MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3.pdf__Part4.pdf

PDF 44 MB Posted

Attached to
Construct Readiness Center Federal contract opportunity
Solicitation number
W912JB-24-B-0001
Issued by
Department of the Army Michigan Army National Guard

About this file

This document outlines a federal contract opportunity to construct a new Michigan Army National Guard Readiness Center. The solicitation number is W912JB-24-B-0001 and seeks the design and construction of up to 46,831 square feet of a new National Guard Readiness Center to support training, administrative, and logistical requirements for the Michigan Army National Guard. The project scope includes all necessary utility services, information systems, fire detection and alarm systems, roads, walls, curbs, storm drainage, parking areas, and site improvements. The new facility must meet industry standards as well as all local, state and federal building codes and Public Law 90-480. It should have a minimum 50-year life span and incorporate energy efficiencies, building envelope standards, and integrated building systems per DoD and ASA(IE&E) policies. Access for individuals with disabilities and DoD antiterrorism standards are also requirements.

View the file

Other files for this federal contract opportunity

Other files attached to Construct Readiness Center, newest first.
File Type Posted
Abstract Pg 1.pdf PDF
Abstract Pg 2.pdf PDF
w912JB24B00001 Updated.pdf PDF
w912JB24B00001 AMEND 5.pdf PDF
2024-01-31 MARNG RFI LOG (1).xlsx XLSX spreadsheet
W912JB24B0001 Amend 4.pdf PDF
Amendment 3.pdf PDF
W912JB24B0001 Amend 2.pdf PDF
2024-01-29 MARNG RFI LOG (1).xlsx XLSX spreadsheet
RFI Log as of 29.xlsx XLSX spreadsheet
W912JB24B0001 Amendment.pdf PDF
RFI LOG as of 23 Jan 24.xlsx XLSX spreadsheet
Geotech Report MI ARNG GAAF RC.pdf PDF
RFI Log as of 18 Jan.xlsx XLSX spreadsheet
Readiness Center Pre-Bid Conference_Site Visit.pptx PPTX presentation
Pre-Bid Site Visit Sign-in sheet.pdf PDF
RFI Log.docx DOCX document
GAAF Vetting Access Roster.xlsx XLSX spreadsheet
W912JB24B0001 1229.pdf PDF
MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3.pdf__Part3.pdf PDF
MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3.pdf__Part5.pdf PDF
MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3.pdf__Part1.pdf PDF
MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3.pdf__Part2.pdf PDF
MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3.pdf Part 2.pdf PDF
MI ARNG GAAF RC Volume 2 TYPE B 100 Drawings FULL_R3 Part 1.pdf PDF
W912JB24B0001 Signed.pdf PDF
MI ARNG GAFF RC Volume 3 TYPE B 100 Specifications_R1.pdf PDF
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. CONTRACTOR SHALL VERIFY FUSE/BREAKER SIZE AND CABLING REQUIREMENTS WITH FINAL APPROVED

VENDOR DRAWINGS.

2. ALL WIRES SHALL BE COPPER THWN OR AS OTHERWISE NOTED ON THESE PLANS.

3. EQUIPMENT INSIDE ELECTRICAL ROOMS TO COMPLY WITH NEC 110.26.

4. PROVIDE PERMANENT PLAQUE FOR EACH SERVICE LOCATION AS PER NEC 230.2.

5. PROVIDE CABLE SUPPORT IN ALL VERTICAL RACEWAYS AS PER NEC TABLE 300.19(A).

6. ALL ELECTRICAL EQUIPMENT WILL BE LABELED TO INDICATE POTENTIAL ELECTRIC ARC FLASH HAZARDS IN

FULL COMPLIANCE WITH NEC 110.16.

7. DESIGN BASIS IS SQUARE D I-LINE PANELS, QED-2 AND BREAKERS.

8. ALL ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE CONNECTED TO GROUND.

GENERAL SHEET NOTES:

480V, 3 PHASE, 4 WIRE + GROUND BUS42KAIC

MDP

ELECTRICAL ROOM 132

1600A

1000AT

1200AF

1000 kVA 8320V-480Y

600AT

800AF

SPD

30AT

90AF

100AT

150AF

LSIG

60AT

150AF

BAS

400AT

400AF

EXISTING DEAD FRONT SWITCH

ENCLOSURE 25KV RATED, 200A, WITH 4

INTERFACE POINTS PER PHASE.

1 SET OF 15kV INSULATED EPR

133% (3) 1/C #2 (AL) IN 5" CONDUIT

4" C

3 SETS OF

(4) 600 KCMIL (AL)

800 A

277/480V, 3-PHASE, 4 WIRE(22,000 AIC)

DP1

3 1/2" C

2 SETS OF

(4) 350 KCMIL

(1) #1

800AF

600AT

SPD

EM BAS

RP1

480V- 120/208V

#4

T-RP1

45 kVA

1" C

(3) #6

(1) #10

2" C

(4) #1/0

(1) #6

LP1

1 1/2" C

(4) #2

(1) #8

100AT

150AF

125AT

150AF

EM

SPD

RP2

480V- 120/208V

#2

T-RP2

75 kVA

2" C

(3) #1

(1) #6

3" C

(4) 250 KCMIL

(1) #4

LP2

1 1/2" C

(4) #2

(1) #8

EM BAS

SPD

SPD

30AT

150AF

EM

BAS

EMBAS

SPD

5 BAS

EM

SPD

NET2

BAS

SPD

EM BAS

LP3

SPD

EM BAS

RP3

480V- 120/208V

#2

T-110-01 75 kVA

2" C

(3) #1

(1) #6

4" C

(4) 500 KCMIL

(1) #3TRAINING

BAY

(OPTION #3)

1/

4" C

(4

(1

3" C

(4) 250 KCMIL

(1) #4

SPARESPARE

150AF SPACESPACE

100 A 90 A

RTU-SE

125AT

150AF

SPARESPARE

100AF

40AT

SPARE

150AF SPACESPACE

SPD

EM BAS

K

480V- 120/208V

#2

T-K 75 kVA

2" C

(3) #1

(1) #6

3" C

(4) 250 KCMIL

(1) #4

125AT

150AF

KITCHEN

(OPTION #4)

110AT

150AF

RTU-NE

100AT

150AF

RTU-NW

100AF

20AT

HWP-2

HP

FIRE PUMP

HP

480V, 3PH, 60HZ

1 1/2" C

(4) #2 (AL)

M

1 1/4" C

(3) #3

(1) #8

1 1/4" C

(3) #3

(1) #8

100 A 90 A

100 A 70 A

1" C

(3) #6

(1) #10

3/4" C

(3) #12

(1) #12

ATS-FP

200 A

G 150KW

480V, 3PH, 60HZ

175AT

225AF

80AT

100AF

100AT

100AF

NATURAL GAS EMERGENCY GENERATOR,

LEVEL 1, TYPE 10.

SPD

EM BAS

LSH1

SPD

EM BAS

LSL1

480V- 120/208V

#6

T-LSL1

30 kVA

1" C

(3) #6

(1) #10

1 1/2" C

(4) #2

(1) #8

SPD

EM BAS

LSL2

1 1/4" C

(4) #4

(1) #8

SPD

EM BAS

LSH2

SPD

EM BAS

NEH1

SPD

EM BAS

NEL1

480V- 120/208V

#6

T-NEL1

30 kVA

1" C

(3) #6

(1) #10

1 1/2" C

(4) #2

(1) #8

SPD

EM BAS

NEL2

1 1/4" C

(4) #4

(1) #8

1 1/2" C

(4) #1 (AL)

(1) #8

3" C

(4) #4/0 (AL)

(1) #6

1 1/2" C

(4) #2 (AL)

(1) #8

ATS-NE

225 A

ATS-LS

125 A

1-1/2"" C

(4) #1 (AL)

3" C

(4) #4/0 (AL)

GENERATOR LOAD CALCULATION:

LOAD NAME: TOTAL LOAD (AMP) TOATL LOAD (VA)

