McEntire ANG SC (MNT)-FMP.xlsx
XLSX spreadsheet 101 KB Posted
- Solicitation number
- W912DY26RA017
About this file
This file is a detailed Facility Maintenance Plan (Appendix K) for the McEntire Air National Guard Base (MNT) fuel facility located in Eastover, South Carolina. The comprehensive document provides an exhaustive inventory and maintenance matrix for multiple fuel infrastructure components, including two bulk storage tanks (one diesel DS-2 and one MOGAS), two jet fuel tanks, two truck offload stations, two truck fillstands, and associated pumping, piping, and electrical systems.
The maintenance plan covers a wide range of equipment including pumps, valves, meters, pressure gauges, motors, grounding systems, and safety features like eye wash stations. The contract is part of a larger Defense Logistics Agency - Energy (DLA-E) maintenance support contract for the South Atlantic Division, with Weston Solutions as the current contractor (Contract #47QSHA18D0016 / W912DY20F4075). Each component has detailed maintenance requirements, with specific instructions for routine maintenance, calibration, potential service order needs, and requirements for lock-out/tag-out procedures. Key points of contact include personnel from DLA, U.S. Army Corps of Engineers, and the contractor, with maintenance activities designed to ensure operational readiness and safety of the fuel handling infrastructure.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Installation Name | McEntire JNGB |
| DLA Site Code | MNT | |
| Hours of Operation | 0700 - 1600 | |
| Address | 1325 South Carolina Rd, Suite 8, Eastover, SC 29044 | |
| Contract | Contractor | Weston Solutions |
| Contract # | 47QSHA18D0016 / W912DY20F4075 | |
| Local POCs | QAE Phone | 803-647-8143 |
| QAE Email | stephen.rector.1@us.af.mil | |
| Alt QAE Phone | 803-647-8397 | |
| Alt QAE Email | christian.j.huettmann.nfg@mail.mil | |
| DLA/SCP POCs | DLA PM Phone | 571-767-8133 |
| DLA PM Email | patricia.beyer@dla.mil | |
| SCP PM Phone | 571-767-0726 | |
| SCP PM Email | david.w.king@dla.mil | |
| Contractor POCs | Contractor PM Phone | 770-325-7907 |
| Contractor PM Email | john.deahl@westonsolutions.com | |
| Contractor QC Phone | 207-841-3530 | |
| Contractor QC Email | matt.altekruse@westonsolutions.com | |
| Contractor SM Phone | 229-834-4663 | |
| Contractor SM Email | kenric.smith@westonsolutions.com | |
| USACE POCs | USACE PM Phone | 256-895-1067 |
| USACE PM Email | richard.a.resler@usace.army.mil | |
| USACE COR Phone | 256-895-1745 | |
| USACE COR Email | moon.h.hemm@usace.army.mil | |
| USACE PE Phone | 256-895-1947 | |
| USACE PE Email | corey.a.asher@usace.army.mil | |
| USACE KO Phone | 256-895-1117 | |
| USACE KO Email | aquiller.e.cole@usace.army.mil |
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
mailto:john.deahl@westonsolutions.commailto:matt.altekruse@westonsolutions.commailto:patricia.beyer@dla.milmailto:david.w.king@dla.milmailto:kenric.smith@westonsolutions.commailto:corey.a.asher@usace.army.milmailto:aquiller.e.cole@usace.army.milmailto:richard.a.resler@usace.army.milmailto:moon.h.hemm@usace.army.mil General Facility Description
Appendix K - Facility Maintenance Plan
&P of &N
Installation includes a pump station with two (2) bulk storage tanks. There is a fuel station with a MOGAS and DS-2 tank. Additionally, there are two (2) truck offloads and two (2) truck fillstands.
Communication Plan
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, etc.
