AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The reason for this modif ication is to incorporate Addendum 01 dated 30 march 2012.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 30
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 09-Apr-2012
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912J6-12-R-0002
X 9B. DATED (SEE ITEM 11)
28-Feb-2012
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
09-Apr-2012
CODE
USPFO FOR HAWAII
CPT MANUEL LLANES
91-1179 ENTERPRISE AVE
KAPOLEI HI 96707-2150
W912J6 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912J6-12-R-0002
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
ADDENDUM 01
ADDENDUM 001
30 March 2012
This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and Amendment No. 1 as noted below. Acknowledge receipt of this Addendum in the space provided in the Bid Form. Failure to do so may subject Bidder to disqualification.
This Amendment consists of 24 pages including all attachments noted herein.
MODIFICATIONS TO SOLICITATION:
1) Solicitation Document W912J6-12-R-0002_BDE_RC_Phase#1.pdf a. Revise paragraph 2.2.1.3.2. to read: “Proposal adequately discusses approach and time-line for commissioning.”
b. Paragraph 2.2.1.3.2. sentence reading: “Use of an independent, qualified commissioning agent/firm may receive additional consideration.” is deleted from the solicitation.
MODIFICATIONS TO SPECIFICATIONS:
1) New specification section issued: a. Section 21 13 13 – WET PIPE SPRINKLER SYSTEMS
MODIFICATIONS TO DRAWINGS:
ARCHITECTURAL
1) SHEET A-101A – FIRST FLOOR PLAN – SECTOR A
SHEET A-101B – FIRST FLOOR PLAN – SECTOR B
SHEET A-102A – SECOND FLOOR PLAN – SECTOR B
SHEET A-102B – SECOND FLOOR PLAN – SECTOR B
a. Keynotes List, Keynote 24 – Delete OBI #5 reference and associated bubble.
ATTACHMENTS:
1) New specification section: a. Section 21 13 13 – WET PIPE SPRINKLER SYSTEMS
END OF ADDENDUM 001
SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
B. Related Sections:
Section 013520 LEED COMPLIANCE AND DOCUMENTATION
Section 017700 CLOSEOUT PROCEDURES AND DD 1354
Section 017823 OPERATION AND MAINTENANCE DATA
Section 018200 DEMONSTRATION AND TRAINING
Section 019113 GENERAL COMMISSIONING REQUIREMENTS
Section 078413 PENETRATION FIRESTOPPING
Section 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
Section 283111 COMBINED DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM AND MASS NOTIFICATION
SYSTEM
Section 330501 WATER DISTRIBUTION
C. References: The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)
ASSE 1015 Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies (2009) - (ANSI approved 2010)
AMERICAN WATER WORKS ASSOCIATION (AWWA)
AWWA C110/A21.10 Ductile-Iron and Gray-Iron Fittings for Water (2008)
WWA C550 Protective Epoxy Interior Coatings for Valves and Hydrants (2005)
AWWA C606 Grooved and Shouldered Joints (2006)
ASME INTERNATIONAL (ASME)
ASME B1.20.1 Pipe Threads, General Purpose (Inch) (1983; R 2006)
ASME B16.1 Gray Iron Threaded Fittings; Classes 25, 125 and 250 (2010)
ASME B16.4 Standard for Gray Iron Threaded Fittings; Classes 125 and 250 (2006)
ASME B16.5 Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24 Metric/Inch Standard (2007)
ASME B16.9 Standard for Factory-Made Wrought Steel Butt welding Fittings (2007)
ANSI/ASME B18.2.1 Square and Hex Bolts and Screws - Inch Series (1996; R2005)
ASME B31.9 Building Services Piping Section Committee (2008)
AMERICAN SOCIETY OF CIVIL ENGINEERS / STRUCTURAL ENGINEERING INSTITUTE
ASCE/SEI 7-05 Minimum Design Loads for Buildings and Other Structures
ASTM INTERNATIONAL (ASTM)
ASTM A183 Standard Specification for Carbon Steel Track Bolts and Nuts (2003; R 2009)
ASTM A234 / A234M Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service (2011)
ASTM A47/A47M Standard Specification for Ferritic Malleable Iron Castings (1999; R 2009)
ASTM A53/A53M Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless (2010)
ASTM A536 Standard Specification for Ductile Iron Castings (1984; R 2009)
ASTM A563 Standard Specification for Carbon and Alloy Steel Nuts (2007a)
ASTM A563M Standard Specification for Carbon and Alloy Steel Nuts (Metric) (2007)
ASTM A733 - Standard Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples (2003; R 2009 e1)
