Specifications_Volume_3_-_IFC_Reception_Phase_I_AMD1.pdf

PDF 141 KB Posted

Attached to
Reception Complex Phase 1 Federal contract opportunity
Solicitation number
W912HP19R2000
Issued by
Department of the Army Corps of Engineers Engineering District Charleston

About this file

This document announces a solicitation for the Reception Complex Phase 1 project at Fort Jackson. The solicitation package includes drawings, specifications, and attachments requesting proposal and past performance information. Offerors are invited to attend a site visit on August 20, 2019 to view the project location. Proposals are due by September 6, 2019. The solicitation is for construction services to build the Reception Complex as detailed in the drawings and specifications volumes. The Corps of Engineers is the contracting agency managing this project.

Spec Vol3

View the file

Other files for this federal contract opportunity

Other files attached to Reception Complex Phase 1, newest first.
File Type Posted
B._AMD_0006_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
B._AMD0006_Solicitation_W912HP19R2001_BTC4.pdf PDF
B._AMD_0005_Solicitation_19R2000_Reception_Complex_Phase_1.pdf PDF
Specifications_Volume_5_-_IFC_Reception_Phase_1_AMD4.pdf PDF
B._AMD_0004_Solicitation_W912HP19R20000_Reception_Complex.pdf PDF
Drawings_Volume_2_-_IFC_Reception_Phase_1_AMD3.pdf PDF
B._AMD_0003_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
Drawings_Volume_3_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Drawings_Volume_2_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Specifications_Volume_2_-_IFC_Reception_Phase_1_AMD2.PDF PDF
Drawings_Volume_1_-_IFC_Reception_Phase_1_AMD2.pdf PDF
Specifications_Volume_1_-_IFC_Reception_Phase_1_AMD2.PDF PDF
B._AMD_0002_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
Specifications_Volume_5_-_IFC_Reception_Phase_1_AMD2.pdf PDF
B._AMD_0001_Solicitation_W912HP19R2000_Reception_Complex.pdf PDF
Specifications_Volume_1_-_IFC_Reception_Phase_I_AMD1.pdf PDF
A._Site_Visit_Sign-In_Sheet.pdf PDF
Specifications_Volume_2_-_IFC_Reception_Phase_I_AMD1.pdf PDF
Drawings_Volume_1_-_IFC_Reception_Phase_1_AMD1.pdf PDF
Drawings_Volume_3_-_IFC_Reception_Phase_I_AMD1.pdf PDF
Specifications_Volume_5_-_IFC_Reception_Phase_AMD1.pdf PDF
Drawings_Volume_2_-_IFC_Recepton_Phase_1_AMD1.pdf PDF
junc-sp1.dgn —
junc-up.dgn —
junv-rp.dgn —
junc-sp.dgn —
junc-gp1.dgn —
junc-gp.dgn —
junc-dp.dgn —
junv-tp.dgn —
Specifications_Volume_2_-_IFC_Reception_Phase_I.PDF PDF
Specifications_Volume_1_-_IFC_Reception_Phase_I.PDF PDF
Drawings_Volume_1_-_IFC_Reception_Phase_I.pdf PDF
Specifications_Volume_4_-_IFC_Reception_Phase_I.PDF PDF
B._Attachment_2_-_Descriptive_Summary_Sheet.pdf PDF
Drawings_Volume_3_-_IFC_Reception_Phase_I.pdf PDF
B._Solicitation_W912HP19R2000_Reception_Complex_Phase_1,_Ft._Jax.pdf PDF
Drawings_Volume_4_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_1_-_Proposal_Data_Sheet.pdf PDF
Drawings_Volume_2_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_3_-_Past_Performance_Questionnaire.pdf PDF
Specifications_Volume_3_-_IFC_Reception_Phase_I.PDF PDF
Specifications_Volume_5_-_IFC_Reception_Phase_I.pdf PDF
B._Attachment_4_-_Small_Business_Participation_Plan.pdf PDF
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Reception Complex JA76149 Ft. Jackson, SC

PROJECT TABLE OF CONTENTS

DIVISION 01 - GENERAL REQUIREMENTS

01 11 00 SUMMARY OF WORK

01 30 00 ADMINISTRATIVE REQUIREMENTS

01 32 01 PROJECT SCHEDULE

01 33 00 SUBMITTAL PROCEDURES

01 33 29 SUSTAINABILITY REPORTING

01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS

01 42 00 SOURCES FOR REFERENCE PUBLICATIONS

01 45 00 QUALITY CONTROL

01 45 00.15 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)

01 45 35 SPECIAL INSPECTIONS

01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS

01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS

01 57 19.37 INDOOR AIR QUALITY (IAQ) MANAGEMENT

01 74 19.37 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT

01 78 00 CLOSEOUT SUBMITTALS

01 78 23 OPERATION AND MAINTENANCE DATA

01 91 00 COMMISSIONING

DIVISION 02 - EXISTING CONDITIONS

02 41 00 *1 DEMOLITION

02 82 00 *1 ASBESTOS REMEDIATION

02 83 13 LEAD IN CONSTRUCTION

DIVISION 03 - CONCRETE

03 11 13 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING

03 15 00 CONCRETE ACCESSORIES

03 20 00 CONCRETE REINFORCING

03 30 00 CAST-IN-PLACE CONCRETE

03 35 00 CONCRETE FINISHING

03 39 00 CONCRETE CURING

DIVISION 04 - MASONRY

04 20 00 MASONRY

DIVISION 05 - METALS

05 12 00 STRUCTURAL STEEL

05 30 00 STEEL DECKS

05 40 00 COLD-FORMED METAL FRAMING

05 50 13 MISCELLANEOUS METAL FABRICATIONS

05 51 33 METAL LADDERS

05 52 00 METAL RAILINGS

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 20 00 FINISH CARPENTRY

06 41 16 LAMINATE CLAD ARCHITECTURAL CASEWORK

06 61 16 SOLID POLYMER (SOLID SURFACING) FABRICATIONS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

PROJECT TABLE OF CONTENTS Page 1 (revised by Amendment 0001)

07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS

07 21 13 BOARD AND BLOCK INSULATION

07 21 16 MINERAL FIBER BLANKET INSULATION

07 22 00 ROOF AND DECK INSULATION

07 27 10 BUILDING AIR BARRIER SYSTEM

07 41 00 METAL SOFFIT PANELS

07 41 13 METAL ROOF PANELS

07 42 13 METAL WALL PANELS

07 60 00 FLASHING AND SHEET METAL

07 61 14 STEEL STANDING SEAM ROOFING

07 84 00 FIRESTOPPING

07 92 00 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 STEEL DOORS AND FRAMES

08 11 16 ALUMINUM DOORS AND FRAMES

08 14 00 WOOD DOORS

08 34 73 SOUND CONTROL DOOR ASSEMBLIES

08 51 13 ALUMINUM WINDOWS

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 91 00 METAL WALL LOUVERS

DIVISION 09 - FINISHES

09 06 00 SCHEDULES FOR FINISHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 30 10 CERAMIC, QUARRY, AND GLASS TILING

09 51 00 ACOUSTICAL CEILINGS

09 65 00 RESILIENT FLOORING

09 68 00 CARPETING

09 90 00 PAINTS AND COATINGS

DIVISION 10 - SPECIALTIES

10 10 00 VISUAL COMMUNICATIONS SPECIALTIES

10 14 01 EXTERIOR SIGNAGE

10 14 02 INTERIOR SIGNAGE

10 21 13 TOILET COMPARTMENTS

10 26 00 WALL AND DOOR PROTECTION

10 28 13 TOILET ACCESSORIES

10 56 13 STEEL SHELVING

DIVISION 11 - EQUIPMENT

11 13 19.13 LOADING DOCK LEVELERS

11 21 73 VERTICAL CAROUSELS

DIVISION 12 - FURNISHINGS

12 24 13 ROLLER WINDOW SHADES

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

12 50 00 FURNITURE AND FURNITURE INSTALLATION

DIVISION 13 - SPECIAL CONSTRUCTION

13 34 19 METAL BUILDING SYSTEMS

PROJECT TABLE OF CONTENTS Page 2 (revised by Amendment 0001)