Safety
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
| APPENDIX J - EXISTING MAINTENANCE SCHEDULES | |||||||||||||||||||||
| # | Installation Name | Site Name | DLA Site Code | RPSUID | Location | City | ST | Existing Max Freq | 1st Quarter | ||||||||||||
| Contract PoP 14 Aug 20 -13 Aug 21 | 2nd Quarter | 3rd Quarter | 4th Quarter | ||||||||||||||||||
| Aug-24 | Sep-24 | Oct-24 | Nov-24 | Dec-24 | Jan-25 | Feb-25 | Mar-25 | Apr-25 | May-25 | Jun-25 | Jul-25 | ||||||||||
| 1 | SI CAPE CANAVERAL | Cape Canaveral AFS Site #1 | DBE | 1555 | Cape Canaveral AFS | Cape Canaveral | FL | 1 | Annual |
2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21
| 3 | JACKSONVILLE IAP | Jacksonville IAP Site #1 | JVL | 2390 | Jacksonville ANG | Jacksonville | FL | 1 | SA1/Q1 | |
| 10/16-10/18 | Q2 | |||||||||
| 1/21-1/22 | A/SA2/Q3 | |||||||||
| 4/22-4/25 | Q4 |
7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10
| 5 | ROBINS AFB | Robins Air Force Base Site 1 | ROB | 3219 | Robins ANG, GA | Warner Robins | GA | 4 | SA1/Q1 | |
| 8/28-8/30 | Q2 | |||||||||
| 11/21-11/22 | A/SA2/Q3 | |||||||||
| 3/3-3/6 | Q4 |
6/3-6/4
| 6 | SI MOODY | Moody AFB | MDY | 3020 | Moody AFB, GA | Valdosta | GA | 4 | Q1 | |
| 9/16-9/18 | A-SA1-Q2 | |||||||||
| 12/02-12/11 | Q3 | |||||||||
| 3/24-3/26 | SA2-Q4 |
6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16
| 8 | SAVANNAH HILTON HEAD IAP | Savannah ANG (IAP ID 107) | SAG | 17105 | Savannah ANG, GA (IAP ID 107) | Savannah | GA | 1 | Annual | |
| 12/17-12/19 | MC | |||||||||
| 9 | SAVANNAH HILTON HEAD IAP | Savannah/Hilton Head IAP Site #3 | SHH | 3358 | SAVANNAH/HILTON HEAD IAP SITE #5 | Savannah | GA | 4 | Annual |
12/20
| 10 | JB CHARLESTON | DFSP Charleston | CHS | 1580 | DFSP Charleston | Charleston | SC | 1 | SA1/Q1 | |
| 8/19-8/23 | Q2 | |||||||||
| 11/13-11/15 | A/SA2/Q3 | |||||||||
| 2/3-2/21 | Q4 |
5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22
| 12 | JB CHARLESTON | Joint Base Charleston NWS | JBC | 213 | JOINT BASE CHARLESTON NAVAL WEAPONS STATION | Charleston | SC | 4 | Q1 | |
| 9/10 | SA1-Q2 | |||||||||
| 12/10-12/11 | Q3 | |||||||||
| 3/11-3/12 | A-SA2-Q4 |
6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24
| 15 | CHARLOTTE IAP | Douglas MAP ANG (ID 146) | DGL | 1661 | Douglas MAP ANG, NC (ID 146) | Charlotte | NC | 1 | Annual | |
| 11/04-11/06 | MC | |||||||||
| 16 | CHARLOTTE IAP | Stanly County Airport | WEF | 3312 | Stanly County Airport | New London | NC | 1 | Annual |
11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17
Task Matrix
| UFC System Level Maintenance Frequency | Special Considerations | |||||||||||||||||||
| EBS Facility # | iNFADS Facility # | ACES/ NEXGEN Facility # | Real Property Unique Identifier | Facility Name | Operational Area | Component Type | CUID | Make | Model | Capacity/Size | Q | S | A | UFC Section Reference | Manufacturer Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments | |
| 1161 | 1161 | 488905 | PMP STN, LF | Pump House | Eye wash/Signage | MNT-1161-SIGN-0001 | X | 2-7 | See Mfr. O&M | |||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT | PRT/Signage | MNT-1161-SIGN-0002 | Highland | 1200 Gallons | X | 2-7 | See Mfr. O&M | |||||||||
| 3058 | 3058 | 489201 | OPG STOR, DIESEL | DS-2 Tank | Tank/Signage | MNT-3058-SIGN-0001 | 20K | X | 2-7 | See Mfr. O&M | ||||||||||
| 3059 | 3059 | 489202 | OPG STOR, MOGAS | GUR Tank | Tank/Signage | MNT-3059-SIGN-0001 | 20K | X | 2-7 | See Mfr. O&M | ||||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | API 653 Tank/Signage | MNT-3157-SIGN-0001 | 105K Gal | X | 2-7 | See Mfr. O&M | ||||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | PRT | PRT/Signage | MNT-3157-SIGN-0002 | Schultz | 100 Gallon | X | 2-7 | See Mfr. O&M | |||||||||
| 3158 | 3158 | 486224 | OPG STOR, JET FL | Tank # 2 | API 653 Tank | MNT-3158-SIGN-0001 | 105K Gal | X | 2-7 | See Mfr. O&M | ||||||||||
| 3158 | 3158 | 486224 | OPG STOR, JET FL | PRT | PRT/Signage | MNT-3158-SIGN-0002 | Schultz | 100 Gallon | X | 2-7 | See Mfr. O&M | |||||||||
| 3159 | 3159 | 486225 | LF STD UNLOAD | RT System | PRT/Signage | MNT-3159-SIGN-0001 | S/S 20 gallon tank | X | 2-7 | See Mfr. O&M | ||||||||||
| 3160 | 3160 | 486226 | LF FIL STD, TRK | Truck Fillstand # 1 | EFSO/Signage | MNT-3160-SIGN-0001 | Cooper Crouse | DS441 | X | 2-7 | See Mfr. O&M | |||||||||
| 3160 | 3160 | 486226 | LF FIL STD, TRK | Misc | Eye Wash/Signage | MNT-3160-SIGN-0002 | X | 2-7 | See Mfr. O&M | |||||||||||
