This is a solicitation for a firm fixed price construction contract to replace Kinnick High School located at Commander Fleet Activities in Yokosuka, Japan. The project includes construction of a new four story, 14,700 square meter high school building with classrooms, labs, and support spaces. Additional work involves athletic field improvements at the adjacent Briggs Bay site including play courts, fields, fencing and a 280 square meter field house. The estimated value is between 10 to 25 billion Japanese Yen. The period of performance is 47 months. Electronic proposals are due prior to a mandatory pre-proposal teleconference and site visit. The contract will be awarded using lowest price technically acceptable procedures to a local Japanese contractor licensed for this type of construction work.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Replace Kinnick High School CFA Yokosuka, Japan

PA00109

Final Design RTA

AM-0001 SECTION 01 20 00 Page 2

PART 1 GENERAL

1.1 GENERAL

SECTION 01 20 00

PRICE AND PAYMENT PROCEDURES

Payment items for the work of this Contract for which payments shall be made are listed in the CONTRACT LINE ITEM NUMBER (CLIN) SCHEDULE and described below. All costs for items of work, which are not specifically mentioned to be included in a particular job or unit price payment item, are included in the listed job item most closely associated with the work involved. The price and payment made for each item listed constitutes full compensation for furnishing all plant, labor, materials, and equipment, and performing any associated Contractor quality control, environmental protection, meeting safety requirements, tests and reports, topographic surveys, cost of bond premiums, and for performing all work required by drawings and specifications for which separate payment is not otherwise provided. Work paid for under one item shall not be paid for under any other item.No separate payment shall be made for the work, services, or operations required by the Contractor, as specified in DIVISION 01, GENERAL REQUIREMENTS, to complete the project in accordance with these specifications; all costs thereof shall be considered as incidental to the work.

1.2 Submittals

Government approval is required for submittals with a "G" designation;

DESIGN-BID-BUILD:submittals not haveing a "G" designation are for information only; DESIGN-BUILD: submittals not having a "G" designation are for Contractor Quality Control or Designer of Record appproval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-07 Certificates

Bill Of Lading; G

1.3 LINE ITEMS

1.3.1 CLIN 0001, Replace Kinnick High School(BASE)

1.3.1.1 Payment

Payment shall be made at the Contract job price for CLIN 0001 "Replace Kinnick High School (BASE)" for work completed including, but not limited to construction of the four (4) story Kinnick High School building.

Construction of supporting systems, construction of athletic fields at Briggs Bay, Demolition of Existing Buildings 1396 and 4375, and Demolition of Existing Building 3382. Payment for work completed shall constitute full compensation of CLIN 0001, complete.

1.3.1.2 Unit of Measure

Unit of measure: job.

Replace Kinnick High School CFA Yokosuka, Japan

PA00109

Final Design RTA

AM-0001 SECTION 01 20 00 Page 3

1.3.2 CLIN 0002, Construct New Field House (OPTION 1)

Payment shall be made at the Contract job price for CLIN 0002 "Construct New Field House (OPTION 1)" for work completed including, but not limited to, construction of a new one(1) story field house at Briggs Bay. Payment for work completed shall constitute full compenstation of CLIN 0002, complete.

1.3.2.1 Unit of Measure

Unit of measure: job.

PART 2 PRODUCTS (NOT USED)

PART 3 EXECUTION

3.1 PROGRESS PAYMENT INVOICE

Requests for payment shall be submitted in accordance with Federal Acquisition Regulations (FAR) Subpart 32.9, entitled "PROMPT PAYMENT", and Paragraphs 52.232-5 and 52.232-27, entitled "Payments Under Fixed-Price Construction Contracts", and "Prompt Payment for Construction Contracts", respectively. In addition each request shall be submitted in the number of copies and to the designated billing office as shown in the Contract.

When submitting payment requests, the Contractor shall complete Blocks 1 through 12 of the "PROGRESS PAYMENT INVOICE" Form as directed by the Contracting Officer (provided in RMS CM). The completed form shall then become the cover document to which all other support data shall be attached.

One additional copy of the entire request for payment, to include the "PROGRESS PAYMENT INVOICE" cover document, shall be forwarded to a separate address as designated by the Contracting Officer.

The Contractor shall submit with each pay request, a list of subcontractors that have worked during that pay period. The listing shall be broken down into weeks, identifying each subcontractor that has worked during a particular week, and indicate the total number of employees that have worked on site for each subcontractor for each week. The prime Contractor shall also indicate the total number of employees for its on site staff for each week.

Formal invoices shall be submitted every month between the first and the tenth of the month. Any invoice received after the tenth will be considered as not meeting the contract requirements and rejected. It may be resubmitted on the first of the following month.

3.2 TRANSPORTATION OF SUPPLIES BY SEA, BILL OF LADING

The Contractor shall, within 30 days after each shipment covered by Defense Federal Acquisition Regulation (DFAR) Subpart 252.247-7023, provide the Contracting Officer and the Maritime Administration (MARAD) one copy of the rated on board vessel operating carrier's ocean Bill of Lading. See DFAR 252.247-7023 for information required in the bill of lading. MARAD contact information: usarmy.scott.sddc.mbx.g3-ffw-team@mail.mil and msc.n101.ffw@navy.mil.

