Specifications_Volume_4_-_IFC_Reception_Phase_I.PDF

PDF 12 MB Posted

Attached to
Reception Complex Phase 1 Federal contract opportunity
Solicitation number
W912HP19R2000
Issued by
Department of the Army Corps of Engineers Engineering District Charleston

About this file

This solicitation package includes specifications and drawings for the Reception Complex Phase 1 project at Fort Jackson, South Carolina. The U.S. Army Corps of Engineers, Charleston District is seeking proposals for construction services, to be submitted by September 6, 2019. Four volumes of drawings and five volumes of specifications describe the project scope. A site visit is scheduled for August 20 to review details. The solicitation includes attachments for past performance questionnaires, small business participation plans, and proposal data sheets. Questions must be submitted through Projnet.

Specs Vol 4

View the file

Other files for this federal contract opportunity

Other files attached to Reception Complex Phase 1, newest first.
File Type Posted
B._AMD_0006_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
B._AMD0006_Solicitation_W912HP19R2001_BTC4.pdf PDF
B._AMD_0005_Solicitation_19R2000_Reception_Complex_Phase_1.pdf PDF
Specifications_Volume_5_-_IFC_Reception_Phase_1_AMD4.pdf PDF
B._AMD_0004_Solicitation_W912HP19R20000_Reception_Complex.pdf PDF
Drawings_Volume_2_-_IFC_Reception_Phase_1_AMD3.pdf PDF
B._AMD_0003_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
Drawings_Volume_3_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Drawings_Volume_2_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Specifications_Volume_2_-_IFC_Reception_Phase_1_AMD2.PDF PDF
Drawings_Volume_1_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Specifications_Volume_5_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Specifications_Volume_1_-_IFC_Reception_Phase_1_AMD2.PDF PDF
B._AMD_0002_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
B._AMD_0001_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
Specifications_Volume_1_-_IFC_Reception_Phase_I_AMD1.pdf PDF
A._Site_Visit_Sign-In_Sheet.pdf PDF
Specifications_Volume_2_-_IFC_Reception_Phase_I_AMD1.pdf PDF
Drawings_Volume_1_-_IFC_Reception_Phase_1_AMD1.pdf PDF
Drawings_Volume_3_-_IFC_Reception_Phase_I_AMD1.pdf PDF
Specifications_Volume_5_-_IFC_Reception_Phase_AMD1.pdf PDF
Drawings_Volume_2_-_IFC_Recepton_Phase_1_AMD1.pdf PDF
Specifications_Volume_3_-_IFC_Reception_Phase_I_AMD1.pdf PDF
junc-sp1.dgn —
junc-up.dgn —
junv-rp.dgn —
junc-gp1.dgn —
junc-gp.dgn —
junc-dp.dgn —
junv-tp.dgn —
junc-sp.dgn —
Specifications_Volume_2_-_IFC_Reception_Phase_I.PDF PDF
Specifications_Volume_1_-_IFC_Reception_Phase_I.PDF PDF
Drawings_Volume_1_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_2_-_Descriptive_Summary_Sheet.pdf PDF
Drawings_Volume_2_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_3_-_Past_Performance_Questionnaire.pdf PDF
Specifications_Volume_3_-_IFC_Reception_Phase_I.PDF PDF
Specifications_Volume_5_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_4_-_Small_Business_Participation_Plan.pdf PDF
Drawings_Volume_3_-_IFC_Reception_Phase_I.pdf PDF
B._Solicitation_W912HP19R2000_Reception_Complex_Phase_1,_Ft._Jax.pdf PDF
Drawings_Volume_4_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_1_-_Proposal_Data_Sheet.pdf PDF
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fort Jackson, South Carolina

Solicitation Number

W912HP-19-R-2000

Reception Complex Volume 4 of 5: Appendices

PN 76149

June 2019

U.S. ARMY ENGINEER DISTRICT, SAVANNAH

CORPS OF ENGINEERS

100 WEST OGLETHORPE AVENUE

SAVANNAH, GEORGIA 31401-3640

US Army Corps of Engineers Charleston District

Recept i on Compl ex JA76149 Ft . Jackson, SC

PROJECT TABLE OF CONTENTS

DI VI SI ON 01 - GENERAL REQUI REMENTS

01 11 00 SUMMARY OF WORK

01 30 00 ADMI NI STRATI VE REQUI REMENTS

01 32 01 PROJECT SCHEDULE

01 33 00 SUBMI TTAL PROCEDURES

01 33 29 SUSTAI NABI LI TY REPORTI NG

01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS

01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS

01 45 00 QUALI TY CONTROL

01 45 00. 15 RESI DENT MANAGEMENT SYSTEM CONTRACTOR MODE ( RMS CM)

01 45 35 SPECI AL I NSPECTI ONS

01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS

01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS

01 57 19. 37 I NDOOR AI R QUALI TY ( I AQ) MANAGEMENT

01 74 19. 37 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT

01 78 00 CLOSEOUT SUBMI TTALS

01 78 23 OPERATI ON AND MAI NTENANCE DATA

01 91 00 COMMISSIONING

DI VI SI ON 02 - EXI STI NG CONDI TI ONS

02 83 13 LEAD I N CONSTRUCTI ON

DI VI SI ON 03 - CONCRETE

03 11 13 STRUCTURAL CAST- I N- PLACE CONCRETE FORMI NG

03 15 00 CONCRETE ACCESSORI ES

03 20 00 CONCRETE REI NFORCI NG

03 30 00 CAST- I N- PLACE CONCRETE

03 35 00 CONCRETE FI NI SHI NG

03 39 00 CONCRETE CURI NG

DI VI SI ON 04 - MASONRY

04 20 00 MASONRY

DI VI SI ON 05 - METALS

05 12 00 STRUCTURAL STEEL

05 30 00 STEEL DECKS

05 40 00 COLD- FORMED METAL FRAMI NG

05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS

05 51 33 METAL LADDERS

05 52 00 METAL RAI LI NGS

DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES

06 10 00 ROUGH CARPENTRY

06 20 00 FI NI SH CARPENTRY

06 41 16 LAMI NATE CLAD ARCHI TECTURAL CASEWORK

06 61 16 SOLI D POLYMER ( SOLI D SURFACI NG) FABRI CATI ONS

DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON

07 05 23 PRESSURE TESTI NG AN AI R BARRI ER SYSTEM FOR AI R TI GHTNESS

07 21 13 BOARD AND BLOCK I NSULATI ON

PROJECT TABLE OF CONTENTS Page 1

07 21 16 MI NERAL FI BER BLANKET I NSULATI ON

07 22 00 ROOF AND DECK I NSULATI ON

07 27 10 BUI LDI NG AI R BARRI ER SYSTEM

07 41 00 METAL SOFFI T PANELS

07 41 13 METAL ROOF PANELS

07 42 13 METAL WALL PANELS

07 60 00 FLASHI NG AND SHEET METAL

07 61 14 STEEL STANDI NG SEAM ROOFI NG

07 84 00 FIRESTOPPING

07 92 00 JOI NT SEALANTS

DI VI SI ON 08 - OPENI NGS

08 11 13 STEEL DOORS AND FRAMES

08 11 16 ALUMI NUM DOORS AND FRAMES

08 14 00 WOOD DOORS

08 34 73 SOUND CONTROL DOOR ASSEMBLI ES

08 51 13 ALUMI NUM WI NDOWS

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 91 00 METAL WALL LOUVERS

DI VI SI ON 09 - FI NI SHES

09 06 00 SCHEDULES FOR FI NI SHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 30 10 CERAMI C, QUARRY, AND GLASS TI LI NG

