This document provides details regarding a federal contract opportunity for the replacement of Kinnick High School at Commander Fleet Activities in Yokosuka, Japan. The solicitation seeks a firm-fixed price contract to construct a new four story, 14,700 square meter high school building along with associated site work including athletic fields and infrastructure over a 47 month period of performance. The high school and site work will be conducted in separate phases. The contract will be awarded using lowest price technically acceptable procedures to the offeror submitting the lowest priced proposal deemed technically acceptable based on non-price factors. Electronic proposals are due by the response date listed on SAM.gov where the full solicitation will be posted along with any subsequent amendments. Only firms authorized and licensed to perform construction work in Japan will be considered as the work must comply with all applicable Japanese laws and regulations.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS VOL 4 CODE 6 FINAL DESIGN RTA
Project No: PA00109
Administered By:
U.S. Army Engineering District, Japan
APO AP 96338-5010
For:
The Department of Defense Education Activity (DoDEA)
Arlington, VA 22203
Prepared By:
23 JULY 2021
REPLACE KINNICK HIGH SCHOOL
Commander Fleet Activities Yokosuka, Japan
W912HV-22-R-0003
Replace Kinnick High School
CFA Yokosuka, Japan
PA00109
Final Design RTA
PROJECT TABLE OF CONTENTS Page 1
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00.00 10 GENERAL CONTRACT REQUIREMENTS
01 20 00 PRICE AND PAYMENT PROCEDURES
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 00-A ENG FORM 4025
01 33 00-B SUBMITTAL REGISTER
01 33 29 SUSTAINABILITY REPORTING
01 33 29-A LEED PROJECT TRACKING CHECKLIST
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 35 26-A USACE ACCIDENT PREVENTION PLAN CHECKLIST
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 42 15 METRIC MEASUREMENTS
01 45 00.00 10 QUALITY CONTROL
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 35 SPECIAL INSPECTIONS
01 45 35-A STATEMENT OF SPECIAL INSPECTIONS
01 45 35-B SCHEDULE OF SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 50 00-A CONSTRUCTION PROJECT SIGNS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS - MASTER DRAFT - Reduced
Submittals
01 57 19-A ENVIRONMENTAL PROTECTION PLAN
01 57 19-B ENVIRONMENTAL BRIEF CHECKLIST
01 57 19-C DIRECT DISCHARGE EFFLUENT LIMITATIONS
01 57 19-D NOEP Review Request Form
01 57 19-E NOEP Requirements Form
01 57 19-F NOEP ROND Form
01 57 19-G BMP Biological Resources
01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMITTALS
01 78 00-A DD FORM 1354
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 TOTAL BUILDING COMMISSIONING
01 91 00.15-A COMMISSIONING PLAN
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
02 61 13 EXCAVATION AND HANDLING OF CONTAMINATED MATERIAL
02 61 13-A SITE INSPECTION
02 82 13.00 10 ASBESTOS ABATEMENT
02 82 13.00 10-A REPORT OF FINDINGS HAZMAT TESTING
02 82 13.00 10-B AHERA ASBESTOS MANAGEMENT PLAN
02 83 13.00 20 LEAD IN CONSTRUCTION
02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBS
AND MERCURY - MASTER DRAFT
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
03 31 01.00 10 CAST-IN-PLACE STRUCTURAL CONCRETE FOR CIVIL WORKS
03 33 00 CAST-IN-PLACE ARCHITECTURAL CONCRETE
PA00109
PROJECT TABLE OF CONTENTS Page 2
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
04 23 00 GLASS UNIT MASONRY
DIVISION 05 - METALS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
06 61 17 HOMOGENEOUS QUARTZ (SOLID SURFACING) FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 12 00 BUILT-UP BITUMINOUS WATERPROOFING
07 13 53 ELASTOMERIC SHEET WATERPROOFING
07 21 13 BOARD INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 32 13 ROOF TILES
07 41 63 FABRICATED ROOF PANEL ASSEMBLIES
07 52 00 MODIFIED BITUMINOUS MEMBRANE ROOFING
07 56 00 FLUID-APPLIED ROOFING
07 60 00 FLASHING AND SHEET METAL
07 81 00 SPRAY-APPLIED FIREPROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
PA00109
PROJECT TABLE OF CONTENTS Page 3
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS, FRAMES, AND WINDOW WALL
08 14 00 WOOD DOORS
08 31 00 ACCESS DOORS AND PANELS
08 32 13 ALUMINUM SLIDING/FOLDING GLASS DOORS
08 33 13 COILING COUNTER DOORS
08 33 23 OVERHEAD COILING DOORS
08 34 73 SOUND CONTROL DOOR AND WINDOW ASSEMBLIES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND WINDOW WALL
08 51 13 ALUMINUM WINDOWS
08 60 45 TRANSLUCENT PANELS
08 62 00 SKYLIGHTS
08 71 00 DOOR HARDWARE
08 71 00-A DOOR HARDWARE SCHEDULE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC AND QUARRY TILING
09 51 00 ACOUSTICAL CEILINGS
09 64 66 WOOD ATHLETIC FLOORING
09 65 00 RESILIENT FLOORING
09 65 66 RESILIENT ATHLETIC FLOORING
09 68 00 CARPETING
09 72 00 WALLCOVERINGS
09 84 20 ACOUSTICAL WALL PANELS
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 11 00 VISUAL DISPLAY UNITS
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 PLAQUE SIGNAGE
10 14 53 TRAFFIC SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 21 23.16 CUBICLE TRACK AND HARDWARE
10 22 39 FOLDING PANEL PARTITIONS
10 26 13 WALL AND CORNER GUARDS
10 28 13 TOILET ACCESSORIES
10 28 13-A TOILET ACCESSORY SCHEDULE
10 35 00 FLAGPOLES
10 44 16 FIRE EXTINGUISHER CABINETS
10 51 13 METAL LOCKERS
10 99 00 MISCELLANEOUS SPECIALTIES
PA00109
PROJECT TABLE OF CONTENTS Page 4
DIVISION 11 - EQUIPMENT
11 05 40 COMMON WORK RESULTS FOR FOODSERVICE EQUIPMENT
11 06 40.13 FOODSERVICE EQUIPMENT SCHEDULE
11 06 40.13-A FOODSERVICE EQUIPMENT SCHEDULE
11 41 11 REFRIGERATED AND FROZEN FOOD STORAGE EQUIPMENT
