McEntire ANG SC (MNT)-FMP.xlsx

XLSX spreadsheet 101 KB Posted

Attached to
Draft Solicitation: Fuels South Atlantic Division - Air Force (SAD-AF2)
Solicitation number
W912DY26RA017
Issued by

About this file

This file is a detailed Facility Maintenance Plan (Appendix K) for the McEntire Air National Guard Base (MNT) fuel facility located in Eastover, South Carolina. The comprehensive document provides an exhaustive inventory and maintenance matrix for multiple fuel infrastructure components, including two bulk storage tanks (one diesel DS-2 and one MOGAS), two jet fuel tanks, two truck offload stations, two truck fillstands, and associated pumping, piping, and electrical systems.

The maintenance plan covers a wide range of equipment including pumps, valves, meters, pressure gauges, motors, grounding systems, and safety features like eye wash stations. The contract is part of a larger Defense Logistics Agency - Energy (DLA-E) maintenance support contract for the South Atlantic Division, with Weston Solutions as the current contractor (Contract #47QSHA18D0016 / W912DY20F4075). Each component has detailed maintenance requirements, with specific instructions for routine maintenance, calibration, potential service order needs, and requirements for lock-out/tag-out procedures. Key points of contact include personnel from DLA, U.S. Army Corps of Engineers, and the contractor, with maintenance activities designed to ensure operational readiness and safety of the fuel handling infrastructure.

View the file

Other files

File Type Posted
Moody AFB GA (MDY)-FMP.xlsx XLSX spreadsheet
Shaw AFB SC (SHW)-FMP.xlsx XLSX spreadsheet
Attachment 6 Draft QASP.pdf PDF
Attachment 4 - PPQ Sample (3).pdf PDF
DFSP Charleston SC (CHS)-FMP.xlsx XLSX spreadsheet
CDRL Set 16 60-64.pdf PDF
Attachment 3 Technical Evaluation Form.pdf PDF
Savannah ANG GA (SAG)-FMP.xlsx XLSX spreadsheet
Savannah-Hilton Head GA (SHH)-FMP.xlsx XLSX spreadsheet
Attachment 1 Performance Work Statement SAD-AF2.pdf PDF
Fuels SAD-AF2 Draft Solicitation W912DY26RA017.pdf PDF
Attachment 5 Instructions and Evaluation Factors.pdf PDF
CDRL Set 1 1-4.pdf PDF
CDRL Set 12 45-48.pdf PDF
CDRL Set 5 17-20.pdf PDF
CDRL Set 10 37-40.pdf PDF
CDRL Set 17 65-67.pdf PDF
CDRL Set 11 41-44.pdf PDF
Seymour Johnson AFB NC (SMJ)-FMP.xlsx XLSX spreadsheet
Joint Base Charleston SC (JBC)-FMP.xlsx XLSX spreadsheet
2.1 Appendix A - Attachment 1 Service Order Form-v11.5_20251027.xlsx XLSX spreadsheet
Attachment 8 Small Business Participation Plan Template.pdf PDF
Stanly County Airport NC (WEF)-FMP.xlsx XLSX spreadsheet
Glynco ANG Station GA (JAS)-FMP.xlsx XLSX spreadsheet
Cape Canaveral AFS FL (DBE)-FMP.xlsx XLSX spreadsheet
Robins AFB GA (ROB-TBD)-FMP.xlsx XLSX spreadsheet
CDRL Set 15 57-60.pdf PDF
CDRL Set 2 5-8.pdf PDF
CDRL Set 3 9-12.pdf PDF
CDRL Set 9 33-36.pdf PDF
CDRL Set 6 21-24.pdf PDF
Douglas MAP ANG NC (DGL)-FMP.xlsx XLSX spreadsheet
Dobbins ARB GA (DOB)-FMP.xlsx XLSX spreadsheet
Attachment 2 Sample Service Order (Appendix A - Attachment 1 Service Order Form).xlsx XLSX spreadsheet
Attachment 7 Pricing Worksheet SAD-AF2.xlsx XLSX spreadsheet
Charleston AFB SC (CAF)-FMP.xlsx XLSX spreadsheet
CDRL Set 13 49-52.pdf PDF
CDRL Set 4 13-16.pdf PDF
CDRL Set 7 25-28.pdf PDF
CDRL Set 8 29-32.pdf PDF
CDRL Set 14 53-56.pdf PDF
12.0 PWS Appendix K SAD-AF2 Real Property Data SAD-AF2 Final 20250225.xlsx XLSX spreadsheet
Jacksonville IAP FL (JVL)-FMP.xlsx XLSX spreadsheet
Patrick AFB FL (PAT)-FMP.xlsx XLSX spreadsheet
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationInstallation NameMcEntire JNGB
DLA Site CodeMNT
Hours of Operation0700 - 1600
Address1325 South Carolina Rd, Suite 8, Eastover, SC 29044
ContractContractorWeston Solutions
Contract #47QSHA18D0016 / W912DY20F4075
Local POCsQAE Phone803-647-8143
QAE Emailstephen.rector.1@us.af.mil
Alt QAE Phone803-647-8397
Alt QAE Emailchristian.j.huettmann.nfg@mail.mil
DLA/SCP POCsDLA PM Phone571-767-8133
DLA PM Emailpatricia.beyer@dla.mil
SCP PM Phone571-767-0726
SCP PM Emaildavid.w.king@dla.mil
Contractor POCsContractor PM Phone770-325-7907
Contractor PM Emailjohn.deahl@westonsolutions.com
Contractor QC Phone207-841-3530
Contractor QC Emailmatt.altekruse@westonsolutions.com
Contractor SM Phone229-834-4663
Contractor SM Emailkenric.smith@westonsolutions.com
USACE POCsUSACE PM Phone256-895-1067
USACE PM Emailrichard.a.resler@usace.army.mil
USACE COR Phone256-895-1745
USACE COR Emailmoon.h.hemm@usace.army.mil
USACE PE Phone256-895-1947
USACE PE Emailcorey.a.asher@usace.army.mil
USACE KO Phone256-895-1117
USACE KO Emailaquiller.e.cole@usace.army.mil

