3) #6
(1) #10
1 1/2" C
(4) #2
(1) #8
SPD
EM BAS
NEL2
1 1/4" C
(4) #4
(1) #8
1 1/2" C
(4) #1 (AL)
(1) #8
3" C
(4) #4/0 (AL)
(1) #6
1 1/2" C
(4) #2 (AL)
(1) #8
ATS-NE
225 A
ATS-LS
125 A
1-1/2"" C
(4) #1 (AL)
3" C
(4) #4/0 (AL)
GENERATOR LOAD CALCULATION:
LOAD NAME: TOTAL LOAD (AMP) TOATL LOAD (VA)
- FIRE PUMP: 34 28,267
- ATS-LS: 9 7,328
- ATS-NE 157 130,854
TOTAL= 200 166,359
8 8
1 1/4" C
(4) #4
(1) #8
2 1/2" C
(4) #3/0
(1) #6
1 1/4" C
(4) #4
(1) #8
EM
SPD
NET1
BAS
SPARESPARE
100AF
40AT
SPARESPARE
100AF
40AT
SPARESPARE
100AF
40AT
FOUR (4) SPARE BREAKERS FUTURE EV CHARGERS
LIFT
STATION
HP
100AF
20AT
GENERATOR 225 188,000
DATA
K
DUAL BRAKER
DOCKING STATION
WITH INDIVIDUALLY
KIRK KEYED
BREAKERS
250A, 480V, 3-POLE, NEMA 4X
K
K
K K K
EF-4
1.5
HP
100AF
20AT
SF-4
HP
100AF
20AT
3/4" C
(3) #12
(1) #12
3/4" C
(3) #12
(1) #12
3/4" C
(3) #10
(1) #10
100AF
20AT
HWP-5
HP
15 A
3/4" C
(3) #12
(1) #12
SPD
EM BAS
NEH2
1 1/2" C
(3) #2
(1) #8
1" C
(3) #6
(1) #10
100AF
20AT
HWP-3
HP
3/4" C
(3) #12
(1) #12
4 POLE
4 POLE
4 POLE
N
G N
G
N
GN
G
PROJECT TITLE
CLIENT
In c h e s
/2
/4
REV. DATE DESCRIPTION
ISSUE FOR CONSTRUCTION DATE
DESIGNEDSCALE
DRAWING TITLE
DRAWN CHECKED
ORIGINAL SHEET SIZE
PROJECT NUMBER
PROJECT STATUS
SHEET NUMBER
REVISION NO.
www.atkinsglobal.com
Copyright © Atkins Limited (2015)
+1 703 535 3008 +1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040 Alexandria VA 22314
DO NOT SCALE
A ARCHD24X36
ATKINS DESIGN TEAM
ARCHITECTURE, INTERIORS
CIVIL, STRUCTURAL, LANDSCAPE
MECHANICAL, PLUMBING, FIRE PROTECTION
ELECTRICAL, FIRE ALARM
CONSULTANTS
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10
PROFESSIONAL SEAL
NTS
A u to d e sk
D o c s:
-M I A
R N
G R e a d in e ss C e n te r/
M
IA
R
N G
G A
A F
R e a d in e s s
C e n te r
E le c
R
O
P T
IO
N
.r vt
/2
/2
:5 :5
P
M
ELECTRICAL
ONE-LINE DIAGRAM
MIARNG GAAF
READINESS CENTER
LS
06/30/2023
JG SE
86608-260247
TYPE B 100% REVISED FINAL DESIGN
GRAYLING TOWNSHIP,
CRAWFORD COUNTY, MICHIGAN
E-501
1 CONNECT NEW MEDIUM VOLTAGE WIRES TO SPARE LOAD BREAKER INSERTER ON DFSE-13.
2 PROVIDE MAIN BONDING JUMPER (#2/0 CU) AT MAIN SERVICE DISCONNECT AS PER NEC 250.24.
3 MAIN SERVICE DISCONNECT SHALL BE PROVIDED WITH ARC ENERGY REDUCTION PER NEC 240.87.
4 PROVIDE MAIN SERVICE DISCONNECT WITH GORUND-FAULT PROTECIOTN PER NEC 230-95.
5 PROVIDE QUALITY METER TO MONITOR CURRENT. PROVIDE COMMUNICATIONS WIRING IN CONDUIT AS
REQUIRED BACK TO BAS SYSTEM CONTROL PANEL.
6 SERVICE RATED FIRE PUMP ATS WITH INTEGRATED MAIN SERCVICE DISCONNECT. PROVIDE MAIN BONDING
JUMPER (#8 CU) AT MAIN SERVICE DISCONNECT AS PER NEC 250.24.
7 SERVICE RATED ATS WITH INTEGRATED DISCONNECT. PROVIDE MAIN BONDING JUMPER (#8 CU) AT MAIN
SERVICE DISCONNECT AS PER NEC 250.24.
8 RTU WITH INTEGRATED VFD AND NON-FUSED DISCONNECT SWITCH.
9 NATURAL GAS EMERGENCY GENERATOR, LEVEL 1, TYPE 10. PROVIDE #4 AWG CU ELECTRODE GROUNDING CONDUCTOR IN 3/4" CONDUIT. IN ADDDITION, CONTRACTOR SHALL PROVIDE 3/4" CONDUITS AND CONTROL
WIRING TO THE FOLLOWING LOCATION:
- FIRE ALARM CONTROL PANEL
- FIRE PUMP ATS
- LIFE SAFETY ATS
- NON-ESSENTIAL ATS
- REMOTE ANNUNCIATOR
- REMOTE PUSH BUTTON
KEYED NOTES: #
06/30/2023
1. CONTRACTOR SHALL VERIFY FUSE/BREAKER SIZE AND CABLING REQUIREMENTS WITH FINAL APPROVED
VENDOR DRAWINGS.
2. ALL WIRES SHALL BE COPPER THWN OR AS OTHERWISE NOTED ON THESE PLANS.
3. EQUIPMENT INSIDE ELECTRICAL ROOMS TO COMPLY WITH NEC 110.26.
4. PROVIDE PERMANENT PLAQUE FOR EACH SERVICE LOCATION AS PER NEC 230.2.
5. PROVIDE CABLE SUPPORT IN ALL VERTICAL RACEWAYS AS PER NEC TABLE 300.19(A).
6. ALL ELECTRICAL EQUIPMENT WILL BE LABELED TO INDICATE POTENTIAL ELECTRIC ARC FLASH HAZARDS IN
FULL COMPLIANCE WITH NEC 110.16.
7. DESIGN BASIS IS SQUARE D I-LINE PANELS, QED-2 AND BREAKERS.
8. ALL ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE CONNECTED TO GROUND.
GENERAL SHEET NOTES:
480V, 3 PHASE, 4 WIRE + GROUND BUS42KAIC
MDP
ELECTRICAL ROOM 132
1600A
1000AT
1200AF
1000 kVA 8320V-480Y
600AT
800AF
SPD
30AT
90AF
100AT
150AF
LSIG
60AT
150AF
BAS
400AT
400AF
EXISTING DEAD FRONT SWITCH
ENCLOSURE 25KV RATED, 200A, WITH 4
INTERFACE POINTS PER PHASE.