ASTM A856 / A856M Standard Specification for Zinc-5% Aluminum-Mischmetal Alloy-Coated Carbon Steel Wire (2003; R 2009)
DEPARTMENT of DEFENSE - UNIFIED FACILITIES CRITERIA (UFC)
UFC 3-600-01 Fire Protection Engineering for Facilities (26 September 2006; Change 1, 14 July 2009)
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/ http://www.approvalguide.com/�
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 13 Standard for the Installation of Sprinkler Systems (2010; Errata 10-1; TIA 10-1)
NFPA 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances (2010)
NFPA 70® National Electrical Code® (2011)
NFPA 291 Recommended Practice for Fire Flow Testing and Marking of Hydrants (2010)
NFPA 1963 Standard for Fire Hose Connections (2009; Errata 09-1)
NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES
(NICET)
NICET 1014-7 Program Detail Manual for Certification in the Field of Fire Protection Engineering Technology (Field Code 003) Subfield of Automatic Sprinkler System Layout (2003)
UNDERWRITERS LABORATORIES (UL)
UL Bld Mat Dir (2011) Building Materials Directory
UL Fire Prot Dir (2011) Fire Protection Equipment Directory
1.2 SUMMARY
A. Section Includes:
1. Pipes, fittings, and specialties.
2. Fire-protection valves.
3. Fire-department connections.
4. Sprinklers.
5. Alarm devices.
6. Pressure gages.
B. LEED: The work of this section contributes to the following credits, IEQ CR 3.2 and IEQ CR 4.1. Refer to Section 013520, “LEED Compliance and Documentation” for LEED submittals and compliance.
1. Some LEED requirements may already be listed herein but that does not relieve the Contractor of meeting the requirements of Section 013520, “LEED Compliance And Documentation”. Any conflicts arise between this section and Section 013520, Section 013520 shall take precedence.
1.3 DEFINITIONS
A. High-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure higher than standard 175 psig, but not higher than 250 psig.
B. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum.
1.4 SYSTEM DESCRIPTIONS
A. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. Hose connections are included if indicated.
1.5 PERFORMANCE REQUIREMENTS
A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.
B. Delegated Design: Design and provide piping offsets, fittings, and any other accessories as required to provide a complete installation and to eliminate interference with other construction. Install sprinkler system over and under ducts, piping and platforms when such equipment can negatively affect or disrupt the sprinkler discharge pattern and coverage. Provide wet pipe sprinkler system in all areas of the building. In addition to the requirements of the contract documents, the system shall be designed and installed in accordance with the requirements of UFC 3-600-01, NFPA 13, and NFPA 24. Pipe sizes which are not indicated on drawings shall be determined by hydraulic calculation. Design any portions of the sprinkler system that are not indicated on the drawings including locating sprinklers, piping and equipment, and size piping and equipment when this information is not indicated on the drawings or is not specified herein. The design of the sprinkler system shall be based on hydraulic calculations, and the other provisions specified herein and on the construction documents.
C. Design and provide sprinkler system(s), including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
1. Available fire-hydrant flow test records indicate the following conditions at the point of connection of the building service to the existing water main is shown on the drawings. Contractor shall conduct water flow tests, in accordance with the procedures contained in NFPA 291, to determine available water supply for the water-based fire extinguishing systems.
D. Sprinkler system design shall be approved by authorities having jurisdiction.
1. Margin of Safety for Available Water Flow and Pressure: 10 percent or 5 psi, including losses through water-service piping, valves, and backflow preventers.
2. Sprinkler Occupancy Hazard Classifications:
a. As shown on drawings.
3. Minimum Density for Automatic-Sprinkler Piping Design:
a. As shown on drawings.