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

mailto:john.deahl@westonsolutions.commailto:matt.altekruse@westonsolutions.commailto:patricia.beyer@dla.milmailto:david.w.king@dla.milmailto:kenric.smith@westonsolutions.commailto:corey.a.asher@usace.army.milmailto:aquiller.e.cole@usace.army.milmailto:richard.a.resler@usace.army.milmailto:moon.h.hemm@usace.army.mil General Facility Description

Appendix K - Facility Maintenance Plan

&P of &N

Installation includes a pump station with two (2) bulk storage tanks. There is a fuel station with a MOGAS and DS-2 tank. Additionally, there are two (2) truck offloads and two (2) truck fillstands.

Communication Plan

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, etc.

Safety

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

APPENDIX J - EXISTING MAINTENANCE SCHEDULES
#Installation NameSite NameDLA Site CodeRPSUIDLocationCitySTExisting Max Freq1st Quarter
Contract PoP 14 Aug 20 -13 Aug 212nd Quarter3rd Quarter4th Quarter
Aug-24Sep-24Oct-24Nov-24Dec-24Jan-25Feb-25Mar-25Apr-25May-25Jun-25Jul-25
1SI CAPE CANAVERALCape Canaveral AFS Site #1DBE1555Cape Canaveral AFSCape CanaveralFL1Annual

2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21

3JACKSONVILLE IAPJacksonville IAP Site #1JVL2390Jacksonville ANGJacksonvilleFL1SA1/Q1
10/16-10/18Q2
1/21-1/22A/SA2/Q3
4/22-4/25Q4

7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10

5ROBINS AFBRobins Air Force Base Site 1ROB3219Robins ANG, GAWarner RobinsGA4SA1/Q1
8/28-8/30Q2
11/21-11/22A/SA2/Q3
3/3-3/6Q4

6/3-6/4

6SI MOODYMoody AFBMDY3020Moody AFB, GAValdostaGA4Q1
9/16-9/18A-SA1-Q2
12/02-12/11Q3
3/24-3/26SA2-Q4

6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16

8SAVANNAH HILTON HEAD IAPSavannah ANG (IAP ID 107)SAG17105Savannah ANG, GA (IAP ID 107)SavannahGA1Annual
12/17-12/19MC
9SAVANNAH HILTON HEAD IAPSavannah/Hilton Head IAP Site #3SHH3358SAVANNAH/HILTON HEAD IAP SITE #5SavannahGA4Annual

12/20

10JB CHARLESTONDFSP CharlestonCHS1580DFSP CharlestonCharlestonSC1SA1/Q1
8/19-8/23Q2
11/13-11/15A/SA2/Q3
2/3-2/21Q4