1 SET OF 15kV INSULATED EPR
133% (3) 1/C #2 (AL) IN 5" CONDUIT
4" C
3 SETS OF
(4) 600 KCMIL (AL)
800 A
277/480V, 3-PHASE, 4 WIRE(22,000 AIC)
DP1
3 1/2" C
2 SETS OF
(4) 350 KCMIL
(1) #1
800AF
600AT
SPD
EM BAS
RP1
480V- 120/208V
#4
T-RP1
45 kVA
1" C
(3) #6
(1) #10
2" C
(4) #1/0
(1) #6
LP1
1 1/2" C
(4) #2
(1) #8
100AT
150AF
125AT
150AF
EM
SPD
RP2
480V- 120/208V
#2
T-RP2
75 kVA
2" C
(3) #1
(1) #6
3" C
(4) 250 KCMIL
(1) #4
LP2
1 1/2" C
(4) #2
(1) #8
EM BAS
SPD
SPD
30AT
150AF
EM
BAS
EMBAS
SPD
5 BAS
EM
SPD
NET2
BAS
SPD
EM BAS
LP3
SPD
EM BAS
RP3
480V- 120/208V
#2
T-110-01 75 kVA
2" C
(3) #1
(1) #6
4" C
(4) 500 KCMIL
(1) #3TRAINING
BAY
(OPTION #3)
1/
4" C
(4
(1
3" C
(4) 250 KCMIL
(1) #4
SPARESPARE
150AF SPACESPACE
100 A 90 A
RTU-SE
125AT
150AF
SPARESPARE
100AF
40AT
SPARE
150AF SPACESPACE
SPD
EM BAS
K
480V- 120/208V
#2
T-K 75 kVA
2" C
(3) #1
(1) #6
3" C
(4) 250 KCMIL
(1) #4
125AT
150AF
KITCHEN
(OPTION #4)
110AT
150AF
RTU-NE
100AT
150AF
RTU-NW
100AF
20AT
HWP-2
HP
FIRE PUMP
HP
480V, 3PH, 60HZ
1 1/2" C
(4) #2 (AL)
M
1 1/4" C
(3) #3
(1) #8
1 1/4" C
(3) #3
(1) #8
100 A 90 A
100 A 70 A
1" C
(3) #6
(1) #10
3/4" C
(3) #12
(1) #12
SPD
EM BAS
LSH1
SPD
EM BAS
LSL1
480V- 120/208V
#6
T-LSL1
30 kVA
1" C
(3) #6
(1) #10
1 1/2" C
(4) #2
(1) #8
SPD
EM BAS
LSL2
1 1/4" C
(4) #4
(1) #8
SPD
EM BAS
LSH2
5 SPD
EM BAS
NEH1
SPD
EM BAS
NEL1
480V- 120/208V
#6
T-NEL1
30 kVA
1" C
(3) #6
(1) #10
1 1/2" C
(4) #2
(1) #8
SPD
EM BAS
NEL2
1 1/4" C
(4) #4
(1) #8
8 8
1 1/4" C
(4) #4
(1) #8
EM
SPD
NET1
BAS
SPARESPARE
100AF
40AT
SPARESPARE
100AF
40AT
SPARESPARE
100AF
40AT
FOUR (4) SPARE BREAKERS FUTURE EV CHARGERS
LIFT
STATION
HP
100AF
20AT
EF-4
1.5
HP
100AF
20AT
SF-4
HP
100AF
20AT
3/4" C
(3) #12
(1) #12
3/4" C
(3) #12
(1) #12
3/4" C
(3) #10
(1) #10
100AF
20AT
HWP-5
HP
15 A
3/4" C
(3) #12
(1) #12
SPD
EM BAS
NEH2
1 1/2" C
(3) #2
(1) #8
1" C
(3) #6
(1) #10
100AF
20AT
HWP-3
HP
3/4" C
(3) #12
(1) #12
N
G
N
G
70AT
100AF
200AT
225AF
2 1/2" C
(4) #3/0
(1) #61 1/4" C
(4) #4
(1) #8
1 CONNECT NEW MEDIUM VOLTAGE WIRES TO SPARE LOAD BREAKER INSERTER ON DFSE-13.
2 PROVIDE MAIN BONDING JUMPER (#2/0 CU) AT MAIN SERVICE DISCONNECT AS PER NEC 250.24.
3 MAIN SERVICE DISCONNECT SHALL BE PROVIDED WITH ARC ENERGY REDUCTION PER NEC 240.87.
4 PROVIDE MAIN SERVICE DISCONNECT WITH GORUND-FAULT PROTECIOTN PER NEC 230-95.
5 PROVIDE QUALITY METER TO MONITOR CURRENT. PROVIDE COMMUNICATIONS WIRING IN CONDUIT AS
REQUIRED BACK TO BAS SYSTEM CONTROL PANEL.
6 200 AMP MAIN SERVICE DISCONNECT (SERVICE RATED ). PROVIDE MAIN BONDING JUMPER (#8 CU) AT MAIN
SERVICE DISCONNECT AS PER NEC 250.24.
7 NOT IN USE.
8 RTU WITH INTEGRATED VFD AND NON-FUSED DISCONNECT SWITCH.
9 NOT IN USE.
10 LIFT STATION PUMPS AND CONTROLLER PROVIDED BY THE PLUMBING CONTRACTOR. ELECTRRICAL CONTRACTRIOR SHALL COORDINATE WITH THE PLUMBING CONTRACTOR THE CONNECTION OF THE LIFT STATION CONTROLLER. PROVIDE 3FT OF WORKING SPACE TO THE CONTROLLER AND DISCONNECT SWITCH.
KEYED NOTES: #
PROJECT TITLE
CLIENT
In c h e s
/2
/4
REV. DATE DESCRIPTION
ISSUE FOR CONSTRUCTION DATE
DESIGNEDSCALE
DRAWING TITLE
DRAWN CHECKED
ORIGINAL SHEET SIZE
PROJECT NUMBER
PROJECT STATUS
SHEET NUMBER
REVISION NO.
www.atkinsglobal.com
Copyright © Atkins Limited (2015)
+1 703 535 3008 +1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040 Alexandria VA 22314
DO NOT SCALE
A ARCHD24X36
ATKINS DESIGN TEAM
ARCHITECTURE, INTERIORS
CIVIL, STRUCTURAL, LANDSCAPE
MECHANICAL, PLUMBING, FIRE PROTECTION
ELECTRICAL, FIRE ALARM
CONSULTANTS
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10
PROFESSIONAL SEAL
A u to d e sk
D o c s:
-M I A
R N
G R e a d in e ss C e n te r/
M
IA
R
N G
G A
A F
R e a d in e s s
C e n te r
E le
O
P T
IO
N
.r vt
/2
/2
:5 :5
P
M
PANEL SCHEDULES
MIARNG GAAF
READINESS CENTER
LS
06/30/2023
JG SE
86608-260247
TYPE B 100% REVISED FINAL DESIGN
GRAYLING TOWNSHIP,
CRAWFORD COUNTY, MICHIGAN
E-601
(1) OPTION #3. REFER TO DRAWING E-732 FOR PANEL LP-101-01 SCHEDULE.
(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
(3) NON-CONCURRENT LOAD. STANDBY SYSTEM PUMP.