mailto:usarmy.scott.sddc.mbx.g3-ffw-team@mail.mil mailto:msc.n101.ffw@navy.mil

Replace Kinnick High School PA00109 CFA Yokosuka, Japan Final Design RTA

SECTION TABLE OF CONTENTS

DIVISION 26 - ELECTRICAL

SECTION 26 51 00

INTERIOR LIGHTING

05/16

PART 1 GENERAL

1.1 REFERENCES

1.2 RELATED REQUIREMENTS

1.3 DEFINITIONS

1.4 SUBMITTALS

1.5 QUALITY CONTROL

1.5.1 Luminaire Drawings

1.5.2 Occupancy/Vacancy Sensor Coverage Layout

1.5.3 LED Driver and Dimming Switch Compatibility Certificate

1.5.4 Luminaire Design Data

1.5.5 LED Luminaire - IES LM-79 Test Report

1.5.6 LED Light Source - IES LM-80 Test Report

1.5.7 LED Light Source - IES TM-21 Test Report

1.5.8 Occupancy/Vacancy Sensor Verification Tests

1.5.9 Test Laboratories

1.5.10 Regulatory Requirements

1.5.11 Standard Products

1.5.11.1 Alternative Qualifications

1.5.11.2 Material and Equipment Manufacturing Date

1.5.11.3 Energy Efficiency

1.6 WARRANTY

1.6.1 LED Luminaire Warranty

1.6.1.1 Provide Luminaire Useful Life Certificate

PART 2 PRODUCTS

2.1 PRODUCT COORDINATION

2.2 LUMINAIRES

2.2.1 LED Luminaires

2.3 DRIVERS

2.3.1 LED Drivers

2.4 LIGHT SOURCES

2.4.1 LED Light Sources

2.5 LIGHTING CONTROLS

2.5.1 Toggle Switches

2.5.2 Dimming Controllers (Dimmers)

2.5.3 Sensors for Lighting Control

2.5.3.1 Occupancy Sensors

2.5.3.1.1 Passive Infrared (PIR) Sensors

2.5.3.1.2 Ultrasonic Sensors

2.5.3.1.3 Dual Technology Sensors

2.5.3.1.4 High/Low-Bay Sensors

2.5.3.1.5 Power Packs for Sensors

2.5.3.2 Vacancy Sensors

2.5.4 Light Level Sensor

SECTION 26 51 00 Page 1 AM-0001

2.5.5 Lighting Control Station

2.5.6 Lighting Control System Hub

2.5.7 Lighting Control System Ethernet Switch

2.5.7.1 General

2.5.7.2 Software

2.5.7.3 Ports

2.5.8 Window Shade Power Supply

2.5.9 Lighting Control Module

2.5.9.1 0-10V Module

2.5.9.2 Digital Addressable Module

2.5.10 Power Interfaces

2.5.10.1 Switching Power Module

2.5.10.2 Phase-Adaptive Power Module

2.5.11 Low Voltage Control Interfaces

2.5.11.1 Contact Closure Interface

2.5.11.2 DMX Interface

2.5.11.3 Sensor Module

2.5.11.4 Emergency Lighting Interface

2.5.12 Power Panels

2.5.12.1 Dimming Panels

2.5.12.2 Branch Circuit Protection

2.5.12.3 Branch Circuit Breakers

2.5.13 DMX Enclosure

2.5.14 Performance Space - Lighting Control System

2.5.14.1 Ethernet Switch

2.5.14.2 Performance and House Lighting Control Stations

2.5.14.3 Performance Space - Architectural Lighting Control

Processing System

2.5.15 Performance Lighting Relay Panel

2.5.15.1 Intelligent Breaker System

2.5.15.2 DMX Controlled Relay Distribution Mini Panele

2.5.16 Local Area Lighting Controller

2.6 EXIT AND EMERGENCY LIGHTING EQUIPMENT

2.6.1 Exit Signs

2.6.1.1 LED Self-Powered Exit Signs

2.6.2 LED Emergency Drivers

2.6.3 Self-Diagnostic Circuitry for LED Emergency Drivers/Ballasts

2.6.4 Central Emergency Lighting System

2.6.4.1 System Operation

2.6.4.2 Battery Charger

2.6.4.3 Batteries

2.6.4.4 Enclosure

2.6.4.5 Accessories

2.7 LUMINAIRE SUPPORT HARDWARE

2.7.1 Wire

2.7.2 Wire for Humid Spaces

2.7.3 Threaded Rods

2.7.4 Straps

2.8 EQUIPMENT IDENTIFICATION

2.8.1 Manufacturer's Nameplate

2.8.2 Labels

2.9 FACTORY APPLIED FINISH

2.10 RECESS- AND FLUSH-MOUNTED LUMINAIRES

2.11 SUSPENDED LUMINAIRES

2.12 MOTORIZED HOIST SYSTEM

PART 3 EXECUTION

3.1 INSTALLATION

SECTION 26 51 00 Page 2 AM-0001

3.1.1 Light Sources

3.1.2 Luminaires

3.1.3 Suspended Luminaires

3.1.4 Ballasts, Generators and Power Supplies

3.1.5 Exit Signs and Emergency Lighting Units

3.1.5.1 Emergency Lighting from Central Emergency System

3.1.6 Photocell Switch Aiming

3.1.7 Occupancy/Vacancy Sensors

3.1.8 Daylight or Ambient Light Level Sensor

3.1.9 Lighting Control Systems

3.2 SERVICE AND SUPPORT

3.2.1 Startup and Programming

3.2.1.1 First Visit

3.2.1.2 Second Visit

3.2.1.3 Third Visit

3.2.1.4 Startup

3.3 Training of Customer's Representatives

3.4 FIELD APPLIED PAINTING

-- End of Section Table of Contents --

SECTION 26 51 00 Page 3 AM-0001

SECTION 26 51 00

INTERIOR LIGHTING

05/16

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING

ENGINEERS (ASHRAE)

ASHRAE 189.1 (2014) Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings

ASHRAE 90.1 - IP (2016; ERTA 1-8 2017; INT 1-5 2017) Energy Standard for Buildings Except Low-Rise Residential Buildings

ASTM INTERNATIONAL (ASTM)

ASTM A1008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable

ASTM A580/A580M (2016) Standard Specification for Stainless Steel Wire

ASTM A641/A641M (2009a; R 2014) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire

ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM B633 (2015) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel

ASTM D4674 REV A (2002; R 2010) Standard Practice for Accelerated Testing for Color Stability of Plastics Exposed to Indoor Office Environments

CALIFORNIA ENERGY COMMISSION (CEC)