11 44 00 FOOD COOKING EQUIPMENT
11 48 00 CLEANING AND DISPOSAL EQUIPMENT
11 52 13 MOTORIZED PROJECTION SCREENS
11 53 00 LABORATORY EQUIPMENT AND FUMEHOODS
11 61 43 STAGE CURTAINS AND TRACK
11 84 00 ATHLETIC EQUIPMENT
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 35 53 MANUFACTURED WOOD LABORATORY CASEWORK
12 36 53 EPOXY COUNTERTOPS
12 48 13 ENTRANCE FLOOR MATS
12 61 13 UPHOLSTERED AUDIENCE SEATING
12 76 00 TELESCOPING GYM SEATS
12 86 00 BLEACHERS AND PRESS BOX
12 93 00 SITE FURNISHINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT
13 48 00.00 10 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT
DIVISION 14 - CONVEYING EQUIPMENT
14 21 23 ELECTRIC TRACTION PASSENGER ELEVATOR
14 42 00 WHEELCHAIR LIFT
DIVISION 21 - FIRE SUPPRESSION
21 12 00 STANDPIPE SYSTEMS
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 23 00.00 20 WET CHEMICAL FIRE EXTINGUISHING FOR KITCHEN CABINET
21 30 00 FIRE PUMPS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
PA00109
PROJECT TABLE OF CONTENTS Page 5
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 09 93 SEQUENCES OF OPERATION FOR HVAC CONTROL
23 23 00 REFRIGERANT PIPING
23 25 00 CHEMICAL TREATMENT OF WATER FOR MECHANICAL SYSTEMS
23 30 00 HVAC AIR DISTRIBUTION
23 57 10.00 10 FORCED HOT WATER HEATING SYSTEMS USING WATER AND STEAM
HEAT EXCHANGERS
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED-HOT, WATER PIPING SYSTEMS
23 70 03.00 10 HEATING AND UTILITIES SYSTEMS, CENTRAL STEAM
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.01 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - HVAC
25 05 11.01-A DESIGNER CONTROLS
25 05 11.02 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS -
(LIGHTING, PUBLIC ADDRESS, INTERCOMMUNICATION, PROGRAM
BELL/MASTER CLOCK)
25 05 11.02-A DESIGNER CONTROLS
25 05 11.03 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - FIRE
REPORTING AND PUMP CONTROLLER
25 05 11.03-A DESIGNER CONTROLS
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
26 08 00.00 10 ELECTRICAL LIGHTING CONTROL SYSTEMS COMMISSIONING
REQUIREMENTS
26 11 16.00 33 THREE-PHASE, CUBICLE-TYPE PAD-MOUNTED TRANSFORMER
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 27 14.00 20 ELECTRICITY METERING
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 41 00 AUDIO/VISUAL SYSTEMS
27 51 16 PUBLIC ADDRESS SYSTEMS
27 51 23.10 INTERCOMMUNICATION SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 10 05 ELECTRONIC SECURITY SYSTEMS (ESS)
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
PA00109
PROJECT TABLE OF CONTENTS Page 6
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 23 00.00 20 EXCAVATION AND FILL
31 23 01.00 20 EXCAVATION AND FILL UNDER BUILDINGS
31 31 16.13 CHEMICAL TERMITE CONTROL
31 62 13.24 CONCRETE CYLINDER PILES
31 62 13.24-A PILE AND DRIVING EQUIPMENT DATA FORM
31 62 13.24-B PILE DRIVING LOG
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 16.16 BASE COURSE FOR RIGID AND SUBBASE COURSE FOR FLEXIBLE
SUBBASE COURSE FOR PAVING
32 11 20 BASE COURSE FOR RIGID AND SUBBASES FOR FLEXIBLE PAVING
32 11 23 AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 12 16.16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 12 17 HOT MIX BITUMINOUS PAVEMENT
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
32 16 15 CONCRETE BLOCK PAVEMENTS
32 17 23 PAVEMENT MARKINGS
32 18 16.13 PLAYCOURT PROTECTIVE SURFACING
32 18 23 OUTDOOR ATHLETIC COURTS
32 31 13 CHAIN LINK FENCES AND GATES
32 84 24 IRRIGATION SPRINKLER SYSTEMS
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 12 33.00 30 WATER METERS
33 30 00 SANITARY SEWERS
33 40 00 STORM DRAINAGE UTILITIES
33 46 16 SUBDRAINAGE PIPING
33 61 14 EXTERIOR BURIED PREINSULATED WATER PIPING
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 34 - TRANSPORTATION
34 71 13.19 ACTIVE VEHICLE BARRIERS
-- End of Project Table of Contents --
Replace Kinnick High School PA00109 CFA Yokosuka, Japan Final Design RTA
SECTION TABLE OF CONTENTS
DIVISION 27 - COMMUNICATIONS
SECTION 27 05 14.00 10
CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
04/06
PART 1 GENERAL
1.1 REFERENCES
1.2 SUMMARY
1.3 SUBMITTALS
1.4 QUALIFICATIONS
1.4.1 Minimum Contractor Qualifications
1.4.2 Minimum Manufacturer Qualifications
1.5 DELIVERY, STORAGE, AND HANDLING
1.6 ENVIRONMENTAL REQUIREMENTS
1.7 EXTRA MATERIALS
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.1.1 Outlet Boxes
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Pull Cords
3.2 GROUNDING
-- End of Section Table of Contents --
SECTION 27 05 14.00 10 Page 1
SECTION 27 05 14.00 10
CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
04/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3) National Electrical Code
1.2 SUMMARY
Provide a cable TV premises distribution system consisting of cable tray, conduit with pullstring, and outlet boxes (coaxial cables and connecting hardware to be provided and installed by Americable) to transport television signals throughout the building to user locations as indicated. Submit detail drawings including outlet face plate details for each outlet configuration, and descriptions and types of cables, conduits, and cable trays, if used. Drawings shall show proposed layout and anchorage of equipment and appurtenances.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REQUIREMENTS.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Cable TV Premises Distribution System Installation ; G
SD-03 Product Data
Spare Parts
1.4 QUALIFICATIONS
Submit proof of the qualifications of the Contractor, Installers, and Manufacturers that will perform the work, and provide the specified products.
