SELFRIDGE_REPAIR_NW_SEWER_RFI_1.pdf
PDF 190 KB Posted
- Attached to
- Repair NW Gravity Sewer Line
- Solicitation number
- W912JB-19-B-5001
About this file
RFI Document
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SELFRIDGE REPAIR NW SEWER
W912JB-19-B-5001
RFI’S
1. Can Govt. provide soil borings in the area where new sanitary line to be installed?
Please see the Specification Book developed for the project.
1.04 SITE CONDITIONS
Soil borings were made during the design of this project at locations identified on the Drawings. The logs of the borings and soil data for this project are provided to the CONTRACTOR. Interpretation of all data and reports for construction purposes is the responsibility of the CONTRACTOR.
Please see the ATTACHMENTS Section for soil boring information
2. In absence soil borings, what would contractor base their bid on regarding dewatering, excavation bracing, and other excavation related issues?
Please see the Specification Book developed for the project.
3. Materials Submittals AF66 file indicate we need to provide CCTV Inspection. Is this for the existing system? Please clarify what you need CCTV for?
Please see the Specification Book developed for the project.
ARTICLE 4 – TESTING AND ACCEPTANCE – Page S-7
The Contractor shall provide for Closed Circuit Television (CCTV) inspection, in accordance with
The General Requirements, of all sanitary sewers Constructed.
File details come from the government source that posted it.