Shaw AFB SC (SHW)-FMP.xlsx
XLSX spreadsheet 147 KB Posted
- Solicitation number
- W912DY26RA017
About this file
This file is a detailed Facility Maintenance Plan spreadsheet for Shaw Air Force Base in South Carolina, documenting extensive maintenance requirements for multiple fuel storage, transfer, and dispensing systems. The document covers numerous components across different facility areas including fill stands, pumps, valves, tanks, and electrical systems, with specific maintenance schedules, unique identifiers, manufacturers, and technical specifications for each asset.
The maintenance plan includes comprehensive details for facilities such as petroleum operations buildings, vehicle fueling stations, diesel and mogas storage tanks, and jet fuel storage tanks. Each component has specific maintenance instructions, with most requiring lock-out/tag-out procedures and system placement out-of-service during maintenance. The plan is associated with a draft solicitation (W912DY26RA017) by the U.S. Army Corps of Engineers for preventive and corrective maintenance supporting Defense Logistics Agency - Energy (DLA-E) in the South Atlantic Division, covering maintenance services for U.S. Air Force facilities in multiple southeastern states and territories.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Installation Name | Shaw AFB |
| DLA Site Code | SHW | |
| Hours of Operation | 0700 - 1600 | |
| Address | 784 Fighting Falcon St, Shaw AFB, SC 29152 | |
| Contract | Contractor | Weston Solutions |
| Contract # | 47QSHA18D0016 / W912DY20F4075 | |
| Local POCs | QAE Phone | 803-895-2218 |
| QAE Email | james.brown.209@us.af.mil | |
| Alt QAE Phone | 803-895-2218 | |
| Alt QAE Email | curtis.mourey@us.af.mil | |
| DLA/SCP POCs | DLA PM Phone | 571-767-8133 |
| DLA PM Email | patricia.beyer@dla.mil | |
| SCP PM Phone | 571-767-0726 | |
| SCP PM Email | david.w.king@dla.mil | |
| Contractor POCs | Contractor PM Phone | 770-325-7907 |
| Contractor PM Email | john.deahl@westonsolutions.com | |
| Contractor QC Phone | 207-841-3530 | |
| Contractor QC Email | matt.altekruse@westonsolutions.com | |
| Contractor SM Phone | 229-834-4663 | |
| Contractor SM Email | kenric.smith@westonsolutions.com | |
| USACE POCs | USACE PM Phone | 256-895-1067 |
| USACE PM Email | richard.a.resler@usace.army.mil | |
| USACE COR Phone | 256-895-1745 | |
| USACE COR Email | moon.h.hemm@usace.army.mil | |
| USACE PE Phone | 256-895-1947 | |
| USACE PE Email | corey.a.asher@usace.army.mil | |
| USACE KO Phone | 256-895-1117 | |
| USACE KO Email | aquiller.e.cole@usace.army.mil |
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
mailto:john.deahl@westonsolutions.commailto:matt.altekruse@westonsolutions.commailto:patricia.beyer@dla.milmailto:david.w.king@dla.milmailto:kenric.smith@westonsolutions.commailto:corey.a.asher@usace.army.milmailto:aquiller.e.cole@usace.army.milmailto:richard.a.resler@usace.army.milmailto:moon.h.hemm@usace.army.mil General Facility Description
Appendix K - Facility Maintenance Plan
&P of &N
Installation includes a main petrol operations building, (3) API 653 tanks [one of which is under construction as of October 2020], (6) fillstands [two of which are for Mogas and Diesel], (4) offload stations, (2) diesel tanks, a mogas tank, and (2) service stations.
Communication Plan
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, etc.