1.4.1 Minimum Contractor Qualifications
Work under this section shall be performed, and equipment shall be
SECTION 27 05 14.00 10 Page 2 furnished and installed, by a qualified Contractor as defined herein. The Contractor shall have a minimum of two years of experience in the installation and testing of coaxial cable-based TV distribution systems and equipment. Installers assigned to the installation of this system or its components shall have a minimum of two years of experience in the installation of the specified coaxial cable and components.
1.4.2 Minimum Manufacturer Qualifications
The equipment and hardware provided under this contract shall be products of manufacturers that have a minimum of two years of experience in producing the types of systems and equipment specified.
1.5 DELIVERY, STORAGE, AND HANDLING
Protect equipment delivered and placed in storage from the weather, humidity and temperature variation, dirt and dust or other contaminants.
1.6 ENVIRONMENTAL REQUIREMENTS
Connecting hardware shall be rated for operation under ambient conditions of 0 to 60 degrees C and in the range of 0 to 95 percent relative humidity, non-condensing.
1.7 EXTRA MATERIALS
Submit spare parts data for each different item of material and equipment specified, after approval of detail drawings, not later than 2 months prior to the date of beneficial occupancy. The data shall include a complete list of parts, tools, test equipment and supplies, with current unit prices and source of supply, and a list of spare parts recommended for stocking.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
Provide materials and equipment which are the standard products of a manufacturer regularly engaged in the manufacture of the products and that are the manufacturer's latest standard design that has been in satisfactory use for at least one year prior to installation. Where materials or equipment are specified to conform, be constructed or tested to meet specific requirements, submit certification that the items provided conform to such requirements. Certification by a nationally recognized testing laboratory that a representative sample has been tested to meet the requirements, or a published catalog specification statement to the effect that the item meets the referenced standard, is acceptable as evidence that the item conforms. Compliance with these requirements does not relieve the Contractor from compliance with other requirements of the specifications. Materials and equipment shall conform to the respective publications and other requirements specified below and to the applicable requirements of NFPA 70 . Cables shall be labeled on both ends with circuit number, room number, or other appropriate marking allowing for correct identification of the cable and its destination. Each faceplate shall be labeled with its function and a unique number to identify the cable run.
SECTION 27 05 14.00 10 Page 3
2.1.1 Outlet Boxes
Electrical boxes for cable television outlets shall be 117 mm square by 53 mm deep with minimum 9 mm deep single or two gang plaster ring as shown.
Conduits shall be minimum 27 mm in diameter.
PART 3 EXECUTION
3.1 INSTALLATION
Install system components and appurtenances in accordance with NFPA 70 , manufacturer's instructions and as shown. Submit record drawings for the installed cable system showing the locations of cable terminations, including outlets, and location and routing of cables. The identifier for each termination and cable shall appear on the drawings. Provide necessary interconnections, services, and adjustments required for a complete cable television distribution system, ready to connect to external television signal sources. Penetrations in fire-rated construction shall be firestopped in accordance with Section 07 84 00 FIRESTOPPING. Install conduits, outlets, raceways, and wiring in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Cables and outlets shall be individually labeled and marked. Cables shall not be installed in the same cable tray, utility pole compartment, or floor trench compartment with ac power cables. Cables not installed in conduit or wireways shall be properly secured and neat in appearance and, if installed in plenums or other spaces used for environmental air, shall comply with NFPA 70 requirements for this type of installation.
3.1.1 Pull Cords
Pull cords shall be installed in conduits serving the cable television premises distribution system which do not initially have cable installed.
3.2 GROUNDING
The cable television distribution system ground shall be installed in the cable television entrance facility and in any auxiliary closet identified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM or otherwise indicated.
Equipment racks shall be connected to the electrical safety ground.