CEC Title 24 (2008; Effective Jan 2010) California's Energy Efficiency Standards for

SECTION 26 51 00 Page 4 AM-0001

Residential and Nonresidential Buildings

ILLUMINATING ENGINEERING SOCIETY (IES)

IES HB-10 (2011; Errata 2015) IES Lighting Handbook

IES LM-79 (2008) Electrical and Photometric Measurements of Solid-State Lighting Products

IES LM-80 (2015) Measuring Lumen Maintenance of LED Light Sources

IES RP-16 (2010; Addendum A 2008; Addenda B 2009;

Addendum C 2016) Nomenclature and Definitions for Illuminating Engineering

IES TM-21 (2011; Addendum B 2015) Projecting Long Term Lumen Maintenance of LED Light Sources

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms

IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code

IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits

JAPANESE INDUSTRIAL STANDARDS (JIS)

JIS C 8304 (1950, R2009) Small Switches for Indoor Use

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)

NEMA ANSLG C78.377 (2017) Electric Lamps— Specifications for the Chromaticity of Solid State Lighting Products

NEMA C82.77 (2002) Harmonic Emission Limits - Related Power Quality Requirements for Lighting Equipment

NEMA SSL 1 (2010) Electronic Drivers for Led Devices, Arrays, or Systems

NEMA SSL 3 (2011) High-Power White LED Binning for General Illumination

NEMA SSL 7A (2015) Phase-Cut Dimming for Solid State Lighting: Basic Compatibility

NEMA WD 1 (1999; R 2015) Standard for General Color

SECTION 26 51 00 Page 5 AM-0001

Requirements for Wiring Devices

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 101 (2015; ERTA 2016) Life Safety Code

NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;

TIA 17-3) National Electrical Code

U.S. DEPARTMENT OF DEFENSE (DOD)

DOD 8500.01 (2014) Cybersecurity

DOD 8510.01 (2014; Change 1-2016; Change 2-2017) Risk Management Framework (RMF) for DoD Information Technology (IT)

UNDERWRITERS LABORATORIES (UL)

UL 1472 (2015) UL Standard for Safety Solid-State Dimming Controls

UL 1598 (2008; Reprint Oct 2012) Luminaires

UL 20 (2010; Reprint Feb 2012) General-Use Snap Switches

UL 2043 (2013) Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces

UL 508 (1999; Reprint Oct 2013) Industrial Control Equipment

UL 8750 (2015; Reprint Aug 2017) UL Standard for Safety Light Emitting Diode (LED) Equipment for Use in Lighting Products

UL 916 (2007; Reprint Aug 2014) Standard for Energy Management Equipment

UL 924 (2016; Reprint Mar 2017) UL Standard for Safety Emergency Lighting and Power Equipment

UL 94 (2013; Reprint Mar 2016) UL Standard for Safety Tests for Flammability of Plastic Materials for Parts in Devices and Appliances

1.2 RELATED REQUIREMENTS

Materials not considered to be luminaires or luminaire accessories are specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Luminaires and accessories mounted on exterior surfaces of buildings are specified in Section 26 56 00 EXTERIOR LIGHTING.

SECTION 26 51 00 Page 6 AM-0001

1.3 DEFINITIONS

a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, must be as defined in IEEE 100 and IES RP-16 .

b. For LED luminaire light sources, "Useful Life" is the operating hours before reaching 70 percent of the initial rated lumen output (L70) with no catastrophic failures under normal operating conditions. This is also know as 70 percent "Rated Lumen Maintenance Life" as defined in IES LM-80 .

c. For LED luminaires, "Luminaire Efficacy" (LE) is the appropriate measure of energy efficiency, measured in lumens/watt. This is gathered from LM-79 data for the luminaire, in which absolute photometry is used to measure the lumen output of the luminaire as one entity, not the source separately and then the source and housing together.

d. Total harmonic distortion (THD) is the root mean square (RMS) of all the harmonic components divided by the total fundamental current.

1.4 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING.

Data, drawings, and reports must employ the terminology, classifications and methods prescribed by the IES HB-10 as applicable, for the lighting system specified. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Luminaire Drawings ; G

Occupancy/Vacancy Sensor Coverage Layout ; G

SD-03 Product Data

Luminaires ; G

Light Sources ; G

Drivers ; G

LED Luminaire Warranty ; G

Luminaire Design Data ; G

Vacancy Sensors ; G

Dimming Controllers (Dimmers) ; G

Exit Signs ; G

LED Emergency Drivers ; G

SECTION 26 51 00 Page 7 AM-0001

Occupancy Sensors ; G

Ambient Light Level Sensor ; G

Lighting Control System ; G

SD-06 Test Reports

LED Luminaire - IES LM-79 Test Report ; G

LED Light Source - IES LM-80 Test Report ; G

LED Light Source - IES TM-21 Test Report ; G

Occupancy/Vacancy Sensor Verification Tests ; G

Energy Efficiency ; G

SD-07 Certificates

Luminaire Useful Life Certificate ; G

LED Driver and Dimming Switch Compatibility Certificate ; G

1.5 QUALITY CONTROL

1.5.1 Luminaire Drawings

Include dimensions, accessories, and installation and construction details. Photometric data, including zonal lumen data, average and minimum ratio, aiming diagram, and computerized candlepower distribution data must accompany shop drawings.

1.5.2 Occupancy/Vacancy Sensor Coverage Layout

Provide floor plans showing coverage layouts of all devices using manufacturer's product information.

1.5.3 LED Driver and Dimming Switch Compatibility Certificate

Submit certification from the luminaire, driver, or dimmer switch manufacturer that ensures compatibility and operability between devices.

1.5.4 Luminaire Design Data

a. Provide safety certification and file number for the luminaire family that must be listed, labeled, or identified per the NFPA 70 (NEC).