Safety
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
| APPENDIX J - EXISTING MAINTENANCE SCHEDULES | |||||||||||||||||||||
| # | Installation Name | Site Name | DLA Site Code | RPSUID | Location | City | ST | Existing Max Freq | 1st Quarter | ||||||||||||
| Contract PoP 14 Aug 20 -13 Aug 21 | 2nd Quarter | 3rd Quarter | 4th Quarter | ||||||||||||||||||
| Aug-24 | Sep-24 | Oct-24 | Nov-24 | Dec-24 | Jan-25 | Feb-25 | Mar-25 | Apr-25 | May-25 | Jun-25 | Jul-25 | ||||||||||
| 1 | SI CAPE CANAVERAL | Cape Canaveral AFS Site #1 | DBE | 1555 | Cape Canaveral AFS | Cape Canaveral | FL | 1 | Annual |
2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21
| 3 | JACKSONVILLE IAP | Jacksonville IAP Site #1 | JVL | 2390 | Jacksonville ANG | Jacksonville | FL | 1 | SA1/Q1 | |
| 10/16-10/18 | Q2 | |||||||||
| 1/21-1/22 | A/SA2/Q3 | |||||||||
| 4/22-4/25 | Q4 |
7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10
| 5 | ROBINS AFB | Robins Air Force Base Site 1 | ROB | 3219 | Robins ANG, GA | Warner Robins | GA | 4 | SA1/Q1 | |
| 8/28-8/30 | Q2 | |||||||||
| 11/21-11/22 | A/SA2/Q3 | |||||||||
| 3/3-3/6 | Q4 |
6/3-6/4
| 6 | SI MOODY | Moody AFB | MDY | 3020 | Moody AFB, GA | Valdosta | GA | 4 | Q1 | |
| 9/16-9/18 | A-SA1-Q2 | |||||||||
| 12/02-12/11 | Q3 | |||||||||
| 3/24-3/26 | SA2-Q4 |
6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16
| 8 | SAVANNAH HILTON HEAD IAP | Savannah ANG (IAP ID 107) | SAG | 17105 | Savannah ANG, GA (IAP ID 107) | Savannah | GA | 1 | Annual | |
| 12/17-12/19 | MC | |||||||||
| 9 | SAVANNAH HILTON HEAD IAP | Savannah/Hilton Head IAP Site #3 | SHH | 3358 | SAVANNAH/HILTON HEAD IAP SITE #5 | Savannah | GA | 4 | Annual |
12/20
| 10 | JB CHARLESTON | DFSP Charleston | CHS | 1580 | DFSP Charleston | Charleston | SC | 1 | SA1/Q1 | |
| 8/19-8/23 | Q2 | |||||||||
| 11/13-11/15 | A/SA2/Q3 | |||||||||
| 2/3-2/21 | Q4 |
5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22
| 12 | JB CHARLESTON | Joint Base Charleston NWS | JBC | 213 | JOINT BASE CHARLESTON NAVAL WEAPONS STATION | Charleston | SC | 4 | Q1 | |
| 9/10 | SA1-Q2 | |||||||||
| 12/10-12/11 | Q3 | |||||||||
| 3/11-3/12 | A-SA2-Q4 |
6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24
| 15 | CHARLOTTE IAP | Douglas MAP ANG (ID 146) | DGL | 1661 | Douglas MAP ANG, NC (ID 146) | Charlotte | NC | 1 | Annual | |
| 11/04-11/06 | MC | |||||||||
| 16 | CHARLOTTE IAP | Stanly County Airport | WEF | 3312 | Stanly County Airport | New London | NC | 1 | Annual |
11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17
Task Matrix
| UFC System Level Maintenance Frequency | Special Considerations | |||||||||||||||||||
| EBS Facility # | iNFADS Facility # | ACES/ NEXGEN Facility # | Real Property Unique Identifier | Facility Name | Operational Area | Component Type | CUID | Make | Model | Capacity/Size | Q | S | A | UFC Section Reference | Manufacturer Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments | |
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | PRT/Signage | SHW-109-SIGN-0001 | 25 Gallom | X | 2-7 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | PRT/Signage | SHW-109-SIGN-0002 | 25 Gallom | X | 2-7 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | PRT/Signage | SHW-109-SIGN-0003 | 25 Gallom | X | 2-7 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | PRT/Signage | SHW-109-SIGN-0004 | 25 Gallom | X | 2-7 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Scully Truck Grounding | SHW-109-GRVS-0001 | X | 9-5 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Scully Truck Grounding | SHW-109-GRVS-0002 | X | 9-5 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Scully Truck Grounding | SHW-109-GRVS-0003 | X | 9-5 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Scully Truck Grounding | SHW-109-GRVS-0004 | X | 9-5 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | FS Air Elimanator | SHW-109-AAVT-0001 | 1" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | FS Air Elimanator | SHW-109-AAVT-0002 | 1" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | FS Air Elimanator | SHW-109-AAVT-0003 | 1" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | FS Air Elimanator | SHW-109-AAVT-0004 | 1" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | F/S | SHW-109-FLSP-0001 | ME Industries | VCS-543-236 | 6 Filters | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||||||||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | F/S | SHW-109-FLSP-0002 | ME Industries | VCS-543-236 | 6 Filters | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||||||||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | F/S | SHW-109-FLSP-0003 | ME Industries | VCS-543-236 | 6 Filters | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||||||||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | F/S | SHW-109-FLSP-0004 | ME Industries | VCS-543-236 | 6 Filters | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||||||||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Meter | SHW-109-PDMT-0001 | Smith | SF6-NF | 4" | X | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Meter | SHW-109-PDMT-0002 | Smith | SF6-NF | 4" | X | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Meter | SHW-109-PDMT-0003 | Smith | SF6-NF | 4" | X | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Meter | SHW-109-PDMT-0004 | Smith | SF6-NF | 4" | X | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Hose | SHW-109-LDHS-0001 | 3" | X | X | 3-9.1 | See Mfr. O&M | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Hose | SHW-109-LDHS-0002 | 3" | X | X | 3-9.1 | See Mfr. O&M | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Hose | SHW-109-LDHS-0003 | 3" | X | X | 3-9.1 | See Mfr. O&M | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Hose | SHW-109-LDHS-0004 | 3" | X | X | 3-9.1 | See Mfr. O&M | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Cla Val | SHW-109-GSCVL-0001 | Cla Val | 4 90-53ASKX | 4" | X | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Cla Val | SHW-109-GSCVL-0002 | Cla Val | 4 90-53ASKX | 4" | X | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Cla Val | SHW-109-GSCVL-0003 | Cla Val | 4" | X | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Cla Val | SHW-109-GSCVL-0004 | Cla Val | 4" | X | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Cla Val | SHW-109-GSCVL-0005 | Cla Val | 40-28AF | 6" | X | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Cla Val | SHW-109-GSCVL-0006 | Cla Val | 40-28AF | 6" | X | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | D-3 Snigle Point Nozzle | SHW-109-FLNZ-0001 | Cla Val | D3 - 3416F | 3" | 4-7.4 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | D-3 Snigle Point Nozzle | SHW-109-FLNZ-0002 | Cla Val | D3 - 3416F | 3" | 4-7.4 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | D-3 Snigle Point Nozzle | SHW-109-FLNZ-0003 | Cla Val | D3 - 3416F | 3" | 4-7.4 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | D-3 Snigle Point Nozzle | SHW-109-FLNZ-0004 | Cla Val | D3 - 3416F | 3" | 4-7.4 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | VISI FLOW | SHW-109-SFND-0001 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | VISI FLOW | SHW-109-SFND-0002 | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | VISI FLOW | SHW-109-SFND-0003 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | VISI FLOW | SHW-109-SFND-0004 | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | VISI FLOW | SHW-109-SFND-0005 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | VISI FLOW | SHW-109-SFND-0006 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | VISI FLOW | SHW-109-SFND-0007 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | VISI FLOW | SHW-109-SFND-0008 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | VISI FLOW | SHW-109-SFND-0009 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | VISI FLOW | SHW-109-SFND-0010 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | VISI FLOW | SHW-109-SFND-0011 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | VISI FLOW | SHW-109-SFND-0012 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # F/S 1 & 2 Rec Line | VISI FLOW | SHW-109-SFND-0013 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Ball Val | SHW-109-BLVL-0001 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Ball Val | SHW-109-BLVL-0002 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Ball Val | SHW-109-BLVL-0003 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Ball Val | SHW-109-BLVL-0004 | 1"" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Ball Val | SHW-109-BLVL-0005 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Ball Val | SHW-109-BLVL-0006 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Ball Val | SHW-109-BLVL-0007 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Ball Val | SHW-109-BLVL-0008 | 1"" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Ball Val | SHW-109-BLVL-0009 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0010 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0011 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Flandge Ball Val | SHW-109-BLVL-0012 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Flandge Ball Val | SHW-109-BLVL-0013 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Flandge Ball Val | SHW-109-BLVL-0014 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Flandge Ball Val | SHW-109-BLVL-0015 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Ball Val | SHW-109-BLVL-0016 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Ball Val | SHW-109-BLVL-0017 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Ball Val | SHW-109-BLVL-0018 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0019 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0020 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Flandge Ball Val | SHW-109-BLVL-0021 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Flandge Ball Val | SHW-109-BLVL-0022 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Flandge Ball Val | SHW-109-BLVL-0023 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Flandge Ball Val | SHW-109-BLVL-0024 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Ball Val | SHW-109-BLVL-0025 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Ball