4. Maximum Protection Area per Sprinkler: Minimum of UL listing or as noted on the drawings.
5. Total Combined Hose-Stream Demand Requirement:
a. As shown on drawings.
E. Seismic Performance: Sprinkler piping shall withstand the effects of earthquake motions determined according to NFPA 13 and ASCE/SEI 7.
1.6 SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
B. LEED Submittal:
1. Product Data for Credit EQ 4.1: For solvent cements and adhesive primers, including printed statement of VOC content and chemical components.
C. Shop Drawings: Working plans, prepared according to NFPA 13, including hydraulic calculations if applicable. For wet-pipe sprinkler systems, include plans, elevations, sections, details, and attachments to other work.
1. Working drawings shall be stamped and signed by the Fire Protection Engineer.
D. Record Documents: At Project Closeout, provide working drawings and hydraulic calculations corrected to reflect as installed condition. Provide CAD and hydraulic analysis data files used by respective programs to generate shop drawings and calculations submittal documents. Documents shall be provided in paper and electronic format. Provide copies of printed documents in PDF format. Copies of electronic file shall be provided in CD disk or flash drive format.
E. Delegated-Design Submittal: For sprinkler systems indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the Fire Protection Engineer.
F. Coordination Drawings: Sprinkler systems, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Domestic water piping.
2. Compressed air piping.
3. HVAC hydronic piping.
4. Items penetrating finished ceiling include the following:
a. Lighting fixtures.
b. Air outlets and inlets.
c. Paging speakers.
G. Qualification Data: For qualified Installer, Fire Protection Specialist, and Fire Protection Engineer.
H. Welding certificates.
I. Fire-hydrant flow test report.
J. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping."
K. Field quality-control reports.
L. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals.
1.7 QUALITY ASSURANCE
A. Fire Protection Specialist:
1. Perform work specified in this section under the supervision of and certified by the Fire Protection Specialist who is an individual registered professional engineer who has passed the fire protection engineering written examination administered by the National Council of Examiners for Engineering and Surveys (NCEES) in a related engineering discipline with a minimum of 5 years experience, dedicated to fire protection engineering that can be verified with documentation or who is certified as a Level III Technician by National Institute for Certification in Engineering Technologies (NICET) in the Automatic Sprinkler System Layout subfield of Fire Protection Engineering Technology in accordance with NICET 1014-7. Submit the name and documentation of certification of the proposed Fire Protection Specialists, no later than 14 days after the Notice to Proceed and prior to the submittal of the sprinkler system drawings and hydraulic calculations. The Fire Protection Specialist shall prepare and submit a list of the fire protection related submittals, no later than 7 days after the approval of the Fire Protection Specialist, from the Contract Submittal Register that relate to the successful installation of the sprinkler systems(s). The submittals identified on this list shall be accompanied by a letter of approval signed and dated by the Fire Protection Specialist when submitted to the Government. The Fire Protection Specialist shall be regularly engaged in the design and installation of the type and complexity of system specified in the contract documents, and shall have served in a similar capacity for at least three systems that have performed in the manner intended for a period of not less than 6 months.
2. Responsibilities include designing sprinkler systems and installation oversight under the supervision of the Fire Protection Engineer.
B. Fire Protection Engineer
1. Supervise and stamp work performed by the Fire Protection Specialist. A Registered Fire Protection Engineer is an individual registered professional engineer who has passed the fire protection engineering written examination administered by the National Council of Examiners for Engineering and Surveys (NCEES) in a related engineering discipline with a minimum of 5 years experience, dedicated to fire protection engineering that can be verified with documentation. Submit the name and documentation of certification of the proposed Fire Protection Engineer, no later than 14 days after the Notice to Proceed and prior to the submittal of the sprinkler system drawings and hydraulic calculations. The submittals identified on this list shall be accompanied by a letter of approval signed and dated by the Fire Protection Engineer when submitted to the Government.
2. Responsibilities include providing professional engineering services needed to assume engineering responsibility.
a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer.
