AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Purpose for this Modif ication is to:
1. Incorporate Addendum 02 dated 3 April 2012.
2. Extend Closing date to 24 April 2012 at 2:00:00PM (HST)
1. CONTRACT ID CODE PAGE OF PAGES
J 1 8
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 09-Apr-2012
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912J6-12-R-0002
X 9B. DATED (SEE ITEM 11)
28-Feb-2012
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
09-Apr-2012
CODE
USPFO FOR HAWAII
CPT MANUEL LLANES
91-1179 ENTERPRISE AVE
KAPOLEI HI 96707-2150
W912J6 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912J6-12-R-0002
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
HIARNG Kalaeloa Readiness Center (RC) W90FY-Q-09-D-0006-9N02 Kalaeloa, Hawaii PN 150043 Addendum 002 03 April 2012 Page 1
ADDENDUM 02
ADDENDUM 002
03 April 2012
This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents, Amendment No. 1, and Addendum 001 as noted below. Acknowledge receipt of this Addendum in the space provided in the Bid Form. Failure to do so may subject Bidder to disqualification.
This Amendment consists of 5 pages including all attachments noted herein.
MODIFICATIONS TO ELECTRONIC FILES:
1) Bookmarks have been added to the electronic files for the following Sections that were missing bookmarks:
a. Section 08 36 13 – SECTIONAL DOORS
b. Section 21 13 13 – WET PIPE SPRINKLER SYSTEMS
c. Section 26 09 36.19 - STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS
2) Note Section 21 13 13 -WET PIPE SPRINKLER SYSTEMS issued in Addendum 001 was in-cluded in the electronic document, but not bookmarked. No changes were made to this Section.
3) Section 26 09 36.19 - STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS was missing page 1, but this has been corrected with the addition of the electronic bookmark. This section is also included in this Addendum.
MODIFICATIONS TO SPECIFICATIONS:
1) Revised specification section issued: a. Section 26 09 36.19 - STANDALONE MULTIPRESET
MODULAR DIMMING CONTROLS
ATTACHMENTS:
1) Revised specification Section 26 09 36.19 - STANDALONE MULTIPRESET MODULAR
DIMMING CONTROLS
END OF ADDENDUM 002HIARNG Kalaeloa Readiness Center (RC) W90FY-Q-09-D-0006-9N02 Kalaeloa, Hawaii PN 150043 Final Submittal STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS 18 November 2011 260936.19 - 1
SECTION 260936.19 - STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Wall-box multiscene dimming controls.
1.3 DEFINITIONS
A. Fade Rate: The time it takes each zone to arrive at the next scene, dependent on the degree of change in lighting level.
B. Low Voltage: As defined in NFPA 70, the term for circuits and equipment operating at less than 50 V or for remote-control, signaling, and power-limited circuits.
C. Scene: The lighting effect created by adjusting several zones of lighting to the desired intensity.
D. SCR: Silicon-controlled rectifier.
E. Zone: A fixture or group of fixtures controlled simultaneously as a single entity. Also known as a "channel."
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. For modular dimming controls; include elevation, dimensions, features, characteristics, ratings, and labels.
2. Device plates and plate color and material.
3. Ballasts and lamp combinations compatible with dimmers.
B. Shop Drawings:
1. Include diagrams for power, signal, and control wiring.HIARNG Kalaeloa Readiness Center (RC) W90FY-Q-09-D-0006-9N02 Kalaeloa, Hawaii PN 150043 Final Submittal STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS 18 November 2011 260936.19 - 2
1.5 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
PART 2 - PRODUCTS
2.1 GENERAL DIMMING DEVICE REQUIREMENTS
A. Compatibility:
1. Dimming control components shall be compatible with lighting fixtures, ballasts, and transformers.
B. Dimmers and Dimmer Modules: Comply with UL 508.
1. Audible Noise and Radio-Frequency Interference Suppression: Solid-state dimmers shall operate smoothly over their operating ranges without audible lamp or dimmer noise or radio-frequency interference. Modules shall include integral or external filters to suppress audible noise and radio-frequency interference.
2. Dimmer or Dimmer-Module Rating: Not less than 125 percent of connected load unless otherwise indicated.
C. Surge Protection: Withstand supply power surges without impairment to performance.
1. Panels: 6000 V, 3000 A, complying with IEEE C62.41.1 and IEEE C62.41.2.
2. Other System Devices: 6000 V, 3000 A, complying with IEEE C62.41.1 and IEEE C62.41.2.
D. Off Control Position: User-selected off position of any control point shall disconnect the load from line supply.
2.2 SYSTEM DESCRIPTION
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Comply with NFPA 70.