Applicable testing bodies are determined by the US Occupational Safety Health Administration (OSHA) as Nationally Recognized Testing Laboratories (NRTL) and include: CSA (Canadian Standards Association), ETL (Edison Testing Laboratory), and UL (Underwriters Laboratories).

b. Provide long term lumen maintenance projections for each LED luminaire in accordance with IES TM-21 . Data used for projections must be obtained from testing in accordance with IES LM-80 .

1.5.5 LED Luminaire - IES LM-79 Test Report

Submit test report on manufacturer's standard production model luminaire.

SECTION 26 51 00 Page 8 AM-0001

Include all applicable and required data as outlined under "14.0 Test Report" in IES LM-79 .

1.5.6 LED Light Source - IES LM-80 Test Report

Submit report on manufacturer's standard production LED light source (package, array, or module). Include all applicable and required data as outlined under "8.0 Test Report" in IES LM-80 .

1.5.7 LED Light Source - IES TM-21 Test Report

Submit test report on manufacturer's standard production LED light source (package, array or module). Include all applicable and required data, as well as required interpolation information as outlined under "7.0 Report" in IES TM-21 .

1.5.8 Occupancy/Vacancy Sensor Verification Tests

Submit test report outlining post-installation coverage and operation of sensors.

1.5.9 Test Laboratories

Test laboratories for the IES LM-79 and IES LM-80 test reports must be one of the following:

a. National Voluntary Laboratory Accreditation Program (NVLAP) accredited for solid-state lighting testing as part of the Energy-Efficient Lighting Products laboratory accreditation program for both LM-79 and LM-80 testing.

b. One of the qualified labs listed on the Department of Energy - LED Lighting Facts Approved Testing Laboratories List at for LM-79 testing.

c. One of the EPA-Recognized Laboratories listed at for LM-80 testing.

1.5.10 Regulatory Requirements

In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of NFPA 70 , unless more stringent requirements are specified or indicated.

1.5.11 Standard Products

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products must have been in satisfactory commercial or industrial use for two years prior to bid opening. The two-year period must include applications of equipment and materials under similar circumstances and of similar size. The product must have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the two-year period. Where two or more items of the same class of equipment are required, these items must be

SECTION 26 51 00 Page 9 AM-0001 products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.

1.5.11.1 Alternative Qualifications

Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.

1.5.11.2 Material and Equipment Manufacturing Date

Products manufactured more than six months prior to date of delivery to site must not be used, unless specified otherwise.

1.5.11.3 Energy Efficiency

Submit data indicating lumens per watt efficacy and color rendering index of light source.

1.6 WARRANTY

Support all equipment items by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.

1.6.1 LED Luminaire Warranty

a. Provide a written 5 year on-site replacement warranty for material, fixture finish, and workmanship. On-site replacement includes transportation, removal, and installation of new products.

(1) Include finish warranty to include failure and substantial deterioration such as blistering, cracking, peeling, chalking, or fading.

(2) Material warranty must include:

(a) All drivers.

(b) Replacement when more than 10 percent of LED sources in any lightbar or subassembly(s) are defective or non-starting.

b. Warranty period must begin on date of beneficial occupancy. Provide the Contracting Officer with signed warranty certificates prior to final payment.

1.6.1.1 Provide Luminaire Useful Life Certificate

Submit certification from the manufacturer indicating the expected useful life of the luminaires provided. The useful life must be directly correlated from the IES LM-80 test data using procedures outlined in IES TM-21 . Thermal properties of the specific luminaire and local ambient operating temperature and conditions must be taken into consideration.

SECTION 26 51 00 Page 10 AM-0001

PART 2 PRODUCTS

2.1 PRODUCT COORDINATION

Products and materials not considered to be luminaires, luminaire controls, or associated equipment are specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Luminaires, luminaire controls, and associated equipment for exterior applications are specified in Section

26 56 00 EXTERIOR LIGHTING.

2.2 LUMINAIRES

UL 1598 , NEMA C82.77 , and UL 8750 . Provide luminaires as indicated in luminaire schedule and NL plates or details on project plans. Provide luminaires complete with light sources of quantity, type, and wattage indicated. Provide all luminaires of the same type by the same manufacturer. Luminaires must be specifically designed for use with the driver, ballast or generator and light source provided.

2.2.1 LED Luminaires

Provide luminaires complete with power supplies (drivers) and light sources. Provide design information including lumen output and design life in luminaire schedule on project plans for LED luminaires. LED luminaires must meet the minimum requirements in the following table:

LUMINAIRE TYPE MINIMUM LUMINAIRE

EFFICACY (LE)

MINIMUM COLOR RENDERING INDEX

(CRI)

LED TROFFER -

300 x 1200 600 x 600 600 x 1200

90 LPW 80

LED Downlight 50 LPW 90

LED Track or Accent 40 LPW 80

LED Low Bay/High Bay 80 LPW 70

LED Linear Ambient 80 LPW 80

LED luminaires must also meet the following minimum requirements:

a. Luminaires must have a minimum 5 year manufacturer's warranty.

b. Luminaires must have a minimum L70 lumen maintenance value of 50,000 hours as calculated by IES TM-21 , with data obtained per IES LM-80 requirements.

c. Luminaire drive current value must be identical to that provided by test data for luminaire in question.

d. Luminaires must be tested to IES LM-79 and IES LM-80 standards, with the results provided as required in the Submittals paragraph of this specification.

e. Luminaires must be listed with the DesignLights Consortium 'Qualified Products List' when falling into category of "General Application" luminaires, i.e. Interior Directional, Display Case, Troffer, Linear Ambient, or Low/High Bay. Requirements are shown in the Designlights

SECTION 26 51 00 Page 11 AM-0001

Consortium "Technical Requirements Table" at https://data.energystar.gov/dataset/EPA-Recognized-Laboratories-For- Lighting-Products/jgwf-7qrr .

f. Provide Department of Energy 'Lighting Facts' label for each luminaire.