Notes:
LARGE MOTOR 137346 VA 125.00% 171683 VA
KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA
EQUIPMENT 221414 VA 100.00% 221414 VA
Lighting - Exterior 651 VA 125.00% 814 VA
RECEPTACLE 51420 VA 100.00% 51420 VA Total Est. Demand Current: 657 A
HVAC 58809 VA 100.00% 58809 VA Total Conn. Current: 625 A
LIGHTING 4189 VA 125.00% 5236 VA Total Est. Demand: 546083 VA
Other 279 VA 100.00% 279 VA Total Conn. Load: 519521 VA
Motor 14904 VA 100.00% 14904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 625 A
Total Connected Load 519521 VA
15 SPACE --
14 SPARE 0 VA
13 SPD --
12 HWP-5 (2) 3984 VA
11 HWP-3 (2)(3) 0 VA
10 RTU-SE (2) 62250 VA
9 LP3 (1) 83514 VA
8 EV CHARGER 4 (FUTURE) 26600 VA
7 EV CHARGER 3 (FUTURE) 26600 VA
6 EV CHARGER 2 (FUTURE) 26600 VA
5 EV CHARGER 1 (FUTURE) 26600 VA
4 HWP-2 (2) 6308 VA
3 DP1 235061 VA
2 LP1 2039 VA
1 T-RP1 20060 VA
CKT Circuit Description Load
Notes:
Enclosure: Type 1 MCB Rating: 1000 A
Mounting: Floor Mounting Wires: 4 Mains Rating: 1200 A
Supply From: Phases: 3 Mains Type: Main Circuit Breaker
Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 42,000
Switchboard: MDP
(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.
(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH
THE CONTROL RELAY (RIB24P30).
Notes:
Total Est. Demand Current: 3 A
Lighting - Dwelling Unit 270 VA 125.00% 338 VA Total Conn. Current: 2 A
Lighting - Exterior 279 VA 125.00% 349 VA Total Est. Demand: 2514 VA
LIGHTING 1352 VA 125.00% 1690 VA Total Conn. Load: 2039 VA
Other 140 VA 100.00% 140 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 3 A 2 A 3 A
Total Load: 871 VA 483 VA 686 VA
29 30
27 28
25 26
23 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 OUTDOOR LIGHTING (2) 20 A 1 260 VA 47 VA 1 20 A OUTDOOR LIGHTING (2) 14
11 ADMIN LOBBY LIGHTING (1) 20 A 1 118 VA 93 VA 1 20 A CORRIDOR 3 LIGHTING 12
9 MENS REST LIGHTING 20 A 1 84 VA 114 VA 1 20 A MENS SHOWER LIGHTING 10
7 WOMENS SHOWER LIGHTING 20 A 1 114 VA 76 VA 1 20 A WOMENS REST LIGHTING 8
5 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 340 VA 1 20 A PES ROOM LIGHTING 6
3 MAINT STORAGE/OFFICE LIGHTING 20 A 1 60 VA 225 VA 1 20 A BREAK ROOM 146 LIGHTING 4
1 ELECTRICAL AND COMM ROOM LIGHTING 20 A 1 136 VA 238 VA 1 20 A MECHANICAL ROOM LIGHITNG 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: MDP Phases: 3 Mains Type: MLO
Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: LP1
(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.
(2) PROVIDE GFI CIRCUIT BREAKER.
(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS
Notes:
Total Est. Demand Current: 56 A
Total Conn. Current: 56 A
EQUIPMENT 10868 VA 100.00% 10868 VA Total Est. Demand: 20060 VA
RECEPTACLE 6660 VA 100.00% 6660 VA Total Conn. Load: 20060 VA
HVAC 2532 VA 100.00% 2532 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 63 A 58 A 48 A
Total Load: 7438 VA 6849 VA 5773 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 34
31 32
29 30
27 725 VA 28
MENS HAND DRYER (2)(3)(4) 20 A 2
725 VA 725 VA 26
23 PES ROOM RECEPTACLES 20 A 1 720 VA 725 VA
2 20 A WOMENS HAND DRYER (2)(3)(4)
21 MAINT STORAGE/OFFICE RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#2 (2) 22
19 BREAK ROOM RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#1 (2) 20
17 ROOF RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A PES ROOM RECEPTACLES 18
15 OUTDOOR RECEPTACLE 20 A 1 360 VA 720 VA 1 20 A RECEPTACLE MECH ROOM 133 16
13 BREAK ROOM TV RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A BREAK ROOM COUNTERTOP RECEPTACLES 14
11 EF-6 & EF-11 20 A 1 728 VA 1600... 1 20 A BOILER #2 12
9 EF-7, EF-8, EF-9, EF-10 20 A 1 960 VA 1500... 1 20 A BREAK ROOM - REF (2) 10
7 WATER FOUNTAIN RECEPTACLE 20 A 1 1200... 1440... 1 20 A VENDING MACHINE 8
5 BREAK ROOM DISPOSAL 20 A 1 500 VA 600 VA 1 20 A UH-5 & UH-6 6
3 SF-3 (2) 20 A 1 100 VA 900 VA 1 20 A WOMENS RESTROOM RECEPTACLES 4
1 UH-7 20 A 1 144 VA 720 VA 1 20 A ADMIN LOBBY RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 150 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-RP1 Phases: 3 Mains Type: MCB
Location: COMM 131 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: RP1
(1) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
Notes:
LARGE MOTOR 75096 VA 125.00% 93870 VA
KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA
EQUIPMENT 10340 VA 100.00% 10340 VA
Lighting - Exterior 372 VA 125.00% 465 VA
RECEPTACLE 44760 VA 100.00% 44760 VA Total Est. Demand Current: 295 A
HVAC 56277 VA 100.00% 56277 VA Total Conn. Current: 283 A
LIGHTING 2841 VA 125.00% 3552 VA Total Est. Demand: 245606 VA
Other 140 VA 100.00% 140 VA Total Conn. Load: 235061 VA
Motor 14904 VA 100.00% 14904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
297 A 276 A 275 A
82364 VA 76454 VA 76244 VA
41 SPARE 0 VA 0 VA SPARE 42
39 SPARE 0 VA 0 VA SPARE 40
37 SPARE 0 VA -- SPACE 38
35 0 VA SPD 36
33 34
31 32
29 30
27 28
25 26
23 24900 VA 24
21 24900 VA 22
RTU-NE (1)
24900 VA 20
17 830 VA 16047 VA 18
15 830 VA 16047 VA 16
EF-4 (1)
830 VA 16047 VA
RTU-NW (1)
11 15758 VA 581 VA 12
9 15894 VA 581 VA 10
T-K
21192 VA 581 VA
SF-4 (1)
5 2984 VA 15220 VA 6
3 1121 VA 17136 VA 4
LP-120-01
2086 VA 16804 VA
RP-120-01 (T-120-01)
CKT Circuit Description A B C Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 600 A
Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: MDP Phases: 3 Mains Type: MCB
Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: DP1
06/30/2023
(1) OPTION #3. REFER TO DRAWING E-732 FOR PANEL LP-101-01 SCHEDULE.
(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
(3) NON-CONCURRENT LOAD. STANDBY SYSTEM PUMP.