3. The Fire Protection Engineer may also be the Fire Protection Specialist.
C. Installer Qualifications:
1. Work specified in this section shall be performed by the Sprinkler System Installer who is regularly engaged in the installation of the type and complexity of system specified in the contract documents, and who has served in a similar capacity for at least three systems that have performed in the manner intended for a period of not less than 6 months. Submit the name and documentation of certification of the proposed Sprinkler System Installer, concurrent with submittal of the Fire Protection Specialist Qualifications.
D. Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code.
E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
F. NFPA Standards: Sprinkler system equipment, specialties, accessories, installation, and testing shall comply with the following:
1. NFPA 13, "Installation of Sprinkler Systems."
2. NFPA 24, "Installation of Private Fire Service Mains and Their Appurtenances."
1.8 COORDINATION
A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including but not limited to light fixtures, HVAC equipment, and partition assemblies.
1.9 EXTRA MATERIALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Sprinkler Cabinets: Finished, wall-mounted, steel cabinet(s) with hinged cover, and with space for minimum of six spare sprinklers plus sprinkler wrench. Include number of sprinklers required by NFPA 13 and sprinkler wrench. Include separate cabinet with sprinklers and wrench for each type of sprinkler used on Project.
PART 2 - PRODUCTS
2.1 PIPING MATERIALS
A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, and fitting materials, and for joining methods for specific services, service locations, and pipe sizes.
2.2 STEEL PIPE AND FITTINGS
A. Standard Weight, Black-Steel Pipe: ASTM A 53/A 53M, Type E, Grade B. Pipe ends may be factory or field formed to match joining method.
B. Galvanized and Black-Steel Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M, standard-weight, seamless steel pipe with threaded ends.
C. Galvanized and Uncoated, Steel Couplings: ASTM A 865, threaded.
D. Galvanized and Uncoated, Gray-Iron Threaded Fittings: ASME B16.4, Class 125, standard pattern.
E. Malleable- or Ductile-Iron Unions: UL 860.
F. Cast-Iron Flanges: ASME 16.1, Class 125.
G. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150.
H. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9.
I. Grooved-Joint, Steel-Pipe Appurtenances:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Anvil International, Inc.
b. Corcoran Piping System Co.
c. National Fittings, Inc.
d. Shurjoint Piping Products.
e. Tyco Fire & Building Products LP.
f. Victaulic Company.
2. Pressure Rating: 175 psig minimum.
3. Grooved-End Fittings for Steel Piping: ASTM A 47/A 47M, malleable-iron casting or ASTM A 536, ductile-iron casting; with dimensions matching steel pipe. Nuts and bolts shall beheat-treated steel conforming to ASTM A 183 and shall be cadmium plated orzinc electroplated
4. Grooved-End-Pipe Couplings for Steel Piping: AWWA C606 and UL 213, rigid pattern, unless otherwise indicated, for steel-pipe dimensions. Include ferrous housing sections, EPDM-rubber gasket, and bolts and nuts.
http://www.specagent.com/LookUp/?ulid=1431&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802326&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802327&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802328&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802329&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802330&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802331&mf=04&src=wd�
2.3 PIPING JOINING MATERIALS
A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick or ASME B16.21, nonmetallic and asbestos free.
1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges: Full-face gaskets.
2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges: Ring-type gaskets.
B. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated.
C. Welding Filler Metals: Comply with AWS D10.12M/D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.
2.4 LISTED FIRE-PROTECTION VALVES
A. General Requirements:
1. Valves shall be UL listed or FM approved.
2. Minimum Pressure Rating for Standard-Pressure Piping: 175 psig.
B. Ball Valves:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. Anvil International, Inc.
b. Victaulic Company.