-- End of Section --
SECTION 27 05 14.00 10 Page 4
SECTION TABLE OF CONTENTS
DIVISION 27 - COMMUNICATIONS
SECTION 27 10 00
BUILDING TELECOMMUNICATIONS CABLING SYSTEM
08/11
PART 1 GENERAL
1.1 REFERENCES
1.2 RELATED REQUIREMENTS
1.3 DEFINITIONS
1.3.1 Campus Distributor (CD)
1.3.2 Building Distributor (BD)
1.3.3 Floor Distributor (FD)
1.3.4 Telecommunications Room (TR)
1.3.5 Entrance Facility (EF) (Telecommunications)
1.3.6 Equipment Room (ER) (Telecommunications)
1.3.7 Open Cable
1.3.8 Open Office
1.3.9 Pathway
1.4 SYSTEM DESCRIPTION
1.5 SUBMITTALS
1.6 QUALITY ASSURANCE
1.6.1 Shop Drawings
1.6.1.1 Telecommunications Drawings
1.6.1.2 Telecommunications Space Drawings
1.6.2 Telecommunications Qualifications
1.6.2.1 Telecommunications Contractor
1.6.2.2 Key Personnel
1.6.2.3 Minimum Manufacturer Qualifications
1.6.3 Test Plan
1.6.4 Regulatory Requirements
1.6.5 Standard Products
1.6.5.1 Alternative Qualifications
1.6.5.2 Material and Equipment Manufacturing Date
1.7 DELIVERY AND STORAGE
1.8 ENVIRONMENTAL REQUIREMENTS
1.9 WARRANTY
1.10 MAINTENANCE
1.10.1 Operation and Maintenance Manuals
1.10.2 Record Documentation
PART 2 PRODUCTS
2.1 COMPONENTS
2.2 TELECOMMUNICATIONS PATHWAY
2.3 TELECOMMUNICATIONS CABLING
2.3.1 Backbone Cabling
2.3.1.1 Backbone Copper
2.3.1.2 Backbone Optical Fiber
2.3.2 Horizontal Cabling
2.3.2.1 Horizontal Copper
SECTION 27 10 00 Page 1
2.4 TELECOMMUNICATIONS SPACES
2.4.1 Backboards
2.4.2 Equipment Support Frame
2.4.3 Connector Blocks
2.4.4 Cable Guides
2.4.5 Patch Panels
2.4.5.1 Modular to 110 Block Patch Panel
2.4.5.2 Fiber Optic Patch Panel
2.5 TELECOMMUNICATIONS OUTLET/CONNECTOR ASSEMBLIES
2.5.1 Outlet/Connector Copper
2.5.2 Optical Fiber Adapters(Couplers)
2.5.3 Optical Fiber Connectors
2.5.4 Cover Plates
2.6 GROUNDING AND BONDING PRODUCTS
2.6.1 2.4.1 Grounding Block
2.7 FIRESTOPPING MATERIAL
2.8 MANUFACTURER'S NAMEPLATE
2.9 FIELD FABRICATED NAMEPLATES
2.10 TESTS, INSPECTIONS, AND VERIFICATIONS
2.10.1 Factory Reel Tests
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Cabling
3.1.1.1 Backbone Cable
3.1.1.2 Horizontal Cabling
3.1.2 Pathway Installations
3.1.3 Service Entrance Conduit, Underground
3.1.4 Cable Tray Installation
3.1.5 Work Area Outlets
3.1.5.1 Terminations
3.1.5.2 Cover Plates
3.1.5.3 Cables
3.1.5.4 Pull Cords
3.1.6 Telecommunications Space Termination
3.1.6.1 Connector Blocks
3.1.6.2 Patch Panels
3.1.6.3 Equipment Support Frames
3.1.7 Electrical Penetrations
3.1.8 Grounding and Bonding
3.2 LABELING
3.2.1 Labels
3.2.2 Cable
3.2.3 Termination Hardware
3.3 FIELD APPLIED PAINTING
3.3.1 Painting Backboards
3.4 FIELD FABRICATED NAMEPLATE MOUNTING
3.5 TESTING
3.5.1 Telecommunications Cabling Testing
3.5.1.1 Inspection
3.5.1.2 Verification Tests
3.5.1.3 Performance Tests
3.5.1.4 Final Verification Tests
-- End of Section Table of Contents --
SECTION 27 10 00 Page 2
SECTION 27 10 00
BUILDING TELECOMMUNICATIONS CABLING SYSTEM
08/11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. Contractor may substitute compatible Japan Industrial Standard (JIS), Japan Architectural Standard Specification (JASS), or Japan Wire Industry Association Standard (JCS) standards for non-Japanese standards, as approved by the Contracting Officer's representative.