- FIRE PUMP: 34 28,267

- ATS-LS: 9 7,328

- ATS-NE 157 130,854

TOTAL= 200 166,359

8 8

1 1/4" C

(4) #4

(1) #8

2 1/2" C

(4) #3/0

(1) #6

1 1/4" C

(4) #4

(1) #8

EM

SPD

NET1

BAS

SPARESPARE

100AF

40AT

SPARESPARE

100AF

40AT

SPARESPARE

100AF

40AT

FOUR (4) SPARE BREAKERS FUTURE EV CHARGERS

LIFT

STATION

HP

100AF

20AT

GENERATOR 225 188,000

DATA

K

DUAL BRAKER

DOCKING STATION

WITH INDIVIDUALLY

KIRK KEYED

BREAKERS

250A, 480V, 3-POLE, NEMA 4X

K

K

K K K

EF-4

1.5

HP

100AF

20AT

SF-4

HP

100AF

20AT

3/4" C

(3) #12

(1) #12

3/4" C

(3) #12

(1) #12

3/4" C

(3) #10

(1) #10

100AF

20AT

HWP-5

HP

15 A

3/4" C

(3) #12

(1) #12

SPD

EM BAS

NEH2

1 1/2" C

(3) #2

(1) #8

1" C

(3) #6

(1) #10

100AF

20AT

HWP-3

HP

3/4" C

(3) #12

(1) #12

4 POLE

4 POLE

4 POLE

N

G N

G

N

GN

G

PROJECT TITLE

CLIENT

In c h e s

/2

/4

REV. DATE DESCRIPTION

ISSUE FOR CONSTRUCTION DATE

DESIGNEDSCALE

DRAWING TITLE

DRAWN CHECKED

ORIGINAL SHEET SIZE

PROJECT NUMBER

PROJECT STATUS

SHEET NUMBER

REVISION NO.

www.atkinsglobal.com

Copyright © Atkins Limited (2015)

+1 703 535 3008 +1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040 Alexandria VA 22314

DO NOT SCALE

A ARCHD24X36

ATKINS DESIGN TEAM

ARCHITECTURE, INTERIORS

CIVIL, STRUCTURAL, LANDSCAPE

MECHANICAL, PLUMBING, FIRE PROTECTION

ELECTRICAL, FIRE ALARM

CONSULTANTS

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

G

H

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10

PROFESSIONAL SEAL

NTS

A u to d e sk

D o c s:

-M I A

R N

G R e a d in e ss C e n te r/

M

IA

R

N G

G A

A F

R e a d in e s s

C e n te r

E le c

R

O

P T

IO

N

.r vt

/2

/2

:5 :5

P

M

ELECTRICAL

ONE-LINE DIAGRAM

MIARNG GAAF

READINESS CENTER

LS

06/30/2023

JG SE

86608-260247

TYPE B 100% REVISED FINAL DESIGN

GRAYLING TOWNSHIP,

CRAWFORD COUNTY, MICHIGAN

E-501

1 CONNECT NEW MEDIUM VOLTAGE WIRES TO SPARE LOAD BREAKER INSERTER ON DFSE-13.

2 PROVIDE MAIN BONDING JUMPER (#2/0 CU) AT MAIN SERVICE DISCONNECT AS PER NEC 250.24.

3 MAIN SERVICE DISCONNECT SHALL BE PROVIDED WITH ARC ENERGY REDUCTION PER NEC 240.87.

4 PROVIDE MAIN SERVICE DISCONNECT WITH GORUND-FAULT PROTECIOTN PER NEC 230-95.

5 PROVIDE QUALITY METER TO MONITOR CURRENT. PROVIDE COMMUNICATIONS WIRING IN CONDUIT AS

REQUIRED BACK TO BAS SYSTEM CONTROL PANEL.

6 SERVICE RATED FIRE PUMP ATS WITH INTEGRATED MAIN SERCVICE DISCONNECT. PROVIDE MAIN BONDING

JUMPER (#8 CU) AT MAIN SERVICE DISCONNECT AS PER NEC 250.24.

7 SERVICE RATED ATS WITH INTEGRATED DISCONNECT. PROVIDE MAIN BONDING JUMPER (#8 CU) AT MAIN

SERVICE DISCONNECT AS PER NEC 250.24.

8 RTU WITH INTEGRATED VFD AND NON-FUSED DISCONNECT SWITCH.

9 NATURAL GAS EMERGENCY GENERATOR, LEVEL 1, TYPE 10. PROVIDE #4 AWG CU ELECTRODE GROUNDING CONDUCTOR IN 3/4" CONDUIT. IN ADDDITION, CONTRACTOR SHALL PROVIDE 3/4" CONDUITS AND CONTROL

WIRING TO THE FOLLOWING LOCATION:

- FIRE ALARM CONTROL PANEL

- FIRE PUMP ATS

- LIFE SAFETY ATS

- NON-ESSENTIAL ATS

- REMOTE ANNUNCIATOR

- REMOTE PUSH BUTTON

KEYED NOTES: #

06/30/2023

1. CONTRACTOR SHALL VERIFY FUSE/BREAKER SIZE AND CABLING REQUIREMENTS WITH FINAL APPROVED

VENDOR DRAWINGS.

2. ALL WIRES SHALL BE COPPER THWN OR AS OTHERWISE NOTED ON THESE PLANS.

3. EQUIPMENT INSIDE ELECTRICAL ROOMS TO COMPLY WITH NEC 110.26.

4. PROVIDE PERMANENT PLAQUE FOR EACH SERVICE LOCATION AS PER NEC 230.2.

5. PROVIDE CABLE SUPPORT IN ALL VERTICAL RACEWAYS AS PER NEC TABLE 300.19(A).

6. ALL ELECTRICAL EQUIPMENT WILL BE LABELED TO INDICATE POTENTIAL ELECTRIC ARC FLASH HAZARDS IN

FULL COMPLIANCE WITH NEC 110.16.

7. DESIGN BASIS IS SQUARE D I-LINE PANELS, QED-2 AND BREAKERS.

8. ALL ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE CONNECTED TO GROUND.

GENERAL SHEET NOTES:

480V, 3 PHASE, 4 WIRE + GROUND BUS42KAIC

MDP

ELECTRICAL ROOM 132

1600A

1000AT

1200AF

1000 kVA 8320V-480Y

600AT

800AF

SPD

30AT

90AF

100AT

150AF

LSIG

60AT

150AF

BAS

400AT

400AF

EXISTING DEAD FRONT SWITCH

ENCLOSURE 25KV RATED, 200A, WITH 4

INTERFACE POINTS PER PHASE.

1 SET OF 15kV INSULATED EPR

133% (3) 1/C #2 (AL) IN 5" CONDUIT

4" C

3 SETS OF

(4) 600 KCMIL (AL)

800 A

277/480V, 3-PHASE, 4 WIRE(22,000 AIC)

DP1

3 1/2" C

2 SETS OF

(4) 350 KCMIL

(1) #1

800AF

600AT

SPD

EM BAS

RP1

480V- 120/208V

#4

T-RP1

45 kVA

1" C

(3) #6

(1) #10

2" C

(4) #1/0

(1) #6

LP1

1 1/2" C

(4) #2

(1) #8

100AT

150AF

125AT

150AF

EM

SPD

RP2

480V- 120/208V

#2

T-RP2

75 kVA

2" C

(3) #1

(1) #6

3" C

(4) 250 KCMIL

(1) #4

LP2

1 1/2" C

(4) #2

(1) #8

EM BAS

SPD

SPD

30AT

150AF

EM

BAS

EMBAS

SPD

5 BAS

EM

SPD

NET2

BAS

SPD

EM BAS

LP3

SPD

EM BAS

RP3

480V- 120/208V

#2

T-110-01 75 kVA

2" C

(3) #1

(1) #6

4" C

(4) 500 KCMIL

(1) #3TRAINING

BAY

(OPTION #3)

1/

4" C

(4

(1

3" C

(4) 250 KCMIL

(1) #4

SPARESPARE

150AF SPACESPACE

100 A 90 A

RTU-SE

125AT

150AF

SPARESPARE

100AF

40AT

SPARE

150AF SPACESPACE

SPD

EM BAS

K

480V- 120/208V

#2

T-K 75 kVA

2" C

(3) #1

(1) #6

3" C

(4) 250 KCMIL

(1) #4

125AT

150AF

KITCHEN

(OPTION #4)

110AT

150AF

RTU-NE

100AT

150AF

RTU-NW

100AF

20AT

HWP-2

HP

FIRE PUMP

HP

480V, 3PH, 60HZ

1 1/2" C

(4) #2 (AL)