13 48 00 SEISMIC BRACING FOR MISCELLANEOUS EQUIPMENT

DIVISION 21 - FIRE SUPPRESSION

21 13 13 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

21 30 00 FIRE PUMPS

DIVISION 22 - PLUMBING

22 00 00 PLUMBING, GENERAL PURPOSE

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS

23 05 48.19 SEISMIC BRACING FOR HVAC

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS

23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC

23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

23 09 23.01 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER

BUILDING CONTROL SYSTEMS

23 11 25 FACILITY GAS PIPING

23 23 00 REFRIGERANT PIPING

23 25 00 CHEMICAL TREATMENT OF WATER FOR MECHANICAL SYSTEMS

23 52 00 HEATING BOILERS

23 57 10 FORCED HOT WATER HEATING SYSTEMS USING WATER AND STEAM

HEAT EXCHANGERS

23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE

23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS

23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT

23 82 46 ELECTRIC UNIT HEATERS

DIVISION 25 - INTEGRATED AUTOMATION

25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

25 05 12 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

(SPECIAL SYSTEMS)

25 05 13 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

(FA/MNS)

DIVISION 26 - ELECTRICAL

26 00 00 BASIC ELECTRICAL MATERIALS AND METHODS

26 05 48 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT

26 08 00 APPARATUS INSPECTION AND TESTING

26 20 00 INTERIOR DISTRIBUTION SYSTEM

26 23 00 SWITCHBOARDS

26 28 01 COORDINATED POWER SYSTEM PROTECTION

26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS

26 41 00 LIGHTNING PROTECTION SYSTEM

26 42 14 CATHODIC PROTECTION SYSTEM (SACRIFICIAL ANODE)

26 51 00 INTERIOR LIGHTING

DIVISION 27 - COMMUNICATIONS

27 05 14 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM

27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM

27 51 16 SOUND REINFORCEMENT SYSTEMS

PROJECT TABLE OF CONTENTS Page 3 (revised by Amendment 0001)

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEMS

DIVISION 31 - EARTHWORK

31 00 00 EARTHWORK

31 05 19 GEOTEXTILE

31 11 00 CLEARING AND GRUBBING

31 31 16.13 CHEMICAL TERMITE CONTROL

31 32 11 SOIL SURFACE EROSION CONTROL

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS IN RIGID

PAVEMENTS

32 05 33 LANDSCAPE ESTABLISHMENT

32 11 16 BASE COURSE FOR RIGID PAVING

32 11 23 AGGREGATE AND/OR GRADED-CRUSHED AGGREGATE BASE COURSE

32 12 13 BITUMINOUS TACK AND PRIME COATS

32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS

32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE

FACILITIES

32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS

32 17 23 PAVEMENT MARKINGS

32 32 23 SEGMENTAL CONCRETE BLOCK RETAINING WALL

DIVISION 33 - UTILITIES

33 40 00 STORM DRAINAGE UTILITIES

33 46 16 SUBDRAINAGE PIPING

33 51 15 NATURAL-GAS / LIQUID PETROLEUM GAS DISTRIBUTION

33 61 13.13 PREFABRICATED UNDERGROUND HYDRONIC ENERGY DISTRIBUTION

33 61 13.19 VALVES, PIPING, AND EQUIPMENT IN VALVE MANHOLES

33 63 13.19 CONCRETE TRENCH HYDRONIC AND STEAM ENERGY DISTRIBUTION

33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)

APPENDICES

Appendix A ACM AND HAZMAT REPORTS Appendix B COMMISSIONING PLAN Appendix C SPECIAL INSPECTIONS

-- End of Project Table of Contents --

PROJECT TABLE OF CONTENTS Page 4 (revised by Amendment 0001)

Recept i on Compl ex JA76149 Ft . Jackson, SC

SECTI ON TABLE OF CONTENTS

DI VI SI ON 26 - ELECTRI CAL

SECTI ON 26 51 00

I NTERI OR LI GHTI NG

05/16

PART 1 GENERAL

1. 1 REFERENCES

1. 2 DEFI NI TI ONS

1. 3 SUBMI TTALS

1. 4 QUALI TY CONTROL

1. 4. 1 Lumi nai r e Dr awi ngs

1. 4. 2 Occupancy Sensor Cover age Layout

1. 4. 3 LED Dr i ver and Di mmi ng Swi t ch Compat i bi l i t y Cer t i f i cat e

1. 4. 4 Lumi nai r e Desi gn Dat a

1. 4. 5 LED Lumi nai r e - I ES LM- 79 Test Repor t

1. 4. 6 LED Li ght Sour ce - I ES LM- 80 Test Repor t

1. 4. 7 LED Li ght Sour ce - I ES TM- 21 Test Repor t

1. 4. 8 Occupancy Sensor Ver i f i cat i on Test s

1. 4. 9 Test Labor at or i es

1. 4. 10 Regul at or y Requi r ement s

1. 4. 11 St andar d Pr oduct s

1. 4. 11. 1 Al t er nat i ve Qual i f i cat i ons

1. 4. 11. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

1. 4. 11. 3 Ener gy Ef f i c i ency

1. 5 WARRANTY

1. 5. 1 LED Lumi nai r e War r ant y

1. 5. 1. 1 Pr ovi de Lumi nai r e Usef ul Li f e Cer t i f i cat e

PART 2 PRODUCTS

2. 1 PRODUCT COORDI NATI ON

2. 2 LUMI NAI RES

2. 2. 1 LED Lumi nai r es

2. 3 DRI VERS

2. 3. 1 LED Dr i ver s

2. 4 LI GHT SOURCES

2. 4. 1 LED Li ght Sour ces

2. 5 LI GHTI NG CONTROLS

2. 5. 1 Toggl e Swi t ches

2. 5. 2 Sensor s f or Li ght i ng Cont r ol

2. 5. 2. 1 Occupancy Sensor s

2. 5. 2. 2 Passi ve I nf r ar ed ( PI R) Sensor s

2. 5. 2. 3 Ul t r asoni c Sensor s

2. 5. 2. 4 Dual Technol ogy Sensor s

2. 5. 2. 5 Swi t chPacks f or Sensor s

2. 5. 3 Di gi t al Ti mer Swi t ch

2. 5. 4 Wal l st at i ons

2. 5. 5 Li ght i ng Cont r ol Panel

2. 5. 6 Local Ar ea Li ght i ng Cont r ol l er ( Li ght i ng Room Cont r ol l er )

2. 6 EXI T AND EMERGENCY LI GHTI NG EQUI PMENT

SECTI ON 26 51 00 Page 1 ( Revi sed by Amendment 0001)

2. 6. 1 Exi t Si gns

2. 6. 2 LED Emer gency Dr i ver s

2. 6. 3 Sel f - Di agnost i c Ci r cui t r y f or LED Emer gency Dr i ver s

2. 7 LUMI NAI RE SUPPORT HARDWARE

2. 7. 1 Wi r e

2. 7. 2 Wi r e f or Humi d Spaces

2. 7. 3 Thr eaded Rods

2. 7. 4 St r aps

2. 8 EQUI PMENT I DENTI FI CATI ON

2. 8. 1 Manuf act ur er ' s Namepl at e

2. 8. 2 Label s

2. 9 FACTORY APPLI ED FI NI SH

2. 10 RECESS- AND FLUSH- MOUNTED LUMI NAI RES

2. 11 SUSPENDED LUMI NAI RES

PART 3 EXECUTI ON

3. 1 I NSTALLATI ON

3. 1. 1 Li ght Sour ces

3. 1. 2 Lumi nai r es

3. 1. 3 Suspended Lumi nai r es

3. 1. 4 Power Suppl i es

3. 1. 5 Exi t Si gns and Emer gency Li ght i ng Uni t s

3. 1. 5. 1 Exi t Si gns

3. 1. 5. 2 Emer gency Li ght i ng f r om Emer gency Li ght i ng I nver t er

3. 1. 6 Occupancy Sensor s

3. 1. 7 Dayl i ght or Ambi ent Li ght Level Sensor

3. 2 FI ELD APPLI ED PAI NTI NG

3. 3 COMMI SSI ONI NG REQUI REMENTS

- - End of Sect i on Tabl e of Cont ent s - -

SECTI ON 26 51 00 Page 2 ( Revi sed by Amendment 0001)