2. Standard: UL 1091 except with ball instead of disc.
3. Valves NPS 1-1/2 and Smaller: Bronze body with threaded ends.
4. Valves NPS 2 and NPS 2-1/2: Bronze body with threaded ends or ductile-iron body with grooved ends.
5. Valves NPS 3: Ductile-iron body with grooved ends.
C. Check Valves:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. AFAC Inc.
b. American Cast Iron Pipe Company; Waterous Company Subsidiary.
c. Anvil International, Inc.
d. Clow Valve Company; a division of McWane, Inc.
e. Crane Co.; Crane Valve Group; Crane Valves.
f. Crane Co.; Crane Valve Group; Jenkins Valves.
g. Crane Co.; Crane Valve Group; Stockham Division.
h. Fire-End & Croker Corporation.
i. Fire Protection Products, Inc.
http://www.specagent.com/LookUp/?ulid=1439&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802338&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802339&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1444&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802351&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456816899&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802352&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817253&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817256&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817258&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817260&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802353&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802354&mf=04&src=wd�
j. Fivalco Inc.
k. Globe Fire Sprinkler Corporation.
l. Groeniger & Company.
m. Kennedy Valve; a division of McWane, Inc.
n. Matco-Norca.
o. Metraflex, Inc.
p. Milwaukee Valve Company.
q. Mueller Co.; Water Products Division.
r. NIBCO INC.
s. Potter Roemer.
t. Reliable Automatic Sprinkler Co., Inc.
u. Shurjoint Piping Products.
v. Tyco Fire & Building Products LP.
w. United Brass Works, Inc.
x. Venus Fire Protection Ltd.
y. Victaulic Company.
z. Viking Corporation.
aa. Watts Water Technologies, Inc.
2. Standard: UL 312.
3. Pressure Rating: 250 psig minimum.
4. Type: Swing check.
5. Body Material: Cast iron.
6. End Connections: Flanged or grooved.
D. Bronze OS&Y Gate Valves:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. Crane Co.; Crane Valve Group; Crane Valves.
b. Crane Co.; Crane Valve Group; Stockham Division.
c. Milwaukee Valve Company.
d. NIBCO INC.
e. United Brass Works, Inc.
2. Standard: UL 262.
3. Pressure Rating: 175 psig.
4. Body Material: Bronze.
5. End Connections: Threaded.
E. Iron OS&Y Gate Valves:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. American Cast Iron Pipe Company; Waterous Company Subsidiary.
b. American Valve, Inc.
c. Clow Valve Company; a division of McWane, Inc.
d. Crane Co.; Crane Valve Group; Crane Valves.
http://www.specagent.com/LookUp/?uid=123456802355&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802356&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802357&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817262&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802358&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802359&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802360&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817264&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802361&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802362&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802363&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802364&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802366&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802367&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802368&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802369&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802370&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802371&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1445&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817265&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817267&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802372&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802373&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802374&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1446&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817268&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802375&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817269&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817272&mf=04&src=wd�
e. Crane Co.; Crane Valve Group; Jenkins Valves.
http://www.specagent.com/LookUp/?uid=123456817275&mf=04&src=wd�
f. Crane Co.; Crane Valve Group; Stockham Division.
g. Hammond Valve.
h. Milwaukee Valve Company.
i. Mueller Co.; Water Products Division.
j. NIBCO INC.
k. Shurjoint Piping Products.
l. Tyco Fire & Building Products LP.
m. United Brass Works, Inc.
n. Watts Water Technologies, Inc.
2. Standard: UL 262.
3. Pressure Rating: 250 psig minimum.
4. Body Material: Cast or ductile iron.
5. End Connections: Flanged or grooved.
2.5 TRIM AND DRAIN VALVES
A. General Requirements:
1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
2. Pressure Rating: 175 psig minimum.
B. Angle Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fire Protection Products, Inc.
b. United Brass Works, Inc.
C. Ball Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Affiliated Distributors.
b. Anvil International, Inc.
c. Barnett.
d. Conbraco Industries, Inc.; Apollo Valves.
e. Fire-End & Croker Corporation.
f. Fire Protection Products, Inc.
g. Flowserve.
h. FNW.
i. Jomar International, Ltd.
j. Kennedy Valve; a division of McWane, Inc.
k. Kitz Corporation.
l. Legend Valve.
http://www.specagent.com/LookUp/?uid=123456817279&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802376&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802377&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817281&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802378&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802379&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802380&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802381&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802382&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1452&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802397&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802398&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1453&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802399&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802400&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802401&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817310&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802402&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802403&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802404&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802405&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802406&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817311&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802407&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802408&mf=04&src=wd�
m. Metso Automation USA Inc.
n. Milwaukee Valve Company.
o. NIBCO INC.
p. Potter Roemer.
q. Red-White Valve Corporation.
r. Southern Manufacturing Group.
s. Stewart, M. A. and Sons Ltd.
t. Tyco Fire & Building Products LP.
u. Victaulic Company.
v. Watts Water Technologies, Inc.