M

1 1/4" C

(3) #3

(1) #8

1 1/4" C

(3) #3

(1) #8

100 A 90 A

100 A 70 A

1" C

(3) #6

(1) #10

3/4" C

(3) #12

(1) #12

SPD

EM BAS

LSH1

SPD

EM BAS

LSL1

480V- 120/208V

#6

T-LSL1

30 kVA

1" C

(3) #6

(1) #10

1 1/2" C

(4) #2

(1) #8

SPD

EM BAS

LSL2

1 1/4" C

(4) #4

(1) #8

SPD

EM BAS

LSH2

5 SPD

EM BAS

NEH1

SPD

EM BAS

NEL1

480V- 120/208V

#6

T-NEL1

30 kVA

1" C

(3) #6

(1) #10

1 1/2" C

(4) #2

(1) #8

SPD

EM BAS

NEL2

1 1/4" C

(4) #4

(1) #8

8 8

1 1/4" C

(4) #4

(1) #8

EM

SPD

NET1

BAS

SPARESPARE

100AF

40AT

SPARESPARE

100AF

40AT

SPARESPARE

100AF

40AT

FOUR (4) SPARE BREAKERS FUTURE EV CHARGERS

LIFT

STATION

HP

100AF

20AT

EF-4

1.5

HP

100AF

20AT

SF-4

HP

100AF

20AT

3/4" C

(3) #12

(1) #12

3/4" C

(3) #12

(1) #12

3/4" C

(3) #10

(1) #10

100AF

20AT

HWP-5

HP

15 A

3/4" C

(3) #12

(1) #12

SPD

EM BAS

NEH2

1 1/2" C

(3) #2

(1) #8

1" C

(3) #6

(1) #10

100AF

20AT

HWP-3

HP

3/4" C

(3) #12

(1) #12

N

G

N

G

70AT

100AF

200AT

225AF

2 1/2" C

(4) #3/0

(1) #61 1/4" C

(4) #4

(1) #8

1 CONNECT NEW MEDIUM VOLTAGE WIRES TO SPARE LOAD BREAKER INSERTER ON DFSE-13.

2 PROVIDE MAIN BONDING JUMPER (#2/0 CU) AT MAIN SERVICE DISCONNECT AS PER NEC 250.24.

3 MAIN SERVICE DISCONNECT SHALL BE PROVIDED WITH ARC ENERGY REDUCTION PER NEC 240.87.

4 PROVIDE MAIN SERVICE DISCONNECT WITH GORUND-FAULT PROTECIOTN PER NEC 230-95.

5 PROVIDE QUALITY METER TO MONITOR CURRENT. PROVIDE COMMUNICATIONS WIRING IN CONDUIT AS

REQUIRED BACK TO BAS SYSTEM CONTROL PANEL.

6 200 AMP MAIN SERVICE DISCONNECT (SERVICE RATED ). PROVIDE MAIN BONDING JUMPER (#8 CU) AT MAIN

SERVICE DISCONNECT AS PER NEC 250.24.

7 NOT IN USE.

8 RTU WITH INTEGRATED VFD AND NON-FUSED DISCONNECT SWITCH.

9 NOT IN USE.

10 LIFT STATION PUMPS AND CONTROLLER PROVIDED BY THE PLUMBING CONTRACTOR. ELECTRRICAL CONTRACTRIOR SHALL COORDINATE WITH THE PLUMBING CONTRACTOR THE CONNECTION OF THE LIFT STATION CONTROLLER. PROVIDE 3FT OF WORKING SPACE TO THE CONTROLLER AND DISCONNECT SWITCH.

KEYED NOTES: #

PROJECT TITLE

CLIENT

In c h e s

/2

/4

REV. DATE DESCRIPTION

ISSUE FOR CONSTRUCTION DATE

DESIGNEDSCALE

DRAWING TITLE

DRAWN CHECKED

ORIGINAL SHEET SIZE

PROJECT NUMBER

PROJECT STATUS

SHEET NUMBER

REVISION NO.

www.atkinsglobal.com

Copyright © Atkins Limited (2015)

+1 703 535 3008 +1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040 Alexandria VA 22314

DO NOT SCALE

A ARCHD24X36

ATKINS DESIGN TEAM

ARCHITECTURE, INTERIORS

CIVIL, STRUCTURAL, LANDSCAPE

MECHANICAL, PLUMBING, FIRE PROTECTION

ELECTRICAL, FIRE ALARM

CONSULTANTS

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

G

H

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10

PROFESSIONAL SEAL

A u to d e sk

D o c s:

-M I A

R N

G R e a d in e ss C e n te r/

M

IA

R

N G

G A

A F

R e a d in e s s

C e n te r

E le

O

P T

IO

N

.r vt

/2

/2

:5 :5

P

M

PANEL SCHEDULES

MIARNG GAAF

READINESS CENTER

LS

06/30/2023

JG SE

86608-260247

TYPE B 100% REVISED FINAL DESIGN

GRAYLING TOWNSHIP,

CRAWFORD COUNTY, MICHIGAN

E-601

(1) OPTION #3. REFER TO DRAWING E-732 FOR PANEL LP-101-01 SCHEDULE.

(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

(3) NON-CONCURRENT LOAD. STANDBY SYSTEM PUMP.

Notes:

LARGE MOTOR 137346 VA 125.00% 171683 VA

KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA

EQUIPMENT 221414 VA 100.00% 221414 VA

Lighting - Exterior 651 VA 125.00% 814 VA

RECEPTACLE 51420 VA 100.00% 51420 VA Total Est. Demand Current: 657 A

HVAC 58809 VA 100.00% 58809 VA Total Conn. Current: 625 A

LIGHTING 4189 VA 125.00% 5236 VA Total Est. Demand: 546083 VA

Other 279 VA 100.00% 279 VA Total Conn. Load: 519521 VA

Motor 14904 VA 100.00% 14904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 625 A

Total Connected Load 519521 VA

15 SPACE --

14 SPARE 0 VA

13 SPD --

12 HWP-5 (2) 3984 VA

11 HWP-3 (2)(3) 0 VA

10 RTU-SE (2) 62250 VA

9 LP3 (1) 83514 VA

8 EV CHARGER 4 (FUTURE) 26600 VA

7 EV CHARGER 3 (FUTURE) 26600 VA

6 EV CHARGER 2 (FUTURE) 26600 VA

5 EV CHARGER 1 (FUTURE) 26600 VA

4 HWP-2 (2) 6308 VA

3 DP1 235061 VA

2 LP1 2039 VA

1 T-RP1 20060 VA

CKT Circuit Description Load

Notes:

Enclosure: Type 1 MCB Rating: 1000 A

Mounting: Floor Mounting Wires: 4 Mains Rating: 1200 A

Supply From: Phases: 3 Mains Type: Main Circuit Breaker

Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 42,000

Switchboard: MDP

(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.

(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH

THE CONTROL RELAY (RIB24P30).

Notes:

Total Est. Demand Current: 3 A

Lighting - Dwelling Unit 270 VA 125.00% 338 VA Total Conn. Current: 2 A

Lighting - Exterior 279 VA 125.00% 349 VA Total Est. Demand: 2514 VA

LIGHTING 1352 VA 125.00% 1690 VA Total Conn. Load: 2039 VA

Other 140 VA 100.00% 140 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 3 A 2 A 3 A

Total Load: 871 VA 483 VA 686 VA

29 30

27 28

25 26

23 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 OUTDOOR LIGHTING (2) 20 A 1 260 VA 47 VA 1 20 A OUTDOOR LIGHTING (2) 14

11 ADMIN LOBBY LIGHTING (1) 20 A 1 118 VA 93 VA 1 20 A CORRIDOR 3 LIGHTING 12

9 MENS REST LIGHTING 20 A 1 84 VA 114 VA 1 20 A MENS SHOWER LIGHTING 10

7 WOMENS SHOWER LIGHTING 20 A 1 114 VA 76 VA 1 20 A WOMENS REST LIGHTING 8

5 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 340 VA 1 20 A PES ROOM LIGHTING 6

3 MAINT STORAGE/OFFICE LIGHTING 20 A 1 60 VA 225 VA 1 20 A BREAK ROOM 146 LIGHTING 4

1 ELECTRICAL AND COMM ROOM LIGHTING 20 A 1 136 VA 238 VA 1 20 A MECHANICAL ROOM LIGHITNG 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: MDP Phases: 3 Mains Type: MLO

Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: LP1

(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.

(2) PROVIDE GFI CIRCUIT BREAKER.