Notes:
LARGE MOTOR 146144 VA 125.00% 182680 VA
KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA
EQUIPMENT 248134 VA 100.00% 248134 VA
Lighting - Exterior 1442 VA 125.00% 1802 VA
RECEPTACLE 65100 VA 100.00% 65100 VA
HVAC 59809 VA 100.00% 59809 VA Total Est. Demand Current: 828 A
LIGHTING 8310 VA 125.00% 10387 VA Total Conn. Current: 792 A
Power 83836 VA 100.00% 83836 VA Total Est. Demand: 688602 VA
Other 279 VA 100.00% 279 VA Total Conn. Load: 658582 VA
Motor 14904 VA 100.00% 14904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 792 A
Total Connected Load 658582 VA
17 SPACE --
16 SPARE 0 VA
15 SPD --
14 HWP-5 (2) 3984 VA
13 HWP-3 (2)(3) 0 VA
12 RTU-SE (2) 62250 VA
11 LP3 (1) 83514 VA
10 EV CHARGER 4 (FUTURE) 26600 VA
9 EV CHARGER 3 (FUTURE) 26600 VA
8 EV CHARGER 2 (FUTURE) 26600 VA
7 EV CHARGER 1 (FUTURE) 26600 VA
6 HWP-2 (2) 6308 VA
5 DP1 235061 VA
4 LP1 2039 VA
3 T-RP1 20240 VA
2 NEH1 130854 VA
1 LSH1 8142 VA
CKT Circuit Description Load
Notes:
Enclosure: Type 1 MCB Rating: 1000 A
Mounting: Floor Mounting Wires: 4 Mains Rating: 1200 A
Supply From: Phases: 3 Mains Type: Main Circuit Breaker
Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 42,000
Switchboard: MDP
(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.
(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH
THE CONTROL RELAY (RIB24P30).
Notes:
Total Est. Demand Current: 3 A
Lighting - Dwelling Unit 270 VA 125.00% 338 VA Total Conn. Current: 2 A
Lighting - Exterior 279 VA 125.00% 349 VA Total Est. Demand: 2514 VA
LIGHTING 1352 VA 125.00% 1690 VA Total Conn. Load: 2039 VA
Other 140 VA 100.00% 140 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 3 A 2 A 3 A
Total Load: 871 VA 483 VA 686 VA
29 30
27 28
25 26
23 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 OUTDOOR LIGHTING (2) 20 A 1 260 VA 47 VA 1 20 A OUTDOOR LIGHTING (2) 14
11 ADMIN LOBBY LIGHTING (1) 20 A 1 118 VA 93 VA 1 20 A CORRIDOR 3 LIGHTING 12
9 MENS REST LIGHTING 20 A 1 84 VA 114 VA 1 20 A MENS SHOWER LIGHTING 10
7 WOMENS SHOWER LIGHTING 20 A 1 114 VA 76 VA 1 20 A WOMENS REST LIGHTING 8
5 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 340 VA 1 20 A PES ROOM LIGHTING 6
3 MAINT STORAGE/OFFICE LIGHTING 20 A 1 60 VA 225 VA 1 20 A BREAK ROOM 146 LIGHTING 4
1 ELECTRICAL AND COMM ROOM LIGHTING 20 A 1 136 VA 238 VA 1 20 A MECHANICAL ROOM LIGHITNG 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: MDP Phases: 3 Mains Type: MLO
Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: LP1
(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.
(2) PROVIDE GFI CIRCUIT BREAKER.
(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS
Notes:
Total Est. Demand Current: 56 A
Total Conn. Current: 56 A
EQUIPMENT 10868 VA 100.00% 10868 VA Total Est. Demand: 20240 VA
RECEPTACLE 6840 VA 100.00% 6840 VA Total Conn. Load: 20240 VA
HVAC 2532 VA 100.00% 2532 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 64 A 60 A 48 A
Total Load: 7438 VA 7029 VA 5773 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 34
31 32
29 30
27 725 VA 28
MENS HAND DRYER (2)(3)(4) 20 A 2
725 VA 725 VA 26
23 PES ROOM RECEPTACLES 20 A 1 720 VA 725 VA
2 20 A WOMENS HAND DRYER (2)(3)(4)
21 MAINT STORAGE/OFFICE RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#2 (2) 22
19 BREAK ROOM RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#1 (2) 20
17 ROOF RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A PES ROOM RECEPTACLES 18
15 OUTDOOR RECEPTACLE 20 A 1 360 VA 900 VA 1 20 A RECEPTACLE MECH ROOM 133 16
13 BREAK ROOM TV RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A BREAK ROOM COUNTERTOP RECEPTACLES 14
11 EF-6 & EF-11 20 A 1 728 VA 1600... 1 20 A BOILER #2 12
9 EF-7, EF-8, EF-9, EF-10 20 A 1 960 VA 1500... 1 20 A BREAK ROOM - REF (2) 10
7 WATER FOUNTAIN RECEPTACLE 20 A 1 1200... 1440... 1 20 A VENDING MACHINE 8
5 BREAK ROOM DISPOSAL 20 A 1 500 VA 600 VA 1 20 A UH-5 & UH-6 6
3 SF-3 (2) 20 A 1 100 VA 900 VA 1 20 A WOMENS RESTROOM RECEPTACLES 4
1 UH-7 20 A 1 144 VA 720 VA 1 20 A ADMIN LOBBY RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 150 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-RP1 Phases: 3 Mains Type: MCB
Location: COMM 131 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: RP1
(1) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
Notes:
LARGE MOTOR 75096 VA 125.00% 93870 VA
KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA
EQUIPMENT 10340 VA 100.00% 10340 VA
Lighting - Exterior 372 VA 125.00% 465 VA
RECEPTACLE 44760 VA 100.00% 44760 VA Total Est. Demand Current: 295 A
HVAC 56277 VA 100.00% 56277 VA Total Conn. Current: 283 A
LIGHTING 2841 VA 125.00% 3552 VA Total Est. Demand: 245606 VA
Other 140 VA 100.00% 140 VA Total Conn. Load: 235061 VA
Motor 14904 VA 100.00% 14904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
297 A 276 A 275 A
82364 VA 76454 VA 76244 VA
41 SPARE 0 VA 0 VA SPARE 42
39 SPARE 0 VA 0 VA SPARE 40
37 SPARE 0 VA -- SPACE 38
35 0 VA SPD 36
33 34
31 32
29 30
27 28
25 26
23 24900 VA 24
21 24900 VA 22
RTU-NE (1)
24900 VA 20
17 830 VA 16047 VA 18
15 830 VA 16047 VA 16
EF-4 (1)
830 VA 16047 VA
RTU-NW (1)
11 15758 VA 581 VA 12
9 15894 VA 581 VA 10
T-K
21192 VA 581 VA
SF-4 (1)
5 2984 VA 15220 VA 6
3 1121 VA 17136 VA 4
LP-120-01
2086 VA 16804 VA
RP-120-01 (T-120-01)
CKT Circuit Description A B C Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 600 A
Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: MDP Phases: 3 Mains Type: MCB
Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: DP1
In c h e s
/2
/4
REV. DATE DESCRIPTION
ISSUE FOR CONSTRUCTION DATE
DESIGNEDSCALE
DRAWING TITLE
DRAWN CHECKED
ORIGINAL SHEET SIZE
PROJECT NUMBER
PROJECT STATUS
SHEET NUMBER
REVISION NO.
www.atkinsglobal.com
Copyright © Atkins Limited (2015)
+1 703 535 3008 +1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040 Alexandria VA 22314
DO NOT SCALE
A ARCHD24X36
ATKINS DESIGN TEAM
ARCHITECTURE, INTERIORS
CIVIL, STRUCTURAL, LANDSCAPE
MECHANICAL, PLUMBING, FIRE PROTECTION
ELECTRICAL, FIRE ALARM
CONSULTANTS
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10
PROFESSIONAL SEAL
A u to d e sk
D o c s:
-M I A
R N
G R e a d in e ss C e n te r/
M
IA
R
N G
G A
A F
R e a d in e s s
C e n te r
E le
O
P T
IO
N
.r vt
/2
/2
:5 :5
P
M
PANEL SCHEDULES
& LIGHTING FIXTURE
SCHEDULE
MIARNG GAAF
READINESS CENTER
LS
06/30/2023
JG SE
86608-260247
TYPE B 100% REVISED FINAL DESIGN
GRAYLING TOWNSHIP,
CRAWFORD COUNTY, MICHIGAN
E-602
(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.