| 3162 | 3162 | 1140767 | LF FIL STD, TRK | Truck Fillstand # 2 | EFSO/Signage | MNT-3162-SIGN-0001 | Cooper Crouse | DS441 | X | 2-7 | See Mfr. O&M | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | Air Elimanator | MNT-1161-AAVT-0001 | 3/4" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | Air Elimanator | MNT-1161-AAVT-0002 | 3/4" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | F/S | MNT-1161-FLSP-0001 | Facet International | CFCS-D-3N3SSB-163GT2M | 300 GPM; 3 Filters, 1 Coalescer | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | F/S | MNT-1161-FLSP-0002 | Facet International | CFCS-D-3N3SSB-163GT2M | 300 GPM; 3 Filters, 1 Coalescer | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||||||||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 Suction | Basket Straner | MNT-1161-BSTR-0001 | ISLIP Flow Controls | B15OFSS4BW1 | 3-6.4 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 Suction | Basket Straner | MNT-1161-BSTR-0002 | ISLIP Flow Controls | B15OFSS4BW1 | 3-6.4 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 | Pump | MNT-1161-CENP-0001 | Goulds Pumps | 3700 | 600 GPM | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 | Pump | MNT-1161-CENP-0002 | Goulds Pumps | 3700 | 600 GPM | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump #1 Pressure Bypass Line | Watts Val | MNT-1161-GSCVL-0001 | Watts Val | 116-5R | X | 4-3.2.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump #2 Pressure Bypass Line | Watts Val | MNT-1161-GSCVL-0002 | Watts Val | 116-5R | X | 4-3.2.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | Watts Val | MNT-1161-FSCVL-0001 | Watts Valve | 124-9R | 3" | X | X | 4-4.2.2 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | Watts Val | MNT-1161-FSCVL-0002 | Watts Valve | 124-9R | 3" | X | X | 4-4.2.2 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #1 | VISI FLOW | MNT-1161-SFND-0001 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #2 | VISI FLOW | MNT-1161-SFND-0002 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | VISI FLOW | MNT-1161-SFND-0003 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | VISI FLOW | MNT-1161-SFND-0004 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S Discharge Header | VISI FLOW | MNT-1161-SFND-0005 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pressure Bypass Line | VISI FLOW | MNT-1161-SFND-0006 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump Suction Header | VISI FLOW | MNT-1161-SFND-0007 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #1 | Ball Val | MNT-1161-BLVL-0001 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #1 | Flanged Ball Val | MNT-1161-BLVL-0002 | Flotite | SF150 | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #2 | Ball Val | MNT-1161-BLVL-0003 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #2 | Flanged Ball Val | MNT-1161-BLVL-0004 | Flotite | SF150 | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S By-Pass Line | Flanged Ball Val | MNT-1161-BLVL-0005 | NIBCO | 4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S By-Pass Line | Flanged Ball Val | MNT-1161-BLVL-0006 | NIBCO | 4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S By-Pass Line | Flanged Ball Val | MNT-1161-BLVL-0007 | NIBCO | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | Flanged Ball Val | MNT-1161-BLVL-0008 | Flotite | SF150 | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | Flanged Ball Val - Drain | MNT-1161-BLVL-0009 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | Flanged Ball Val | MNT-1161-BLVL-0010 | Flotite | SF150 | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | Flanged Ball Val - Drain | MNT-1161-BLVL-0011 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S Discharge Header | Flanged Ball Val | MNT-1161-BLVL-0012 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | Valve is very hard to open / Takes 2 people | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S Discharge Header | Flanged Ball Val | MNT-1161-BLVL-0013 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | Valve is very hard to open / Takes 2 people | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S Discharge Header | Flanged Ball Val | MNT-1161-BLVL-0014 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | Valve is very hard to open / Takes 2 people | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S Discharge Header | Flanged Ball Val | MNT-1161-BLVL-0015 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | Valve is very hard to open / Takes 2 people | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 Suction | Flanged Ball Val | MNT-1161-BLVL-0016 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 Suction | Ball Vall - Basket Straner Drain | MNT-1161-BLVL-0017 | NIBCO | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 Suction | Ball Val | MNT-1161-BLVL-0018 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 Suction | Flanged Ball Val | MNT-1161-BLVL-0019 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 