09 51 00 ACOUSTI CAL CEI LI NGS

09 65 00 RESI LI ENT FLOORI NG

09 68 00 CARPETING

09 90 00 PAI NTS AND COATI NGS

DI VI SI ON 10 - SPECI ALTI ES

10 10 00 VI SUAL COMMUNI CATI ONS SPECI ALTI ES

10 14 01 EXTERI OR SI GNAGE

10 14 02 I NTERI OR SI GNAGE

10 21 13 TOI LET COMPARTMENTS

10 26 00 WALL AND DOOR PROTECTI ON

10 28 13 TOI LET ACCESSORI ES

10 56 13 STEEL SHELVI NG

DI VI SI ON 11 - EQUI PMENT

11 13 19. 13 LOADI NG DOCK LEVELERS

11 21 73 VERTI CAL CAROUSELS

DI VI SI ON 12 - FURNI SHI NGS

12 24 13 ROLLER WI NDOW SHADES

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

12 50 00 FURNI TURE AND FURNI TURE I NSTALLATI ON

DI VI SI ON 13 - SPECI AL CONSTRUCTI ON

13 34 19 METAL BUI LDI NG SYSTEMS

13 48 00 SEI SMI C BRACI NG FOR MI SCELLANEOUS EQUI PMENT

PROJECT TABLE OF CONTENTS Page 2

DI VI SI ON 21 - FI RE SUPPRESSI ON

21 13 13 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON

21 30 00 FI RE PUMPS

DI VI SI ON 22 - PLUMBI NG

22 00 00 PLUMBI NG, GENERAL PURPOSE

DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)

23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

23 05 48. 19 SEI SMI C BRACI NG FOR HVAC

23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC

23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS

23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC

23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC

23 09 23. 01 LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER

BUI LDI NG CONTROL SYSTEMS

23 11 25 FACI LI TY GAS PI PI NG

23 23 00 REFRI GERANT PI PI NG

23 25 00 CHEMI CAL TREATMENT OF WATER FOR MECHANI CAL SYSTEMS

23 52 00 HEATI NG BOI LERS

23 57 10 FORCED HOT WATER HEATI NG SYSTEMS USI NG WATER AND STEAM

HEAT EXCHANGERS

23 64 10 WATER CHI LLERS, VAPOR COMPRESSI ON TYPE

23 64 26 CHI LLED, CHI LLED- HOT, AND CONDENSER WATER PI PI NG SYSTEMS

23 81 00 DECENTRALI ZED UNI TARY HVAC EQUI PMENT

23 82 46 ELECTRI C UNI T HEATERS

DI VI SI ON 25 - I NTEGRATED AUTOMATI ON

25 05 11 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS

25 05 12 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS

( SPECI AL SYSTEMS)

25 05 13 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS

(FA/MNS)

DI VI SI ON 26 - ELECTRI CAL

26 00 00 BASI C ELECTRI CAL MATERI ALS AND METHODS

26 05 48 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT

26 08 00 APPARATUS I NSPECTI ON AND TESTI NG

26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM

26 23 00 SWITCHBOARDS

26 28 01 COORDI NATED POWER SYSTEM PROTECTI ON

26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS

26 41 00 LI GHTNI NG PROTECTI ON SYSTEM

26 42 14 CATHODI C PROTECTI ON SYSTEM ( SACRI FI CI AL ANODE)

26 51 00 I NTERI OR LI GHTI NG

DI VI SI ON 27 - COMMUNI CATI ONS

27 05 14 CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM

27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM

27 51 16 SOUND REI NFORCEMENT SYSTEMS

DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY

PROJECT TABLE OF CONTENTS Page 3

28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEMS

DI VI SI ON 31 - EARTHWORK

31 00 00 EARTHWORK

31 05 19 GEOTEXTILE

31 11 00 CLEARI NG AND GRUBBI NG

31 31 16. 13 CHEMI CAL TERMI TE CONTROL

31 32 11 SOI L SURFACE EROSI ON CONTROL

DI VI SI ON 32 - EXTERI OR I MPROVEMENTS

32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D

PAVEMENTS

32 05 33 LANDSCAPE ESTABLI SHMENT

32 11 16 BASE COURSE FOR RI GI D PAVI NG

32 11 23 AGGREGATE AND/ OR GRADED- CRUSHED AGGREGATE BASE COURSE

32 12 13 BI TUMI NOUS TACK AND PRI ME COATS

32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS

32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE

FACILITIES

32 16 19 CONCRETE CURBS, GUTTERS AND SI DEWALKS

32 17 23 PAVEMENT MARKI NGS

32 32 23 SEGMENTAL CONCRETE BLOCK RETAI NI NG WALL

DI VI SI ON 33 - UTI LI TI ES

33 40 00 STORM DRAI NAGE UTI LI TI ES

33 46 16 SUBDRAI NAGE PI PI NG

33 51 15 NATURAL- GAS / LI QUI D PETROLEUM GAS DI STRI BUTI ON

33 61 13. 13 PREFABRI CATED UNDERGROUND HYDRONI C ENERGY DI STRI BUTI ON

33 61 13. 19 VALVES, PI PI NG, AND EQUI PMENT I N VALVE MANHOLES

33 63 13. 19 CONCRETE TRENCH HYDRONI C AND STEAM ENERGY DI STRI BUTI ON

33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON

33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)

APPENDICES

Appendi x A ACM AND HAZMAT REPORTS Appendi x B COMMI SSI ONI NG PLAN Appendi x C SPECI AL I NSPECTI ONS

- - End of Pr oj ect Tabl e of Cont ent s - -

PROJECT TABLE OF CONTENTS Page 4

APPENDIX A

ACM AND HAZMAT REPORTS

Building 1744 Building 1745 Building 1867 Building 1875

Sa va nn ah

D is tr ic t En vi ro nm en ta l a nd M at er ia ls

U ni t

Asbestos Survey Of:

Building 1744 Washington Street Fort Jackson, South Carolina 29207

Inspected: 31 July 2017 Report Generated: 25 September 2017

For: By:

US Army Corps of Engineers Timothy A. Jones Savannah District SC Inspector # BI-00363 Engineering Section US Army Corps of Engineers Savannah District Environmental & Materials Unit 200 N. Cobb Parkway, Suite 404 Marietta, GA 30062 678-354-0310

The contents of this report are not to be used for advertising, publication, or promotional purposes.