(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH
THE CONTROL RELAY (RIB24P30).
Notes:
Total Est. Demand Current: 9 A
Total Conn. Current: 7 A
Lighting - Exterior 372 VA 125.00% 465 VA Total Est. Demand: 7700 VA
LIGHTING 2841 VA 125.00% 3552 VA Total Conn. Load: 6187 VA
Other 140 VA 100.00% 140 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 8 A 4 A 11 A
Total Load: 2086 VA 1121 VA 2984 VA
29 SPARE 20 A 1 0 VA 240 VA 1 20 A KITCHEN LIGHTING 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 OUTDOOR LIGHTNG (2) 20 A 1 279 VA 0 VA 1 20 A SPARE 26
23 VAULTS LIGHITNG 20 A 1 340 VA 536 VA 1 20 A EOD LUPPLY & OFFICE LIGHTING 24
21 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 408 VA 1 20 A MAINT SUPPLY 120 LIGHTING 22
19 KITCHEN AND PANTRY LIGHTING 20 A 1 34 VA 79 VA 1 20 A ELECT AND COMM ROOMS LIGHTING 20
17 ASSEMBLY HALL LIGHTING 20 A 1 420 VA 420 VA 1 20 A ASSEMBLY HALL LIGHTING 18
15 CORRIDOR LIGHTING 20 A 1 118 VA 121 VA 1 20 A OUTDOOR LIGHTNG (2) 16
13 CLASSROOM 1 LIGHTING 20 A 1 383 VA 419 VA 1 20 A LOBBY LIGHTNG (1) 14
11 CLASSROOM 3 LIGHTING 20 A 1 383 VA 375 VA 1 20 A CLASSROOM 2 LIGHTING 12
9 COMM ROOM 121 LIGHTING 20 A 1 45 VA 23 VA 1 20 A OFFICES 140-142, AND LACTATION RMS LTS 10
7 OFFICES 143, 144, AND, 148 LIGHTING 20 A 1 270 VA 330 VA 1 20 A OFFICES 142, 141, AND 140 LIGHTING 8
5 OFFICES 149 AND 150 LIGHTING 20 A 1 180 VA 120 VA 1 20 A CORRIDOR 4 LIGHITNG 6
3 OFFICES 152, 153, 160, AND, 161 LIGHTING 20 A 1 120 VA 150 VA 1 20 A EOD OFFICE LIGHITNG 4
1 OFFICES 155, 156, 158, AND, 159 LIGHTING 20 A 1 120 VA 180 VA 1 20 A OFFICE 157 LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: DP1 Phases: 3 Mains Type: MLO
Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: LP2
(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.
(2) PROVIDE GFI RECEPTACLE.
(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
Notes:
Total Est. Demand Current: 137 A
LARGE MOTOR 396 VA 125.00% 495 VA Total Conn. Current: 136 A
EQUIPMENT 1000 VA 100.00% 1000 VA Total Est. Demand: 49259 VA
RECEPTACLE 43860 VA 100.00% 43860 VA Total Conn. Load: 49160 VA
HVAC 3904 VA 100.00% 3904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 142 A 145 A 127 A
Total Load: 16804 VA 17136 VA 15220 VA
83 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 84
81 SPARE 20 A 1 0 VA -- 1 -- SPARE 82
79 SPARE 20 A 1 0 VA 80
77 78
75 76
73 74
71 CUH-1 (2) 20 A 1 100 VA 72
69 EF-5 (2) 20 A 1 396 VA 480 VA 1 20 A SF1 & SF-2 (2) 70
67 EF-12 & EF-2 (2) 20 A 1 768 VA 1056... 1 20 A EF-1 & EF-3 (2) 68
65 OFFICE 149 RECEPTACLES 20 A 1 1080... 1080... 1 20 A CLASSROOM #1 GENERAL RECEPTACLES 66
63 ASSEMBLY HALL RECEPTACLES 20 A 1 1080... 600 VA 1 20 A UH-3 & UH-4 (2) 64
61 CLASSROOM #2 GENERAL RECEPTACLES 20 A 1 1080... 1080... 1 20 A ASSEMBLY HALL RECEPTACLES 62
59 OFFICE 142 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 150 RECEPTACLES 60
57 OFFICE 150 RECEPTACLES 20 A 1 1080... 1080... 1 20 A EOD SUPPLY RECEPTACLES 58
55 CORRIDOR #2 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 149 RECEPTACLES 56
53 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A VAULTS RECEPTACLES 54
51 RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A MENS RESTROOM RECEPTACLES 52
49 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A OFFICE 154 RECEPTACLES 50
47 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #2 FLOOR RECEPTACLES 48
45 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 46
43 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 44
41 OFFICE 143 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 42
39 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 40
37 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 38
35 720 VA 1 20 A OFFICE 149 AND 150 RECEPTACLES 36
33 OFFICE 148 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 34
31 CORRIDOR #1 RECEPTACLES 20 A 1 540 VA 720 VA 1 20 A OFFICE 144 RECEPTACLES 32
29 OFFICE 156 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 152 RECEPTACLES 30
27 KITCHEN GENERAL RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A FAMILY READINESS OFFICE RECEPTACLES 28
25 OFFICE 153 RECEPTACLES 20 A 1 540 VA 26
23 RETENTION OFFICE RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 159 RECEPTACLES 24
21 OFFICE 158 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 155 RECEPTACLES 22
19 OFFICE 160 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 157 RECEPTACLES 20
17 LACTATION AREA RECEPTACLES 20 A 1 180 VA 300 VA 1 20 A HVAC WORKBAY OFFICE 125 18
15 TABLE/CHAIR STORAGE RECEPTACLES 20 A 1 360 VA 540 VA 1 20 A OFFICE 161 RECEPTACLES 16
13 360 VA 1 20 A OFFICE 157 RECEPTACLES 14
11 CLASSROOM #3 GENERAL RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A CLASSROOM #3 GENERAL RECEPTACLES 12
9 CORRIDOR #1 RECEPTACLES 20 A 1 1440... 180 VA 1 20 A LACTATION AREA COUNTERTOP... 10
7 CONTROL TRANSFORMER PANEL 20 A 1 1000... 1200... 1 20 A LACTATION AREA DISHWASHER (2) 8
5 UH-1 & UH-2 (2) 20 A 1 600 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 6
3 EXTERIOR RECEPTACLE 20 A 1 360 VA 1260... 1 20 A ASSEMBLY HALL RECEPTACLES 4
1 JC RECEPTACLE 20 A 1 180 VA 720 VA 1 20 A ASSEMBLY HALL RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-RP2 Phases: 3 Mains Type: MCB
Location: COMM 121 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: RP2
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL VOLTAGE LAMP LOAD COMMENTS
A2 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-22-3500L-AOK (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K
A2E 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE CONNECTED
TO GENERATOR
FSC LIGHTING FPB-22-3500L-AOK (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K
A4 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-24-5000L-AOK (5000K) <varies> LED 30 VA <varies>
A4E 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE CONNECTED TO
GENERATOR
FSC LIGHTING FPB-24-5000L-AOK (5000K) <varies> LED 30 VA <varies>