(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS

Notes:

Total Est. Demand Current: 56 A

Total Conn. Current: 56 A

EQUIPMENT 10868 VA 100.00% 10868 VA Total Est. Demand: 20060 VA

RECEPTACLE 6660 VA 100.00% 6660 VA Total Conn. Load: 20060 VA

HVAC 2532 VA 100.00% 2532 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 63 A 58 A 48 A

Total Load: 7438 VA 6849 VA 5773 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 34

31 32

29 30

27 725 VA 28

MENS HAND DRYER (2)(3)(4) 20 A 2

725 VA 725 VA 26

23 PES ROOM RECEPTACLES 20 A 1 720 VA 725 VA

2 20 A WOMENS HAND DRYER (2)(3)(4)

21 MAINT STORAGE/OFFICE RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#2 (2) 22

19 BREAK ROOM RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#1 (2) 20

17 ROOF RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A PES ROOM RECEPTACLES 18

15 OUTDOOR RECEPTACLE 20 A 1 360 VA 720 VA 1 20 A RECEPTACLE MECH ROOM 133 16

13 BREAK ROOM TV RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A BREAK ROOM COUNTERTOP RECEPTACLES 14

11 EF-6 & EF-11 20 A 1 728 VA 1600... 1 20 A BOILER #2 12

9 EF-7, EF-8, EF-9, EF-10 20 A 1 960 VA 1500... 1 20 A BREAK ROOM - REF (2) 10

7 WATER FOUNTAIN RECEPTACLE 20 A 1 1200... 1440... 1 20 A VENDING MACHINE 8

5 BREAK ROOM DISPOSAL 20 A 1 500 VA 600 VA 1 20 A UH-5 & UH-6 6

3 SF-3 (2) 20 A 1 100 VA 900 VA 1 20 A WOMENS RESTROOM RECEPTACLES 4

1 UH-7 20 A 1 144 VA 720 VA 1 20 A ADMIN LOBBY RECEPTACLES 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 150 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-RP1 Phases: 3 Mains Type: MCB

Location: COMM 131 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: RP1

(1) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

Notes:

LARGE MOTOR 75096 VA 125.00% 93870 VA

KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA

EQUIPMENT 10340 VA 100.00% 10340 VA

Lighting - Exterior 372 VA 125.00% 465 VA

RECEPTACLE 44760 VA 100.00% 44760 VA Total Est. Demand Current: 295 A

HVAC 56277 VA 100.00% 56277 VA Total Conn. Current: 283 A

LIGHTING 2841 VA 125.00% 3552 VA Total Est. Demand: 245606 VA

Other 140 VA 100.00% 140 VA Total Conn. Load: 235061 VA

Motor 14904 VA 100.00% 14904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

297 A 276 A 275 A

82364 VA 76454 VA 76244 VA

41 SPARE 0 VA 0 VA SPARE 42

39 SPARE 0 VA 0 VA SPARE 40

37 SPARE 0 VA -- SPACE 38

35 0 VA SPD 36

33 34

31 32

29 30

27 28

25 26

23 24900 VA 24

21 24900 VA 22

RTU-NE (1)

24900 VA 20

17 830 VA 16047 VA 18

15 830 VA 16047 VA 16

EF-4 (1)

830 VA 16047 VA

RTU-NW (1)

11 15758 VA 581 VA 12

9 15894 VA 581 VA 10

T-K

21192 VA 581 VA

SF-4 (1)

5 2984 VA 15220 VA 6

3 1121 VA 17136 VA 4

LP-120-01

2086 VA 16804 VA

RP-120-01 (T-120-01)

CKT Circuit Description A B C Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 600 A

Mounting: Surface Wires: 4 Mains Rating: 800 A

Supply From: MDP Phases: 3 Mains Type: MCB

Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: DP1

06/30/2023

(1) OPTION #3. REFER TO DRAWING E-732 FOR PANEL LP-101-01 SCHEDULE.

(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

(3) NON-CONCURRENT LOAD. STANDBY SYSTEM PUMP.

Notes:

LARGE MOTOR 146144 VA 125.00% 182680 VA

KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA

EQUIPMENT 248134 VA 100.00% 248134 VA

Lighting - Exterior 1442 VA 125.00% 1802 VA

RECEPTACLE 65100 VA 100.00% 65100 VA

HVAC 59809 VA 100.00% 59809 VA Total Est. Demand Current: 828 A

LIGHTING 8310 VA 125.00% 10387 VA Total Conn. Current: 792 A

Power 83836 VA 100.00% 83836 VA Total Est. Demand: 688602 VA

Other 279 VA 100.00% 279 VA Total Conn. Load: 658582 VA

Motor 14904 VA 100.00% 14904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 792 A

Total Connected Load 658582 VA

17 SPACE --

16 SPARE 0 VA

15 SPD --

14 HWP-5 (2) 3984 VA

13 HWP-3 (2)(3) 0 VA

12 RTU-SE (2) 62250 VA

11 LP3 (1) 83514 VA

10 EV CHARGER 4 (FUTURE) 26600 VA

9 EV CHARGER 3 (FUTURE) 26600 VA

8 EV CHARGER 2 (FUTURE) 26600 VA

7 EV CHARGER 1 (FUTURE) 26600 VA

6 HWP-2 (2) 6308 VA

5 DP1 235061 VA

4 LP1 2039 VA

3 T-RP1 20240 VA

2 NEH1 130854 VA

1 LSH1 8142 VA

CKT Circuit Description Load

Notes:

Enclosure: Type 1 MCB Rating: 1000 A

Mounting: Floor Mounting Wires: 4 Mains Rating: 1200 A

Supply From: Phases: 3 Mains Type: Main Circuit Breaker

Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 42,000

Switchboard: MDP

(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.

(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH

THE CONTROL RELAY (RIB24P30).

Notes:

Total Est. Demand Current: 3 A

Lighting - Dwelling Unit 270 VA 125.00% 338 VA Total Conn. Current: 2 A

Lighting - Exterior 279 VA 125.00% 349 VA Total Est. Demand: 2514 VA

LIGHTING 1352 VA 125.00% 1690 VA Total Conn. Load: 2039 VA

Other 140 VA 100.00% 140 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 3 A 2 A 3 A

Total Load: 871 VA 483 VA 686 VA

29 30

27 28

25 26

23 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 OUTDOOR LIGHTING (2) 20 A 1 260 VA 47 VA 1 20 A OUTDOOR LIGHTING (2) 14

11 ADMIN LOBBY LIGHTING (1) 20 A 1 118 VA 93 VA 1 20 A CORRIDOR 3 LIGHTING 12

9 MENS REST LIGHTING 20 A 1 84 VA 114 VA 1 20 A MENS SHOWER LIGHTING 10

7 WOMENS SHOWER LIGHTING 20 A 1 114 VA 76 VA 1 20 A WOMENS REST LIGHTING 8

5 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 340 VA 1 20 A PES ROOM LIGHTING 6

3 MAINT STORAGE/OFFICE LIGHTING 20 A 1 60 VA 225 VA 1 20 A BREAK ROOM 146 LIGHTING 4

1 ELECTRICAL AND COMM ROOM LIGHTING 20 A 1 136 VA 238 VA 1 20 A MECHANICAL ROOM LIGHITNG 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: MDP Phases: 3 Mains Type: MLO

Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: LP1

(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.

(2) PROVIDE GFI CIRCUIT BREAKER.

(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS

Notes:

Total Est. Demand Current: 56 A

Total Conn. Current: 56 A

EQUIPMENT 10868 VA 100.00% 10868 VA Total Est. Demand: 20240 VA

RECEPTACLE 6840 VA 100.00% 6840 VA Total Conn. Load: 20240 VA

HVAC 2532 VA 100.00% 2532 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 64 A 60 A 48 A

Total Load: 7438 VA 7029 VA 5773 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 34

31 32

29 30

27 725 VA 28

MENS HAND DRYER (2)(3)(4) 20 A 2

725 VA 725 VA 26

23 PES ROOM RECEPTACLES 20 A 1 720 VA 725 VA

2 20 A WOMENS HAND DRYER (2)(3)(4)

21 MAINT STORAGE/OFFICE RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#2 (2) 22

19 BREAK ROOM RECEPTACLES 20 A 1 720 VA 864 VA 1 20 A GF-1 - CKT-#1 (2) 20

17 ROOF RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A PES ROOM RECEPTACLES 18

15 OUTDOOR RECEPTACLE 20 A 1 360 VA 900 VA 1 20 A RECEPTACLE MECH ROOM 133 16

13 BREAK ROOM TV RECEPTACLE 20 A 1 360 VA 540 VA 1 20 A BREAK ROOM COUNTERTOP RECEPTACLES 14

11 EF-6 & EF-11 20 A 1 728 VA 1600... 1 20 A BOILER #2 12

9 EF-7, EF-8, EF-9, EF-10 20 A 1 960 VA 1500... 1 20 A BREAK ROOM - REF (2) 10

7 WATER FOUNTAIN RECEPTACLE 20 A 1 1200... 1440... 1 20 A VENDING MACHINE 8

5 BREAK ROOM DISPOSAL 20 A 1 500 VA 600 VA 1 20 A UH-5 & UH-6 6

3 SF-3 (2) 20 A 1 100 VA 900 VA 1 20 A WOMENS RESTROOM RECEPTACLES 4

1 UH-7 20 A 1 144 VA 720 VA 1 20 A ADMIN LOBBY RECEPTACLES 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 150 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-RP1 Phases: 3 Mains Type: MCB

Location: COMM 131 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: RP1

(1) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

Notes:

LARGE MOTOR 75096 VA 125.00% 93870 VA

KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA

EQUIPMENT 10340 VA 100.00% 10340 VA

Lighting - Exterior 372 VA 125.00% 465 VA

RECEPTACLE 44760 VA 100.00% 44760 VA Total Est. Demand Current: 295 A

HVAC 56277 VA 100.00% 56277 VA Total Conn. Current: 283 A

LIGHTING 2841 VA 125.00% 3552 VA Total Est. Demand: 245606 VA

Other 140 VA 100.00% 140 VA Total Conn. Load: 235061 VA

Motor 14904 VA 100.00% 14904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

297 A 276 A 275 A

82364 VA 76454 VA 76244 VA

41 SPARE 0 VA 0 VA SPARE 42

39 SPARE 0 VA 0 VA SPARE 40

37 SPARE 0 VA -- SPACE 38

35 0 VA SPD 36

33 34

31 32

29 30

27 28

25 26

23 24900 VA 24

21 24900 VA 22

RTU-NE (1)

24900 VA 20

17 830 VA 16047 VA 18

15 830 VA 16047 VA 16

EF-4 (1)

830 VA 16047 VA

RTU-NW (1)

11 15758 VA 581 VA 12

9 15894 VA 581 VA 10

T-K

21192 VA 581 VA

SF-4 (1)

5 2984 VA 15220 VA 6

3 1121 VA 17136 VA 4

LP-120-01

2086 VA 16804 VA

RP-120-01 (T-120-01)

CKT Circuit Description A B C Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 600 A

Mounting: Surface Wires: 4 Mains Rating: 800 A

Supply From: MDP Phases: 3 Mains Type: MCB

Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: DP1

In c h e s

/2

/4

REV. DATE DESCRIPTION

ISSUE FOR CONSTRUCTION DATE

DESIGNEDSCALE

DRAWING TITLE

DRAWN CHECKED

ORIGINAL SHEET SIZE

PROJECT NUMBER

PROJECT STATUS

SHEET NUMBER

REVISION NO.

www.atkinsglobal.com

Copyright © Atkins Limited (2015)

+1 703 535 3008 +1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040 Alexandria VA 22314

DO NOT SCALE

A ARCHD24X36

ATKINS DESIGN TEAM

ARCHITECTURE, INTERIORS

CIVIL, STRUCTURAL, LANDSCAPE

MECHANICAL, PLUMBING, FIRE PROTECTION

ELECTRICAL, FIRE ALARM

CONSULTANTS

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

G

H

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10

PROFESSIONAL SEAL

A u to d e sk

D o c s:

-M I A

R N

G R e a d in e ss C e n te r/

M

IA

R

N G

G A

A F

R e a d in e s s

C e n te r

E le

O

P T

IO

N

.r vt

/2

/2

:5 :5

P

M

PANEL SCHEDULES

& LIGHTING FIXTURE

SCHEDULE

MIARNG GAAF

READINESS CENTER

LS

06/30/2023

JG SE

86608-260247

TYPE B 100% REVISED FINAL DESIGN

GRAYLING TOWNSHIP,

CRAWFORD COUNTY, MICHIGAN

E-602

(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.

(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH

THE CONTROL RELAY (RIB24P30).

Notes:

Total Est. Demand Current: 9 A

Total Conn. Current: 7 A

Lighting - Exterior 372 VA 125.00% 465 VA Total Est. Demand: 7700 VA

LIGHTING 2841 VA 125.00% 3552 VA Total Conn. Load: 6187 VA

Other 140 VA 100.00% 140 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 8 A 4 A 11 A

Total Load: 2086 VA 1121 VA 2984 VA

29 SPARE 20 A 1 0 VA 240 VA 1 20 A KITCHEN LIGHTING 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 OUTDOOR LIGHTNG (2) 20 A 1 279 VA 0 VA 1 20 A SPARE 26

23 VAULTS LIGHITNG 20 A 1 340 VA 536 VA 1 20 A EOD LUPPLY & OFFICE LIGHTING 24

21 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 408 VA 1 20 A MAINT SUPPLY 120 LIGHTING 22

19 KITCHEN AND PANTRY LIGHTING 20 A 1 34 VA 79 VA 1 20 A ELECT AND COMM ROOMS LIGHTING 20

17 ASSEMBLY HALL LIGHTING 20 A 1 420 VA 420 VA 1 20 A ASSEMBLY HALL LIGHTING 18

15 CORRIDOR LIGHTING 20 A 1 118 VA 121 VA 1 20 A OUTDOOR LIGHTNG (2) 16

13 CLASSROOM 1 LIGHTING 20 A 1 383 VA 419 VA 1 20 A LOBBY LIGHTNG (1) 14

11 CLASSROOM 3 LIGHTING 20 A 1 383 VA 375 VA 1 20 A CLASSROOM 2 LIGHTING 12

9 COMM ROOM 121 LIGHTING 20 A 1 45 VA 23 VA 1 20 A OFFICES 140-142, AND LACTATION RMS LTS 10

7 OFFICES 143, 144, AND, 148 LIGHTING 20 A 1 270 VA 330 VA 1 20 A OFFICES 142, 141, AND 140 LIGHTING 8

5 OFFICES 149 AND 150 LIGHTING 20 A 1 180 VA 120 VA 1 20 A CORRIDOR 4 LIGHITNG 6

3 OFFICES 152, 153, 160, AND, 161 LIGHTING 20 A 1 120 VA 150 VA 1 20 A EOD OFFICE LIGHITNG 4

1 OFFICES 155, 156, 158, AND, 159 LIGHTING 20 A 1 120 VA 180 VA 1 20 A OFFICE 157 LIGHTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: DP1 Phases: 3 Mains Type: MLO

Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: LP2

(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.

(2) PROVIDE GFI RECEPTACLE.

(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

Notes:

Total Est. Demand Current: 137 A

LARGE MOTOR 396 VA 125.00% 495 VA Total Conn. Current: 136 A

EQUIPMENT 1000 VA 100.00% 1000 VA Total Est. Demand: 49259 VA

RECEPTACLE 43860 VA 100.00% 43860 VA Total Conn. Load: 49160 VA

HVAC 3904 VA 100.00% 3904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 142 A 145 A 127 A

Total Load: 16804 VA 17136 VA 15220 VA

83 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 84

81 SPARE 20 A 1 0 VA -- 1 -- SPARE 82

79 SPARE 20 A 1 0 VA 80

77 78

75 76

73 74

71 CUH-1 (2) 20 A 1 100 VA 72

69 EF-5 (2) 20 A 1 396 VA 480 VA 1 20 A SF1 & SF-2 (2) 70

67 EF-12 & EF-2 (2) 20 A 1 768 VA 1056... 1 20 A EF-1 & EF-3 (2) 68

65 OFFICE 149 RECEPTACLES 20 A 1 1080... 1080... 1 20 A CLASSROOM #1 GENERAL RECEPTACLES 66

63 ASSEMBLY HALL RECEPTACLES 20 A 1 1080... 600 VA 1 20 A UH-3 & UH-4 (2) 64

61 CLASSROOM #2 GENERAL RECEPTACLES 20 A 1 1080... 1080... 1 20 A ASSEMBLY HALL RECEPTACLES 62

59 OFFICE 142 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 150 RECEPTACLES 60

57 OFFICE 150 RECEPTACLES 20 A 1 1080... 1080... 1 20 A EOD SUPPLY RECEPTACLES 58

55 CORRIDOR #2 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 149 RECEPTACLES 56

53 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A VAULTS RECEPTACLES 54

51 RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A MENS RESTROOM RECEPTACLES 52

49 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A OFFICE 154 RECEPTACLES 50

47 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #2 FLOOR RECEPTACLES 48

45 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 46

43 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 44

41 OFFICE 143 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 42

39 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 40

37 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 38

35 720 VA 1 20 A OFFICE 149 AND 150 RECEPTACLES 36

33 OFFICE 148 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 34

31 CORRIDOR #1 RECEPTACLES 20 A 1 540 VA 720 VA 1 20 A OFFICE 144 RECEPTACLES 32

29 OFFICE 156 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 152 RECEPTACLES 30

27 KITCHEN GENERAL RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A FAMILY READINESS OFFICE RECEPTACLES 28

25 OFFICE 153 RECEPTACLES 20 A 1 540 VA 26

23 RETENTION OFFICE RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 159 RECEPTACLES 24

21 OFFICE 158 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 155 RECEPTACLES 22

19 OFFICE 160 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 157 RECEPTACLES 20

17 LACTATION AREA RECEPTACLES 20 A 1 180 VA 300 VA 1 20 A HVAC WORKBAY OFFICE 125 18

15 TABLE/CHAIR STORAGE RECEPTACLES 20 A 1 360 VA 540 VA 1 20 A OFFICE 161 RECEPTACLES 16

13 360 VA 1 20 A OFFICE 157 RECEPTACLES 14

11 CLASSROOM #3 GENERAL RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A CLASSROOM #3 GENERAL RECEPTACLES 12

9 CORRIDOR #1 RECEPTACLES 20 A 1 1440... 180 VA 1 20 A LACTATION AREA COUNTERTOP... 10

7 CONTROL TRANSFORMER PANEL 20 A 1 1000... 1200... 1 20 A LACTATION AREA DISHWASHER (2) 8

5 UH-1 & UH-2 (2) 20 A 1 600 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 6

3 EXTERIOR RECEPTACLE 20 A 1 360 VA 1260... 1 20 A ASSEMBLY HALL RECEPTACLES 4

1 JC RECEPTACLE 20 A 1 180 VA 720 VA 1 20 A ASSEMBLY HALL RECEPTACLES 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-RP2 Phases: 3 Mains Type: MCB