JAPAN WIRE INDUSTRY ASSOCIATION STANDARD (JCS)
JCS 5507 (2010) LAN Twisted Pair Cable
JAPANESE INDUSTRIAL STANDARDS (JIS)
JIS C 3665-1-1 (2007) Tests on electric and optical fibre cables under fire conditions -- Part 1-1:
Test for vertical flame propagation for a single insulated wire or cable -- Apparatus
JIS C 5964-20 (2015) Fiber optic connector interfaces -- Part 20: Type LC connector family
JIS C 6011-1 (2015) Mechanical structures for electronic equipment -- Tests for IEC 60917 and IEC 60297 series -- Part 1:
Environmental requirements, test set-up and safety aspects for cabinets, racks, subracks and chassis under indoor conditions
JIS C 6012-3-100 (2015) Mechanical structures for electronic equipment -- Dimensions of mechanical structures of the 482.6 mm (19
in) series -- Part 3-100: Basic dimensions of front panels, subracks, chassis, racks and cabinets
JIS C 6185-2 (2014) Optical time-domain reflectometers (OTDR) -- Part 2: Calibration of OTDR for single mode fibers
JIS C 6185-3 (2014) Optical time-domain reflectometers (OTDR) -- Part 3: Calibration of OTDR for multimode fibers
JIS C 6820 (2018) General rules of optical fibers
JIS C 6850 (2006) General rules of optical fiber
SECTION 27 10 00 Page 3 cables
JIS C 6870-2 (2006) Indoor optical fiber cables -- Part 2: Sectional specification
JIS C 8435 (2018) Boxes And Box Covers Of Plastic Conduits
JIS C 60364-4-42 (2006) Electrical installations of buildings -- Part 4-42: Protection for safety -- Protection against thermal effects
JIS C 60364-5-54 (2006) Building Electrical Equipment-Part 5-54: Selection Of Electrical Equipment and Contruction-Grounding Equipment, Protective Conductor and Protective Bonding Conductor
JIS C 61300-2-2 (2011) Fiber optic interconnecting devices and passive components -- Basic test and measurement procedures -- Part 2-2: Tests -- Mating durability
JIS K 6911 (2006) Thermosetting plastic general test method
JIS X 5150 (R2016) Information Technology-Generic Cabling for Customer Premises
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA VE 2 (2013; ERTA 2016) Cable Tray Installation Guidelines
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.0 (2009; Add 1 2010; Add 2 2012) Generic Telecommunications Cabling for Customer Premises
TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial Building Telecommunications Cabling Standard
TIA-569 (2015d) Commercial Building Standard for Telecommunications Pathways and Spaces
TIA-606 (2017c) Administration Standard for the Telecommunications Infrastructure
TIA-607 (2015c; Addendum 1 2017) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. ARMY INFORMATION SYSTEMS ENGINEERING COMMAND (USAISEC)
I3A (2010) Technical Criteria for the Installation Information Infrastructure
SECTION 27 10 00 Page 4
Architecture
UNIFIED FACILITIES CRITERIA (UFC)
UFC 3-580-01 (2016) Telecommunications Infrastructure Planning and Design, With Change 1
UNDERWRITERS LABORATORIES (UL)
UL 1666 (2007; Reprint Jun 2012) Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts
UL 723 (2018) UL Standard for Safety Test for Surface Burning Characteristics of Building Materials
1.2 RELATED REQUIREMENTS
Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM and Section 33 82 00 TELECOMMUNICATIONS, OUTSIDE PLANT (OSP), apply to this section with additions and modifications specified herein.
1.3 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in this specification shall be as defined in JIS X 5150 , JCS 5507 , JIS C 6820 , JIS C 6850 , and herein.
1.3.1 Campus Distributor (CD)
A distributor from which the campus backbone cabling emanates.
(International expression for main cross-connect (MC).)
1.3.2 Building Distributor (BD)
A distributor in which the building backbone cables terminate and at which connections to the campus backbone cables may be made. (International expression for intermediate cross-connect (IC).)
1.3.3 Floor Distributor (FD)
A distributor used to connect horizontal cable and cabling subsystems or equipment. (International expression for horizontal cross-connect (HC).)
1.3.4 Telecommunications Room (TR)
An enclosed space for housing telecommunications equipment, cable, terminations, and cross-connects. The room is the recognized cross-connect between the backbone cable and the horizontal cabling.
1.3.5 Entrance Facility (EF) (Telecommunications)
An entrance to the building for both private and public network service cables (including wireless) including the entrance point at the building wall and continuing to the equipment room.
SECTION 27 10 00 Page 5
1.3.6 Equipment Room (ER) (Telecommunications)
An environmentally controlled centralized space for telecommunications equipment that serves the occupants of a building. Equipment housed therein is considered distinct from a telecommunications room because of the nature of its complexity.
1.3.7 Open Cable
Cabling that is not run in a raceway as defined by applicable codes and standards. This refers to cabling that is "open" to the space in which the cable has been installed and is therefore exposed to the environmental conditions associated with that space.
1.3.8 Open Office
A floor space division provided by furniture, moveable partitions, or other means instead of by building walls.
1.3.9 Pathway
A physical infrastructure utilized for the placement and routing of telecommunications cable.
1.4 SYSTEM DESCRIPTION
The building telecommunications cabling and pathway system shall include permanently installed backbone and horizontal cabling, horizontal and backbone pathways, service entrance facilities, work area pathways, telecommunications outlet assemblies, conduit, raceway, and hardware for splicing, terminating, and interconnecting cabling necessary to transport telephone and data (including LAN) between equipment items in a building. The horizontal system shall be wired in a star topology from the telecommunications work area to the floor distributor or campus distributor at the center or hub of the star. The backbone cabling and pathway system includes intrabuilding and interbuilding interconnecting cabling, pathway, and terminal hardware. The intrabuilding backbone provides connectivity from the floor distributors to the building distributors or to the campus distributor and from the building distributors to the campus distributor as required. The backbone system shall be wired in a star topology with the campus distributor at the center or hub of the star. The interbuilding backbone system provides connectivity between the campus distributors and is specified in Section 33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP). Provide telecommunications pathway systems referenced herein as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Telecommunications drawings ; G
Telecommunications Space Drawings ; G
SECTION 27 10 00 Page 6
In addition to Section 01 33 00 SUBMITTAL PROCEDURES, provide shop drawings in accordance with paragraph SHOP DRAWINGS.
SD-03 Product Data
Telecommunications cabling (backbone and horizontal); G
Patch panels ; G
Telecommunications outlet/connector assemblies ; G
Equipment support frame ; G
Connector blocks ; G
Grounding Block ; G
SD-06 Test Reports
Telecommunications cabling testing ; G
SD-10 Operation and Maintenance Data
Telecommunications Cabling And Pathway System Data Package 5; G
SD-11 Closeout Submittals
Record Documentation ;
1.6 QUALITY ASSURANCE
1.6.1 Shop Drawings
In exception to Section 01 33 00 SUBMITTAL PROCEDURES, submitted plan drawings shall be a minimum of 279 by 432 mm in size using a minimum scale of one mm per 100 mm . Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment.
Drawings shall indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices. Submittals shall include the nameplate data, size, and capacity. Submittals shall also include applicable federal, military, industry, and technical society publication references. Shop drawings shall comply with UFC 3-580-01 and I3A . As-built drawings (soft copy) shall be submitted to NCTS FE N21 after project completion.