Suction | Ball Vall - Basket Straner Drain | MNT-1161-BLVL-0020 | NIBCO | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 Suction | Ball Val | MNT-1161-BLVL-0021 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump #1 Pressure Bypass Line | Flanged Ball Val | MNT-1161-BLVL-0022 | NIBCO | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump #2 Pressure Bypass Line | Flanged Ball Val | MNT-1161-BLVL-0023 | NIBCO | 3" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #1 | PRV | MNT-1161-PRVL-0001 | Taylor Tools | 82-75151-00-10-0 | 3/4" R 60-175 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec Line #2 | PRV | MNT-1161-PRVL-0002 | Taylor Tools | 82-75151-00-10-0 | 3/4" R 60-175 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | PRV | MNT-1161-PRVL-0003 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | PRV | MNT-1161-PRVL-0004 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Rec F/S Discharge Header | PRV | MNT-1161-PRVL-0005 | Taylor Tools | 82-75151-00-10-0 | 3/4" R 60-175 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pressure Bypass Line | PRV | MNT-1161-PRVL-0006 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump Suction Header | PRV | MNT-1161-PRVL-0007 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | Pressure Gauge | MNT-1161-PVGA-0001 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | Pressure Gauge | MNT-1161-PVGA-0002 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 Suction | Vac Pressure Gauge | MNT-1161-PVGA-0003 | 1/4" -30 - 30 | X | X | X | 6-7.1 | See Mfr. O&M | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 Suction | Vac Pressure Gauge | MNT-1161-PVGA-0004 | 1/4" -30 - 30 | X | X | X | 6-7.1 | See Mfr. O&M | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 1 | DP Guage | MNT-1161-DPGA-0001 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | REC F/S # 2 | DP Guage | MNT-1161-DPGA-0002 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #1 | Motor | MNT-1161-ELEMT-0001 | Reliance Electric | 1MF78697 | 50 HP / 60 Hz / 3555 RPM | X | X | X | 9-1.7 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Pump #2 | Motor | MNT-1161-ELEMT-0002 | Reliance Electric | 1MF78697 | 50 HP / 60 Hz / 3555 RPM | X | X | X | 9-1.7 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #1 Discharge | PRV | MNT-1161-PRVL-0008 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #1 Discharge | VISI FLOW | MNT-1161-SFND-0008 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #1 Discharge | Pressure Gauge | MNT-1161-PVGA-0005 | Weston | 0 - 160 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #1 Discharge | Watts Val | MNT-1161-GSCVL-0003 | Watts Val | 6" | X | 4-3.2.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #1 Discharge | Flanged Ball Val | MNT-1161-BLVL-0024 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #1 Discharge | Flanged Ball Val | MNT-1161-BLVL-0025 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #2 Discharge | PRV | MNT-1161-PRVL-0009 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #2 Discharge | VISI FLOW | MNT-1161-SFND-0009 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #2 Discharge | Pressure Gauge | MNT-1161-PVGA-0006 | Weston | 0 - 160 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #2 Discharge | Cla Val | MNT-1161-GSCVL-0004 | Cla Val | 6" | X | 4-3.2.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #2 Discharge | Flanged Ball Val | MNT-1161-BLVL-0026 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue #2 Discharge | Flanged Ball Val | MNT-1161-BLVL-0027 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Discharge By Pass | Flanged Ball Val | MNT-1161-BLVL-0028 | NIBCO | F510-S6-R-66 FS | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Discharge By Pass | PRV | MNT-1161-PRVL-0010 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Discharge By Pass | VISI FLOW | MNT-1161-SFND-0010 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | F/S | MNT-1161-FLSP-0003 | Facet International | CFCS-D-7K38SB-1263T2M | 300 GPM; 7 Filters, 1 Coalescer | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||||||||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | DP Guage | MNT-1161-DPGA-0003 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | Pressure Gauge | MNT-1161-PVGA-0007 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | PRV | MNT-1161-PRVL-0011 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | Air Elimanator | MNT-1161-AAVT-0003 | 3/4" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | Watts Val | MNT-1161-FSCVL-0003 | Watts Valve | 124-9R | 6" | X | X | 4-4.2.2 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | Flanged Ball Val | MNT-1161-BLVL-0029 | Flotite | SF150 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | Flanged Ball Val - Drain | MNT-1161-BLVL-0030 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 1 | VISI FLOW | MNT-1161-SFND-0011 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | F/S | MNT-1161-FLSP-0004 | Facet International | CFCS-D-7K38SB-1263T2M | 300 GPM; 7 Filters, 1 Coalescer | X | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | |||||||
| Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||||||||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | DP Guage | MNT-1161-DPGA-0004 | Gammon | GTP-690-1 | 0-30 | X | X | 6-7.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | Pressure Gauge | MNT-1161-PVGA-0008 | Palmer | 1/4" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | PRV | MNT-1161-PRVL-0012 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | Air Elimanator | MNT-1161-AAVT-0004 | 3/4" | X | 3-10.2 | See Mfr. O&M | ||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | Watts Val | MNT-1161-FSCVL-0004 | Watts Valve | 124-9R | 6" | X | X | 4-4.2.2 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | Flanged Ball Val | MNT-1161-BLVL-0031 | Flotite | SF150 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | Flanged Ball Val - Drain | MNT-1161-BLVL-0032 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue F/S # 2 | VISI FLOW | MNT-1161-SFND-0012 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Header | PRV | MNT-1161-PRVL-0013 | Taylor | 82E4751311-00-00-0 | 3/4" | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Header | VISI FLOW | MNT-1161-SFND-0013 | VISI Flow | 1471-F 1 | 3/4" | 6-12.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Issue Header Bypass | Flanged Ball Val | MNT-1161-BLVL-0033 | Flotite | SF150 | 6" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Pump House | Eye wash / Shower | MNT-1161-EMEWSH-0001 | X | X | X | 11-3 | See Mfr. O&M | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT | PRT | MNT-1161-PRDST-0001 | Highland | 1200 Gallons | X | 8-9.10 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT | Pump | MNT-1161-CENP-0003 | Blackmer | HRO-GX | 3.3 HP | X | X | 3-8.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT | Motor | MNT-1161-ELEMT-0003 | Marathon | NH143TTGN6526AAP | X | X | X | 9-1.7 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT | Flanged Ball Val | MNT-1161-BLVL-0034 | Flow Tite | F150 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Discharge | Flanged Ball Val | MNT-1161-BLVL-0035 | Flow Tite | F150 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Discharge | Pressure Gauge w Stubber | MNT-1161-PVGA-0009 | Palmer | 1/2" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Discharge | Inline Check Valve | MNT-1161-CKVL-0001 | Titan | CV404142434446 | 2" | X | 6-6.2.8 | See Mfr. O&M | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Discharge | Flanged Ball Val | MNT-1161-BLVL-0036 | Flow Tite | F150 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Discharge | PRV | MNT-1161-PRVL-0014 | Taylor | 82E3751311-10-10-0 | 1" R 51 - 100 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Suction | Flanged Ball Val | MNT-1161-BLVL-0037 | Flow Tite | F150 | 1/2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Suction | Pressure Gauge | MNT-1161-PVGA-0010 | Palmer | 1/2" 0-300 | X | X | X | 6-7.1 | See Mfr. O&M | |||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Suction | Flanged Ball Val | MNT-1161-BLVL-0038 | Flow Tite | F150 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Suction | Flanged Ball Val | MNT-1161-BLVL-0039 | Flow Tite | F150 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Suction | Inline Check Valve | MNT-1161-CKVL-0002 | Titan | CV404142434446 | 2" | X | 6-6.2.8 | See Mfr. O&M | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | PRT Pump Suction | Flanged Ball Val | MNT-1161-BLVL-0040 | Flow Tite | F150 | 2" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Canopy | MNT-1161-CNPY-0001 | 11-2.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | |||||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0001 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0002 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0003 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0004 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0005 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0006 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0007 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0008 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Canopy | Explosion Proof Lights | MNT-1161-LIGHT-0009 | X | X | 9-1.8 | See Mfr. O&M | Repairs shall be performed through a service order. | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0001 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0002 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0003 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0004 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0005 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0006 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0007 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0008 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0009 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0010 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0011 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0012 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0013 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0014 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0015 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0016 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0017 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0018 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0019 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0020 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0021 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0022 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0023 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0024 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0025 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0026 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0027 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0028 | 6" covers | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0029 | 4" | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 1161 | 1161 | 488905 | PMP STN, LF | Bollards | Bollard | MNT-1161-BLRD-0030 | 4" | X | 11-2.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 3058 | 3058 | 489201 | OPG STOR, DIESEL | DS-2 Tank | Tank | MNT-3058-AGSFP-0001 | 20K | 8-5.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||||||
| 3058 | 3058 | 489201 | OPG STOR, DIESEL | DS-2 Tank | Ball Val | MNT-3058-BLVL-0001 | 4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3058 | 3058 | 489201 | OPG STOR, DIESEL | DS-2 Tank | Pump | MNT-3058-VTSP-0001 | Red Jacket | X | X | X | 3-8.1.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||||
| 3059 | 3059 | 489202 | OPG STOR, MOGAS | GUR Tank | Tank | MNT-3059-AGSFP-0001 | 20K | 8-5.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||||||
| 3059 | 3059 | 489202 | OPG STOR, MOGAS | GUR Tank | Ball Val | MNT-3059-BLVL-0001 | 4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3059 | 3059 | 489202 | OPG STOR, MOGAS | GUR Tank | Pump | MNT-3059-VTSP-0001 | Red Jacket | X | X | X | 3-8.1.3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | DS-2 | Meter | MNT-3060-PDMT-0001 | Total Control | 700-15SPA2AT2 | X | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO and System placed Out-of-Service | |||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | DS-2 | Swivel | MNT-3060-DSSW-0001 | OPW | 1" | 7-5 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | Remove by 09/20 | ||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | DS-2 | Breakaway | MNT-3060-DSBW-0001 | OPW | 66V-1300 | 1" | 7-4 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | Remove by 04/22 | |||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | DS-2 | Hose | MNT-3060-DSHS-0001 | 1' x 10' | 7-3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | DS-2 | Swivel | MNT-3060-DSSW-0002 | OPW | 1" | 7-5 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | Remove by 09/20 | ||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | DS-2 | Nozzle | MNT-3060-DSNZ-0001 | Harco | 1" | 7-2 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | No stamped dates | ||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | MUR | Meter | MNT-3060-PDMT-0002 | Total Control | 700-15SPA2AT2 | X | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO and System placed Out-of-Service | |||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | MUR | Swivel | MNT-3060-DSSW-0003 | OPW | 3/4" | 7-5 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | Remove by 9/20 | ||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | MUR | Breakaway | MNT-3060-DSBW-0002 | OPW | 66V-1300 | 3/4" | 7-4 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | No stamped dates | |||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | MUR | Hose | MNT-3060-DSHS-0002 | 3/4" x 10' | 7-3 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | MUR | Swivel | MNT-3060-DSSW-0004 | OPW | 3/4" | 7-5 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | No stamped dates | ||||||||