Location: COMM 121 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: RP2

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL VOLTAGE LAMP LOAD COMMENTS

A2 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-22-3500L-AOK (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K

A2E 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE CONNECTED

TO GENERATOR

FSC LIGHTING FPB-22-3500L-AOK (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K

A4 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-24-5000L-AOK (5000K) <varies> LED 30 VA <varies>

A4E 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE CONNECTED TO

GENERATOR

FSC LIGHTING FPB-24-5000L-AOK (5000K) <varies> LED 30 VA <varies>

C 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (34W4000K) 277 V LED 34 VA KELVIN TEMP: 5000K

C-H 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (45W4000K) 277 V LED 45 VA KELVIN TEMP: 5000K

CE 1x4 PENDANT LIGHT FIXTURE CONNECTED TO GENERATOR FSC LIGHTING L28548-45W-AOK-S5 (34W5000K) 277 V LED 34 VA KELVIN TEMP: 5000K

CE-H <varies> FSC LIGHTING L25848-45W-AOK-S5 (45W5000K) 277 V LED 45 VA KELVIN TEMP: 5000K

D 4-INCH RECESSED CAN LIGHT WHITE TRIM PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1_LFR-4RDS-T-S 277 V LED 8 VA

DE 4-INCH RECESSED CAN LIGHT WHITE TRIM CONNECTED TO

GENERATOR

PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1_LFR-4RDS-T-S 277 V LED 8 VA

EM EMERGENCY LIGHT FIXTURE BEGHELLI TBD 277 V LED 100 VA

LP8 LINEAR PENDANT 8FT LITECONTROL 3L-P-ID-STD-8-SOF-C1-50K-I045-D045-D01-2C-UNV-FA1-W2 277 V LED 35 VA

LR8 LINEAR RECESSED 8FT LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 21 VA SELECT MOUNTING OPTION BASE ON THE

CEILING TYPE

LR8-E LINEAR RECESSED 8FT CONNECTED TO GENERATOR LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 21 VA SELECT MOUNTING OPTION BASE ON THE

CEILING TYPE

LR12 LINEAR RECESSED 12FT LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 32 VA SELECT MOUNTING OPTION BASE ON THE

CEILING TYPE

LR12-E LINEAR RECESSED 12FT CONNECTED TO GENERATOR LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 32 VA SELECT MOUNTING OPTION BASE ON THE

CEILING TYPE

S 6-INCH SURFACE MOUNTED LIGHT PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL 277 V LED 28 VA

SE 6-INCH SURFACE MOUNTED LIGHT CONNECTED TO

GENERATOR

PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL 277 V LED 28 VA

SL3BC The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.

Current Lighting VP-1-160L-35-4K7-3-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA

SL4 The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.

Current Lighting VP-1-160L-35-4K7-4W-UNV-ASQ-DBT / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA

SL4BC The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.

Current Lighting VP-1-160L-35-4K7-4W-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT

SSS-B-25-40-A-1-B3-DBT

277 V LED 35 VA

SL5 The Viper is an extremely versatile area/site luminaire which blends design, performance, and technology for a variety of applications.

Current Lighting VP-1-160L-50-4K7-5QW / SSS-B-25-40-A-1-B3-DBT 277 V LED 51 VA

W WALLPACK ARCHITECTURAL EGRESS LIGHTING BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC 277 V LED 47 VA

WE WALLPACK ARCHITECTURAL EGRESS LIGHTING CONNECTED TO

GENERATOR

BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC 277 V LED 47 VA

X CEILING MOUNTED EXIT SIGN SIGNIFY ER45VXL 277 V LED 4 VA

X1 WALL MOUNTED EXIT SIGN SIGNIFY ER45VXLW <varies> LED 4 VA

(1) GFI CIRCUIT BREAKER

(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

(3)LOCK-ON CIRCUIT BREAKER.

Notes:

Total Est. Demand Current: 120 A

Total Conn. Current: 147 A

KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA Total Est. Demand: 43149 VA

RECEPTACLE 900 VA 100.00% 900 VA Total Conn. Load: 52844 VA

Motor 14904 VA 100.00% 14904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 177 A 133 A 131 A

Total Load: 21192 VA 15894 VA 15758 VA

41 42

39 40

37 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 GAS RANGE (1)(2) 20 A 1 924 VA 0 VA 30

27 0 VA 28

25 0 VA 4968...

3 20 A GARBAGE DISPOSAL (1)(2)(3)

23 0 VA 0 VA 24

GARBAGE DISPOSAL (1)(2)(3) 20 A 3

4968... 0 VA 22

19 4482... 4968...

3 20 A GARBAGE DISPOSAL (1)(2)

DISWASHER (1)(2)(3) 20 A 2

4482... 5022... 18

15 5022...

2 20 A COFEE MACHINE (1)(2)

13 1250... 0 VA 14

FOOD WARMING CABINET (1)(2)(3) 20 A 2

1250... 2520...

2 20 A ICE MARKER (1)(2)(3)

9 3420... 924 VA 1 20 A CONV OVEN (1)(2) 10

WARMING CABINET (1)(2) 20 A 2

3420... 924 VA 1 20 A CONV OVEN (1)(2) 8

5 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 6

3 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 4

1 COUNTERTOP RECEPTACLE 20 A 1 180 VA 1000... 1 20 A HOOD (1)(2) 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-K Phases: 3 Mains Type: MCB

Location: KITCHEN 117 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: K

06/30/2023

(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSSING.

(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH

THE CONTROL RELAY (RIB24P30).

Notes:

Total Est. Demand Current: 9 A

Total Conn. Current: 7 A

Lighting - Exterior 372 VA 125.00% 465 VA Total Est. Demand: 7700 VA

LIGHTING 2841 VA 125.00% 3552 VA Total Conn. Load: 6187 VA

Other 140 VA 100.00% 140 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 8 A 4 A 11 A

Total Load: 2086 VA 1121 VA 2984 VA

29 SPARE 20 A 1 0 VA 240 VA 1 20 A KITCHEN LIGHTING 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 OUTDOOR LIGHTNG (2) 20 A 1 279 VA 0 VA 1 20 A SPARE 26

23 VAULTS LIGHITNG 20 A 1 340 VA 536 VA 1 20 A EOD LUPPLY & OFFICE LIGHTING 24

21 EXTERIOR POLE LIGHTING (2) 20 A 1 140 VA 408 VA 1 20 A MAINT SUPPLY 120 LIGHTING 22

19 KITCHEN AND PANTRY LIGHTING 20 A 1 34 VA 79 VA 1 20 A ELECT AND COMM ROOMS LIGHTING 20

17 ASSEMBLY HALL LIGHTING 20 A 1 420 VA 420 VA 1 20 A ASSEMBLY HALL LIGHTING 18

15 CORRIDOR LIGHTING 20 A 1 118 VA 121 VA 1 20 A OUTDOOR LIGHTNG (2) 16

13 CLASSROOM 1 LIGHTING 20 A 1 383 VA 419 VA 1 20 A LOBBY LIGHTNG (1) 14

11 CLASSROOM 3 LIGHTING 20 A 1 383 VA 375 VA 1 20 A CLASSROOM 2 LIGHTING 12

9 COMM ROOM 121 LIGHTING 20 A 1 45 VA 23 VA 1 20 A OFFICES 140-142, AND LACTATION RMS LTS 10

7 OFFICES 143, 144, AND, 148 LIGHTING 20 A 1 270 VA 330 VA 1 20 A OFFICES 142, 141, AND 140 LIGHTING 8

5 OFFICES 149 AND 150 LIGHTING 20 A 1 180 VA 120 VA 1 20 A CORRIDOR 4 LIGHITNG 6

3 OFFICES 152, 153, 160, AND, 161 LIGHTING 20 A 1 120 VA 150 VA 1 20 A EOD OFFICE LIGHITNG 4

1 OFFICES 155, 156, 158, AND, 159 LIGHTING 20 A 1 120 VA 180 VA 1 20 A OFFICE 157 LIGHTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: DP1 Phases: 3 Mains Type: MLO

Location: COMM 121 Volts: 480/277 Wye A.I.C. Rating: 22,000

Branch Panel: LP2

(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.