SECTI ON 26 51 00

I NTERI OR LI GHTI NG

05/16

AMENDED PER AMENDMENT 01

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE 189. 1 ( 2014) St andar d f or t he Desi gn of Hi gh- Per f or mance Gr een Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASHRAE 90. 1 - I P ( 2013) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASTM I NTERNATI ONAL ( ASTM)

ASTM A1008/ A1008M ( 2016) St andar d Speci f i cat i on f or St eel , Sheet , Col d- Rol l ed, Car bon, St r uct ur al , Hi gh- St r engt h Low- Al l oy, Hi gh- St r engt h Low- Al l oy wi t h I mpr oved For mabi l i t y , Sol ut i on Har dened, and Bake Har denabl e

ASTM A580/ A580M ( 2018) St andar d Speci f i cat i on f or St ai nl ess St eel Wi r e

ASTM A641/ A641M ( 2009a; R 2014) St andar d Speci f i cat i on f or Zi nc- Coat ed ( Gal vani zed) Car bon St eel Wi r e

ASTM A653/ A653M ( 2017) St andar d Speci f i cat i on f or St eel Sheet , Zi nc- Coat ed ( Gal vani zed) or Zi nc- I r on Al l oy- Coat ed ( Gal vanneal ed) by t he Hot - Di p Pr ocess

ASTM B164 ( 2003; R 2014) St andar d Speci f i cat i on f or Ni ckel - Copper Al l oy Rod, Bar , and Wi r e

ASTM B633 ( 2015) St andar d Speci f i cat i on f or El ect r odeposi t ed Coat i ngs of Zi nc on I r on and St eel

ASTM D4674 REV A ( 2002; R 2010) St andar d Pr act i ce f or Accel er at ed Test i ng f or Col or St abi l i t y of Pl ast i cs Exposed t o I ndoor Of f i ce Environments

CALI FORNI A ENERGY COMMI SSI ON ( CEC)

CEC Ti t l e 24 ( 2016) Bui l di ng Ener gy Ef f i c i ency

SECTI ON 26 51 00 Page 3 ( Revi sed by Amendment 0001)

St andar ds For Resi dent i al and Nonr esi dent i al Bui l di ngs

I LLUMI NATI NG ENGI NEERI NG SOCI ETY ( I ES)

I ES HB- 10 ( 2011; Er r at a 2015) I ES Li ght i ng Handbook

I ES LM- 79 ( 2008) El ect r i cal and Phot omet r i c Measur ement s of Sol i d- St at e Li ght i ng Products

I ES LM- 80 ( 2015) Measur i ng Lumen Mai nt enance of LED Li ght Sour ces

I ES RP- 16 ( 2010; Addendum A 2008; Addenda B 2009;

Addendum C 2016) Nomencl at ur e and Def i ni t i ons f or I l l umi nat i ng Engi neer i ng

I ES TM- 21 ( 2011; Addendum B 2015) Pr oj ect i ng Long Ter m Lumen Mai nt enance of LED Li ght Sour ces

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms

I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code

I EEE C62. 41 ( 1991; R 1995) Recommended Pr act i ce on Sur ge Vol t ages i n Low- Vol t age AC Power Circuits

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NEMA ANSLG C78. 377 ( 2017) El ect r i c Lamps— Speci f i cat i ons f or t he Chr omat i c i t y of Sol i d St at e Li ght i ng Products

NEMA C82. 77 ( 2002) Har moni c Emi ssi on Li mi t s - Rel at ed Power Qual i t y Requi r ement s f or Li ght i ng Equipment

NEMA SSL 1 ( 2010) El ect r oni c Dr i ver s f or Led Devi ces, Ar r ays, or Syst ems

NEMA SSL 3 ( 2011) Hi gh- Power Whi t e LED Bi nni ng f or Gener al I l l umi nat i on

NEMA SSL 7A ( 2015) Phase- Cut Di mmi ng f or Sol i d St at e Li ght i ng: Basi c Compat i bi l i t y

NEMA WD 1 ( 1999; R 2015) St andar d f or Gener al Col or Requi r ement s f or Wi r i ng Devi ces

NEMA WD 7 ( 2011; R 2016) Occupancy Mot i on Sensor s

SECTI ON 26 51 00 Page 4 ( Revi sed by Amendment 0001)

Standard

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 101 ( 2018; TI A 18- 1; TI A 18- 2; TI A 18- 3) Li f e Saf et y Code

NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;

TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;

TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;

TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A

17- 14; TI A 17- 15; TI A 17- 16; TI A 17- 17)

Nat i onal El ect r i cal Code

U. S. DEPARTMENT OF DEFENSE ( DOD)

DOD 8500. 01 ( 2014) Cyber secur i t y

DOD 8510. 01 ( 2014; Change 1- 2016; Change 2- 2017) Ri sk Management Fr amewor k ( RMF) f or DoD I nf or mat i on Technol ogy ( I T)

UNDERWRI TERS LABORATORI ES ( UL)

UL 1598 ( 2008; Repr i nt Oct 2012) Lumi nai r es

UL 2043 ( 2013) Fi r e Test f or Heat and Vi s i bl e Smoke Rel ease f or Di scr et e Pr oduct s and Thei r Accessor i es I nst al l ed i n Ai r - Handl i ng Spaces

UL 508 ( 2018) UL St andar d f or I ndust r i al Cont r ol Equipment

UL 8750 ( 2015; Repr i nt Feb 2018) UL St andar d f or Saf et y Li ght Emi t t i ng Di ode ( LED) Equi pment f or Use i n Li ght i ng Pr oduct s

UL 916 ( 2007; Repr i nt Aug 2014) St andar d f or Ener gy Management Equi pment

UL 924 ( 2016; Repr i nt May 2018) UL St andar d f or Saf et y Emer gency Li ght i ng and Power Equipment

UL 94 ( 2013; Repr i nt Sep 2017) UL St andar d f or Saf et y Test s f or Fl ammabi l i t y of Pl ast i c Mat er i al s f or Par t s i n Devi ces and Appliances

1. 2 DEFINITIONS

a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, must be as def i ned i n I EEE 100 and I ES RP- 16.

b. For LED l umi nai r e l i ght sour ces, " Usef ul Li f e" i s t he oper at i ng hour s bef or e r eachi ng 70 per cent of t he i ni t i al r at ed l umen out put ( L70) wi t h no cat ast r ophi c f ai l ur es under nor mal oper at i ng condi t i ons. Thi s i s

SECTI ON 26 51 00 Page 5 ( Revi sed by Amendment 0001) al so know as 70 per cent " Rat ed Lumen Mai nt enance Li f e" as def i ned i n

I ES LM- 80.

c. For LED l umi nai r es, " Lumi nai r e Ef f i cacy" ( LE) i s t he appr opr i at e measur e of ener gy ef f i c i ency, measur ed i n l umens/ wat t . Thi s i s gat her ed f r om LM- 79 dat a f or t he l umi nai r e, i n whi ch absol ut e phot omet r y i s used t o measur e t he l umen out put of t he l umi nai r e as one ent i t y, not t he sour ce separ at el y and t hen t he sour ce and housi ng together.

d. Tot al har moni c di st or t i on ( THD) i s t he r oot mean squar e ( RMS) of al l t he har moni c component s di v i ded by t he t ot al f undament al cur r ent .