2.3 WALL-BOX MULTISCENE DIMMING CONTROLS
A. Description: Factory-fabricated equipment providing manual dimming consisting of a wall-box-mounted master controller and indicated number of wall-box zone stations. Controls and dimmers shall be integrated for mounting in multigang wall box under a single wall plate. Each zone shall be adjustable to indicated number of scenes, which shall reside in the memory of zone controller.HIARNG Kalaeloa Readiness Center (RC) W90FY-Q-09-D-0006-9N02 Kalaeloa, Hawaii PN 150043 Final Submittal STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS 18 November 2011 260936.19 -
B. Each zone shall be configurable to control the following loads:
1. Fluorescent lamps with electronic ballasts.
2. LED lamps.
3. Non-dim, on-off switching only.
C. Dimmers: Regulate voltages to maintain a constant light level, with no visible flicker, when the source voltage varies plus or minus 2 percent rms.
D. Memory:
1. Retain preset scenes and fade rates through momentary (up to 3-second) power interruptions.
2. Retain preset scenes through power failures for at least seven days.
E. Device Plates: Style, material, and color shall comply with Section 262726 "Wiring Devices." Master-control cover plate shall be one piece.
F. Master controller shall include the following:
1. Cover-mounted switches, including master off, all bright, and selectors for each scene.
2. Cover-mounted LED indicator lights, one associated with each scene switch, and one for the master off switch.
3. Concealed switches and indicators for specified function.
4. A raise/lower switch for each zone for temporary adjustments of the zone, without altering scene values stored in memory.
5. Fade time indicated by digital display for current scene while fading.
6. Cover-mounted infrared receiver.
G. Infrared Transmitters: Wireless remote control for recalling four of the presets. Operate up to 50 feet within line of sight of the master controller.
2.4 CONDUCTORS AND CABLES
A. Wiring to Supply Side of Remote-Control Power Sources: Not smaller than No. 12 AWG. Comply with requirements in Section 260519 "Low-Voltage Electrical Power Conductors and Cables."
B. Class 2 Control Cable: Multiconductor cable with stranded-copper conductors not smaller than No. 18 AWG. Comply with requirements in Section 260519 "Low-Voltage Electrical Power Conductors and Cables."
PART 3 - EXECUTION
3.1 WIRING INSTALLATION
A. Comply with NECA 1.HIARNG Kalaeloa Readiness Center (RC) W90FY-Q-09-D-0006-9N02 Kalaeloa, Hawaii PN 150043 Final Submittal STANDALONE MULTIPRESET MODULAR DIMMING CONTROLS 18 November 2011 260936.19 - 4
B. Wiring Method: Comply with requirements in Section 260519 "Low-Voltage Electrical Power Conductors and Cables."
C. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points. Separate power-limited and nonpower-limited conductors according to conductor manufacturer's written instructions.
D. Size conductors according to lighting control device manufacturer's written instructions unless otherwise indicated.
E. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.
3.2 IDENTIFICATION
A. Comply with requirements in Section 260553 "Identification for Electrical Systems" for identifying components and power and control wiring.
B. Label each dimmer module with a unique designation.
C. Label each scene control button with approved scene description.
3.3 FIELD QUALITY CONTROL
A. Perform the following tests and inspections:
1. Continuity tests of circuits.
2. Operational Test: Set and operate controls to demonstrate their functions and capabilities in a methodical sequence that cues and reproduces actual operating functions.
a. Include testing of modular dimming control equipment under conditions that simulate actual operational conditions. Record control settings, operations, cues, and functional observations.
B. Remove and replace malfunctioning modular dimming control components and retest as specified above.
C. Test Labeling: After satisfactory completion of tests and inspections, apply a label to tested components indicating test results, date, and responsible agency and representative.
D. Reports: Written reports of tests and observations. Record defective materials and workmanship and unsatisfactory test results. Record repairs and adjustments.
3.4 DEMONSTRATION
A. Train Government’s maintenance personnel to adjust, operate, and maintain modular dimming controls.
END OF SECTION 260936.19
SECTION 00010 - SOLICITATION CONTRACT FORM
The required response date/time has changed from 18-Apr-2012 02:00 PM to 24-Apr-2012 02:00 PM.
(End of Summary of Changes)