Citation of trade names does not constitute an official endorsement or approval of the use of such commercial products.

The findings of this report are not to be construed as an official Department of the Army position, unless so designated by other authorized documents.

Table of Contents

Asbestos Inspection Report Summary………………………………………...1-5

List of Tables

Table 1. Homogeneous Area Descriptions ....................................................... 2-3

Table 2. Suspect ACM Samples ....................................................................... 6-7

Table 3. Material Characterization and Assessment

List of Figures

Figure 1. Asbestos Sample Locations

Appendices

Appendix A. Maxxam Analytics, Analytical Report. ................................... 10-23

Appendix B. Sample Chain of Custody Forms ............................................. 24-25

Appendix C. Certifications and Accreditations ............................................. 26-29

Appendix D. Previous asbestos report

Asbestos Inspection Report

Introduction

Scope of the Investigation

This report documents the asbestos inspection and survey of Building 1744 at Fort.

Jackson; South Carolina conducted on 31 July 2017 by Savannah District U.S. Army Corps of Engineers employee Timothy Jones, a South Carolina accredited inspector. A copy of the inspector’s accreditation card is included in Appendix C. The survey was conducted in accordance with South Carolina Regulation 61-86.1, “Standards of Performance for Asbestos Projects” Section VI. The survey was conducted to locate and quantify existing asbestos containing materials (ACM) prior to demolition of the building. This report details ACM as identified at the time of inspection only and will not account for materials added after the inspection. Prior to the inspection a previous asbestos report produced by Stell Environmental Enterprises, Inc dated May 2012 was reviewed to determine what additional sampling may be required during this current inspection. Scanned copies of their reports are attached at the end of this report as Appendix D. Asbestos Containing Materials were located in this building.

Background

Building 1744, constructed in 1990, is a single story steel framed structure on a concrete slab on grade floor used as a warehouse building. The building contains roughly 4000 square feet of interior space. Floors are concrete slab-on-grade some of which are covered with vinyl floor tiles and carpet in much of the building. Exterior walls are mostly corrugated metal with some small amount of brick. Interior walls are a combination of concrete block, plywood and gypsum drywall. Ceilings in the office and restrooms are ceiling tiles in a metal grid work. Ceiling areas in the warehouse area are open to the roof structure. The roof is standing seam metal. Rooms on the building floor plans are arbitrarily numbered for identification in this report only.

Description of study

Investigation

All accessible areas of Building 1744 were visually inspected for suspected asbestos containing materials. A building walk-through was completed to determine homogeneous areas of building materials present. Bulk samples were collected from homogeneous areas of all accessible suspect ACM’s that were not previously sampled or assumed to be asbestos. Additional samples of previously sampled materials were collected when an insufficient number of samples were collected previously. The following table, Table 1, describes the homogeneous areas investigated in this inspection.

TABLE 1

IDENTIFIED HOMOGENEOUS AREAS

Homogeneous Area Type Sample Numbers ACM, Non-ACM, Non-Suspect

Concrete block walls Miscellaneous Not Sampled Non-suspect Steel framing and decking Miscellaneous Not Sampled Non-suspect

Concrete floor Miscellaneous Not Sampled Non-suspect Metal vents Miscellaneous Not Sampled Non-suspect

Metal walls and roof Miscellaneous Not Sampled Non-suspect Metal doors and frames Miscellaneous Not Sampled Non-suspect

Window glass Miscellaneous Not Sampled Non-suspect Metal window frames Miscellaneous Not Sampled Non-suspect

Fiberglass wall and ceiling insulation Miscellaneous Not Sampled Non-suspect Brick exterior wall Miscellaneous Not Sampled Non-suspect

Plywood interior walls Miscellaneous Not Sampled Non-suspect Plastic skylights Miscellaneous Not Sampled Non-suspect

Fiberglass duct insulation TSI Not Sampled Non-suspect Fiberglass pipe insulation TSI Not Sampled Non-suspect

Rubber pipe insulation TSI Not Sampled Non-suspect

Light gray caulking material on roof at plastic skylights Miscellaneous

1744-R-1 (PLM)

1744-R-2 (PLM)

1744-R-3 (PLM) (TEM)

Non-ACM

White mastic on foil backed fiberglass duct insulation TSI

1744-1-4 (PLM)

1744-1-5 (PLM)

1744-1-6 (PLM) (TEM)

Previously Sampled SEE, INC Samples

FJ-1744-13 (PLM)

FJ-1744-14 (PLM)

FJ-1744-15 (PLM) (TEM)

Non-ACM

Black rubbery caulking material in concrete floor expansion joints Miscellaneous

1744-1-7 (PLM)

1744-1-8 (PLM)

1744-1-9 (PLM) (TEM)

Non-ACM

6” tan rubber base molding Miscellaneous

1744-1-10 (PLM)

1744-1-11 (PLM)

1744-1-12 (PLM) (TEM)

Non-ACM

White exterior caulking material between metal door frame and wall Miscellaneous

1744-E-13 (PLM)

1744-E-14 (PLM)

1744-E-15 (PLM) (TEM)

Non-ACM

Brown exterior caulking material between metal door frame and wall Miscellaneous

1744-E-16 (PLM)

1744-E-17 (PLM)

1744-E-18 (PLM) (TEM)

Non-ACM

Paint on concrete block walls Miscellaneous

1744-M-22 (PLM)

1744-M-23 (PLM)

1744-M-24 (PLM) (TEM)

Non-ACM

12” X 12” tan floor tile Miscellaneous

Previously Sampled SEE, INC Samples

FJ-1744-01 (PLM)

FJ-1744-02 (PLM)

FJ-1744-03 (PLM) (TEM)

Non-ACM

Gypsum wall board Miscellaneous

Previously Sampled SEE, INC Samples

FJ-1744-04 (PLM)

FJ-1744-05 (PLM)

FJ-1744-06 (PLM)

Non-ACM

Drywall joint compound Surfacing

Previously Sampled SEE, INC Samples

FJ-1744-07 (PLM)

FJ-1744-08 (PLM)

FJ-1744-09 (PLM)

Non-ACM

2’ X 4’ ceiling tile Miscellaneous

Previously Sampled SEE, INC Samples

FJ-1744-10 (PLM)

FJ-1744-11 (PLM)

FJ-1744-12 (PLM)

Non-ACM

Mastic for 12” X 12” tan floor tile Miscellaneous

Previously Sampled SEE, INC Samples

FJ-1744-01 (PLM)

FJ-1744-02 (PLM)

FJ-1744-03 (PLM) (TEM)

ACM

Black caulking material between metal door and window glass Miscellaneous

1744-1-19 (PLM)

1744-1-20 (PLM)

1744-1-21 (PLM) (TEM)

ACM

Floor slab moisture proofing Miscellaneous Not Sampled Presumed ACM

Maxxam Analytics, INC analyzed the current bulk samples. The laboratory is accredited by the National Voluntary Laboratory Accredited Program (NVLAP Accreditation sponsored by the National Institute of Standards and Technology (NIST)).