| 3060 | 3060 | 486213 | VEHICLE FUEL STATION | MUR | Nozzle | MNT-3060-DSNZ-0002 | Harco | 3/4" | 7-2 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | No stamped dates | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | API 653 Tank | MNT-3157-AGFET-0001 | 105K Gal | 8-4 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed Out-of-Service | |||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | Tank ground | MNT-3157-STGS-0001 | # 1 | X | X | 9-1.6.2 | See Mfr. O&M | |||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | Tank ground | MNT-3157-STGS-0002 | # 2 | X | X | 9-1.6.2 | See Mfr. O&M | |||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | Tank ground | MNT-3157-STGS-0003 | # 3 | X | X | 9-1.6.2 | See Mfr. O&M | |||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | Tank ground | MNT-3157-STGS-0004 | # 4 | X | X | 9-1.6.2 | See Mfr. O&M | |||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | Varec Gauge | MNT-3157-MOTGA-0001 | Varec | BM13661-111 | X | X | 8-9.8.1 | See Mfr. O&M | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | Low Level Canister | MNT-3157-EMLA-0001 | X | 8-9.9.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Tank # 1 | High Level Canister | MNT-3157-EMLA-0002 | Scully | X | 8-9.9.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | |||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Low Level Canister | Welded Ball Valve | MNT-3157-BLVL-0001 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Low Level Canister | Welded Ball Valve | MNT-3157-BLVL-0002 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Low Level Canister | Welded Ball Valve | MNT-3157-BLVL-0003 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Low Level Canister | Welded Ball Valve | MNT-3157-BLVL-0004 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Low Level Canister | Welded Ball Valve | MNT-3157-BLVL-0005 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | High Level Canister | Welded Ball Valve | MNT-3157-BLVL-0006 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | High Level Canister | Welded Ball Valve | MNT-3157-BLVL-0007 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | High Level Canister | Welded Ball Valve | MNT-3157-BLVL-0008 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | High Level Canister | Welded Ball Valve | MNT-3157-BLVL-0009 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | High Level Canister | Welded Ball Valve | MNT-3157-BLVL-0010 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Issue Line | Flanged Ball Val | MNT-3157-BLVL-0011 | Flow Tite | F150 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Issue Line | PRV | MNT-3157-PRVL-0001 | Taylor Valve | 82E3751311-10-10-0 | 3/4" to 1" R 101 - 225 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Issue Line | Flanged Ball Val | MNT-3157-BLVL-0012 | Flow Tite | F150 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Issue Line | DB&B Val | MNT-3157-DBBVL-0001 | Twin Seal | 8811 | 10" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Stripper Line | Flanged Ball Val | MNT-3157-BLVL-0013 | NIBCO | F510-S6-R-66 FS | 4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Stripper Line | DB&B Val | MNT-3157-DBBVL-0002 | Trus Seal | 4" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Stripper Line | Flanged Ball Val | MNT-3157-BLVL-0014 | Flow Tite | F150 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | Flanged Ball Val | MNT-3157-BLVL-0015 | Flow Tite | F150 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | PRV | MNT-3157-PRVL-0002 | Taylor Valve | 82E3751311-10-10-0 | 3/4" to 1" R 101 - 225 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | HLCV | MNT-3157-EHLSVL-0001 | Cla Val | 413-05AGS | 6" | X | X | 8-9.6.1 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | Flanged Ball Val | MNT-3157-BLVL-0016 | Flow Tite | F150 | 3/4" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | PRV | MNT-3157-PRVL-0003 | Taylor Valve | 82E3751311-10-10-0 | 3/4" to 1" R 101 - 225 | X | X | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair. | Requires LOTO and System placed Out-of-Service | |||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | DB&B Val | MNT-3157-DBBVL-0003 | Trus Seal | 211RF | 6" | X | X | 6-6.2.5 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | |||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | Rec Line | Flanged Ball Val | MNT-3157-BLVL-0017 | Flow Tite | F150 | 1" | X | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO and System placed Out-of-Service | ||||||
| 3157 | 3157 | 1140728 | OPG STOR, JET FL | PRT | PRT | MNT-3157-PRDST-0001 | Schultz | 100 Gallon | X | 8-9.10 | See Mfr. O&M | Requires LOTO and System placed Out-of-Service |