2.3 DRIVERS

2.3.1 LED Drivers

NEMA SSL 1, UL 8750 . LED drivers must be electronic, UL Class 1, constant-current type and comply with the following requirements:

a. Output power (watts)and luminous flux (lumens) as shown in luminaire schedule for each luminaire type to meet minimum luminaire efficacy (LE) value provided.

b. Power Factor (PF) greater than or equal to 0.9 over the full dimming range when provided.

c. Current draw Total Harmonic Distortion (THD) of less than 20 percent.

d. Class A sound rating.

e. Operable at input voltage of 120-277 volts at 50 hertz.

f. Minimum 5 year manufacturer's warranty.

g. RoHS compliant.

h. Integral thermal protection that reduces or eliminates the output power if case temperature exceeds a value detrimental to the driver.

i. UL listed for dry or damp locations typical of interior installations.

j. Non-dimmable, step-dimmable to 50 percent output, or fully-dimmable using 0-10V control as indicated in luminaire schedule.

2.4 LIGHT SOURCES

NEMA ANSLG C78.377 , NEMA SSL 3. Provide type and wattage as indicated in luminaire schedule on project plans.

2.4.1 LED Light Sources

a. Correlated Color Temperature (CCT) of 4000 degrees K.

b. Minimum Color Rendering Index (CRI) R9 value of 80.

c. High power, white light output utilizing phosphor conversion (PC) process.

d. RoHS compliant.

e. Provide light source color consistency by utilizing a binning tolerance within a 4 step McAdam ellipse.

SECTION 26 51 00 Page 12 AM-0001

2.5 LIGHTING CONTROLS

ASHRAE 90.1 - IP ASHRAE 189.1 . Provide network certification for all networked lighting control systems and devices per requirements of DOD 8500.01 and DOD 8510.01 .

2.5.1 Toggle Switches

Provide line-voltage toggle switches as specified in Section 26 20 00

INTERIOR DISTRIBUTION SYSTEM.

2.5.2 Dimming Controllers (Dimmers)

UL 1472 , UL 20 or JIS C 8304 , IEEE C62.41 , NEMA SSL 7A. 120/277 and V0-10 V dimmers must provide flicker-free, continuously variable light output throughout the dimming range. Provide radio frequency interference suppression integral to device. Provide dimmers utilizing pulse width modulation (PWM). Provide device with a vertical slider, paddle, rotary button, or toggle (with adjacent vertical slider) type control, with finish to match switches and outlets in same area. Provide back box in wall with sufficient depth to accommodate body of switch and wiring.

Devices must be capable of operating at their full rated capacity regardless of being single or ganged-mounted, and be compatible with three-way and four-way switching scenarios. Dimmers must be capable of controlling two-wire or three-wire 0-10 volt LED drivers. Ensure compatibility of dimmer with separate power packs when utilized for lighting control. Dimmers and the ballasts or drivers they control, must be provided from the same manufacturer, or tested and certified as compatible for use together. Provide NEMA SSL 7A-compliant devices.

2.5.3 Sensors for Lighting Control

IEEE C62.41 , NEMA WD 1, UL 94 , UL 916 , UL 508 , ASTM D4674 REV A .

2.5.3.1 Occupancy Sensors

Provide occupancy sensors with coverage patterns as indicated on project plans. Provide no less quantity of sensors as shown on plans, but add additional sensors when required to fulfill coverage requirement for the specific model sensor provided. Sensor must be provided with an adaptive learning function that automatically sets sensor in optimum calibration in a set period of time after installation and a non-volatile memory that saves settings after a power outage. Provide sensors designed for ceiling, wall or wall-box installation as indicated. Operating voltage must be 120277 volts. Operating voltage must be 24V in conjunction with a control system or separate power pack which interacts with luminaire being controlled. Provide housing of high-impact, injection-molded thermoplastic with a multi-segmented lens for PIR and dual technology sensors. Sensor operation requires movement to activate luminaires controlled, and turns luminaires off after a set time of inactivity.

2.5.3.1.1 Passive Infrared (PIR) Sensors

Provide ceiling or wall-mounted PIR sensors meeting the following requirements:

a. Temperature compensated, dual element sensor and a multi-element fresnel lens (Poly IR4 material).

SECTION 26 51 00 Page 13 AM-0001

b. Technology to optimize automatic time delay to fit occupant usage patterns.

c. No minimum load requirement for line voltage sensors and be capable of switching from zero to 800 W at 120 VAC, 50/60 Hz and from zero to 1200 W at 277 VAC, 50/60 Hz. Control voltage sensors must not exceed a maximum load requirement of 20 mA at 24VDC.

d. Time delay of five to 30 minutes in increments of five minutes with a walk through and test mode set by DIP switch.

e. LED indicator that remains active during occupancy.

f. Built-in light level sensor that is operational from 0.8 to 18 lux .

g. Coverage pattern tested to NEMA WD 7 standards.

h. Standard five year warranty and be UL listed

i. No leakage current to load when in the off mode.

2.5.3.1.2 Ultrasonic Sensors

Provide ceiling-mounted ultrasonic sensors meeting the following requirements:

a. Operate at an ultrasonic frequency of 25 kHz.

b. LED on exterior of device to indicate occupant detection.

c. Adjustable time delay period of 15 seconds to 30 minutes .

d. UL listed with minimum five year warranty.

2.5.3.1.3 Dual Technology Sensors

Provide dual technology sensors that meet the requirements for PIR sensors and ultrasonic sensors indicated above. If either the passive infrared or ultrasonic sensing registers occupancy, the luminaires must remain on.

2.5.3.1.4 High/Low-Bay Sensors

Provide occupancy sensors specifically designed for high/low-bay mounting application using passive infrared (PIR) technology, with the following characteristics:

a. Input voltage of 120/277 volts, at 50/60 hertz.

b. High-impact, injection-molded thermoplastic housing with interchangeable lenses for 360 degree open area coverage or narrow rectangular, warehouse aisle coverage.

c. Utilize zero-crossing circuitry to prevent damage from high inrush current and to promote long life operation.

d. Be designed to mount directly to or adjacent to high or low-bay luminaires.

e. UL listed, CEC Title 24 and ASHRAE 90.1 - IP compliant.