C 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (34W4000K) 277 V LED 34 VA KELVIN TEMP: 5000K
C-H 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (45W4000K) 277 V LED 45 VA KELVIN TEMP: 5000K
CE 1x4 PENDANT LIGHT FIXTURE CONNECTED TO GENERATOR FSC LIGHTING L28548-45W-AOK-S5 (34W5000K) 277 V LED 34 VA KELVIN TEMP: 5000K
CE-H <varies> FSC LIGHTING L25848-45W-AOK-S5 (45W5000K) 277 V LED 45 VA KELVIN TEMP: 5000K
D 4-INCH RECESSED CAN LIGHT WHITE TRIM PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1_LFR-4RDS-T-S 277 V LED 8 VA
DE 4-INCH RECESSED CAN LIGHT WHITE TRIM CONNECTED TO
GENERATOR
PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1_LFR-4RDS-T-S 277 V LED 8 VA
EM EMERGENCY LIGHT FIXTURE BEGHELLI TBD 277 V LED 100 VA
LP8 LINEAR PENDANT 8FT LITECONTROL 3L-P-ID-STD-8-SOF-C1-50K-I045-D045-D01-2C-UNV-FA1-W2 277 V LED 35 VA
LR8 LINEAR RECESSED 8FT LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 21 VA SELECT MOUNTING OPTION BASE ON THE
CEILING TYPE
LR8-E LINEAR RECESSED 8FT CONNECTED TO GENERATOR LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 21 VA SELECT MOUNTING OPTION BASE ON THE
CEILING TYPE
LR12 LINEAR RECESSED 12FT LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 32 VA SELECT MOUNTING OPTION BASE ON THE
CEILING TYPE
LR12-E LINEAR RECESSED 12FT CONNECTED TO GENERATOR LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 32 VA SELECT MOUNTING OPTION BASE ON THE
CEILING TYPE
S 6-INCH SURFACE MOUNTED LIGHT PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL 277 V LED 28 VA
SE 6-INCH SURFACE MOUNTED LIGHT CONNECTED TO
GENERATOR
PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL 277 V LED 28 VA
SL3BC The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.
Current Lighting VP-1-160L-35-4K7-3-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA
SL4 The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.
Current Lighting VP-1-160L-35-4K7-4W-UNV-ASQ-DBT / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA
SL4BC The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.
Current Lighting VP-1-160L-35-4K7-4W-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT
SSS-B-25-40-A-1-B3-DBT
277 V LED 35 VA
SL5 The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.
Current Lighting VP-1-160L-50-4K7-5QW / SSS-B-25-40-A-1-B3-DBT 277 V LED 51 VA
W WALLPACK ARCHITECTURAL EGRESS LIGHTING BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC 277 V LED 47 VA
WE WALLPACK ARCHITECTURAL EGRESS LIGHTING CONNECTED TO
GENERATOR
BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC 277 V LED 47 VA
X CEILING MOUNTED EXIT SIGN SIGNIFY ER45VXL 277 V LED 4 VA
X1 WALL MOUNTED EXIT SIGN SIGNIFY ER45VXLW <varies> LED 4 VA
(1) GFI CIRCUIT BREAKER
(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
(3)LOCK-ON CIRCUIT BREAKER.
Notes:
Total Est. Demand Current: 120 A
Total Conn. Current: 147 A
KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA Total Est. Demand: 43149 VA
RECEPTACLE 900 VA 100.00% 900 VA Total Conn. Load: 52844 VA
Motor 14904 VA 100.00% 14904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 177 A 133 A 131 A
Total Load: 21192 VA 15894 VA 15758 VA
41 42
39 40
37 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 GAS RANGE (1)(2) 20 A 1 924 VA 0 VA 30
27 0 VA 28
25 0 VA 4968...
3 20 A GARBAGE DISPOSAL (1)(2)(3)
23 0 VA 0 VA 24
GARBAGE DISPOSAL (1)(2)(3) 20 A 3
4968... 0 VA 22
19 4482... 4968...
3 20 A GARBAGE DISPOSAL (1)(2)
DISWASHER (1)(2)(3) 20 A 2
4482... 5022... 18
15 5022...
2 20 A COFEE MACHINE (1)(2)
13 1250... 0 VA 14
FOOD WARMING CABINET (1)(2)(3) 20 A 2
1250... 2520...
2 20 A ICE MARKER (1)(2)(3)
9 3420... 924 VA 1 20 A CONV OVEN (1)(2) 10
WARMING CABINET (1)(2) 20 A 2
3420... 924 VA 1 20 A CONV OVEN (1)(2) 8
5 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 6
3 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 4
1 COUNTERTOP RECEPTACLE 20 A 1 180 VA 1000... 1 20 A HOOD (1)(2) 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-K Phases: 3 Mains Type: MCB
Location: KITCHEN 117 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: K
06/30/2023
(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.
(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH
THE CONTROL RELAY (RIB24P30).
Notes:
Total Est. Demand Current: 9 A
Total Conn. Current: 7 A
Lighting - Exterior 372 VA 125.00% 465 VA Total Est. Demand: 7700 VA
LIGHTING 2841 VA 125.00% 3552 VA Total Conn. Load: 6187 VA
Other 140 VA 100.00% 140 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 8 A 4 A 11 A
Total Load: 2086 VA 1121 VA 2984 VA
29 SPARE 20 A 1 0 VA 240 VA 1 20 A KITCHEN LIGHTING 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 OUTDOOR LIGHTNG (2) 20 A 1 279 VA 0 VA 1 20 A SPARE 26
23 VAULTS LIGHITNG 20 A 1 340 VA 536 VA 1 20 A EOD LUPPLY & OFFICE LIGHTING 24
21 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 408 VA 1 20 A MAINT SUPPLY 120 LIGHTING 22
19 KITCHEN AND PANTRY LIGHTING 20 A 1 34 VA 79 VA 1 20 A ELECT AND COMM ROOMS LIGHTING 20
17 ASSEMBLY HALL LIGHTING 20 A 1 420 VA 420 VA 1 20 A ASSEMBLY HALL LIGHTING 18
15 CORRIDOR LIGHTING 20 A 1 118 VA 121 VA 1 20 A OUTDOOR LIGHTNG (2) 16
13 CLASSROOM 1 LIGHTING 20 A 1 383 VA 419 VA 1 20 A LOBBY LIGHTNG (1) 14
11 CLASSROOM 3 LIGHTING 20 A 1 383 VA 375 VA 1 20 A CLASSROOM 2 LIGHTING 12
9 COMM ROOM 121 LIGHTING 20 A 1 45 VA 23 VA 1 20 A OFFICES 140-142, AND LACTATION RMS LTS 10
7 OFFICES 143, 144, AND, 148 LIGHTING 20 A 1 270 VA 330 VA 1 20 A OFFICES 142, 141, AND 140 LIGHTING 8
5 OFFICES 149 AND 150 LIGHTING 20 A 1 180 VA 120 VA 1 20 A CORRIDOR 4 LIGHITNG 6
3 OFFICES 152, 153, 160, AND, 161 LIGHTING 20 A 1 120 VA 150 VA 1 20 A EOD OFFICE LIGHITNG 4
1 OFFICES 155, 156, 158, AND, 159 LIGHTING 20 A 1 120 VA 180 VA 1 20 A OFFICE 157 LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: DP1 Phases: 3 Mains Type: MLO
Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000
Branch Panel: LP2
(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.