1.6.1.1 Telecommunications Drawings
Provide registered communications distribution designer (RCDD) approved drawings in accordance with applicable codes and standards. The identifier for each termination and cable shall appear on the drawings.
Drawings shall depict final telecommunications installed wiring system infrastructure. The drawings should provide details required to prove that the distribution system shall properly support connectivity from the EF telecommunications and ER telecommunications, CD's, BD's, and FD's to
SECTION 27 10 00 Page 7 the telecommunications work area outlets. Provide a plastic laminated schematic of the as-installed telecommunications cable system showing cabling, CD's, BD's, FD's, and the EF and ER for telecommunications keyed to floor plans by room number. Mount the laminated schematic in the EF telecommunications space as directed by the Contracting Officer. The following drawings shall be provided as a minimum:
a. T1 - Layout of complete building per floor - Building Area/Serving Zone Boundaries, Backbone Systems, and Horizontal Pathways. Layout of complete building per floor. The drawing indicates location of building areas, serving zones, vertical backbone diagrams, telecommunications rooms, access points, pathways, grounding system, and other systems that need to be viewed from the complete building perspective.
b. T2 - Serving Zones/Building Area Drawings - Drop Locations and Cable Identification (ID’S). Shows a building area or serving zone. These drawings show drop locations, telecommunications rooms, access points and detail call outs for common equipment rooms and other congested areas. Provide laminated T2 as-built drawings wall mounted in each telecom room.
c. T4 - Typical Detail Drawings - Faceplate Labeling, Firestopping, Americans with Disabilities Act (ADA), Safety, Department of Transportation (DOT). Detailed drawings of symbols and typicals such as faceplate labeling, faceplate types, faceplate population installation procedures, detail racking, and raceways.
1.6.1.2 Telecommunications Space Drawings
Provide T3 drawings that include telecommunications rooms plan views, pathway layout (cable tray, racks, ladder-racks, etc.), mechanical/electrical layout, and cabinet, rack, backboard and wall elevations. Drawings shall show layout of applicable equipment including incoming cable stub or connector blocks, building protector assembly, outgoing cable connector blocks, patch panels and equipment spaces and cabinet/racks. Drawings shall include a complete list of equipment and material, equipment rack details, proposed layout and anchorage of equipment and appurtenances, and equipment relationship to other parts of the work including clearance for maintenance and operation. Drawings may also be an enlargement of a congested area of T1 or T2 drawings.
1.6.2 Telecommunications Qualifications
Work under this section shall be performed by and the equipment shall be provided by the approved telecommunications contractor and key personnel.
Qualifications shall be provided for: the telecommunications system contractor, the telecommunications system installer, and the supervisor (if different from the installer). A minimum of 30 days prior to installation, submit documentation of the experience of the telecommunications contractor and of the key personnel.
1.6.2.1 Telecommunications Contractor
The telecommunications contractor shall be a firm which is regularly and professionally engaged in the business of the applications, installation, and testing of the specified telecommunications systems and equipment.
The telecommunications contractor shall demonstrate experience in providing successful telecommunications systems within the past 3 years of
SECTION 27 10 00 Page 8 similar scope and size. Submit documentation for a minimum of three and a maximum of five successful telecommunication system installations for the telecommunications contractor.
1.6.2.2 Key Personnel
Provide key personnel who are regularly and professionally engaged in the business of the application, installation and testing of the specified telecommunications systems and equipment. There may be one key person or more key persons proposed for this solicitation depending upon how many of the key roles each has successfully provided. Each of the key personnel shall demonstrate experience in providing successful telecommunications systems within the past 3 years.
Supervisors and installers assigned to the installation of this system or any of its components shall be Building Industry Consulting Services International (BICSI) Registered Cabling Installers, Technician Level.
Submit documentation of current BICSI certification for each of the key personnel.
In lieu of BICSI certification, supervisors and installers assigned to the installation of this system or any of its components shall have a minimum of 3 years experience in the installation of the specified copper and fiber optic cable and components. They shall have factory or factory approved certification from each equipment manufacturer indicating that they are qualified to install and test the provided products. Submit documentation for a minimum of three and a maximum of five successful telecommunication system installations for each of the key personnel.
Documentation for each key person shall include at least two successful system installations provided that are equivalent in system size and in construction complexity to the telecommunications system proposed for this solicitation. Include specific experience in installing and testing telecommunications systems and provide the names and locations of at least two project installations successfully completed using optical fiber and copper telecommunications cabling systems. All of the existing telecommunications system installations offered by the key persons as successful experience shall have been in successful full-time service for at least 18 months prior to the issuance date for this solicitation.
Provide the name and role of the key person, the title, location, and completed installation date of the referenced project, the referenced project owner point of contact information including name, organization, title, and telephone number, and generally, the referenced project description including system size and construction complexity.
Indicate that all key persons are currently employed by the telecommunications contractor, or have a commitment to the telecommunications contractor to work on this project. All key persons shall be employed by the telecommunications contractor at the date of issuance of this solicitation, or if not, have a commitment to the telecommunications contractor to work on this project by the date that the bid was due to the Contracting Officer.
Note that only the key personnel approved by the Contracting Officer in the successful proposal shall do work on this solicitation's telecommunications system. Key personnel shall function in the same roles in this contract, as they functioned in the offered successful experience. Any substitutions for the telecommunications contractor's key personnel requires approval from The Contracting Officer.
SECTION 27 10 00 Page 9
1.6.2.3 Minimum Manufacturer Qualifications
Cabling, equipment and hardware manufacturers shall have a minimum of 3 years experience in the manufacturing, assembly, and factory testing of components which comply with JIS X 5150 , JCS 5507 and JIS C 6820 and
JIS C 6850 .