SECTION 26 51 00 Page 14 AM-0001

2.5.3.1.5 Power Packs for Sensors

UL 2043 , CEC Title 24 , ASHRAE 90.1 - IP . Power packs used to provide power to one or more lighting control sensors must meet the following requirements:

a. Input voltage - 120-277 VAC; output voltage - 24 VDC at 225 mA.

b. Plenum-rated, high-impact thermoplastic enclosure.

c. Utilizes zero-crossing circuitry to prevent damage from inrush current.

d. Maximum load rating of 16 amps for electronic lighting loads.

e. RoHS compliant.

2.5.3.2 Vacancy Sensors

Provide vacancy sensors as indicated above under paragraph OCCUPANCY SENSORS, but with requirement of a manual operation to activate luminaires controlled. Provide automatic operation to turn luminaires off after a set period of inactivity.

2.5.4 Light Level Sensor

UL listed, low voltage. Light level sensor shall be capable of detecting changes in ambient lighting levels, shall provide a dimming range of 20 percent to 100 percent, minimum, and shall be designed for use with addressable dimming ballast and lighting control system to which they are connected. Sensor shall be capable of controlling 40 electronic dimming ballast, minimum. Sensor light level shall be adjustable and have a set level range from 100 to 1000 lux, minimum. Sensor shall have a bypass function to electrically override sensor control. Sensor can be replaced without reprogramming and is mountable on light fixtures. Sensor shall use open loop basis for daylight sensor control scheme.

2.5.5 Lighting Control Station

UL listed. 120 VAC, 50/60 Hz input power. Lighting control stations shall be compatible with the lighting control system and the lighting control hub. It shall be capable of low voltage, diming control and programming of up to 6 zones of lights and window shades using a single control unit.

Each zone has a dedicated raise and lower button to adjust the zone with a 7 LED bar graph showing lighting level status. The lighting control stations shall provide direct low-voltage control of addressable ballasts.

It shall electronically link a digital lighting ballast to a zone for both dimming and turn on/off. Electronically assign daylight sensors to addressable ballasts and dimmers for daylight harvesting. The lighting control station shall be flush mounted and cnsist of a hinged faceplate, information screen, astronomic timeclock, occupant sensor connection and backlit buttons. Provide number of zones as indicated and engrave or provide permanent markings to identify function. Station shall match the color of the adjacent wall plates as specified in Section 26 20 00

INTERIOR DISTRIBUTION SYSTEM.

2.5.6 Lighting Control System Hub

Lighting control system hub shall provide a centralized connection point

SECTION 26 51 00 Page 15 AM-0001 to control, manage and monitor the addressable ballasts, lighting control stations, low voltage wall switches, power panels, and window shade system. It shall be UL listed, with a NEMA 1 surface mounted enclosure.

The hub shall support up to 8 lighting control circuits, (4 bus supplies).

Each lighting control circuit shall be capable of controlling up to 64 ballasts and ballast modules, pIus 16 daylight sensors, and 64 infrared devices. The hub shall be capable of interfacing with a computer to control and display system status. The Lighting Management System software shall be PC compatible Windows based and be used to make system programming and configuration changes. The lighting control system network shall be a dedicated lighting control Ethernet network environment.

2.5.7 Lighting Control System Ethernet Switch

2.5.7.1 General

Switch shall be compatible with the lighting control system. Provide with configurable session timeouts for each service such as SSH, Telnet, and TFTP; multi-level user passwords; support authentication for console access; SSH version2/SSL (128-bit encryption); support SNMPv3 with SHA Authentication Protocol and AES Privacy; enable/disable ports, MAC based port security, VLAN (802.1Q) to segregate and secure network traffic, RADIUS centralized password management, console timeout must be configurable; FIPS 140-2 compliant; support multiple NTP server to synchronize time; compatible with Solar Winds Orion network performance monitoring (SolarWinds Network Configuration Manager SNMPv3), a login banner, and 56-bit encryption.

Provide two-year manufacturer's warranty.

2.5.7.2 Software

Operating System Software shall allow plug and play operation and have automatic learning, negotiation and crossover detection and shall support MSTP 902.1Q-2005, RSTP (802.1w) and Enhanced Rapid Spanning Tree network fault recover (<5ms), SNMPv3 SHA Authentication Protocol, AES Privacy Protocol, Quality of Service (802.1p) for real time traffic, VLAN (802.1Q) with double tagging and GVRP support, Link aggregation (802.3ad), IGMP Snooping for multicast filtering, and provide port configuration, status, statistics, mirroring, and security.

Provide a switch which uses programming software provided by Cisco, GarrettCom, or Ruggedcom.

2.5.7.3 Ports

All ports on each switch shall be fully populated with 10/100 ports in the switch configuration prior to commissioning. Provide a minimum of six (6) ports or one spare port on installed switch whichever is greater.

2.5.8 Window Shade Power Supply

Window shade power supply shall be low voltage, hardwired and compatible with the lighting control system. It shall be UL listed, with a NEMA 1 surface mounted enclosure. The power supply shall contain ten 30W (60W peak) power supply outputs. The input voltage shall be 120VAC and be controlled by the lighting control stations.

SECTION 26 51 00 Page 16 AM-0001

2.5.9 Lighting Control Module

2.5.9.1 0-10V Module

UL listed. 120-277VAC input power. 0-10V Lighting Control Module shall be compatible with the lighting control system and the lighting control hub. Module shall be capable of being electronically linked to a single zone for coordination between low voltage dimming module and line voltage relay. Module shall be capable of 0-10V dimming. Module to integrate up to 4 individually controlled zones, each with a capacity of up to 16 amps of high in-rush lighting load. Rated life of relay minimum 1,000,000 cycles. Module shall connect without interface to wired occupancy sensors and daylight sensors.