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Dat a, dr awi ngs, and r epor t s must empl oy t he t er mi nol ogy, c l assi f i cat i ons and met hods pr escr i bed by t he I ES HB- 10 as appl i cabl e, f or t he l i ght i ng syst em speci f i ed. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Lumi nai r e Dr awi ngs; G, DO

Occupancy Sensor Cover age Layout ; G, DO

SD- 03 Pr oduct Dat a

Luminaires ; G, DO

Li ght Sour ces; G, DO

Drivers ; G, DO

LED Lumi nai r e War r ant y; G, DO

Lumi nai r e Desi gn Dat a; G, DO

Sensor s f or Li ght i ng Cont r ol ; G, DO

Local Ar ea Li ght i ng Cont r ol l er ; G, DO

Wallstations ; G, DO

Exi t Si gns; G, DO

LED Emer gency Dr i ver s; G, DO

Ambi ent Li ght Level Sensor ; G, DO

Li ght i ng Cont r ol Panel ; G, DO

SD- 06 Test Repor t s

LED Lumi nai r e - I ES LM- 79 Test Repor t ; G, RO

SECTI ON 26 51 00 Page 6 ( Revi sed by Amendment 0001)

LED Li ght Sour ce - I ES LM- 80 Test Repor t ; G, RO

LED Li ght Sour ce - I ES TM- 21 Test Repor t ; G, RO

Occupancy Sensor Ver i f i cat i on Test s; G, RO

Ener gy Ef f i c i ency; G, RO

SD- 07 Cer t i f i cat es

Lumi nai r e Usef ul Li f e Cer t i f i cat e; G, RO

LED Dr i ver and Di mmi ng Swi t ch Compat i bi l i t y Cer t i f i cat e; G, RO

1. 4 QUALI TY CONTROL

1. 4. 1 Lumi nai r e Dr awi ngs

I ncl ude di mensi ons, accessor i es, and i nst al l at i on and const r uct i on det ai l s . Phot omet r i c dat a, i ncl udi ng zonal l umen dat a, and comput er i zed candl epower di st r i but i on dat a must accompany shop dr awi ngs.

1. 4. 2 Occupancy Sensor Cover age Layout

Pr ovi de f l oor pl ans showi ng cover age l ayout s of al l devi ces usi ng manuf act ur er ' s pr oduct i nf or mat i on.

1. 4. 3 LED Dr i ver and Di mmi ng Swi t ch Compat i bi l i t y Cer t i f i cat e

Submi t cer t i f i cat i on f r om t he l umi nai r e, dr i ver , or di mmer swi t ch manuf act ur er t hat ensur es compat i bi l i t y and oper abi l i t y bet ween devi ces.

1. 4. 4 Lumi nai r e Desi gn Dat a

a. Pr ovi de saf et y cer t i f i cat i on and f i l e number f or t he l umi nai r e f ami l y t hat must be l i s t ed, l abel ed, or i dent i f i ed per t he NFPA 70 ( NEC) .

Appl i cabl e t est i ng bodi es ar e det er mi ned by t he US Occupat i onal Saf et y Heal t h Admi ni st r at i on ( OSHA) as Nat i onal l y Recogni zed Test i ng Labor at or i es ( NRTL) and i ncl ude: CSA ( Canadi an St andar ds Associ at i on) , ETL ( Edi son Test i ng Labor at or y) , and UL ( Under wr i t er s Labor at or i es) .

b. Pr ovi de l ong t er m l umen mai nt enance pr oj ect i ons f or each LED l umi nai r e i n accor dance wi t h I ES TM- 21. Dat a used f or pr oj ect i ons must be obt ai ned f r om t est i ng i n accor dance wi t h I ES LM- 80.

1. 4. 5 LED Lumi nai r e - I ES LM- 79 Test Repor t

Submi t t est r epor t on manuf act ur er ' s st andar d pr oduct i on model l umi nai r e.

I ncl ude al l appl i cabl e and r equi r ed dat a as out l i ned under " 14. 0 Test Repor t " i n I ES LM- 79.

1. 4. 6 LED Li ght Sour ce - I ES LM- 80 Test Repor t

Submi t r epor t on manuf act ur er ' s st andar d pr oduct i on LED l i ght sour ce ( package, ar r ay, or modul e) . I nc l ude al l appl i cabl e and r equi r ed dat a as out l i ned under " 8. 0 Test Repor t " i n I ES LM- 80.

SECTI ON 26 51 00 Page 7 ( Revi sed by Amendment 0001)

1. 4. 7 LED Li ght Sour ce - I ES TM- 21 Test Repor t

Submi t t est r epor t on manuf act ur er ' s st andar d pr oduct i on LED l i ght sour ce ( package, ar r ay or modul e) . I ncl ude al l appl i cabl e and r equi r ed dat a, as wel l as r equi r ed i nt er pol at i on i nf or mat i on as out l i ned under " 7. 0 Repor t " in I ES TM- 21.

1. 4. 8 Occupancy Sensor Ver i f i cat i on Test s

Submi t t est r epor t out l i ni ng post - i nst al l at i on cover age and oper at i on of sensors.

1. 4. 9 Test Labor at or i es

Test l abor at or i es f or t he I ES LM- 79 and I ES LM- 80 t est r epor t s must be one of t he f ol l owi ng:

a. Nat i onal Vol unt ar y Labor at or y Accr edi t at i on Pr ogr am ( NVLAP) accr edi t ed f or sol i d- st at e l i ght i ng t est i ng as par t of t he Ener gy- Ef f i c i ent Li ght i ng Pr oduct s l abor at or y accr edi t at i on pr ogr am f or bot h LM- 79 and LM- 80 t est i ng.

b. One of t he qual i f i ed l abs l i s t ed on t he Depar t ment of Ener gy - LED Li ght i ng Fact s Appr oved Test i ng Labor at or i es Li st at f or LM- 79 t est i ng.

c. One of t he EPA- Recogni zed Labor at or i es l i s t ed at f or LM- 80 t est i ng.

1. 4. 10 Regul at or y Requi r ement s

I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d " must " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p must be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70, unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.

1. 4. 11 St andar d Pr oduct s

Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s must have been i n sat i s f act or y commer ci al or i ndust r i al use f or t wo year s pr i or t o bi d openi ng. The t wo- year per i od must i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct must have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he t wo- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems must be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.

1. 4. 11. 1 Al t er nat i ve Qual i f i cat i ons

Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.

SECTI ON 26 51 00 Page 8 ( Revi sed by Amendment 0001)

1. 4. 11. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

Pr oduct s manuf act ur ed mor e t han s i x mont hs pr i or t o dat e of del i ver y t o s i t e must not be used, unl ess speci f i ed ot her wi se.

1. 4. 11. 3 Ener gy Ef f i c i ency

Submi t dat a i ndi cat i ng l umens per wat t ef f i cacy and col or r ender i ng i ndex of l i ght sour ce.

1. 5 WARRANTY

Suppor t al l equi pment i t ems by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .

1. 5. 1 LED Lumi nai r e War r ant y

a. Pr ovi de a wr i t t en 5 year on- s i t e r epl acement war r ant y f or mat er i al , f i x t ur e f i ni sh, and wor kmanshi p. On- si t e r epl acement i ncl udes t r anspor t at i on, r emoval , and i nst al l at i on of new pr oduct s.

( 1) I ncl ude f i ni sh war r ant y t o i ncl ude f ai l ur e and subst ant i al det er i or at i on such as bl i s t er i ng, cr acki ng, peel i ng, chal k i ng, or fading.

( 2) Mat er i al war r ant y must i ncl ude:

( a) Al l dr i ver s.

( b) Repl acement when mor e t han 10 per cent of LED sour ces i n any l i ght bar or subassembl y( s) ar e def ect i ve or non- st ar t i ng.

b. War r ant y per i od must begi n on dat e of benef i c i al occupancy. Pr ovi de t he Cont r act i ng Of f i cer wi t h s i gned war r ant y cer t i f i cat es pr i or t o f i nal payment .

1. 5. 1. 1 Provide Lumi nai r e Usef ul Li f e Cer t i f i cat e

Submi t cer t i f i cat i on f r om t he manuf act ur er i ndi cat i ng t he expect ed usef ul l i f e of t he l umi nai r es pr ovi ded. The usef ul l i f e must be di r ect l y cor r el at ed f r om t he I ES LM- 80 t est dat a usi ng pr ocedur es out l i ned i n I ES TM- 21. Ther mal pr oper t i es of t he speci f i c l umi nai r e and l ocal ambi ent oper at i ng t emper at ur e and condi t i ons must be t aken i nt o consi der at i on.