1.6.3 Test Plan
Provide a complete and detailed test plan for the telecommunications cabling system including a complete list of test equipment for the components and accessories for each cable type specified, 60 days prior to the proposed test date. Include procedures for certification, validation, and testing.
1.6.4 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of applicable codes and standards unless more stringent requirements are specified or indicated.
1.6.5 Standard Products
Telecom materials shall be listed in accordance with NCTS FE acceptable material list (AML) for maintenance reasons. Submittals shall be forwarded to NCTS FE for approval. Conflicts with NCTS AML will not be considered reason for dismissal if DoDEA standard will be compromised by a change.
DoDEA will accept the cost and delay burden incurred for maintenance to maintain organization standard.
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.6.5.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.6.5.2 Material and Equipment Manufacturing Date
Products manufactured more than 1 year prior to date of delivery to site shall not be used, unless specified otherwise.
SECTION 27 10 00 Page 10
1.7 DELIVERY AND STORAGE
Provide protection from weather, moisture, extreme heat and cold, dirt, dust, and other contaminants for telecommunications cabling and equipment placed in storage.
1.8 ENVIRONMENTAL REQUIREMENTS
Connecting hardware shall be rated for operation under ambient conditions of 0 to 60 degrees C and in the range of 0 to 95 percent relative humidity, noncondensing.
1.9 WARRANTY
The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.10 MAINTENANCE
1.10.1 Operation and Maintenance Manuals
Commercial off the shelf manuals shall be furnished for operation, installation, configuration, and maintenance of products provided as a part of the telecommunications cabling and pathway system , Data Package
5. Submit operations and maintenance data in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA and as specified herein not later than 2 months prior to the date of beneficial occupancy. In addition to requirements of Data Package 5, include the requirements of paragraphs TELECOMMUNICATIONS DRAWINGS, TELECOMMUNICATIONS SPACE DRAWINGS, and RECORD DOCUMENTATION. Ensure that these drawings and documents depict the as-built configuration.
1.10.2 Record Documentation
Provide T5 drawings including documentation on cables and termination hardware. T5 drawings shall include schedules to show information for cut-overs and cable plant management, patch panel layouts and cover plate assignments, cross-connect information and connecting terminal layout as a minimum. T5 drawings shall be provided in hard copy format Provide the following T5 drawing documentation as a minimum:
a. Cables - A record of installed cable shall be provided. The cable records shall include only the required data fields. Include manufacture date of cable with submittal.
b. Termination Hardware - A record of installed patch panels, cross-connect points, distribution frames, terminating block arrangements and type, and outlets shall be provided. Documentation shall include the required data fields as a minimum.
PART 2 PRODUCTS
2.1 COMPONENTS
Components shall be UL or third party certified. Where equipment or materials are specified to conform to industry and technical society
SECTION 27 10 00 Page 11 reference standards of the organizations, submit proof of such compliance. The label or listing by the specified organization will be acceptable evidence of compliance. In lieu of the label or listing, submit a certificate from an independent testing organization, competent to perform testing, and approved by the Contracting Officer. The certificate shall state that the item has been tested in accordance with the specified organization's test methods and that the item complies with the specified organization's reference standard. Provide a complete system of telecommunications cabling and pathway components using star topology. Provide support structures and pathways, complete with outlets, cables, connecting hardware and telecommunications cabinets/racks.
Cabling and interconnecting hardware and components for telecommunications systems shall be listed or third party independent testing laboratory certified, and shall comply with applicable codes and standards and conform to the requirements specified herein.
2.2 TELECOMMUNICATIONS PATHWAY
Provide telecommunications pathways in accordance with JIS X 5150 and as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.
2.3 TELECOMMUNICATIONS CABLING
Cabling shall be listed for the application and shall comply with JIS X 5150 , JCS 5507 , JIS C 6820 and JIS C 6850 . Provide a labeling system for cabling as required. Ship cable on reels or in boxes bearing manufacture date for for unshielded twisted pair (UTP) in accordance with JCS 5507 and optical fiber cables in accordance with JIS C 6870-2 for all cable used on this project. Cabling manufactured more than 12 months prior to date of installation shall not be used.
2.3.1 Backbone Cabling
2.3.1.1 Backbone Copper
Copper backbone cable shall be solid conductor, 0.2 sqmm, 100 ohm, 200 -pair, Category 3, UTP, in accordance with UFC 3-580-01 , formed into 25 pair binder groups covered with a gray thermoplastic jacket and overall metallic shield. Cable shall be imprinted with manufacturers name or identifier, flammability rating, gauge of conductor, transmission performance rating (category designation) at regular length marking intervals in accordance with JCS 5507 . Provide plenum (CMP), riser (CMR), or general purpose (CM or CMG)communications rated cabling as required.
Substitution of a higher rated cable shall be permitted upon approval prior to installation.
2.3.1.2 Backbone Optical Fiber
Provide in accordance with JIS C 6870-2 , JIS C 6820 , JIS C 6850 , UL 1666 and JIS C 3665-1-1 . Cable shall be imprinted with fiber count, fiber type and aggregate length at regular intervals not to exceed 1 meter .
Provide the number of strands indicated, (but not less than 12 strands between the main telecommunication room and each of the other telecommunication rooms), of single-mode(OS 2), tight buffered fiber optic cable.
Provide tight buffered fiber optic multimode, 50/125-um diameter laser optimized(OM 4) cable as indicated.
SECTION 27 10 00 Page 12
Provide plenum (OFNP), riser (OFNR), or general purpose (OFN or OFNG) rated non-conductive, fiber optic cable as required per application.