Val | SHW-109-BLVL-0026 | 1"" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Flandge Ball | SHW-109-BLVL-0027 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0028 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0029 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | F/S Flandge Ball Val - Fill | SHW-109-BLVL-0030 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | F/S Flandge Ball Val - Fill | SHW-109-BLVL-0031 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Flandge Ball | SHW-109-BLVL-0032 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Flandge Ball | SHW-109-BLVL-0033 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Flandge Ball | SHW-109-BLVL-0034 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Flandge Ball | SHW-109-BLVL-0035 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Flandge Ball | SHW-109-BLVL-0036 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Flandge Ball | SHW-109-BLVL-0037 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0038 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | F/S Flandge Ball Val - Drain | SHW-109-BLVL-0039 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | F/S Flandge Ball Val - Fill | SHW-109-BLVL-0040 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | F/S Flandge Ball Val - Fill | SHW-109-BLVL-0041 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Flandge Ball | SHW-109-BLVL-0042 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Flandge Ball | SHW-109-BLVL-0043 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Flandge Ball | SHW-109-BLVL-0044 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Flandge Ball | SHW-109-BLVL-0045 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Flandge Ball | SHW-109-BLVL-0046 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # F/S 1 & 2 Rec Line | Flandge Ball | SHW-109-BLVL-0047 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # F/S 1 & 2 Rec Line | Flandge Ball | SHW-109-BLVL-0048 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | DB&B | SHW-109-DBBVL-0001 | True Seal | 8811RF | 4" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | DB&B | SHW-109-DBBVL-0002 | True Seal | 8811RF | 4" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | DB&B | SHW-109-DBBVL-0003 | True Seal | 8811RF | 6" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | DB&B | SHW-109-DBBVL-0004 | True Seal | 8811RF | 6" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | PRV | SHW-109-PRVL-0001 | Taylor | 82E4751511-10-00-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | PRV | SHW-109-PRVL-0002 | Taylor | 82E4751511-10-00-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | PRV | SHW-109-PRVL-0003 | Taylor | 82E4751511-10-00-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | PRV | SHW-109-PRVL-0004 | Taylor | 82E4751511-10-00-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | F/S PRV | SHW-109-PRVL-0005 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | PRV | SHW-109-PRVL-0006 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | PRV | SHW-109-PRVL-0007 | Taylor | 82E4751511-10-00-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | F/S PRV | SHW-109-PRVL-0008 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | PRV | SHW-109-PRVL-0009 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | PRV | SHW-109-PRVL-0010 | Taylor | 82E4751511-10-00-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | F/S PRV | SHW-109-PRVL-0011 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | PRV | SHW-109-PRVL-0012 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | PRV | SHW-109-PRVL-0013 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | F/S PRV | SHW-109-PRVL-0014 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | PRV | SHW-109-PRVL-0015 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | PRV | SHW-109-PRVL-0016 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # F/S 1 & 2 Rec Line | PRV | SHW-109-PRVL-0017 | Taylor Val | 77-221055-10-10-0 | 1" | X | X | 6-6.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Dead Man Handle | SHW-109-TFVL-0001 | X | 6-6.5.1 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Dead Man Handle | SHW-109-TFVL-0002 | X | 6-6.5.1 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Dead Man Handle | SHW-109-TFVL-0003 | X | 6-6.5.1 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Dead Man Handle | SHW-109-TFVL-0004 | X | 6-6.5.1 | See Mfr. O&M | |||||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Pressure Gauge | SHW-109-PVGA-0001 | 1/4" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | Defective | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | Pressure Gauge | SHW-109-PVGA-0002 | 1/2" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Pressure Gauge | SHW-109-PVGA-0003 | 1/4" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | Defective | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | Pressure Gauge | SHW-109-PVGA-0004 | 1/2" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Pressure Gauge | SHW-109-PVGA-0005 | USG | 1/2" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | Defective | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Pressure Gauge | SHW-109-PVGA-0006 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | Pressure Gauge | SHW-109-PVGA-0007 | 1/2" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Pressure Gauge | SHW-109-PVGA-0008 | USG | 1/2" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | Defective | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Pressure Gauge | SHW-109-PVGA-0009 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | Pressure Gauge | SHW-109-PVGA-0010 | 1/2" / 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | Pressure Gauge | SHW-109-PVGA-0011 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | Pressure Gauge | SHW-109-PVGA-0012 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | DP Guage | SHW-109-DPGA-0001 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | DP Guage | SHW-109-DPGA-0002 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 1 F/S | DP Guage | SHW-109-DPGA-0003 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 F/S | DP Guage | SHW-109-DPGA-0004 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand #1 | PRT | SHW-109-PRDST-0001 | 25 Gallom | X | 8-9.10 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 2 | PRT | SHW-109-PRDST-0002 | 25 Gallom | X | 8-9.10 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 3 | PRT | SHW-109-PRDST-0003 | 25 Gallom | X | 8-9.10 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 109 | 109 | 516308 | LF FIL STD, TRK | Fill Stand # 4 | PRT | SHW-109-PRDST-0004 | 25 Gallom | X | 8-9.10 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | FS Air Elimanator | SHW-112-AAVT-0001 | 1" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | F/S | SHW-112-FLSP-0001 | ME Industries | VCS-856-344 | 1200 gpm; 6 Filters | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System Placed Out-of-Service | |||||||||||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Discharge | Basket Strainer | SHW-112-BSTR-0001 | Velan | 8" | 3-6.4 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Suction | Pump | SHW-112-CENP-0001 | Union Pump | 470-508 13 | 600 GPM | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | Pump | SHW-112-CENP-0002 | Union Pump | 470-508 13 | 600 GPM | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | Pump | SHW-112-CENP-0003 | Union Pump | 470-508 13 | 600 GPM | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | Pump | SHW-112-CENP-0004 | Union Pump | 470-508 13 | 600 GPM | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | Cla Val | SHW-112-RCVL-0001 | Cal Val | 40-30ACGS | 4" | X | 4-3.2.5 | See Mfr. O&M | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Discharge | Cla Val | SHW-112-RCVL-0002 | Cal Val | 40-30ACGS | 4" | X | 4-3.2.5 | See Mfr. O&M | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Discharge | Cla Val | SHW-112-RCVL-0003 | Cal Val | 40-30ACGS | 4" | X | 4-3.2.5 | See Mfr. O&M | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Discharge | Cla Val | SHW-112-RCVL-0004 | Cal Val | 40-30ACGS | 4" | X | 4-3.2.5 | See Mfr. O&M | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Cla Val | SHW-112-FSCVL-0001 | Cla Val | 40-28AF | 8" | X | X | 4-4.2.2 | See Mfr. O&M | |||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Suction | VISI Flow | SHW-112-SFND-0001 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | VISI Flow | SHW-112-SFND-0002 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | VISI Flow | SHW-112-SFND-0003 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Discharge | VISI Flow | SHW-112-SFND-0004 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | VISI Flow | SHW-112-SFND-0005 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Discharge | VISI Flow | SHW-112-SFND-0006 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | VISI Flow | SHW-112-SFND-0007 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Discharge | VISI Flow | SHW-112-SFND-0008 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | VISI FLOW | SHW-112-SFND-0009 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | VISI FLOW | SHW-112-SFND-0010 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | VISI FLOW | SHW-112-SFND-0011 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | VISI FLOW | SHW-112-SFND-0012 | 1 1/2" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | ||||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | VISI FLOW | SHW-112-SFND-0013 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | VISI FLOW | SHW-112-SFND-0014 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec PRT | VISI FLOW | SHW-112-SFND-0015 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec PRT | VISI FLOW | SHW-112-SFND-0016 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec PRT | VISI FLOW | SHW-112-SFND-0017 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec PRT | VISI FLOW | SHW-112-SFND-0018 | VISI Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Suction | Ball Val | SHW-112-BLVL-0001 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 | Ball Val | SHW-112-BLVL-0002 | 3/4' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 | Ball Val - HP Vent | SHW-112-BLVL-0003 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Suction | Ball Val | SHW-112-BLVL-0004 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Suction | Flandge Ball Val - LP Drain | SHW-112-BLVL-0005 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | Ball Val | SHW-112-BLVL-0006 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | Ball Val - hP Vent | SHW-112-BLVL-0007 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | Ball Val | SHW-112-BLVL-0008 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | Ball Val | SHW-112-BLVL-0009 | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | Ball Val | SHW-112-BLVL-0010 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | Ball Val | SHW-112-BLVL-0011 | 3/4' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | Ball Val - HP Vent | SHW-112-BLVL-0012 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | Ball Val | SHW-112-BLVL-0013 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Suction | Flandge Ball Val - LP Drain | SHW-112-BLVL-0014 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #1 Discharge | Ball Val | SHW-112-BLVL-0015 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Discharge | Ball Val - hP Vent | SHW-112-BLVL-0016 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Discharge | Ball Val | SHW-112-BLVL-0017 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #2 Discharge | Ball Val | SHW-112-BLVL-0018 | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | Ball Val | SHW-112-BLVL-0019 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | Ball Val | SHW-112-BLVL-0020 | 3/4' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | Ball Val - HP Vent | SHW-112-BLVL-0021 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | Ball Val | SHW-112-BLVL-0022 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Suction | Flandge Ball Val - LP Drain | SHW-112-BLVL-0023 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Discharge | Ball Val | SHW-112-BLVL-0024 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Discharge | Ball Val - hP Vent | SHW-112-BLVL-0025 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Discharge | Ball Val | SHW-112-BLVL-0026 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #3 Discharge | Ball Val | SHW-112-BLVL-0027 | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | Ball Val | SHW-112-BLVL-0028 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | Ball Val | SHW-112-BLVL-0029 | 3/4' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | Ball Val - HP Vent | SHW-112-BLVL-0030 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | Ball Val | SHW-112-BLVL-0031 | 1/2' | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Suction | Flandge Ball Val - LP Drain | SHW-112-BLVL-0032 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Discharge | Ball Val | SHW-112-BLVL-0033 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Discharge | Ball Val - hP Vent | SHW-112-BLVL-0034 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Discharge | Ball Val | SHW-112-BLVL-0035 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Issue Pump #4 Discharge | Ball Val | SHW-112-BLVL-0036 | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball Val | SHW-112-BLVL-0037 | Velan | 9609-421 | 8" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball Val | SHW-112-BLVL-0038 | Velan | 9609-421 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball Val | SHW-112-BLVL-0039 | Velan | 9609-421 | 8" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | F/S Flandge Ball Val - Drain | SHW-112-BLVL-0040 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | F/S Flandge Ball Val - Drain | SHW-112-BLVL-0041 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | F/S Flandge Ball Val - Fill | SHW-112-BLVL-0042 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | F/S Flandge Ball Val - Fill | SHW-112-BLVL-0043 | 1 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball | SHW-112-BLVL-0044 | Velan | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball | SHW-112-BLVL-0045 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball | SHW-112-BLVL-0046 | 8" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S | Flandge Ball | SHW-112-BLVL-0047 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball LP Drain | SHW-112-BLVL-0048 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball Val | SHW-112-BLVL-0049 | Velan | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball Val | SHW-112-BLVL-0050 | Velan | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball Val | SHW-112-BLVL-0051 | Velan | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball LP Drain | SHW-112-BLVL-0052 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | ||||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball Val | SHW-112-BLVL-0053 | Velan | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service | |||||||
| 112 | 112 | 516316 | PETROL OPS BLDG | Rec F/S By Pass | Flandge Ball | SHW-112-BLVL-0054 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System Placed Out-of-Service |