PART 2 PRODUCTS

2. 1 PRODUCT COORDI NATI ON

*1

Pr oduct s and mat er i al s not consi der ed t o be l umi nai r es, l umi nai r e cont r ol s, or associ at ed equi pment ar e speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM. Li ght i ng commi ssi oni ng r equi r ement s shal l be i n accor dance wi t h t he sect i on 01 91 00. 00 37, Commi ssi oni ng. Commi ssi on t he l i ght i ng i n accor dance wi t h Sect i on 01 91 00 COMMI SSI ONI NG.

2. 2 LUMINAIRES

UL 1598, NEMA C82. 77, and UL 8750. Pr ovi de l umi nai r es as i ndi cat ed i n

SECTI ON 26 51 00 Page 9 ( Revi sed by Amendment 0001) l umi nai r e schedul e and NL pl at es or det ai l s on pr oj ect pl ans. Pr ovi de l umi nai r es compl et e wi t h l i ght sour ces of quant i t y , t ype, and wat t age i ndi cat ed. Pr ovi de al l l umi nai r es of t he same t ype by t he same manuf act ur er . Lumi nai r es must be speci f i cal l y desi gned f or use wi t h t he dr i ver or gener at or and l i ght sour ce pr ovi ded.

2. 2. 1 LED Lumi nai r es

Pr ovi de l umi nai r es compl et e wi t h power suppl i es ( dr i ver s) and l i ght sour ces. Pr ovi de desi gn i nf or mat i on i ncl udi ng l umen out put and desi gn l i f e i n l umi nai r e schedul e on pr oj ect pl ans f or LED l umi nai r es.

LED l umi nai r es must al so meet t he f ol l owi ng mi ni mum r equi r ement s:

a. Lumi nai r es must have a mi ni mum 5 year manuf act ur er ' s war r ant y.

b. Lumi nai r es must have a l umen mai nt enance val ue as shown on t he dr awi ng, as cal cul at ed by I ES TM- 21, wi t h dat a obt ai ned per I ES LM- 80 requirements.

c. Lumi nai r e dr i ve cur r ent val ue must be i dent i cal t o t hat pr ovi ded by t est dat a f or l umi nai r e i n quest i on.

d. Lumi nai r es must be t est ed t o I ES LM- 79 and I ES LM- 80 st andar ds, wi t h t he r esul t s pr ovi ded as r equi r ed i n t he Submi t t al s par agr aph of t hi s specification.

e. Pr ovi de Depar t ment of Ener gy ' Li ght i ng Fact s ' l abel f or each l umi nai r e.

2. 3 DRIVERS

2. 3. 1 LED Dr i ver s

NEMA SSL 1, UL 8750. LED dr i ver s must be el ect r oni c, UL Cl ass 1, const ant - cur r ent t ype and compl y wi t h t he f ol l owi ng r equi r ement s:

a. Out put power ( wat t s) and l umi nous f l ux ( l umens) as shown i n l umi nai r e schedul e f or each l umi nai r e t ype t o meet mi ni mum l umi nai r e ef f i cacy ( LE) val ue pr ovi ded.

b. Power Fact or ( PF) gr eat er t han or equal t o 0. 9 over t he f ul l di mmi ng r ange when pr ovi ded.

c. Cur r ent dr aw Tot al Har moni c Di st or t i on ( THD) of l ess t han 20 per cent .

d. Cl ass A sound r at i ng.

e. Oper abl e at i nput vol t age of 120- 277 vol t s at 60 her t z.

f . Mi ni mum 5 year manuf act ur er ' s war r ant y.

g. RoHS compl i ant .

h. I nt egr al t her mal pr ot ect i on t hat r educes or el i mi nat es t he out put power i f case t emper at ur e exceeds a val ue det r i ment al t o t he dr i ver .

i . UL l i s t ed f or dr y or damp l ocat i ons t ypi cal of i nt er i or i nst al l at i ons.

j . Non- di mmabl e or f ul l y- di mmabl e usi ng 0- 10V cont r ol as i ndi cat ed i n

SECTI ON 26 51 00 Page 10 ( Revi sed by Amendment 0001) l umi nai r e schedul e.

k. UL 1472, UL 20, I EEE C62. 41, NEMA SSL 7A. 0- 10 V di mmi ng dr i ver s must pr ovi de f l i cker - f r ee, cont i nuousl y var i abl e l i ght out put t hr oughout t he di mmi ng r ange ut i l i z i ng pul se wi dt h modul at i on ( PWM) . Pr ovi de r adi o f r equency i nt er f er ence suppr essi on i nt egr al t o devi ce. Ensur e compat i bi l i t y of di mmi ng dr i ver s wi t h l i ght i ng cont r ol devi ces. Di mmi ng dr i ver s and l i ght i ng cont r ol devi ces must be pr ovi ded f r om t he same manuf act ur er , or t est ed and cer t i f i ed as compat i bl e f or use t oget her .

Provide NEMA SSL 7A- compl i ant devi ces.

2. 4 LI GHT SOURCES

NEMA ANSLG C78. 377, NEMA SSL 3. Pr ovi de t ype and wat t age as i ndi cat ed i n l umi nai r e schedul e on pr oj ect pl ans.

2. 4. 1 LED Li ght Sour ces

a. Cor r el at ed Col or Temper at ur e ( CCT) as shown on t he dr awi ngs.

b. Mi ni mum Col or Render i ng I ndex ( CRI ) R9 val ue of 80.

c. Hi gh power , whi t e l i ght out put ut i l i z i ng phosphor conver si on ( PC) pr ocess or mi xed syst em of col or ed LEDs, t ypi cal l y r ed, gr een and bl ue

(RGB).

d. RoHS compl i ant .

e. Pr ovi de l i ght sour ce col or consi st ency by ut i l i z i ng a bi nni ng t ol er ance wi t hi n a 4- st ep McAdam el l i pse.

2. 5 LI GHTI NG CONTROLS

ASHRAE 90. 1 - I P, ASHRAE 189. 1. Pr ovi de net wor k cer t i f i cat i on f or al l net wor ked l i ght i ng cont r ol syst ems and devi ces per r equi r ement s of DOD 8500. 01 and DOD 8510. 01.

2. 5. 1 Toggl e Swi t ches

Pr ovi de l i ne- vol t age t oggl e swi t ches as speci f i ed i n Sect i on 26 20 00

I NTERI OR DI STRI BUTI ON SYSTEM.

2. 5. 2 Sensor s f or Li ght i ng Cont r ol

I EEE C62. 41, NEMA WD 1, UL 94, UL 916, UL 508, ASTM D4674 REV A.

2. 5. 2. 1 Occupancy Sensor s

Pr ovi de occupancy sensor s wi t h cover age pat t er ns as i ndi cat ed on pr oj ect pl ans. Pr ovi de no l ess quant i t y of sensor s as shown on pl ans, but add addi t i onal sensor s when r equi r ed t o f ul f i l l cover age r equi r ement f or t he speci f i c model sensor pr ovi ded. Sensor must be pr ovi ded wi t h an adapt i ve l ear ni ng f unct i on t hat aut omat i cal l y set s sensor i n opt i mum cal i br at i on i n a set per i od of t i me af t er i nst al l at i on and a non- vol at i l e memor y t hat saves set t i ngs af t er a power out age. Pr ovi de sensor s desi gned f or cei l i ng, wal l or wal l - box i nst al l at i on as i ndi cat ed. Oper at i ng vol t age must be 24V i n conj unct i on wi t h a cont r ol syst em or separ at e power pack whi ch i nt er act s wi t h l umi nai r e bei ng cont r ol l ed. Pr ovi de housi ng of hi gh- i mpact , i nj ect i on- mol ded t her mopl ast i c wi t h a mul t i - segment ed l ens f or PI R and dual

SECTI ON 26 51 00 Page 11 ( Revi sed by Amendment 0001) t echnol ogy sensor s. Sensor oper at i on r equi r es movement t o act i vat e l umi nai r es cont r ol l ed, and t ur ns l umi nai r es of f af t er a set t i me of i nact i v i t y. Pr ovi de i nt egr al phot ocel l mount ed i n occupancy sensor housi ng when i ndi cat ed.