Substitution of a higher rated cable shall be permitted. The cable cordage jacket, fiber, unit, and group color shall be in accordance with JIS X 5150 .
Provide plenum (OFNP) riser (OFNR) , or general purpose (OFN or OFNG) rated non-conductive, fiber optic cable as required per application.
Substitution of a higher rated cable shall be permitted . The cable cordage jacket, fiber, unit, and group color shall be in accordance with
JIS X 5150 .
2.3.2 Horizontal Cabling
Provide horizontal cable and performance characteristics in accordance with JIS X 5150 .
2.3.2.1 Horizontal Copper
Provide horizontal copper cable, UTP, 100 ohm in accordance with UFC 3-580-01 . Provide four each individually twisted pair, minimum size
0.2 sqmm conductors, Category 6, with a Blue for Data, Red for Video Distribution, Orange for Wireless Access Points, Yellow for Voice, Violet for Electronic Security Systems, and Black for School Systems, unless otherwise noted, thermoplastic jacket. All UTP cabling shall be Category 6.
Cable shall be imprinted with manufacturers name or identifier, flammability rating, gauge of conductor, transmission performance rating (category designation) and length marking at regular intervals in accordance with JCS 5507 . Provide plenum (CMP), riser (CMR), or general purpose (CM or CMG) communications rated cabling as required per application. Substitution of a higher rated cable shall be permitted.
Cables installed in conduit within and under slabs shall be listed and labeled for wet locations.
2.4 TELECOMMUNICATIONS SPACES
Provide connecting hardware and termination equipment in the telecommunications entrance facility and telecommunication equipment rooms to facilitate installation as shown on design drawings for terminating and cross-connecting permanent cabling. Provide telecommunications interconnecting hardware color coding in accordance with base standards.
2.4.1 Backboards
Provide void-free, interior grade A-C plywood 19 mm thick 1200 by 2400 mm .
Backboards shall be fire rated by manufacturing process. Fire stamp shall be clearly visible. Paint applied over fire retardant backboard shall be UL 723 and JIS C 60364-4-42 fire retardant paint. Provide label including paint manufacturer, date painted, UL listing and name of Installer. When painted, paint label and fire stamp shall be clearly visible. Backboards shall be provided on a minimum of two adjacent walls in the telecommunication spaces.
2.4.2 Equipment Support Frame
Provide in accordance with JIS C 6011-1 and JIS C 6012-3-100 . Provide full complement of mounting hardware for each rack or cabinet.
a. Racks, floor mounted modular type, 11 gauge aluminum construction, SECTION 27 10 00 Page 13 minimum, treated to resist corrosion. Provide rack with vertical and horizontal cable management channels, top and bottom cable troughs, grounding lug and a surge protected power strip with 6 duplex 20 amp receptacles. Rack shall be compatible with 482.6 mm panel mounting.
b. Cabinets, wall-mounted modular type, 11 gauge aluminum construction , minimum, treated to resist corrosion. Cabinet shall have have lockable front door, louvered side panels, 7 cu. m roof mounted fan, ground lug, and top and bottom cable access. Cabinet shall be compatible with 482.6 mm panel mounting. All cabinets shall be keyed alike. Surge protected power strip with 6 duplex 20 amp receptacles shall be provided within the cabinet.
2.4.3 Connector Blocks
Provide insulation displacement connector (IDC) Type 110 for Category 6 systems. Provide blocks for the number of horizontal and backbone cables terminated on the block plus 25 percent spare.
2.4.4 Cable Guides
Provide cable guides specifically manufactured for the purpose of routing cables, wires and patch cords horizontally and vertically on 482.6 mm equipment racks , cabinets and telecommunications backboards. Cable guides of ring or bracket type devices mounted on rack , cabinet or backboard for horizontal cable management and individually mounted for vertical cable management. Vertical cable managers shall be installed on front and back of racks and cabinets. Mount cable guides with screws or nuts and lockwashers.
2.4.5 Patch Panels
Provide ports for the number of horizontal and backbone cables terminated on the panel plus 25 percent spare. Provide pre-connectorized optical fiber and copper patch cords for patch panels. Provide patch cords, as complete assemblies, with matching connectors as specified. Provide fiber optic patch cables with crossover orientation in accordance with JIS C 6820 and JIS C 6850 . Patch cords shall meet minimum performance requirements specified in JIS X 5150 , JCS 5507 and JIS C 6820 and JIS C 6850 for cables, cable length and hardware specified.
2.4.5.1 Modular to 110 Block Patch Panel
Provide in accordance with JIS X 5150 and JCS 5507 . Panels shall be third party verified and shall comply with EIA/TIA Category 6 requirements.
Panel shall be constructed of 2.2 mm minimum aluminum and shall be cabinet or rack mounted and compatible with JIS C 6012-3-100 482.6 mm equipment cabinet or rack. Panel shall provide 48 non-keyed, 8-pin modular ports, wired to T568B. Patch panels shall terminate the building cabling on Type 110 IDCs and shall utilize a printed circuit board interface. The rear of each panel shall have incoming cable strain-relief and routing guides.
Panels shall have each port factory numbered and be equipped with laminated plastic nameplates above each port.
2.4.5.2 Fiber Optic Patch Panel
Provide panel for maintenance and cross-connecting of optical fiber cables. Panel shall be constructed of 11 gauge aluminum minimum and shall
SECTION 27 10 00 Page 14 be cabinet or rack mounted and compatible with a JIS C 6012-3-100 482.6 mm equipment rack. Each panel shall provide 12 multimode and 12 single-mode adapters as duplex LC/UPC in accordance with JIS C 5964-20 with zirconia ceramic…