Copies of their accreditation certificates are included in Appendix C. The samples were analyzed by the accepted method of polarized light microscopy (PLM) using EPA’s “Method for the Determination of Asbestos in Bulk Building Materials”, EPA/600/R- 93/116. Additionally, one sample from each non-friable organically bound homogeneous area was analyzed by TEM. Friable materials that were found to contain between trace and 1% asbestos were re-analyzed by the Point Count method when applicable. The laboratory’s analytical report is included as Appendix A.

In compliance with the regulations, material is considered an Asbestos Containing Material (ACM) when it contains greater than one percent asbestos. Likewise, in this report, any material containing concentrations greater than one percent asbestos will be considered “positive” for asbestos content. Occasionally, materials containing less than one percent asbestos, or not sampled, are assumed to be a “positive” asbestos containing material at the discretion of the inspectors. A narrative discussion of the ACM types (i.e., thermal systems insulation, miscellaneous and surfacing materials) found in Building 1744 is included in this report where relevant. Bulk sample information of currently collected samples appears on Table 2. Characterization and quantities of asbestos containing materials appears on Table 3. The approximate location where each bulk sample was obtained is shown on the building floor plans, which appear as Figures.

Positive ACM samples are indicated on the floor plan Figures with their numbers enclosed in squares and, where possible, locations of positive ACM are identified.

Samples determined negative for asbestos are indicated on the floor plan Figures with their numbers enclosed in circles. It is reasonable to assume that all materials similar to those testing positive also contain positive amounts of asbestos and should be treated as such. Quantities of asbestos containing materials listed in this report are rough field estimates only and must be verified by contractors prior to disturbance or demolition activities.

Conclusions

Thermal Systems Insulation (TSI)

TSI is insulation material applied to pipes, fittings, tanks, ducts, or on other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes. The following suspect TSI homogeneous areas at Building 1744 were found or assumed to contain asbestos:

No asbestos containing TSI Materials were located in the building.

Miscellaneous Materials

Miscellaneous materials include building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and do not include surfacing or TSI. In the past, there were a great number of miscellaneous building materials that had asbestos fibers added to them during the manufacturing process to increase durability and fireproofing qualities. The following suspect Miscellaneous Materials homogeneous areas at Building 1744 were found or are assumed to contain asbestos:

a. Floor Tile Mastic: Mastic associated with the 12” X 12” tan floor tiles in the office and restroom areas was previously determined to contain asbestos. - (Refer to Tables 1 and 3 for specific information)

b. Caulking Materials: Black caulking material between the metal exterior doors and window glass contains asbestos. - (Refer to Tables 1, 2 and 3 for specific information and drawings for sample locations)

c. Moisture Proofing Materials: Felt moisture proofing materials below the floor slabs, if it exist, is presumed to contain asbestos. - (Refer to Tables 1 and 3 for specific information)

Surfacing Materials

Surfacing material is friable material that is sprayed on, troweled on, or otherwise applied to surfaces for fireproofing, soundproofing, decorative or other purposes. The following Surfacing Material homogeneous areas at Building 1744 were found or

No asbestos containing Surfacing Materials were located in the building.

TABLE 2

SUSPECT ACM SAMPLES

SAMPLE ID DESCRIPTION HA# LOCATION ASBESTOS

TYPE & %

1744-R-1 Light gray caulking material 1 Roof, between metal roofing and plastic skylights

No Asbestos Detected

(PLM)

1744-R-2 Light gray caulking material 1 Roof, between metal roofing and plastic skylights

No Asbestos Detected

(PLM)

1744-R-3 Light gray caulking material 1 Roof, between metal roofing and plastic skylights

No Asbestos Detected

(PLM)

(TEM)

1744-1-4 White mastic 2 Room 104, on foil backed fiberglass duct insulation

No Asbestos Detected

(PLM)

1744-1-5 White mastic 2 Room 104, on foil backed fiberglass duct insulation

No Asbestos Detected

(PLM)

1744-1-6 White mastic 2 Room 104, on foil backed fiberglass duct insulation

No Asbestos Detected

(PLM)

(TEM)

1744-1-7 Black rubbery caulking material 3 Room 104, in concrete floor slab expansion joints

No Asbestos Detected

(PLM)

1744-1-8 Black rubbery caulking material 3 Room 104, in concrete floor slab expansion joints

No Asbestos Detected

(PLM)

1744-1-9 Black rubbery caulking material 3 Room 104, in concrete floor slab expansion joints

No Asbestos Detected

(PLM)

(TEM)

1744-1-10 6” tan rubber base molding & adhesive

4 Room 103 No Asbestos

Detected

(PLM)

1744-1-11 Base molding & adhesive 4 Room 102

No Asbestos Detected

(PLM)

1744-1-12 Base molding & adhesive 4 Room 102

No Asbestos Detected

(TEM)

1744-E-13 White caulking material 5 Exterior, between metal door frame and wall

No Asbestos Detected

(PLM)

1744-E-14 White caulking material 5 Exterior, between metal door frame and wall

No Asbestos Detected

(PLM)

1744-E-15 White caulking material 5 Exterior, between metal door frame and wall

No Asbestos Detected

(PLM)

(TEM)

1744-E-16 Brown caulking material 6 Exterior, between metal door frame and wall

No Asbestos Detected

(PLM)

1744-E-17 Brown caulking material 6 Exterior, between metal window frame and wall

No Asbestos Detected

(PLM)

1744-E-18 Brown caulking material 6 Exterior, between metal window frame and wall

No Asbestos Detected

(PLM)

(TEM)

1744-1-19 Black caulking material 7 Room 104, between metal door and window glass

No Asbestos Detected

(PLM)

1744-1-20 Black caulking material 7 Room 104, between metal door and window glass

No Asbestos Detected

(PLM)

1744-1-21 Black caulking material 7 Room 104, between metal door and window glass

2.6% Chrysotile

(TEM)