2. 5. 2. 2 Passi ve I nf r ar ed ( PI R) Sensor s

Pr ovi de cei l i ng or wal l - mount ed PI R sensor s meet i ng t he f ol l owi ng requirements:

a. Temper at ur e compensat ed, dual el ement sensor and a mul t i - el ement f r esnel l ens ( Pol y I R4 mat er i al ) .

b. Technol ogy t o opt i mi ze aut omat i c t i me del ay t o f i t occupant usage patterns.

c. No mi ni mum l oad r equi r ement f or l i ne vol t age sensor s and be capabl e of swi t chi ng f r om zer o t o 800 W at 120 VAC, 50/ 60 Hz and f r om zer o t o 1200 W at 277 VAC, 50/ 60 Hz. Cont r ol vol t age sensor s must not exceed a maxi mum l oad r equi r ement of 20 mA at 24VDC.

d. Ti me del ay of f i ve t o 30 mi nut es i n i ncr ement s of f i ve mi nut es wi t h a wal k t hr ough and t est mode set by DI P swi t ch.

e. LED i ndi cat or t hat r emai ns act i ve dur i ng occupancy.

f . Bui l t - i n l i ght l evel sensor t hat i s oper at i onal f r om 8 t o 180 foot-candles .

g. Cover age pat t er n t est ed t o NEMA WD 7 st andar ds.

h. St andar d f i ve year war r ant y and be UL l i s t ed i . No l eakage cur r ent t o l oad when i n t he of f mode.

2. 5. 2. 3 Ul t r asoni c Sensor s

Pr ovi de cei l i ng- mount ed ul t r asoni c sensor s meet i ng t he f ol l owi ng requirements:

a. Oper at e at an ul t r asoni c f r equency of 32- 40 kHz.

b. LED on ext er i or of devi ce t o i ndi cat e occupant det ect i on.

c. Adj ust abl e t i me del ay per i od of 15 seconds t o 20.

d. UL l i s t ed wi t h mi ni mum f i ve year war r ant y.

e. Pr ovi de wi t h i sol at ed r el ay f or i nt egr at i ng cont r ol of HVAC or ot her aut omat ed syst ems.

2. 5. 2. 4 Dual Technol ogy Sensor s

Pr ovi de dual t echnol ogy sensor s t hat meet t he r equi r ement s f or PI R sensor s and ul t r asoni c sensor s i ndi cat ed above. I f ei t her t he passi ve i nf r ar ed or ul t r asoni c sensi ng r egi st er s occupancy, t he l umi nai r es must r emai n on.

SECTI ON 26 51 00 Page 12 ( Revi sed by Amendment 0001)

2. 5. 2. 5 Swi t chPacks f or Sensor s

UL 2043, CEC Ti t l e 24, ASHRAE 90. 1 - I P. Power packs used t o pr ovi de power t o one or mor e l i ght i ng cont r ol sensor s must meet t he f ol l owi ng requirements:

a. I nput vol t age - 120- 277 VAC; out put vol t age - 24 VDC at 225 mA.

b. Pl enum- r at ed, hi gh- i mpact t her mopl ast i c encl osur e.

c. Ut i l i zes zer o- cr ossi ng c i r cui t r y t o pr event damage f r om i nr ush cur r ent .

d. Maxi mum l oad r at i ng of 16 amps f or el ect r oni c dr i ver l i ght i ng l oads.

e. RoHS compl i ant .

2. 5. 3 Di gi t al Ti mer Swi t ch

Pr ovi de a f i el d pr ogr ammabl e di gi t al wal l swi t ch t i mer wi t h count - down t i mer di spl ay. Moment ar i l y pr essi ng t he st ar t / st op but t on l ocat ed on t he f r ont of t he uni t wi l l t ur n t he l oad ON and st ar t t he count down t i me ( adj ust abl e 5 mi nut es t o 12 hour s) . When t he count - down t i me el apses, t he l oad must t ur n OFF. When necessar y, moment ar i l y pr essi ng t he st ar t / st op but t on must al so t ur n t he l oad OFF bef or e t he count - down t i me has expi r ed.

Pr ogr am t he swi t ch t o f l i cker l i ght s and/ or beep as a war ni ng t hat t he l oad i s about t o be t ur ned OFF. Hol di ng i n t he pushbut t on f or 1 t o 2 seconds whi l e t he l oad i s on must r eset t he t i mer t o i t s or i gi nal pr eset i nt er val .

The swi t ch must be r at ed f or 10 amps at 120/ 277 vol t s wi t h no mi ni mum l oad required.

2. 5. 4 Wallstations

Low vol t age moment ar y pushbut t on swi t ches i n mul t i - but t on conf i gur at i on i n whi t e f i ni sh and mat chi ng whi t e wal l pl at es wi t h decor at or openi ng.

Wal l st at i ons shal l i ncl ude f act or y engr aved t ext as i ndi cat ed and shal l i ncl ude r emovabl e but t ons f or f i el d r epl acement wi t hout r emovi ng t he swi t ch f r om t he wal l . Wal l st at i ons shal l f ul l y i nt er f ace wi t h t he Local Ar ea Li ght i ng Cont r ol l er or Li ght i ng Cont r ol Panel , as appl i cabl e.

2. 5. 5 Li ght i ng Cont r ol Panel

Pr ovi de an el ect r oni c, pr ogr ammabl e l i ght i ng cont r ol panel , capabl e of pr ovi di ng l i ght i ng cont r ol wi t h i nput f r om i nt er nal pr ogr ammi ng, di gi t al swi t ches, t i me c l ocks, and ot her l ow- vol t age cont r ol devi ces. The l i ght i ng cont r ol panel shal l be st and- al one wi t h no r emot e connect i on out s i de t he building.

Encl ose panel har dwar e i n a sur f ace- mount ed, NEMA 1, pai nt ed, st eel encl osur e, wi t h hi nged, l ockabl e access door and vent i l at i on openi ngs.

I nt er nal l ow- vol t age compar t ment must be separ at ed f r om l i ne- vol t age compar t ment of encl osur e wi t h onl y l ow- vol t age compar t ment accessi bl e upon openi ng of door .

I nput vol t age - 120/ 277 V, 60 Hz, wi t h i nt er nal 24 VDC power suppl y.

*1

Pr ovi de t he i ndi cat ed quant i t y of s i ngl e- pol e l at chi ng r el ays r at ed at 20 amps, 277 vol t s. Wher e emer gency oper at i on i s i ndi cat ed, Pr ovi de pr ovi s i on f or r el ays t o c l ose upon power f ai l ur e. Emer gency pr ovi s i on shal l meet UL 924. Wher e f i r e al ar m oper at i on i s i ndi cat ed, make pr ovi s i on f or r el ays

SECTI ON 26 51 00 Page 13 ( Revi sed by Amendment 0001) t o c l ose upon power f ai l ur e. Emer gency pr ovi s i on must meet UL 924.

Rel ay cont r ol modul e must oper at e at 24 VDC and be r at ed t o cont r ol no f ewer t han t he i ndi cat ed quant i t y of r el ays.

2. 5. 6 Local Ar ea Li ght i ng Cont r ol l er ( Li ght i ng Room Cont r ol l er )

ASHRAE 90. 1 - I P compl i ant . Cont r ol l er s must be f ul l y f unct i onal out - of - t he- box t o t he connect ed devi ces i n t he space. Mat ch t he r oom l i ght i ng l oad and cont r ol r equi r ement s. Pr ovi de cont r ol l er desi gned f or s i ngl e ar ea or r oom wi t h t he f ol l owi ng r equi r ement s:

a. 277 vol t i nput , desi gned wi t h zer o cr oss c i r cui t r y LED l i ght i ng l oads.

b. 3 zone, wi t h 3 r el ays r at ed 20 amps each.

c. Pr ovi de f ul l - r ange di mmi ng cont r ol wi t h dayl i ght har vest i ng capabi l i t y wi t h f ul l - r ange di mmi ng cont r ol .

d. I nput s f or occupancy sensor , phot ocel l , and l ow- vol t age wal l swi t ch.

e. Pr ovi de capabi l i t y f or r ecept acl e l oad cont r ol .

f . Pr ovi de f ul l ' OFF' f unct i on wi t h i nput f r om ext er nal t i me cl ock i nput wher e i ndi cat ed.

g. Pr ovi de qui ck l ow vol t age connect i ons t o cont r ol devi ces.