D. Globe Valves:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fire Protection Products, Inc.
b. United Brass Works, Inc.
2.6 SPECIALTY VALVES
A. General Requirements:
1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
2. Pressure Rating:
a. Standard-Pressure Piping Specialty Valves: 175 psig minimum.
3. Body Material: Cast or ductile iron.
4. Size: Same as connected piping.
5. End Connections: Flanged or grooved.
B. Riser Check Valves:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. AFAC Inc.
b. Globe Fire Sprinkler Corporation.
c. Reliable Automatic Sprinkler Co., Inc.
d. Tyco Fire & Building Products LP.
e. Venus Fire Protection Ltd.
f. Victaulic Company.
g. Viking Corporation.
2. Standard: UL 312
3. Design: For horizontal or vertical installation.
4. Include trim sets for drain and pressure gages.
http://www.specagent.com/LookUp/?uid=123456802409&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802410&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802411&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802413&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802414&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802415&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817312&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802416&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802417&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802418&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1455&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802419&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802420&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1458&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802422&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802423&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802424&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802425&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802426&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802427&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802428&mf=04&src=wd�
5. Pressure Rating: 250 psig minimum.
6. Type: Swing check.
7. Body Material: Cast iron.
8. End Connections: Flanged or grooved.
9.
C. Automatic (Ball Drip) Drain Valves:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. AFAC Inc.
b. Reliable Automatic Sprinkler Co., Inc.
c. Tyco Fire & Building Products LP.
2. Standard: UL 1726.
3. Pressure Rating: 175 psig minimum.
4. Type: Automatic draining, ball check.
5. Size: NPS 3/4.
6. End Connections: Threaded.
2.7 FIRE-DEPARTMENT CONNECTIONS
A. Exposed-Type, Fire-Department Connection:
1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
a. AFAC Inc.
b. Elkhart Brass Mfg. Company, Inc.
c. Fire-End & Croker Corporation.
d. Fire Protection Products, Inc.
e. GMR International Equipment Corporation.
f. Guardian Fire Equipment, Inc.
g. Tyco Fire & Building Products LP.
h. Wilson & Cousins Inc.
2. Standard: UL 405.
3. Type: Exposed, projecting, for wall mounting.
4. Pressure Rating: 175 psig minimum.
5. Body Material: Corrosion-resistant metal.
6. Inlets: Brass with threads according to NFPA 1963 and matching local fire-department sizes and threads.
Include extension pipe nipples, brass lugged swivel connections, and check devices or clappers.
7. Caps: Brass, lugged type, with gasket and chain.
8. Escutcheon Plate: Round, brass, wall type.
9. Outlet: Back, with pipe threads.
10. Number of Inlets: Two. Size 2 1/2”.
http://www.specagent.com/LookUp/?ulid=1460&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802439&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802440&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802441&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1462&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802442&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802443&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802444&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802445&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802446&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802447&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802448&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802449&mf=04&src=wd�
11. Escutcheon Plate Marking: Similar to “AUTO SPKR."
12. Finish: Rough brass or bronze or Rough chrome plated.
13. Outlet Size: 4”.
2.8 SPRINKLER SPECIALTY PIPE FITTINGS
A. Branch Outlet Fittings:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Anvil International, Inc.
b. National Fittings, Inc.
c. Shurjoint Piping Products.
d. Tyco Fire & Building Products LP.
e. Victaulic Company.
2. Standard: UL 213.
3. Pressure Rating: 175 psig minimum.
4. Body Material: Ductile-iron housing with EPDM seals and bolts and nuts.
5. Type: Mechanical-T and -cross fittings.
6. Configurations: Snap-on and strapless, ductile-iron housing with branch outlets.
7. Size: Of dimension to fit onto sprinkler main and with outlet connections as required to match connected branch piping.