1744-M-22 Paint 8 Room 101, on concrete block wall No Asbestos

Detected

(PLM)

1744-M-23 Paint 8 Room 101, on concrete block wall No Asbestos

Detected

(PLM)

1744-M-24 Paint 8 Room 101, on concrete block wall

No Asbestos Detected

Samples testing positive for asbestos indicated in BOLD type NAD = No Asbestos Detected

TABLE 3

MATERIAL CHARACTERIZATION AND ASSESSMENT

Homogeneous Area Functional Space Characteristics Assessment

Description Type Asbestos Yes/No/Assumed Quantity Friability Condition Disturbance

Potential Accessibility

Floor tile mastic Miscellaneous Interior Yes 500 S.F. Non-Friable Good Low Not Accessible Black window caulking material Miscellaneous Room 104 Yes 30 L.F. Non-Friable Good Low Partially Accessible

Floor slab felt moisture proofing materials Miscellaneous Exterior Presumed 4000 S.F. ? ? ? Not Accessible

S.F. = Square Foot, L.F. = Linear Foot, C.F. = Cubic Foot, Ea. = Each

Disturbance Potential is based on normal building occupancy. Aggressive demolition methods could change assessment.

Figure 1

Appendix A

Laboratory’s Analytical Report

Appendix B

Sample Chain of Custody Forms

Appendix C

Certifications & Accreditations

APPENDIX D

Previous Asbestos Reports

BASELINE ASBESTOS SURVEY

BUILDING 1744

FORT JACKSON

COLUMBIA, SOUTH CAROLINA

MAY 2012

Prepared for:

US Army Corps of Engineers Savannah District

CESAS-PM-H

100 W. Oglethorpe Avenue Savannah, GA 31401

US Army Garrison Fort Jackson

ISME-GOR-PWE

5411 Leesburg Rd Fort Jackson, South Carolina 30905

Contract No. W912HN-11-D-0019 Task Order 0002

Prepared by:

Stell Environmental Enterprises, Inc.

25 East Main Street Elverson, PA 19520

Weston Solutions, Inc.

1625 Pumphrey Avenue

Auburn, Al 36832

Stell Environmental Enterprises, Inc. i Fort Jackson ACM Updates 5/23/12

SIGNATURE APPROVALS

The original version of this document and the associated laboratory results have been reviewed for compliance with the project scope of work and South Carolina requirements by the undersigned individuals and is hereby approved for release to Ft. Jackson. This information should be used in conjunction with previous survey documentation for the referenced building/facility.

PRINTED

NAME

SIGNATURE LICENSE NO. DATE

Kevin Johnson BI00389 2-20-2013

Elizabeth Doomes BI01105 9-16-2012

EXCEPTIONS, DELETIONS, AND GAPS

The information contained in this document should not be considered “comprehensive” or final.

Although every effort was made to identify and sample suspect asbestos-containing materials, some materials may have been overlooked as the result of inaccessibility, painting, areas where access was restricted, or system integrity issues. Should any questions arise during renovation or demolition projects, the discovered suspect ACM should be sampled and tested in accordance with South Carolina Regulation 61-86.1 - Standards of Performance for Asbestos Projects.

6/4/12

TABLE OF CONTENTS

ES Executive Summary

1.0 Purpose and Objectives ............................................................................... 1-1

1.1 GENERAL ........................................................................................................................ 1-1

1.2 SUSPECT ACM SAMPLING ................................................................................................. 1-1

1.3 SUSPECT ACM VERSUS ASBESTOS-CONTAINING MATERIALS ............................................. 1-1

1.4 POSITIVE VERSUS NEGATIVE ANALYTICAL RESULTS ........................................................... 1-2

1.5 STATE-SPECIFIC REQUIREMENTS ...................................................................................... 1-2

2.0 SURVEY FINDINGS .................................................................................. 2-1

2.1 FRIABLE ASBESTOS-CONTAINING MATERIALS .................................................................... 2-1

2.2 NONFRIABLE ASBESTOS-CONTAINING MATERIALS ............................................................. 2-1

2.3 ASSUMED MATERIALS ...................................................................................................... 2-1

2.4 NON-ASBESTOS CONTAINING MATERIALS ......................................................................... 2-1

2.5 ASBESTOS MATERIAL CONDITION ASSESSMENT .................................................................. 2-1

TABLES

Table 2-1: ASSESSMENT SUMMARY .................................................................................... 2-1

APPENDICES

A Sample Locations, Descriptions, and Extent Drawings B Representative Photographs C Laboratory Analysis Results D Personnel Certifications

Stell Environmental Enterprises, Inc. ii Fort Jackson ACM Updates

ACRONYMS AND ABBREVIATIONS

ACBM asbestos‐containing building material

ACM asbestos‐containing material

AHERA Asbestos Hazard Emergency Response Act

AIHA American Industrial Hygiene Association

ASTM American Society for Testing and Materials

CFR Code of Federal Regulations

CIH certified industrial hygienist

COR contracting officer's representative

EPA Environmental Protection Agency, U.S.

HEPA high‐efficiency particulate air

HA homogeneous area

HM homogenous material

HVAC heating, ventilation, and air‐conditioning

NESHAP National Emission Standards for Hazardous Air Pollutants

NIOSH National Institute of Occupational Safety and Health

NOB Nonfriable organically bound

O&M operations and maintenance

OSHA Occupational Safety and Health Administration

PACM presumed asbestos‐containing material

PLM polarized light microscopy

PPE Personal Protective Equipment

RACM regulated asbestos‐containing material

SEE Stell Environmental Enterprises, Inc.

SCDHEC South Carolina Department of Health and Environmental Control

SF Square feet

TEM transmission electron microscopy

TSI thermal system insulation

USACE United States Army Corps of Engineers

VAT vinyl asbestos tile

Stell Environmental Enterprises, Inc. ES-1 Fort Jackson ACM Updates

EXECUTIVE SUMMARY

Stell Environmental Enterprises, Inc. (SEE) under United States Army Corps of Engineers (USACE) contract and the Environmental Directorate, Fort Jackson, South Carolina subcontracted Weston Solutions, Inc. (WESTON®) to collect suspect asbestos samples from designated buildings at Fort Jackson. Results from this effort were used to fill data gaps from previous investigations on a priority basis. WESTON was also tasked with conducting full surveys for specific buildings as instructed by Fort Jackson.

The objectives of this full survey were to identify and analyze materials suspected of containing asbestos, to document the locations where ACM was found, and to assess the quantity and condition of ACM identified in the facility. Roof samples were collected as part of this contract if the roof system integrity would not be adversely affected. The survey of Building 1744 was performed by WESTON personnel with asbestos building inspector credentials on 2 February, 2012.