*1

h. Pr ovi de capabi l i t y f or f i r e al ar m over r i de of l i ght i ng cont r ol s, f or c i ng l i ght s ON.

2. 6 EXI T AND EMERGENCY LI GHTI NG EQUI PMENT

UL 924, NFPA 101, and NFPA 70 compl i ant .

2. 6. 1 Exi t Si gns

Pr ovi de exi t s i gns consumi ng a maxi mum of f i ve wat t s t ot al .

Pr ovi de sel f - power ed exi t s i gns i n pai nt ed, di e- cast al umi num housi ng wi t h UL damp l abel , conf i gur ed f or cei l i ng, wal l , or end mount i ng as i ndi cat ed.

Provide 6-inch hi gh, 3/ 4 i nch st r oke r ed l et t er i ng on f ace of s i gn.

Pr ovi de chevr ons on ei t her s i de of l et t er i ng t o i ndi cat e di r ect i on.

Pr ovi de s i ngl e or doubl e f ace as i ndi cat ed. Equi p wi t h aut omat i c power f ai l ur e devi ce, t est swi t ch, pi l ot l i ght , and f ul l y aut omat i c hi gh/ l ow t r i ck l e char ger i n a sel f - cont ai ned power pack. Bat t er y must be seal ed, mai nt enance- f r ee ni ckel - cadmi um t ype, and must oper at e unat t ended f or a per i od of not l ess t han 5 year s. Emer gency r un t i me must be a mi ni mum of 1 1/ 2 hour s. LEDs must have a mi ni mum r at ed l i f e of 10 year s. Pr ovi de sel f - di agnost i c c i r cui t r y i nt egr al t o emer gency LED dr i ver .

2. 6. 2 LED Emer gency Dr i ver s

Pr ovi de LED emer gency dr i ver wi t h aut omat i c power f ai l ur e det ect i on, t est swi t ch, and LED i ndi cat or ( or combi nat i on swi t ch/ i ndi cat or ) l ocat ed on l umi nai r e ext er i or , and f ul l y- aut omat i c sol i d- st at e char ger , bat t er y and i nver t er i nt egr al t o a sel f - cont ai ned housi ng. Pr ovi de sel f - di agnost i c f unct i on i nt egr al t o emer gency dr i ver . I nt egr al ni ckel - cadmi um bat t er y i s r equi r ed t o suppl y a mi ni mum of 90 mi nut es of emer gency power at 7 wat t s, SECTI ON 26 51 00 Page 14 ( Revi sed by Amendment 0001)

50 VDC compat i bl e wi t h LED f or war d vol t age r equi r ement s, const ant out put .

Dr i ver must be RoHS compl i ant , r at ed f or i nst al l at i on i n pl enum- r at ed spaces and damp l ocat i ons, and be war r ant ed f or a mi ni mum of f i ve year s.

2. 6. 3 Sel f - Di agnost i c Ci r cui t r y f or LED Emer gency Dr i ver s

Pr ovi de emer gency l i ght i ng uni t wi t h f ul l y- aut omat i c, i nt egr al sel f - t est i ng/ di agnost i c el ect r oni c c i r cui t r y. Ci r cui t r y must pr ovi de f or a one mi nut e di agnost i c t est ever y 28 days, and a 30 mi nut e di agnost i c t est ever y s i x mont hs, mi ni mum. Any mal f unct i on of t he uni t must be i ndi cat ed by LED( s) v i s i bl e f r om t he ext er i or of t he l umi nai r e. A manual t est swi t ch must al so be pr ovi ded t o per f or m a di agnost i c t est at any gi ven t i me.

2. 7 LUMI NAI RE SUPPORT HARDWARE

2. 7. 1 Wire

ASTM A641/ A641M; Gal vani zed, sof t t emper ed st eel , mi ni mum 0. 11 i nches i n di amet er , or gal vani zed, br ai ded st eel , mi ni mum 0. 08 i nches i n di amet er .

2. 7. 2 Wi r e f or Humi d Spaces

ASTM A580/ A580M; Composi t i on 302 or 304, anneal ed st ai nl ess st eel , mi ni mum

0. 11 i nches i n di amet er .

ASTM B164; UNS NO4400, anneal ed ni ckel - copper al l oy, mi ni mum 0. 11 i nches i n di amet er .

2. 7. 3 Thr eaded Rods

Thr eaded st eel r ods, 3/ 16 i nch di amet er , z i nc or cadmi um coat ed.

2. 7. 4 Straps

Gal vani zed st eel , one by 3/ 16 i nch, conf or mi ng t o ASTM A653/ A653M, wi t h a l i ght commer ci al z i nc coat i ng or ASTM A1008/ A1008M wi t h an el ect r odeposi t ed z i nc coat i ng conf or mi ng t o ASTM B633, Type RS.

2. 8 EQUI PMENT I DENTI FI CATI ON

2. 8. 1 Manuf act ur er ' s Namepl at e

Each i t em of equi pment must have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be acceptable.

2. 8. 2 Labels

Pr ovi de l abel ed l umi nai r es i n accor dance wi t h UL 1598 r equi r ement s. Al l l umi nai r es must be c l ear l y mar ked f or oper at i on of speci f i c l i ght sour ces, gener at or s or dr i ver s. Not e t he Cor r el at ed col or t emper at ur e ( CCT) and col or r ender i ng i ndex ( CRI ) f or al l l umi nai r es i n t he f or mat " Use Onl y

Al l mar ki ngs r el at ed t o l i ght sour ce t ype must be c l ear and l ocat ed t o be r eadi l y v i s i bl e t o ser vi ce per sonnel , but unseen f r om nor mal v i ewi ng angl es when l i ght sour ces ar e i n pl ace. Gener at or s or dr i ver s must have c l ear mar ki ngs i ndi cat i ng mul t i - l evel out put s and i ndi cat e pr oper t er mi nal s f or

SECTI ON 26 51 00 Page 15 ( Revi sed by Amendment 0001) t he var i ous out put s.

2. 9 FACTORY APPLI ED FI NI SH

Pr ovi de al l l umi nai r es and l i ght i ng equi pment wi t h f act or y- appl i ed pai nt i ng syst em t hat as a mi ni mum, meet s r equi r ement s of NEMA 250 cor r osi on- r esi st ance t est .

2. 10 RECESS- AND FLUSH- MOUNTED LUMI NAI RES

Pr ovi de access t o l amp and dr i ver f r om bot t om of l umi nai r e. Pr ovi de t r i m and l enses f or t he exposed sur f ace of f l ush- mount ed l umi nai r es as i ndi cat ed on pr oj ect dr awi ngs and speci f i cat i ons.

2. 11 SUSPENDED LUMI NAI RES

Pr ovi de hanger s capabl e of suppor t i ng t wi ce t he combi ned wei ght of l umi nai r es suppor t ed by hanger s. Pr ovi de wi t h swi vel hanger s t o ensur e a pl umb i nst al l at i on. Pr ovi de cadmi um- pl at ed st eel wi t h a swi vel - bal l t apped f or t he condui t s i ze i ndi cat ed. Hanger s must al l ow f i x t ur es t o swi ng wi t hi n an angl e of 45 degr ees. Br ace pendant s 4 f eet or l onger t o l i mi t swi ngi ng. Si ngl e- uni t suspended l umi nai r es must have t wi n- st em hanger s.

Mul t i pl e- uni t or cont i nuous r ow l umi nai r es must have a t ubi ng or st em f or wi r i ng at one poi nt and a t ubi ng or r od suspensi on pr ovi ded f or each uni t l engt h of chassi s, i ncl udi ng one at each end. Pr ovi de r ods i n mi ni mum 0. 18 inch di amet er .