8. Branch Outlets: Grooved, plain-end pipe, or threaded.
B. Flow Detection and Test Assemblies:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. AGF Manufacturing Inc.
b. Reliable Automatic Sprinkler Co., Inc.
c. Tyco Fire & Building Products LP.
d. Victaulic Company.
2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
3. Pressure Rating: 175 psig minimum.
4. Body Material: Cast- or ductile-iron housing with orifice, sight glass, and integral test valve.
5. Size: Same as connected piping.
6. Inlet and Outlet: Threaded.
http://www.specagent.com/LookUp/?ulid=1466&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802462&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802463&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802464&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802465&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802466&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1467&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802467&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802468&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802469&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802470&mf=04&src=wd�
C. Branch Line Testers:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Elkhart Brass Mfg. Company, Inc.
b. Fire-End & Croker Corporation.
c. Potter Roemer.
2. Standard: UL 199.
3. Pressure Rating: 175 psig.
4. Body Material: Brass.
5. Size: Same as connected piping.
6. Inlet: Threaded.
7. Drain Outlet: Threaded and capped.
8. Branch Outlet: Threaded, for sprinkler.
D. Sprinkler Inspector's Test Fittings:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. AGF Manufacturing Inc.
b. Triple R Specialty.
c. Tyco Fire & Building Products LP.
d. Victaulic Company.
e. Viking Corporation.
2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
3. Pressure Rating: 175 psig minimum.
4. Body Material: Cast- or ductile-iron housing with sight glass.
5. Size: Same as connected piping.
6. Inlet and Outlet: Threaded.
2.9 DOUBLE-CHECK VALVE BACKFLOW PREVENTION ASSEMBLY
A. Double-Check, Backflow-Prevention Assemblies:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Ames Fire & Waterworks; a division of Watts Regulator Co.
b. Conbraco Industries, Inc.
c. FEBCO; SPX Valves & Controls.
d. Flomatic Corporation.
e. Watts Water Technologies, Inc.
f. Wilkins; a Zurn company.
http://www.specagent.com/LookUp/?ulid=1468&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802471&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802472&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802473&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1469&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802474&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802475&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802476&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802477&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802478&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456822786&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456808668&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456822791&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456808669&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456808670&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456822794&mf=04&src=wd�
2. Standard: ASSE 1015.
3. Operation: Continuous-pressure applications, unless otherwise indicated.
4. Pressure Rating: 175 psig minimum.
5. Pressure Loss: 6 psig maximum, through middle 1/3 of flow range.
6. Size: 6” NPS.
7. Body: cast iron with interior lining complying with AWWA C550 or that is FDA approved.
8. End Connections: Flanged.
9. Configuration: Designed for vertical, straight through flow.
10. Accessories: OS&Y gate valves with flanged ends on inlet and outlet.
2.10 SPRINKLERS
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
1. AFAC Inc.
2. Globe Fire Sprinkler Corporation.
3. Reliable Automatic Sprinkler Co., Inc.
4. Tyco Fire & Building Products LP.
5. Venus Fire Protection Ltd.
6. Victaulic Company.
7. Viking Corporation.
B. General Requirements:
1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.
2. Pressure Rating for Automatic Sprinklers: 175 psig minimum.
C. Automatic Sprinklers with Heat-Responsive Element:
1. Provide standard spray, QR, concealed sprinklers in all areas with ceilings.
2. Provide standard spray, QR, upright sprinklers in all exposed areas.
3. Characteristics: Nominal 1/2-inch orifice with Discharge Coefficient K of 5.6, and for "Ordinary" temperature classification rating unless otherwise indicated or required by application.
D. Sprinkler Finishes:
1. Concealed Sprinklers:
a. Drop ceilings – Provide factory painted “pure white” (SW 7005) to match ceiling tiles.
b. Wood ceilings – Provide gloss black cover plates in all wood ceilings.
http://www.specagent.com/LookUp/?ulid=1473&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802484&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802485&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802486&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802487&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802488&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802489&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802490&mf=04&src=wd�
2. Upright Sprinklers
a. Exposed areas – Provide chrome uprights in all exposed areas.