The original construction date of Building 1744 was not provided. The information provided to WESTON indicates that there have been at least two previous asbestos surveys of the building since the original construction. A photograph of the exterior of Building 1744 is shown on Appendix B, page 1.

ES-1 ASBESTOS-CONTAINING MATERIALS (ACM)

Suspect ACM was identified throughout the building during the survey and each distinct area of these material types was assigned a “homogeneous material” (HM) number.

As described later in this document, a material that is either damaged or can be readily crumbled under hand pressure is called “friable” and a material that is in good condition and is not readily crumbled under hand pressure is called “nonfriable.” ACM found at Building 1744 consists of the following materials:

• Nonfriable – Floor tile mastic

Sample locations and the extent of ACM are indicated on the floor plans in Appendix A.

Photographs of suspect material identified are presented in Appendix B. The location and description of each bulk sample are shown in Appendix C. The analytical results are shown in Appendix D.

ES-2 ASSESSMENTS AND RECOMMENDATIONS

The nonfriable asbestos-containing materials found at the facility are in good condition and pose little risk of exposure provided they are maintained in good repair.

WESTON recommends inclusion of all ACM components in the Operations and Maintenance (O&M) Plan and Asbestos Management Program pending future removal. Prior to renovation activities, all friable ACM that would potentially be disturbed by those activities must be removed. Nonfriable ACM may remain in place during building demolition in most instances.

Under federal law, all ACM abatement activities must be designed by an EPA certified project designer and must be performed by EPA-certified project supervisors and project workers.

WESTON recommends that this report be kept with permanent records of the facility.

METHODOLOGY

Stell Environmental Enterprises, Inc. 1-1 Fort Jackson ACM Updates

1.0 PURPOSE AND OBJECTIVES

The United States Army is engaged in efforts to improve the safety and working environments of personnel associated with the Fort Jackson facilities. As an ongoing part of these efforts, SEE/WESTON was engaged to survey Building 1744 for the presence of asbestos.

The objectives of this survey were to:

Review existing facility records to determine use of asbestos-containing materials.

Visually inspect the facility to assess and identify suspect ACM locations and quantities.

Sample and analyze suspect friable and nonfriable ACM using USEPA and SCDHEC protocols to determine whether or not they contain asbestos.

Identify sample locations and the extent of ACM using supporting floor plans and photographs.

1.1 GENERAL

The survey of Building 1744 was conducted on 2 February, 2012. The inspection was performed by WESTON personnel trained through an Environmental Protection Agency (EPA) approved AHERA asbestos inspector course and licenses in the State of South Carolina.

1.2 SUSPECT ACM SAMPLING

The inspector conducted a preliminary walk-through of each area in the building in order to develop a building-specific inspection strategy based on the homogeneous sampling areas present. A homogeneous material (HM) is an area of material that is uniform in color, texture, and appearance. After the HM’s were defined, the inspector collected random bulk samples from each sampling area in accordance with the sampling requirements for suspect ACM identified by the state and USEPA. Material description and quantity data, as well as physical condition, were also recorded.

Collected samples remained in the control of the inspector until delivery to the laboratory for analysis. Appropriate chain-of-custody protocols were utilized for all sample transfers.

Included in this report are appendices containing Sample Location and Extent Drawings (Appendix A), Photographs (Appendix B), Polarized Light Microscopy Analysis Results (Appendix C), Personnel Certifications (Appendix D), and Previous Asbestos Report (Appendix E).

1.3 SUSPECT ACM VERSUS ASBESTOS-CONTAINING MATERIALS

For every type of material that contains asbestos, there are similar or equivalent materials that do not contain asbestos. As a result, all such material (e.g. floor tile or insulation on tanks, fittings, pipes, and air ducts) is considered suspect material until actual asbestos content is determined.

Laboratory analysis by a qualified microscopist is necessary to distinguish ACM from non asbestos materials. Any suspect material of unknown asbestos content should be handled as if it were ACM. The sampling program was designed to collect bulk samples from each homogeneous area of suspect material.

Stell Environmental Enterprises, Inc. 1-2 Fort Jackson ACM Updates

1.4 POSITIVE VERSUS NEGATIVE ANALYTICAL RESULTS

A “positive” analytical result signifies a material contains asbestos and should be considered ACM for the purposes of remedial action. Suspect materials are grouped into homogeneous areas for the purpose of sampling. Based on the type of material and its quantity, between one and seven samples may be collected. If any of the samples constituting a homogeneous area of material test positive for asbestos, all instances of the material are considered as being ACM, even if other samples of the sample material test negative.

The samples for this work were delivered via FedEx® to EMSL, Inc. (Kernersville, NC). The EMSL laboratories are certified through the National Institute of Standards Technology/National Voluntary Laboratory Accreditation Program (NIST/NVLAP) and accredited by AIHA.

The United States Environmental Protection Agency (EPA) defines ACM as material, which contains greater than one percent asbestos. Material with one percent or less is technically not considered ACM and may be excluded from any plan of remedial action. In many instances, however, a single sample of suspect material actually consists of several layers of different material. As an example, a sample collected from a resilient floor tile may actually consist of two layers: a mastic layer and a tile layer. The two layers may have significantly different concentrations and the total content would be affected by the volume of each layer. In some cases, even though a mastic layer on the floor tile contains asbestos, the layer comprises such a small percentage of the total floor tile sample that the asbestos content of the whole sample might be recorded as one percent asbestos, which is technically considered non-ACM by EPA definitions. WESTON, however, recommends that due to the inability to effectively separate layers during abatement, any sample with a distinct layer or component containing greater than one percent asbestos be considered as ACM, regardless of the results of the total sample.

Samples in which the total results are one percent or less and have no distinct layers containing greater than one percent asbestos will be considered non-ACM.

1.5 STATE-SPECIFIC REQUIREMENTS

In some instances, state agencies enact requirements that are more stringent than the USEPA or OSHA guidelines. SCDHEC requires that a minimum of three samples of nonfriable materials be taken (in most instances). If the results are negative and the material it is considered to be nonfriable, organically bound (NOB), then at least one sample be confirmed by transmission electron microscopy (TEM) analysis.

The American Society for Testing and Materials (ASTM E 2356-04) defines NOB materials as “materials that are not friable and that consist of fibers and other particulate matter embedded in a solid matrix of asphaltic, vinyl or other organic substances.” South Carolina lists examples of NOB materials as components such as flooring materials (vinyl or asphaltic floor tiles and sheet flooring), adhesives, mastics, asphalt shingles, roofing materials, glazing, caulks, and cove base.

NOB materials are considered miscellaneous materials (Category I) and a minimum of three samples must be collected by a Department-licensed asbestos building inspector from each homogeneous area of a these materials.