PART 3 EXECUTI ON

3. 1 INSTALLATION

El ect r i cal i nst al l at i ons must conf or m t o I EEE C2, NFPA 70, and t o t he r equi r ement s speci f i ed her ei n. I nst al l l umi nai r es and l i ght i ng cont r ol s t o meet t he r equi r ement s of ASHRAE 90. 1 - I P and ASHRAE 189. 1. To encour age consi st ency and uni f or mi t y, i nst al l l umi nai r es of t he same manuf act ur er and model number when r esi di ng i n t he same f aci l i t y or bui l di ng.

3. 1. 1 Li ght Sour ces

When l i ght sour ces ar e not pr ovi ded as an i nt egr al par t of t he l umi nai r e, del i ver l i ght sour ces of t he t ype, wat t age, l umen out put , col or t emper at ur e, col or r ender i ng i ndex, and vol t age r at i ng i ndi cat ed t o t he pr oj ect s i t e and i nst al l j ust pr i or t o pr oj ect compl et i on, i f not al r eady i nst al l ed i n t he l umi nai r es f r om t he f act or y.

3. 1. 2 Luminaires

Set l umi nai r es pl umb, squar e, and l evel wi t h cei l i ng and wal l s, i n al i gnment wi t h adj acent l umi nai r es and secur e i n accor dance wi t h manuf act ur er s ' di r ect i ons and appr oved dr awi ngs. I nst al l at i on must meet r equi r ement s of NFPA 70. Mount i ng hei ght s speci f i ed or i ndi cat ed must be t o t he bot t om of t he l umi nai r e f or cei l i ng- mount ed l umi nai r es and t o cent er of l umi nai r e f or wal l - mount ed l umi nai r es. Obt ai n appr oval of t he exact mount i ng hei ght on t he j ob bef or e commenci ng i nst al l at i on and, wher e appl i cabl e, af t er coor di nat i ng wi t h t he t ype, st y l e, and pat t er n of t he cei l i ng bei ng i nst al l ed. Recessed and semi - r ecessed l umi nai r es must be i ndependent l y suppor t ed f r om t he bui l di ng st r uct ur e by a mi ni mum of f our wi r es, st r aps or r ods per l umi nai r e and l ocat ed near each cor ner of t he l umi nai r e. Cei l i ng gr i d c l i ps ar e not al l owed as an al t er nat i ve t o

SECTI ON 26 51 00 Page 16 ( Revi sed by Amendment 0001) i ndependent l y suppor t ed l umi nai r es. Round l umi nai r es or l umi nai r es smal l er i n s i ze t han t he cei l i ng gr i d must be i ndependent l y suppor t ed f r om t he bui l di ng st r uct ur e by a mi ni mum of f our wi r es, st r aps or r ods per l umi nai r e, spaced appr oxi mat el y equi di st ant ar ound. Do not suppor t l umi nai r es by acoust i cal t i l e cei l i ng panel s. Wher e l umi nai r es of s i zes l ess t han t he cei l i ng gr i d ar e i ndi cat ed t o be cent er ed i n t he acoust i cal panel , suppor t each i ndependent l y and pr ovi de at l east t wo 3/ 4 i nch met al channel s spanni ng, and secur ed t o, t he cei l i ng t ees f or cent er i ng and al i gni ng t he l umi nai r e. Pr ovi de wi r es, st r aps, or r ods f or l umi nai r e suppor t i n t hi s sect i on. Lumi nai r es i nst al l ed i n suspended cei l i ngs must al so compl y wi t h t he r equi r ement s of Sect i on 09 51 00 ACOUSTI CAL CEI LI NGS.

3. 1. 3 Suspended Lumi nai r es

Pr ovi de suspended l umi nai r es wi t h 45 degr ee swi vel hanger s so t hat t hey hang pl umb and l evel . Locat e so t hat t her e ar e no obst r uct i ons wi t hi n t he 45 degr ee r ange i n al l di r ect i ons. The st em, canopy and l umi nai r e must be capabl e of 45 degr ee swi ng. Pendant s, r ods, or chai ns 4 f eet or l onger excl udi ng l umi nai r e must be br aced t o pr event swayi ng usi ng t hr ee cabl es at 120 degr ee separ at i on. Suspended l umi nai r es i n cont i nuous r ows must have i nt er nal wi r eway syst ems f or end t o end wi r i ng and must be pr oper l y al i gned t o pr ovi de a st r ai ght and cont i nuous r ow wi t hout bends, gaps, l i ght l eaks or f i l l er pi eces. Ut i l i ze al i gni ng spl i nes on ext r uded al umi num l umi nai r es t o assur e mi ni mal hai r l i ne j oi nt s. Suppor t st eel l umi nai r es t o pr event " oi l - canni ng" ef f ect s. Lumi nai r e f i ni shes must be f r ee of scr at ches, ni cks, dent s, and war ps, and must mat ch t he col or and gl oss speci f i ed.

Mat ch suppor t i ng pendant s wi t h suppor t ed l umi nai r e. Ai r cr af t cabl e must be st ai nl ess st eel . Canopi es must be f i ni shed t o mat ch t he cei l i ng and must be l ow pr of i l e unl ess ot her wi se shown. Maxi mum di st ance bet ween suspensi on poi nt s must be 10 f eet or as r ecommended by t he manuf act ur er , whi chever i s less.

3. 1. 4 Power Suppl i es

Typi cal l y, G power suppl i es ( dr i ver s) i nt egr al t o l umi nai r e as const r uct ed by t he manuf act ur er .

3. 1. 5 Exi t Si gns and Emer gency Li ght i ng Uni t s

Wi r e exi t s i gns and emer gency l i ght i ng uni t s ahead of t he l ocal swi t ch, t o t he nor mal l i ght i ng c i r cui t l ocat ed i n t he same r oom or ar ea.

3. 1. 5. 1 Exi t Si gns

Connect exi t s i gns on separ at e c i r cui t s and ser ve f r om a separ at e c i r cui t br eaker . Pr ovi de onl y one sour ce of cont r ol , whi ch woul d be t he separ at e c i r cui t br eaker . Pai nt sour ce of cont r ol r ed and pr ovi de l ockout capability.

3. 1. 5. 2 Emer gency Li ght i ng f r om Emer gency Li ght i ng I nver t er

Connect emer gency l i ght i ng f r om an emer gency l i ght i ng i nver t er as i ndi cat ed on t he pr oj ect dr awi ngs.

3. 1. 6 Occupancy Sensor s

Pr ovi de t est i ng of sensor cover age i n al l spaces wher e sensor s ar e pl aced.

Thi s shoul d be done onl y af t er al l f ur ni shi ngs ( car pet , f ur ni t ur e, wor kst at i ons, et c. ) have been i nst al l ed. Pr ovi de quant i t y of sensor uni t s

SECTI ON 26 51 00 Page 17 ( Revi sed by Amendment 0001) i ndi cat ed as a mi ni mum. Pr ovi de addi t i onal uni t s t o gi ve f ul l cover age over cont r ol l ed ar ea. Ful l cover age must pr ovi de hand and ar m mot i on det ect i on f or of f i ce and admi ni st r at i on t ype ar eas and wal k i ng mot i on f or i ndust r i al ar eas, war ehouses, st or age r ooms and hal l ways. Locat e t he sensor ( s) as i ndi cat ed and i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons t o maxi mi ze ener gy savi ngs and t o avoi d nui sance act i vat i on and deact i vat i on due t o sudden t emper at ur e or ai r f l ow changes and usage.

3. 1. 7 Dayl i ght or Ambi ent Li ght Level Sensor

Locat e sensor as i ndi cat ed and i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons. Adj ust sensor f or f or t he i ndi cat ed l i ght l evel measur ed at t he wor k pl ane f or t hat par t i cul ar ar ea.

3. 2 FI ELD APPLI ED PAI NTI NG

Pai nt l i ght i ng equi pment as r equi r ed t o mat ch f i ni sh of adj acent sur f aces or t o meet t he i ndi cat ed or speci f i ed saf et y cr i t er i a.

This is the start of the file's text. The full file is on GovTribe.