E. Special Coatings:
1. Corrosion-resistant paint.
F. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications.
Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.
1. Ceiling Mounting: Chrome-plated steel, two piece, with 1-inch vertical adjustment or Plastic, white finish, one piece, flat.
2. Sidewall Mounting: Chrome-plated steel, one piece, flat.
G. Sprinkler Guards:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Reliable Automatic Sprinkler Co., Inc.
b. Tyco Fire & Building Products LP.
c. Victaulic Company.
d. Viking Corporation.
2. Standard: UL 199.
3. Type: Wire cage with fastening device for attaching to sprinkler.
2.11 ALARM DEVICES
A. Alarm-device types shall match piping and equipment connections.
B. Electrically Operated Alarm Bell:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fire-Lite Alarms, Inc.; a Honeywell company.
b. Notifier; a Honeywell company.
c. Potter Electric Signal Company.
2. Standard: UL 464.
3. Type: Vibrating, metal alarm bell.
4. Size: 6-inch minimum- diameter.
5. Finish: Red-enamel factory finish, suitable for outdoor use.
C. Water-Flow Indicators:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
http://www.specagent.com/LookUp/?ulid=1474&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802491&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802492&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802493&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802494&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1477&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817315&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817318&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802499&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1479&mf=04&src=wd�
a. ADT Security Services, Inc.
b. McDonnell & Miller; ITT Industries.
c. Potter Electric Signal Company.
d. System Sensor; a Honeywell company.
e. Viking Corporation.
f. Watts Industries (Canada) Inc.
2. Standard: UL 346.
3. Water-Flow Detector: Electrically supervised.
4. Components: Two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends signal if removed.
5. Type: Paddle operated.
6. Pressure Rating: 250 psig.
7. Design Installation: Horizontal or vertical.
D. Valve Supervisory Switches:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Fire-Lite Alarms, Inc.; a Honeywell company.
b. Kennedy Valve; a division of McWane, Inc.
c. Potter Electric Signal Company.
d. System Sensor; a Honeywell company.
2. Standard: UL 346.
3. Type: Electrically supervised.
4. Components: Single-pole, double-throw switch with normally closed contacts.
5. Design: Signals that controlled valve is in other than fully open position.
2.12 PRESSURE GAGES
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
1. AMETEK; U.S. Gauge Division.
2. Ashcroft, Inc.
3. Brecco Corporation.
4. WIKA Instrument Corporation.
B. Standard: UL 393.
C. Dial Size: 3-1/2- to 4-1/2-inch diameter.
D. Pressure Gage Range: 0 to 250 psig minimum.
http://www.specagent.com/LookUp/?uid=123456802500&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817319&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802501&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817322&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802502&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802503&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1482&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817326&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817327&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802511&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817328&mf=04&src=wd� http://www.specagent.com/LookUp/?ulid=1485&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456817332&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802513&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802514&mf=04&src=wd� http://www.specagent.com/LookUp/?uid=123456802515&mf=04&src=wd�
E. Water System Piping Gage: Include "WATER" or "AIR/WATER" label on dial face.
F. Air System Piping Gage: Include "AIR" or "AIR/WATER" label on dial face.
PART 3 - EXECUTION
3.1 PREPARATION
A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design calculations required in "Quality Assurance" Article.
B. Report test results promptly and in writing.
3.2 SERVICE-ENTRANCE PIPING
A. Connect sprinkler piping to water-service piping for service entrance to building. Comply with requirements for exterior piping in Section 330501 “Water Distribution”.
B. Install shutoff valve, backflow preventer, pressure gage, drain, and other accessories indicated at connection to water-service piping.
3.3 PIPING INSTALLATION
A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical.
1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans.
B. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13.
C. Install seismic restraints on piping. Comply with requirements for seismic-restraint device materials and installation in NFPA 13. Reference structural documents for additional seismic design data.
D. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes.
E. Install unions adjacent to each valve in pipes NPS 2 and smaller.
F. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections.
G. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, and sized and located according to NFPA 13.
H. Install sprinkler piping with drains for complete system drainage.
I. Install sprinkler control valves, test assemblies, and drain risers…