SURVEY FINDINGS AND RECOMMENDATIONS

Stell Environmental Enterprises, Inc. 2-1 Fort Jackson ACM Updates

2.0 SURVEY FINDINGS

The following section discusses the information obtained from the sampling and laboratory analysis for this building.

2.1 FRIABLE ASBESTOS-CONTAINING MATERIALS

Friable ACMs are those materials, which can be easily crumbled or reduced to powder under hand pressure.

No friable materials were identified during the survey of Building 1744.

2.2 NONFRIABLE ASBESTOS-CONTAINING MATERIALS

Nonfriable ACMs are those materials which cannot be easily crumbled or reduced to powder under hand pressure. The following nonfriable asbestos-containing materials were found in Building 1744:

HM 001 Black Mastic of 12” x 12” Tan Floor Tile

Photographs of each of the nonfriable asbestos-containing materials are included in Appendix B.

The photographs are arranged by material type.

2.3 ASSUMED MATERIALS

In cases where sampling a suspect material would breach the integrity of the structure, or its components, the material was assumed to contain asbestos. Any fire rated doors should be assumed to contain asbestos. No other suspect materials were assumed to contain asbestos in Building 1744.

2.4 NON-ASBESTOS CONTAINING MATERIALS

Non-asbestos containing materials are those materials which contain asbestos in concentrations of one percent or less and, when appropriate, have been verified by NOB analysis. The following homogeneous areas of non asbestos containing materials were in Building 1744.

HM 001 Tan 12” x 12” Floor Tile HM 002 Wall Board HM 003 Joint Compound HM 004 2’ x 4’Acoustical Ceiling Tile HM 005 White TSI Mastic

Photographs of each of these materials are included in Appendix B. The photographs are arranged by material type.

2.5 ASBESTOS MATERIAL CONDITION ASSESSMENT

The evaluation of a particular ACM is performed by the inspector while conducting the building survey. Each evaluation categorizes the ACM based on the general condition and location within the building (e.g. high traffic, easily damaged, etc.). The inspector lists the material in

Stell Environmental Enterprises, Inc. 2-2 Fort Jackson ACM Updates either good, fair, damaged, or damaged beyond repair. This information may then be used to determine the appropriate facility response for the listed ACM components. The following response actions were selected for the ACM found in Building 1744.

Table 2-1: ASSESSMENT SUMMARY

HM Area Material Description Quantity Material Condition

1 Office Areas Black Mastic of Floor Tile 500 SF Good

Because it is not feasible to conduct immediate, one-time removal of asbestos (abatement) from all areas of each building, an O&M Plan should be established as a part of an Asbestos Management Program to manage ACM safely during the interim period prior to its removal.

Ongoing maintenance activities may involve ACM being removed during the time between preparation of this report and the development and implementation of the O&M Plan.

Consequently, locations where ACM has been removed should be designated and documented during the removal and included in the O&M Plan.

Stell Environmental Enterprises, Inc. A-1 Fort Jackson ACM Updates

SAMPLE LOCATIONS, DESCRIPTIONS, AND EXTENT DRAWINGS

OfficeWorkshop

Mechanical Latrine

03, 08

North

11 12

Building 1744

= Sample number and location

MISSILDB

Rectangle

Stell Environmental Enterprises, Inc. B-1 Fort Jackson ACM Updates

APPENDIX B

REPRESENTATIVE PHOTOGRAPHS

1744 - ACM Assessment - Fort Jackson, SC

Doomes

Exterior view of Building 1744.

Photographer:

Description:

2/2/2012Date:

PHOTOGRAPH NO:

Direction:

Doomes

12x12 tan floor tile and mastic (HA-1).

Photographer:

Description:

2/2/2012Date:

PHOTOGRAPH NO:

Direction:

Wallboard and joint compound (HA-2).

Photographer:

Description:

2/2/2012Date:

PHOTOGRAPH NO:

Direction:

Doomes

Ceiling tile (HA-4).

Photographer:

Description:

2/2/2012Date:

PHOTOGRAPH NO:

TSI wrap (HA-5).

Photographer:

Description:

2/2/2012Date:

PHOTOGRAPH NO:

Stell Environmental Enterprises, Inc. C-1 Fort Jackson ACM Updates

APPENDIX C

LABORATORY ANALYSIS RESULTS

EMSL Analytical, Inc.

706 Gralin Street, Kernersville, NC 27284 Phone/Fax: (336) 992-1025 / (336) 992-4175 greensborolab@emsl.com

021200709 CustomerID: RFWE50 CustomerPO:

ProjectID: Fort Jackson

EMSL Order:

Attn: Bret Missildine Weston Solutions 1625 Pumphrey Ave.

Auburn, AL 36832

Received: 02/06/12 9:30 AM

Ft Jackson

Fax: (334) 466-5660 Phone: (334) 466-5600

Project:

2/15/2012Analysis Date:

Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 and/or EPA 600/M4-82-020 Method(s) using Polarized Light Microscopy

FJ 1744-01-Floor Tile 021200709-0001

Floor Tile Tan None Detected

Non-Fibrous

Heterogeneous

Non-fibrous (other)100%

FJ 1744-01-Mastic 021200709-0001A

Floor Tile Black Non-Fibrous Heterogeneous

Chrysotile5%Non-fibrous (other)95%

FJ 1744-02-Floor Tile 021200709-0002

Floor Tile Tan None Detected

Non-Fibrous

Heterogeneous

Non-fibrous (other)100%

FJ 1744-02-Mastic 021200709-0002A

Floor Tile Stop Positive (Not Analyzed)

FJ 1744-03-Floor Tile 021200709-0003

Floor Tile Tan None Detected

Non-Fibrous

Heterogeneous

Non-fibrous (other)100%

FJ 1744-03-Mastic 021200709-0003A

Floor Tile Stop Positive (Not Analyzed)

FJ 1744-04

021200709-0004

Wallboard Brown/Gray None Detected

Fibrous Heterogeneous

Non-fibrous (other)100%

1Test Report PLM-7.23.0 Printed: 2/29/2012 4:11:54 PM

Stephen Bennett, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. None Detected = <1% Samples analyzed by EMSL Analytical, Inc. Charlotte, NC

Initial report from 02/17/2012 16:36:37

Kyle Collins (12) Lee Plumley (6) mailto:greensborolab@emsl.com

Phone/Fax: (336) 992-1025 / (336) 992-4175 greensborolab@emsl.com

021200709 CustomerID: RFWE50 CustomerPO:

ProjectID: Fort Jackson

EMSL Order:

Attn: Bret Missildine Weston Solutions 1625 Pumphrey Ave.