2.5.9.2 Digital Addressable Module

UL listed. 120-277VAC input power. Digital Addressable Module shall be compatible with the lighting control system and the lighting control hub.

Module shall support up to two low-voltage digital communication links of up to 64 addressable ballasts per link.

2.5.10 Power Interfaces

2.5.10.1 Switching Power Module

120VAC control voltage, 120-277VAC load voltage. Capacity, 16A.

Switching power module shall be capable of switching the following load types: Incandescent (tungsten), Halogen, Magnetic low-voltage transformer, Electronic low-voltage transformer, Magnetic and electronic fluorescent dimming ballasts, Neon/cold-cathode, and HID.

2.5.10.2 Phase-Adaptive Power Module

120VAC control voltage, 120-277VAC load voltage. Capacity, 16A.

Phase-Adaptive power module shall be capable of operating the following sources with a smooth continuous Square Law dimming curve: Incandescent (tungsten), Halogen, Magnetic low-voltage transformer, Electronic low-voltage transformer (reverse-phase control dimming), Neon/Cold cathode, and fluorescent dimming ballasts.

2.5.11 Low Voltage Control Interfaces

2.5.11.1 Contact Closure Interface

The contact closure input device shall accept both momentary and maintained contact closures and can be configured for maintained or pulsed outputs. Contact closure can be programmed using conditional logic off of a state variable such as time of day or partition status.

2.5.11.2 DMX Interface

Interface shall have the following capabilities:

a. Map a single zone intensity to a single DMX512 lighting channel.

b. Map a single zone intensity to 3 DMX512 channels for RGB/CMY color-control.

c. Map a single zone intensity to a single DMX512 integration channel.

d. Smoothly transition from one color to another in a cross fade.

e. Able to automatically sequence through a variety of colors.

SECTION 26 51 00 Page 17 AM-0001

2.5.11.3 Sensor Module

Sensor module shall provide wired inputs for occupancy sensors, daylight sensors, and digital ballast control stations.

2.5.11.4 Emergency Lighting Interface

Emergency lighting interface shall sense all three phases of building power and provide an output to power panels or digital ballast interfaces if power on any phase fails. Interface shall send all lights controlled by these devices to an emergency light level setting. Lights to return to their previous intensities when normal power is restored. Interface shall accept a contact closure input from a fire alarm control panel.

2.5.12 Power Panels

2.5.12.1 Dimming Panels

Panels shall be delivered and installed as a UL listed factory assembled panel, field wiring shall be accessible from front of panel without need to remove dimmer assemblies or other components. Panel shall utilize universal 16A continuous-use UL listed dimmer.

2.5.12.2 Branch Circuit Protection

Panels shall contain branch circuit protection for each input circuit unless otherwise indicated.

2.5.12.3 Branch Circuit Breakers

Branch circuit breakers shall meet the following performance requirements:

a. UL listed as molded case circuit breaker for use on lighting circuits.

b. Contain visual trip indicator, rated at 10,000 AIC, 120V Dimming.

c. Thermal-magnetic construction for overload, short-circuit, and over-temperature protection.

d. Accept tag-out/lock-out devices.

e. Replaceable without moving or replacing dimmer/relay assemblies or other components.

f. Listed for switching duty (SWD).

2.5.13 DMX Enclosure

Surface mounted cold rolled steel enclosure. Matte black powder coat finish. 35mm x 7.5mm DIN rail mounting with 495mm minimum available rail space. Enclosure shall have earth grounding lug and high voltage physical barrier.

2.5.14 Performance Space - Lighting Control System

2.5.14.1 Ethernet Switch

Switch shall be compatible with the lighting control system. Provide with configurable session timeouts for each service such as SSH, Telnet, and TFTP; multi-level user passwords; support authentication for console access; SSH version2/SSL (128-bit encryption); support SNMPv3 with SHA Authentication Protocol and AES Privacy; enable/disable ports, MAC based port security, VLAN (802.1Q) to segregate and secure network traffic, SECTION 26 51 00 Page 18 AM-0001

RADIUS centralized password management, console timeout must be configurable; FIPS 140-2 compliant; support multiple NTP server to synchronize time; compatible with Solar Winds Orion network performance monitoring (SolarWinds Network Configuration Manager SNMPv3), a login banner, and 56-bit encryption.

Provide two-year manufacturer's warranty.

Connections shall be made between consoles, face panels, architectural processors, dimmers, Net3 Gateways, and computers over standard Ethernet distribution systems using 100BaseT, 100BaseFL, or greater wiring. All installations shall conform to established Ethernet wiring practice, and installation shall be performed by contractors qualified to do this type of work. All wiring shall be tested at Category 6 or higher for full bandwidth operation to the appropriate IEEE standard.

The Lighting Control system must be supplied by a single manufacturer and must have seamless integration over Ethernet between the Entertainment and Architectural lighting control.

a. Capacities

1. The network shall support DMX routing, patching, and prioritization for up to 63,399 universes (32,767,488 DMX addresses). Each address may be input or output from any port on any DMX gateway in the system. DMX input, routing and output shall be specifically supported on the system from multiple sources and locations up to the maximum number of gateways supported by the Ethernet topology.

2. The network shall support multiple network hosts including consoles, gateways, dimming racks, computers, file servers, printers, and architectural control processors with discrete command lines and control. The lighting network shall support multiple venues within a system and discrete systems on the same network.

b. System Configuration and Monitoring

1. Network device configuration shall be via Net3 Gateway

Configuration Editor (GCE) software and/or ANSI E1.17 Architecture for Control Networks (ACN).

2. Patch addresses shall support viewing and manipulation via ANSI

E1.17 ACN.

a) The system shall permit complete user flexibility allowing the system operator to patch each DMX input address to any ANSI E1.31 streaming ACN address, and DMX output to span streaming ACN universes.

b) The lighting system shall support assignment of DMX offsets, truncation of DMX universes, and provide choice of DMX port prioritization.

c) The lighting system shall support the DD start code extension to ANSI E1.31 which provides priority per address such that multiple control sources can share universes with discrete control per address.