(2) PROVIDE GFI RECEPTACLE.
(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
Notes:
Total Est. Demand Current: 137 A
LARGE MOTOR 396 VA 125.00% 495 VA Total Conn. Current: 136 A
EQUIPMENT 1000 VA 100.00% 1000 VA Total Est. Demand: 49259 VA
RECEPTACLE 43860 VA 100.00% 43860 VA Total Conn. Load: 49160 VA
HVAC 3904 VA 100.00% 3904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 142 A 145 A 127 A
Total Load: 16804 VA 17136 VA 15220 VA
83 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 84
81 SPARE 20 A 1 0 VA -- 1 -- SPARE 82
79 SPARE 20 A 1 0 VA 80
77 78
75 76
73 74
71 CUH-1 (2) 20 A 1 100 VA 72
69 EF-5 (2) 20 A 1 396 VA 480 VA 1 20 A SF1 & SF-2 (2) 70
67 EF-12 & EF-2 (2) 20 A 1 768 VA 1056... 1 20 A EF-1 & EF-3 (2) 68
65 OFFICE 149 RECEPTACLES 20 A 1 1080... 1080... 1 20 A CLASSROOM #1 GENERAL RECEPTACLES 66
63 ASSEMBLY HALL RECEPTACLES 20 A 1 1080... 600 VA 1 20 A UH-3 & UH-4 (2) 64
61 CLASSROOM #2 GENERAL RECEPTACLES 20 A 1 1080... 1080... 1 20 A ASSEMBLY HALL RECEPTACLES 62
59 OFFICE 142 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 150 RECEPTACLES 60
57 OFFICE 150 RECEPTACLES 20 A 1 1080... 1080... 1 20 A EOD SUPPLY RECEPTACLES 58
55 CORRIDOR #2 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 149 RECEPTACLES 56
53 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A VAULTS RECEPTACLES 54
51 RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A MENS RESTROOM RECEPTACLES 52
49 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A OFFICE 154 RECEPTACLES 50
47 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #2 FLOOR RECEPTACLES 48
45 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 46
43 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 44
41 OFFICE 143 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 42
39 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 40
37 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 38
35 720 VA 1 20 A OFFICE 149 AND 150 RECEPTACLES 36
33 OFFICE 148 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 34
31 CORRIDOR #1 RECEPTACLES 20 A 1 540 VA 720 VA 1 20 A OFFICE 144 RECEPTACLES 32
29 OFFICE 156 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 152 RECEPTACLES 30
27 KITCHEN GENERAL RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A FAMILY READINESS OFFICE RECEPTACLES 28
25 OFFICE 153 RECEPTACLES 20 A 1 540 VA 26
23 RETENTION OFFICE RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 159 RECEPTACLES 24
21 OFFICE 158 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 155 RECEPTACLES 22
19 OFFICE 160 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 157 RECEPTACLES 20
17 LACTATION AREA RECEPTACLES 20 A 1 180 VA 300 VA 1 20 A HVAC WORKBAY OFFICE 125 18
15 TABLE/CHAIR STORAGE RECEPTACLES 20 A 1 360 VA 540 VA 1 20 A OFFICE 161 RECEPTACLES 16
13 360 VA 1 20 A OFFICE 157 RECEPTACLES 14
11 CLASSROOM #3 GENERAL RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A CLASSROOM #3 GENERAL RECEPTACLES 12
9 CORRIDOR #1 RECEPTACLES 20 A 1 1440... 180 VA 1 20 A LACTATION AREA COUNTERTOP... 10
7 CONTROL TRANSFORMER PANEL 20 A 1 1000... 1200... 1 20 A LACTATION AREA DISHWASHER (2) 8
5 UH-1 & UH-2 (2) 20 A 1 600 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 6
3 EXTERIOR RECEPTACLE 20 A 1 360 VA 1260... 1 20 A ASSEMBLY HALL RECEPTACLES 4
1 JC RECEPTACLE 20 A 1 180 VA 720 VA 1 20 A ASSEMBLY HALL RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-RP2 Phases: 3 Mains Type: MCB
Location: COMM 121 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: RP2
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL VOLTAGE LAMP LOAD COMMENTS
A2 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-22-3500L-AOK (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K
A2E 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE WITH BATTERY BACKUP
OPTION
FSC LIGHTING FPB-22-3500L-AOK EM10W (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K
A4 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-24-5000L-AOK (5000K) 277 V LED 30 VA KELVIN TEMP: 5000K
A4E 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE WITH BATTERY BACKUP
OPTION
FSC LIGHTING FPB-24-5000L-AOK EM10W (5000K) 277 V LED 30 VA KELVIN TEMP: 5000K
C 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (34W4000K) 277 V LED 34 VA KELVIN TEMP: 5000K
C-H 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (45W4000K) 277 V LED 45 VA KELVIN TEMP: 5000K
CE 1x4 PENDANT LIGHT FIXTURE WITH BATTERY BACKUP OPTION FSC LIGHTING L28548-45W-AOK-S5 EM10W (34W5000K) 277 V LED 34 VA KELVIN TEMP: 5000K
CE-H 1x4 PENDANT LIGHT FIXTURE WITH BATTERY BACKUP OPTION FSC LIGHTING L25848-45W-AOK-S5 EM10W (45W5000K) 277 V LED 45 VA KELVIN TEMP: 5000K
D 4-INCH RECESSED CAN LIGHT WHITE TRIM PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1_LFR-4RDS-T-S 277 V LED 8 VA
DE 4-INCH RECESSED CAN LIGHT WHITE TRIM WITH BATTERY BACKUP
OPTION
PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1-EMR_LFR-4RDS-T-S 277 V LED 8 VA
EM EMERGENCY LIGHT FIXTURE BEGHELLI TBD 277 V LED 100 VA
LP8 LINEAR PENDANT 8FT LITECONTROL 3L-P-ID-STD-8-SOF-C1-50K-I045-D045-D01-2C-UNV-FA1-W2 277 V LED 35 VA
LR8 LINEAR RECESSED 8FT LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 21 VA SELECT MOUNTING OPTION BASE
ON THE CEILING TYPE
LR8-E LINEAR RECESSED 8FT WITH BATTERY BACKUP OPTION LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV-EF 277 V LED 21 VA SELECT MOUNTING OPTION BASE
ON THE CEILING TYPE
LR12 LINEAR RECESSED 12FT LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 32 VA SELECT MOUNTING OPTION BASE
ON THE CEILING TYPE
LR12-E LINEAR RECESSED 12FT WITH BATTERY BACKUP OPTION LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV-EF 277 V LED 32 VA SELECT MOUNTING OPTION BASE
ON THE CEILING TYPE
S 6-INCH SURFACE MOUNTED LIGHT PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL 277 V LED 28 VA
SE 6-INCH SURFACE MOUNTED LIGHT WITH BATTERY BACKUP OPTION PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL-EM 277 V LED 28 VA
SL3BC AREA POLE LIGHT CURRENT
LIGHTING
VP-1-160L-35-4K7-3-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA
SL4 AREA POLE LIGHT CURRENT
LIGHTING
VP-1-160L-35-4K7-4W-UNV-ASQ-DBT / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA
SL4BC AREA POLE LIGHT CURRENT
LIGHTING
VP-1-160L-35-4K7-4W-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT
SSS-B-25-40-A-1-B3-DBT
277 V LED 35 VA
SL5 AREA POLE LIGHT CURRENT
LIGHTING
VP-1-160L-50-4K7-5QW / SSS-B-25-40-A-1-B3-DBT 277 V LED 51 VA
W WALLPACK ARCHITECTURAL EGRESS LIGHTING BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC 277 V LED 47 VA
WE WALLPACK ARCHITECTURAL EGRESS LIGHTING WITH BATTERY BACKUP
OPTION
BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC-E 277 V LED 47 VA
X CEILING MOUNTED EXIT SIGN SIGNIFY ER45VXL 277 V LED 4 VA
X1 WALL MOUNTED EXIT SIGN SIGNIFY ER45VXLW 277 V LED 4 VA
(1) GFI CIRCUIT BREAKER
(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE
DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.