(2) PROVIDE GFI RECEPTACLE.

(3) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

Notes:

Total Est. Demand Current: 137 A

LARGE MOTOR 396 VA 125.00% 495 VA Total Conn. Current: 136 A

EQUIPMENT 1000 VA 100.00% 1000 VA Total Est. Demand: 49259 VA

RECEPTACLE 43860 VA 100.00% 43860 VA Total Conn. Load: 49160 VA

HVAC 3904 VA 100.00% 3904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 142 A 145 A 127 A

Total Load: 16804 VA 17136 VA 15220 VA

83 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 84

81 SPARE 20 A 1 0 VA -- 1 -- SPARE 82

79 SPARE 20 A 1 0 VA 80

77 78

75 76

73 74

71 CUH-1 (2) 20 A 1 100 VA 72

69 EF-5 (2) 20 A 1 396 VA 480 VA 1 20 A SF1 & SF-2 (2) 70

67 EF-12 & EF-2 (2) 20 A 1 768 VA 1056... 1 20 A EF-1 & EF-3 (2) 68

65 OFFICE 149 RECEPTACLES 20 A 1 1080... 1080... 1 20 A CLASSROOM #1 GENERAL RECEPTACLES 66

63 ASSEMBLY HALL RECEPTACLES 20 A 1 1080... 600 VA 1 20 A UH-3 & UH-4 (2) 64

61 CLASSROOM #2 GENERAL RECEPTACLES 20 A 1 1080... 1080... 1 20 A ASSEMBLY HALL RECEPTACLES 62

59 OFFICE 142 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 150 RECEPTACLES 60

57 OFFICE 150 RECEPTACLES 20 A 1 1080... 1080... 1 20 A EOD SUPPLY RECEPTACLES 58

55 CORRIDOR #2 RECEPTACLES 20 A 1 900 VA 1080... 1 20 A OFFICE 149 RECEPTACLES 56

53 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A VAULTS RECEPTACLES 54

51 RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A MENS RESTROOM RECEPTACLES 52

49 CLASSROOM #1 FLOOR RECEPTACLES 20 A 1 720 VA 900 VA 1 20 A OFFICE 154 RECEPTACLES 50

47 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #2 FLOOR RECEPTACLES 48

45 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 46

43 CLASSROOM #2 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 44

41 OFFICE 143 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 42

39 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 40

37 CLASSROOM #3 FLOOR RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 38

35 720 VA 1 20 A OFFICE 149 AND 150 RECEPTACLES 36

33 OFFICE 148 RECEPTACLES 20 A 1 720 VA 720 VA 1 20 A CLASSROOM #3 FLOOR RECEPTACLES 34

31 CORRIDOR #1 RECEPTACLES 20 A 1 540 VA 720 VA 1 20 A OFFICE 144 RECEPTACLES 32

29 OFFICE 156 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 152 RECEPTACLES 30

27 KITCHEN GENERAL RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A FAMILY READINESS OFFICE RECEPTACLES 28

25 OFFICE 153 RECEPTACLES 20 A 1 540 VA 26

23 RETENTION OFFICE RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 159 RECEPTACLES 24

21 OFFICE 158 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 155 RECEPTACLES 22

19 OFFICE 160 RECEPTACLES 20 A 1 540 VA 540 VA 1 20 A OFFICE 157 RECEPTACLES 20

17 LACTATION AREA RECEPTACLES 20 A 1 180 VA 300 VA 1 20 A HVAC WORKBAY OFFICE 125 18

15 TABLE/CHAIR STORAGE RECEPTACLES 20 A 1 360 VA 540 VA 1 20 A OFFICE 161 RECEPTACLES 16

13 360 VA 1 20 A OFFICE 157 RECEPTACLES 14

11 CLASSROOM #3 GENERAL RECEPTACLES 20 A 1 900 VA 900 VA 1 20 A CLASSROOM #3 GENERAL RECEPTACLES 12

9 CORRIDOR #1 RECEPTACLES 20 A 1 1440... 180 VA 1 20 A LACTATION AREA COUNTERTOP... 10

7 CONTROL TRANSFORMER PANEL 20 A 1 1000... 1200... 1 20 A LACTATION AREA DISHWASHER (2) 8

5 UH-1 & UH-2 (2) 20 A 1 600 VA 720 VA 1 20 A CLASSROOM #1 FLOOR RECEPTACLES 6

3 EXTERIOR RECEPTACLE 20 A 1 360 VA 1260... 1 20 A ASSEMBLY HALL RECEPTACLES 4

1 JC RECEPTACLE 20 A 1 180 VA 720 VA 1 20 A ASSEMBLY HALL RECEPTACLES 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-RP2 Phases: 3 Mains Type: MCB

Location: COMM 121 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: RP2

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL VOLTAGE LAMP LOAD COMMENTS

A2 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-22-3500L-AOK (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K

A2E 2X2 GRID MOUNTED RECESSED LIGHT FIXTURE WITH BATTERY BACKUP

OPTION

FSC LIGHTING FPB-22-3500L-AOK EM10W (5000K) 277 V LED 20 VA KELVIN TEMP: 5000K

A4 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE FSC LIGHTING FPB-24-5000L-AOK (5000K) 277 V LED 30 VA KELVIN TEMP: 5000K

A4E 2X4 GRID MOUNTED RECESSED LIGHT FIXTURE WITH BATTERY BACKUP

OPTION

FSC LIGHTING FPB-24-5000L-AOK EM10W (5000K) 277 V LED 30 VA KELVIN TEMP: 5000K

C 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (34W4000K) 277 V LED 34 VA KELVIN TEMP: 5000K

C-H 1x4 PENDANT LIGHT FIXTURE FSC LIGHTING L28548-45W-AOK-S5 (45W4000K) 277 V LED 45 VA KELVIN TEMP: 5000K

CE 1x4 PENDANT LIGHT FIXTURE WITH BATTERY BACKUP OPTION FSC LIGHTING L28548-45W-AOK-S5 EM10W (34W5000K) 277 V LED 34 VA KELVIN TEMP: 5000K

CE-H 1x4 PENDANT LIGHT FIXTURE WITH BATTERY BACKUP OPTION FSC LIGHTING L25848-45W-AOK-S5 EM10W (45W5000K) 277 V LED 45 VA KELVIN TEMP: 5000K

D 4-INCH RECESSED CAN LIGHT WHITE TRIM PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1_LFR-4RDS-T-S 277 V LED 8 VA

DE 4-INCH RECESSED CAN LIGHT WHITE TRIM WITH BATTERY BACKUP

OPTION

PRESCOLITE LFR-4RDS-M-10L50K8WD-DM1-EMR_LFR-4RDS-T-S 277 V LED 8 VA

EM EMERGENCY LIGHT FIXTURE BEGHELLI TBD 277 V LED 100 VA

LP8 LINEAR PENDANT 8FT LITECONTROL 3L-P-ID-STD-8-SOF-C1-50K-I045-D045-D01-2C-UNV-FA1-W2 277 V LED 35 VA

LR8 LINEAR RECESSED 8FT LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 21 VA SELECT MOUNTING OPTION BASE

ON THE CEILING TYPE

LR8-E LINEAR RECESSED 8FT WITH BATTERY BACKUP OPTION LITECONTROL 3L-R-D-8-SOF-C1-50K-D030-D01-1C-UNV-EF 277 V LED 21 VA SELECT MOUNTING OPTION BASE

ON THE CEILING TYPE

LR12 LINEAR RECESSED 12FT LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV 277 V LED 32 VA SELECT MOUNTING OPTION BASE

ON THE CEILING TYPE

LR12-E LINEAR RECESSED 12FT WITH BATTERY BACKUP OPTION LITECONTROL 3L-R-D-12-SOF-C1-50K-D030-D01-1C-UNV-EF 277 V LED 32 VA SELECT MOUNTING OPTION BASE

ON THE CEILING TYPE

S 6-INCH SURFACE MOUNTED LIGHT PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL 277 V LED 28 VA