3. Architectural and Entertainment systems connected to the same network shall be capable of arbitrating control over E1.31 Streaming ACN (sACN) level data. The system shall be capable of alternating control of individual address data between architectural and entertainment systems without intervention by the user. The user shall dictate the conditions under which system shall automatically take control. The network shall allow

SECTION 26 51 00 Page 19 AM-0001 user override of the selected defaults. Systems which require direct user intervention to allocate control of dimmers between architectural and entertainment lighting systems shall not be accepted.

4. The Net3 network shall allow multiple DMX input sources to be prioritized on the same universe as network native sources using E1.31 Streaming ACN prioritization. Multiple DMX inputs may be assigned to the same streaming ACN address (this provides multi-source control for a particular address). Likewise, the system shall support E1.31 prioritization of multiple simultaneous network sources. Systems that cannot prioritize multiple DMX inputs and multiple native network sources on a network shall not be deemed suitable.

2.5.14.2 Performance and House Lighting Control Stations

Lighting control stations shall be compatible with the Special Systems performance lighting control system and the lighting control processing equipment. It shall be capable of low voltage, dimming control and programming of the house lights and Special Systems performance lighting fixtures.

The stations shall be provided with backlit buttons. Station shall match the color of the adjacent wall plates as specified in Section 26 20 00

INTERIOR DISTRIBUTION SYSTEM.

2.5.14.3 Performance Space - Architectural Lighting Control Processing System

a. The processor shall utilize microprocessor based, solid state technology to provide multi-scene lighting and building control.

1. Processor shall support functions such as station programming, macro sequencing, electronic lockout, room combine and astronomical time clock events. Processor shall allow configuration of the control system via the menus. See software section for additional system details.

2. When used in a dimming enclosure, the processor shall allow access to dimming control menus including the status screen, dimming configuration screen, backup menu, test menu and configuration menu.

b. One processor shall be rated to drive 1024 channels of control, 1024 zones, 64 rooms, 512 presets, 63 button or button/fader stations and 6 touchscreen stations

c. Processor module electronics shall be convection cooled.

d. The processor shall provide front-panel RJ45 jack, Secure Digital (SD) card slot, and Universal Serial Bus (USB) Port for configuration and data exchange.

e. Architectural Lighting System configuration and program information shall be stored in flash memory, which does not require battery backup.

f. The processor shall be contained in a plug-in assembly and require no discrete wiring connections; all wiring shall be terminated into dimming or control enclosure.

1. The processor shall support the following communications:

a) 10/100BaseTX, auto MDI/MDIX, 802.3af compliant Ethernet networking with TCP/IP, ESTA BSR E1.17 Advanced Control Networks (ACN) and ESTA BSR E1.31 (sACN) protocols

b) EIA-232 serial protocol

c) ESTA DMX512A, configurable as input or output ports

SECTION 26 51 00 Page 20 AM-0001

d) Dry contact closure inputs

e) Dry contact closure outputs, rated at 1A@30VDC

2.5.15 Performance Lighting Relay Panel

2.5.15.1 Intelligent Breaker System

A. Gener al

1. Breaker Panels shall be UL508, UL67, and UL924 Listed, and shall be so labeled when delivered

2. Breakers shall be UL489 listed and shall be labeled when delivered

3. Breaker Panels shall consist of a main enclosure with 48 pole breaker subpanels, integral control electronics for low voltage terminations and provision for accessory cards

a. Up to two accessory shall be supported per breaker panel.

B. Mechani cal

1. The panel shall be constructed of 16-gauge galvannealed steel. All panel components shall be properly treated or finished in fine-textured, scratch resistant paint

2. 277V breaker panels shall be capable of being mounted on the surface of a wall or recessed mounted

3. Breaker panels shall be in 48 pole configurations

a. 48 pole (with provision to add main breaker)

1) 73.00" high, 20.00" wide and 5.11" deep (with front panel attached)

4. Choice of panel covers shall be available for surface or recess mount applications. This outer panel shall ship complete with a locking door to limit access to electronics and breakers

a. Optional center-pin reject security screws shall be available for all accessible screws

b. Optional recess mount doors shall extend 1" beyond all panel edges to hide wall cut-out

5. The unit shall provide interior cover over the control electronics and accessory cards to allow access only to class 2 wiring and prevent direct access to class 1 line voltage components

6. The panel shall support up to 48 single pole branch circuits

a. Branch circuits shall range from 15A to 20A capable of holding full rated load for minimum of three hours continuously

7. Breakers shall provide manual switching control while power is unavailable to the panel such that critical lighting can be set to an on state, without the need for power to the panel

8. Breaker output lugs shall accept 10-14 AWG dual conductor wire

9. Breaker output lug shall support solid or stranded 6-14 AWG class B, C, or K copper wire

10. Control wiring for DMX, station bus, and Emergency input terminations shall land on a removable headers for contractor installation

C. User I nt er f ace

1. The user interface shall contain an LCD display with button pad to include 0-9 number entry, up, down back arrow navigation and enter

2. Test shortcut button shall be available for local activation of preset, sequence and set level overrides

3. The user interface shall have a power status LED indicator (Blue), a

DMX status LED indicator (Green), a network status LED indicator (Green) and an LED indicator (red) for errors

4. Interface shall allow the backlight to timeout and shall provide user editable options to shut off backlight completely as well as adjust screen contrast

SECTION 26 51 00 Page 21 AM-0001

5. Ethernet interface shall default to automatic IP through link local and DHCP. Upon receiving IP address, the address of the Network Interface Card (NIC) shall display in the about menu. Static address and settings shall also be possible

6. The control interface shall support a USB memory stick interface for uploads of configurations and software updates

7. The user interface shall support power input from an external Uninterruptible Power Supply (UPS) supplying 800W-2400W AC power

D. Funct i onal

1. Panel setup shall be user programmable.

This is the start of the file's text. The full file is on GovTribe.