(3)LOCK-ON CIRCUIT BREAKER.
Notes:
Total Est. Demand Current: 120 A
Total Conn. Current: 147 A
KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA Total Est. Demand: 43149 VA
RECEPTACLE 900 VA 100.00% 900 VA Total Conn. Load: 52844 VA
Motor 14904 VA 100.00% 14904 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 177 A 133 A 131 A
Total Load: 21192 VA 15894 VA 15758 VA
41 42
39 40
37 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 GAS RANGE (1)(2) 20 A 1 924 VA 0 VA 30
27 0 VA 28
25 0 VA 4968...
3 20 A GARBAGE DISPOSAL (1)(2)(3)
23 0 VA 0 VA 24
GARBAGE DISPOSAL (1)(2)(3) 20 A 3
4968... 0 VA 22
19 4482... 4968...
3 20 A GARBAGE DISPOSAL (1)(2)
DISWASHER (1)(2)(3) 20 A 2
4482... 5022... 18
15 5022...
2 20 A COFEE MACHINE (1)(2)
13 1250... 0 VA 14
FOOD WARMING CABINET (1)(2)(3) 20 A 2
1250... 2520...
2 20 A ICE MARKER (1)(2)(3)
9 3420... 924 VA 1 20 A CONV OVEN (1)(2) 10
WARMING CABINET (1)(2) 20 A 2
3420... 924 VA 1 20 A CONV OVEN (1)(2) 8
5 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 6
3 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 4
1 COUNTERTOP RECEPTACLE 20 A 1 180 VA 1000... 1 20 A HOOD (1)(2) 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-K Phases: 3 Mains Type: MCB
Location: KITCHEN 117 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: K
In c h e s
/2
/4
REV. DATE DESCRIPTION
ISSUE FOR CONSTRUCTION DATE
DESIGNEDSCALE
DRAWING TITLE
DRAWN CHECKED
ORIGINAL SHEET SIZE
PROJECT NUMBER
PROJECT STATUS
SHEET NUMBER
REVISION NO.
www.atkinsglobal.com
Copyright © Atkins Limited (2015)
+1 703 535 3008 +1 703 535 1031
Tel:
Fax:
2318 Mill Road Suite 1040 Alexandria VA 22314
DO NOT SCALE
A ARCHD24X36
ATKINS DESIGN TEAM
ARCHITECTURE, INTERIORS
CIVIL, STRUCTURAL, LANDSCAPE
MECHANICAL, PLUMBING, FIRE PROTECTION
ELECTRICAL, FIRE ALARM
CONSULTANTS
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10
PROFESSIONAL SEAL
A u to d e sk
D o c s:
-M I A
R N
G R e a d in e ss C e n te r/
M
IA
R
N G
G A
A F
R e a d in e s s
C e n te r
E le
O
P T
IO
N
.r vt
/2
/2
:5 :5
P
M
LIFE SAFETY PANEL
SCHEDULES
MIARNG GAAF
READINESS CENTER
LS
06/30/2023
JG SE
86608-260247
TYPE B 100% REVISED FINAL DESIGN
GRAYLING TOWNSHIP,
CRAWFORD COUNTY, MICHIGAN
E-603
(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSING.
(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH
THE CONTROL RELAY (RIB24P30).
Notes:
Total Est. Demand Current: 11 A
Total Conn. Current: 10 A
EQUIPMENT 3000 VA 100.00% 3000 VA Total Est. Demand: 9440 VA
Lighting - Exterior 791 VA 125.00% 988 VA Total Conn. Load: 8142 VA
LIGHTING 4123 VA 125.00% 5153 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 8 A 14 A 8 A
Total Load: 2181 VA 3824 VA 2161 VA
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 0 VA 872 VA 14
11 1000... 854 VA 12
T-LSL1 50 A 3
2000... 1080...
3 50 A LSH2
7 WORKBAY GENERAL LIGHTING 20 A 1 385 VA 476 VA 1 20 A WORKBAYS GENERAL LIGHTING 8
5 ADMIN LOBBY 146 (1) 20 A 1 139 VA 186 VA 1 20 A WORKBAY EXTERIOR LIGHTING (2) 6
3 OUTDOOR LIGHTING (2) 20 A 1 260 VA 518 VA 1 20 A ELEC, COMM, MECH, STOR. RMS LIGHTING 4
1 OUTDOOR LIGHTING (2) 20 A 1 93 VA 356 VA 1 20 A WOMENS, MENS, PES, BREAK RMS. LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 70 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: Phases: 3 Mains Type: MCB
Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 10,000
Branch Panel: LSH1
(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.
Notes:
Total Est. Demand Current: 8 A
Total Conn. Current: 8 A
Total Est. Demand: 3000 VA
Total Conn. Load: 3000 VA
EQUIPMENT 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 18 A 10 A 0 A
Total Load: 2000 VA 1000 VA 0 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 0 VA 0 VA 1 20 A SPARE 6
3 500 VA 500 VA 1 20 A LOC ADMIN LOBBY (1) 4
LSL2 50 A 3
1000... 1000... 1 20 A FACP (1) 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: T-LSL1 Phases: 3 Mains Type: MCB
Location: COMM 131 Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: LSL1
(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.
Notes:
Total Est. Demand Current: 4 A
Total Conn. Current: 4 A
Total Est. Demand: 1500 VA
Total Conn. Load: 1500 VA
EQUIPMENT 1500 VA 100.00% 1500 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 9 A 5 A 0 A
Total Load: 1000 VA 500 VA 0 VA
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPACE -- 1 -- -- 1 -- SPACE 12
9 SPACE -- 1 -- -- 1 -- SPACE 10
7 SPACE -- 1 -- -- 1 -- SPACE 8
5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6
3 LOC MAIN LOBBY (1) 20 A 1 500 VA 0 VA 1 20 A SPARE 4
1 IDS VAULT 112 20 A 1 500 VA 500 VA 1 20 A IDS VAULT 110 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 50 A
This is the start of the file's text. The full file is on GovTribe.