Auburn, AL 36832

Received: 02/06/12 9:30 AM

Ft Jackson

Fax: (334) 466-5660 Phone: (334) 466-5600

Project:

2/15/2012Analysis Date:

Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 and/or EPA 600/M4-82-020 Method(s) using Polarized Light Microscopy

FJ 1744-05

021200709-0005

Wallboard Brown/Gray None Detected

Fibrous Heterogeneous

Cellulose15% Non-fibrous (other)85%

FJ 1744-06

021200709-0006

Wallboard Brown/Gray None Detected

Fibrous Heterogeneous

Cellulose15% Non-fibrous (other)85%

FJ 1744-07

021200709-0007

Joint Compound White None Detected

Non-Fibrous Heterogeneous

Non-fibrous (other)100%

FJ 1744-08

021200709-0008

Joint Compound White None Detected

Non-Fibrous Heterogeneous

Non-fibrous (other)100%

FJ 1744-09

021200709-0009

Joint Compound White None Detected

Non-Fibrous Heterogeneous

Non-fibrous (other)100%

FJ 1744-10

021200709-0010

Ceiling Tile Gray None Detected

Fibrous Heterogeneous

Cellulose30% Min. Wool20%

Non-fibrous (other)50%

FJ 1744-11

021200709-0011

Ceiling Tile Gray None Detected

Fibrous Heterogeneous

Cellulose30% Min. Wool20%

Non-fibrous (other)50%

2Test Report PLM-7.23.0 Printed: 2/29/2012 4:11:54 PM

Stephen Bennett, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. None Detected = <1% Samples analyzed by EMSL Analytical, Inc. Charlotte, NC

Initial report from 02/17/2012 16:36:37

Kyle Collins (12)

Phone/Fax: (336) 992-1025 / (336) 992-4175 greensborolab@emsl.com

021200709 CustomerID: RFWE50 CustomerPO:

ProjectID: Fort Jackson

EMSL Order:

Attn: Bret Missildine Weston Solutions 1625 Pumphrey Ave.

Auburn, AL 36832

Received: 02/06/12 9:30 AM

Ft Jackson

Fax: (334) 466-5660 Phone: (334) 466-5600

Project:

2/15/2012Analysis Date:

Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 and/or EPA 600/M4-82-020 Method(s) using Polarized Light Microscopy

FJ 1744-12

021200709-0012

Ceiling Tile Gray/White None Detected

Fibrous Heterogeneous

Cellulose30% Min. Wool20%

Non-fibrous (other)50%

FJ 1744-13-Mastic 021200709-0013

TSI Mastic/Wrap White None Detected

Non-Fibrous Heterogeneous

Min. Wool5% Cellulose5%

Non-fibrous (other)90%

FJ 1744-13-

Insulation 021200709-0013A

TSI Mastic/Wrap Yellow None Detected

Fibrous

Heterogeneous

Glass98% Non-fibrous (other)2%

FJ 1744-14-Mastic 021200709-0014

TSI Mastic/Wrap White/Silver None Detected

No Insulation Present

Fibrous Heterogeneous

Glass8% Cellulose5%

Non-fibrous (other)87%

FJ 1744-15-Mastic 021200709-0015

TSI Mastic/Wrap White None Detected

Non-Fibrous Heterogeneous

Glass2% Cellulose2%

Non-fibrous (other)96%

FJ 1744-15-

Insulation 021200709-0015A

TSI Mastic/Wrap Yellow None Detected

Fibrous

Heterogeneous

Glass98% Non-fibrous (other)2%

3THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.23.0 Printed: 2/29/2012 4:11:54 PM

Stephen Bennett, Laboratory Manager or other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. None Detected = <1% Samples analyzed by EMSL Analytical, Inc. Charlotte, NC

Initial report from 02/17/2012 16:36:37

Kyle Collins (12)

SAMPLE ID DESCRIPTION APPEARANCE

% MATRIX

MATERIAL

% NON-ASBESTOS

FIBERS

ASBESTOS

TYPES

Attn: Bret Missildine Weston Solutions 1625 Pumphrey Ave.

Auburn, AL 36832

Received: 02/06/12 9:30 AM

Ft Jackson

Fax: (334) 466-5660 Phone: (334) 466-5600

Project:

2/17/2012Analysis Date:

Collected:

Test Report: Asbestos Analysis of Non-Friable Organically Bound Materials by TEM via EPA/600/R-93/116 Section 2.5.5.1

EMSL Analytical, Inc.

706 Gralin Street, Kernersville, NC 27284 Phone/Fax: (336) 992-1025 / (336) 992-4175 greensborolab@emsl.com

021200709 CustomerID: RFWE50 CustomerPO:

ProjectID: Fort Jackson

EMSL Order:

No Asbestos DetectedFJ 1744--03-Floor Tile 021200709-0016

Gray 100Floor Tile Non-Fibrous

Heterogeneous

None

No Asbestos DetectedFJ 1744-15-Mastic 021200709-0017

White 99.5TSI Mastic/Wrap Non-Fibrous Heterogeneous

Fibrous (other)0.49

Stephen Bennett, Laboratory Manager or other approved signatory

Test Report EPANOB-7.24.0 Printed: 2/29/2012 4:13:27 PM 1

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

This laboratory is not responsible for % asbestos in total sample when the residue only is submitted for analysis. The above report relates only to the items tested. This report may not be reproduced, except in full, without written approval by EMSL Analytical, Inc. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.

Samples analyzed by EMSL Analytical, Inc. Charlotte, NC

Christopher Estes (2)

Initial report from 02/17/2012 16:36:37

Stell Environmental Enterprises, Inc. D-1 Fort Jackson ACM Updates

PERSONNEL CERTIFICATIONS

nn ah

D is tr ic t En vi ro nm en ta l a nd M at er ia ls

U ni t

Hazardous Building Materials Survey

Ft. Jackson, South Carolina

Prepared by Timothy A. Jones

The contents of this report are not to be used for advertising, publication, or promotional purposes. Citation of trade names does not constitute an official endorsement or approval of the use of

The findings of this report are not to be construed as an official Department of the Army position, unless so designated by other authorized documents.

Hazardous Building Materials Survey July 2017

Ft. Jackson, South Carolina

Prepared By: Timothy A. Jones

Final Report

Prepared for: U.S. Army Corps of Engineers

Hazardous Building Materials Survey Report

Background

Building 1744, constructed in 1990, is a single story steel framed structure on a concrete slab on grade floor used as a warehouse building. The building contains roughly 4000 square feet of interior space. Floors are concrete slab-on-grade some of which are covered with vinyl floor tiles and carpet in much of the building. Exterior walls are mostly corrugated metal with some small amount of brick. Interior walls are a combination of concrete block, plywood and gypsum drywall. Ceilings in the office and restrooms are ceiling tiles in a metal grid work.

Ceiling areas in the warehouse area are open to the roof structure. The roof is standing seam metal.

This report documents the hazardous building materials survey of Building 1744 at Ft.