SE 6-INCH SURFACE MOUNTED LIGHT WITH BATTERY BACKUP OPTION PRESCOLITE LTC-6RD-P-25L50K8MD-DM1-S-BL-EM 277 V LED 28 VA

SL3BC AREA POLE LIGHT CURRENT

LIGHTING

VP-1-160L-35-4K7-3-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA

SL4 AREA POLE LIGHT CURRENT

LIGHTING

VP-1-160L-35-4K7-4W-UNV-ASQ-DBT / SSS-B-25-40-A-1-B3-DBT 277 V LED 35 VA

SL4BC AREA POLE LIGHT CURRENT

LIGHTING

VP-1-160L-35-4K7-4W-UNV-ASQ-DBT-BC / SSS-B-25-40-A-1-B3-DBT

SSS-B-25-40-A-1-B3-DBT

277 V LED 35 VA

SL5 AREA POLE LIGHT CURRENT

LIGHTING

VP-1-160L-50-4K7-5QW / SSS-B-25-40-A-1-B3-DBT 277 V LED 51 VA

W WALLPACK ARCHITECTURAL EGRESS LIGHTING BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC 277 V LED 47 VA

WE WALLPACK ARCHITECTURAL EGRESS LIGHTING WITH BATTERY BACKUP

OPTION

BEACON RWL1-48L-45-5K7-4W-UNV-DBT-PC-E 277 V LED 47 VA

X CEILING MOUNTED EXIT SIGN SIGNIFY ER45VXL 277 V LED 4 VA

X1 WALL MOUNTED EXIT SIGN SIGNIFY ER45VXLW 277 V LED 4 VA

(1) GFI CIRCUIT BREAKER

(2) ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION, SPECIFICATIONS, AND REQUIREMENTS PRIOR ROUGH-IN. EQUIPMENT OVERCURRENT PROTECTION SHALL BE

DONE IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

(3)LOCK-ON CIRCUIT BREAKER.

Notes:

Total Est. Demand Current: 120 A

Total Conn. Current: 147 A

KITCHEN APPLIANCES 27700 VA 65.00% 18005 VA Total Est. Demand: 43149 VA

RECEPTACLE 900 VA 100.00% 900 VA Total Conn. Load: 52844 VA

Motor 14904 VA 100.00% 14904 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 177 A 133 A 131 A

Total Load: 21192 VA 15894 VA 15758 VA

41 42

39 40

37 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 GAS RANGE (1)(2) 20 A 1 924 VA 0 VA 30

27 0 VA 28

25 0 VA 4968...

3 20 A GARBAGE DISPOSAL (1)(2)(3)

23 0 VA 0 VA 24

GARBAGE DISPOSAL (1)(2)(3) 20 A 3

4968... 0 VA 22

19 4482... 4968...

3 20 A GARBAGE DISPOSAL (1)(2)

DISWASHER (1)(2)(3) 20 A 2

4482... 5022... 18

15 5022...

2 20 A COFEE MACHINE (1)(2)

13 1250... 0 VA 14

FOOD WARMING CABINET (1)(2)(3) 20 A 2

1250... 2520...

2 20 A ICE MARKER (1)(2)(3)

9 3420... 924 VA 1 20 A CONV OVEN (1)(2) 10

WARMING CABINET (1)(2) 20 A 2

3420... 924 VA 1 20 A CONV OVEN (1)(2) 8

5 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 6

3 KITCHEN GEN RECEPTACLE 20 A 1 360 VA 1200... 1 20 A REFRIGERATOR (1)(2) 4

1 COUNTERTOP RECEPTACLE 20 A 1 180 VA 1000... 1 20 A HOOD (1)(2) 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: T-K Phases: 3 Mains Type: MCB

Location: KITCHEN 117 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: K

In c h e s

/2

/4

REV. DATE DESCRIPTION

ISSUE FOR CONSTRUCTION DATE

DESIGNEDSCALE

DRAWING TITLE

DRAWN CHECKED

ORIGINAL SHEET SIZE

PROJECT NUMBER

PROJECT STATUS

SHEET NUMBER

REVISION NO.

www.atkinsglobal.com

Copyright © Atkins Limited (2015)

+1 703 535 3008 +1 703 535 1031

Tel:

Fax:

2318 Mill Road Suite 1040 Alexandria VA 22314

DO NOT SCALE

A ARCHD24X36

ATKINS DESIGN TEAM

ARCHITECTURE, INTERIORS

CIVIL, STRUCTURAL, LANDSCAPE

MECHANICAL, PLUMBING, FIRE PROTECTION

ELECTRICAL, FIRE ALARM

CONSULTANTS

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

G

H

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10

PROFESSIONAL SEAL

A u to d e sk

D o c s:

-M I A

R N

G R e a d in e ss C e n te r/

M

IA

R

N G

G A

A F

R e a d in e s s

C e n te r

E le

O

P T

IO

N

.r vt

/2

/2

:5 :5

P

M

LIFE SAFETY PANEL

SCHEDULES

MIARNG GAAF

READINESS CENTER

LS

06/30/2023

JG SE

86608-260247

TYPE B 100% REVISED FINAL DESIGN

GRAYLING TOWNSHIP,

CRAWFORD COUNTY, MICHIGAN

E-603

(1) THROUGH A TIMER SWITCH TO AUTOMATIC TURN OFF LIGHITNG AFTER 20 MINUTES OF CLOSING.

(2) CONTROL THE OUTDOOR LIGHTS THROUGH A PHOTOCELL CONNECTED TO THE DDC SYSTEM OF THE BUILDING. THE LIGHTS WILL BE CONNECTED TO THE DDC SYSTEM THROUGH

THE CONTROL RELAY (RIB24P30).

Notes:

Total Est. Demand Current: 11 A

Total Conn. Current: 10 A

EQUIPMENT 3000 VA 100.00% 3000 VA Total Est. Demand: 9440 VA

Lighting - Exterior 791 VA 125.00% 988 VA Total Conn. Load: 8142 VA

LIGHTING 4123 VA 125.00% 5153 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 8 A 14 A 8 A

Total Load: 2181 VA 3824 VA 2161 VA

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 0 VA 872 VA 14

11 1000... 854 VA 12

T-LSL1 50 A 3

2000... 1080...

3 50 A LSH2

7 WORKBAY GENERAL LIGHTING 20 A 1 385 VA 476 VA 1 20 A WORKBAYS GENERAL LIGHTING 8

5 ADMIN LOBBY 146 (1) 20 A 1 139 VA 186 VA 1 20 A WORKBAY EXTERIOR LIGHTING (2) 6

3 OUTDOOR LIGHTING (2) 20 A 1 260 VA 518 VA 1 20 A ELEC, COMM, MECH, STOR. RMS LIGHTING 4

1 OUTDOOR LIGHTING (2) 20 A 1 93 VA 356 VA 1 20 A WOMENS, MENS, PES, BREAK RMS. LIGHTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 70 A

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: Phases: 3 Mains Type: MCB

Location: COMM 131 Volts: 480/277 Wye A.I.C. Rating: 10,000

Branch Panel: LSH1

(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.

Notes:

Total Est. Demand Current: 8 A

Total Conn. Current: 8 A

Total Est. Demand: 3000 VA

Total Conn. Load: 3000 VA

EQUIPMENT 3000 VA 100.00% 3000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 18 A 10 A 0 A

Total Load: 2000 VA 1000 VA 0 VA

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 0 VA 0 VA 1 20 A SPARE 6

3 500 VA 500 VA 1 20 A LOC ADMIN LOBBY (1) 4

LSL2 50 A 3

1000... 1000... 1 20 A FACP (1) 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 100 A

Mounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: T-LSL1 Phases: 3 Mains Type: MCB

Location: COMM 131 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LSL1

(1) LOCK-ON CIRCUIT BREAKER. PROVIDE RED IDENTIFICATION TO THE CIRCUIT BREAKER IN A WAY THAT DOES NOT OBSTRUCT MANUFACTURER'S MARKINGS.

Notes:

Total Est. Demand Current: 4 A

Total Conn. Current: 4 A

Total Est. Demand: 1500 VA

Total Conn. Load: 1500 VA

EQUIPMENT 1500 VA 100.00% 1500 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 9 A 5 A 0 A

Total Load: 1000 VA 500 VA 0 VA

23 SPACE -- 1 -- -- 1 -- SPACE 24

21 SPACE -- 1 -- -- 1 -- SPACE 22

19 SPACE -- 1 -- -- 1 -- SPACE 20

17 SPACE -- 1 -- -- 1 -- SPACE 18

15 SPACE -- 1 -- -- 1 -- SPACE 16

13 SPACE -- 1 -- -- 1 -- SPACE 14

11 SPACE -- 1 -- -- 1 -- SPACE 12

9 SPACE -- 1 -- -- 1 -- SPACE 10

7 SPACE -- 1 -- -- 1 -- SPACE 8

5 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 LOC MAIN LOBBY (1) 20 A 1 500 VA 0 VA 1 20 A SPARE 4

1 IDS VAULT 112 20 A 1 500 VA 500 VA 1 20 A IDS VAULT 110 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 50 A