5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22

12JB CHARLESTONJoint Base Charleston NWSJBC213JOINT BASE CHARLESTON NAVAL WEAPONS STATIONCharlestonSC4Q1
9/10SA1-Q2
12/10-12/11Q3
3/11-3/12A-SA2-Q4

6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24

15CHARLOTTE IAPDouglas MAP ANG (ID 146)DGL1661Douglas MAP ANG, NC (ID 146)CharlotteNC1Annual
11/04-11/06MC
16CHARLOTTE IAPStanly County AirportWEF3312Stanly County AirportNew LondonNC1Annual

11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17

Task Matrix

UFC System Level Maintenance FrequencySpecial Considerations
EBS Facility #iNFADS Facility #ACES/ NEXGEN Facility #Real Property Unique IdentifierFacility NameOperational AreaComponent TypeCUIDMakeModelCapacity/SizeQSAUFC Section ReferenceManufacturer RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
11611161488905PMP STN, LFPump HouseEye wash/SignageMNT-1161-SIGN-0001X2-7See Mfr. O&M
11611161488905PMP STN, LFPRTPRT/SignageMNT-1161-SIGN-0002Highland1200 GallonsX2-7See Mfr. O&M
30583058489201OPG STOR, DIESELDS-2 TankTank/SignageMNT-3058-SIGN-000120KX2-7See Mfr. O&M
30593059489202OPG STOR, MOGASGUR TankTank/SignageMNT-3059-SIGN-000120KX2-7See Mfr. O&M
315731571140728OPG STOR, JET FLTank # 1API 653 Tank/SignageMNT-3157-SIGN-0001105K GalX2-7See Mfr. O&M
315731571140728OPG STOR, JET FLPRTPRT/SignageMNT-3157-SIGN-0002Schultz100 GallonX2-7See Mfr. O&M
31583158486224OPG STOR, JET FLTank # 2API 653 TankMNT-3158-SIGN-0001105K GalX2-7See Mfr. O&M
31583158486224OPG STOR, JET FLPRTPRT/SignageMNT-3158-SIGN-0002Schultz100 GallonX2-7See Mfr. O&M
31593159486225LF STD UNLOADRT SystemPRT/SignageMNT-3159-SIGN-0001S/S 20 gallon tankX2-7See Mfr. O&M
31603160486226LF FIL STD, TRKTruck Fillstand # 1EFSO/SignageMNT-3160-SIGN-0001Cooper CrouseDS441X2-7See Mfr. O&M
31603160486226LF FIL STD, TRKMiscEye Wash/SignageMNT-3160-SIGN-0002X2-7See Mfr. O&M
316231621140767LF FIL STD, TRKTruck Fillstand # 2EFSO/SignageMNT-3162-SIGN-0001Cooper CrouseDS441X2-7See Mfr. O&M
11611161488905PMP STN, LFREC F/S # 1Air ElimanatorMNT-1161-AAVT-00013/4"X3-10.2See Mfr. O&M
11611161488905PMP STN, LFREC F/S # 2Air ElimanatorMNT-1161-AAVT-00023/4"X3-10.2See Mfr. O&M
11611161488905PMP STN, LFREC F/S # 1F/SMNT-1161-FLSP-0001Facet InternationalCFCS-D-3N3SSB-163GT2M300 GPM; 3 Filters, 1 CoalescerX3-6.2See Mfr. O&MRoutine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2F/SMNT-1161-FLSP-0002Facet InternationalCFCS-D-3N3SSB-163GT2M300 GPM; 3 Filters, 1 CoalescerX3-6.2See Mfr. O&MRoutine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order.
Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #1 SuctionBasket StranerMNT-1161-BSTR-0001ISLIP Flow ControlsB15OFSS4BW13-6.4See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #2 SuctionBasket StranerMNT-1161-BSTR-0002ISLIP Flow ControlsB15OFSS4BW13-6.4See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #1PumpMNT-1161-CENP-0001Goulds Pumps3700600 GPMXX3-8.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #2PumpMNT-1161-CENP-0002Goulds Pumps3700600 GPMXX3-8.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump #1 Pressure Bypass LineWatts ValMNT-1161-GSCVL-0001Watts Val116-5RX4-3.2.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump #2 Pressure Bypass LineWatts ValMNT-1161-GSCVL-0002Watts Val116-5RX4-3.2.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 1Watts ValMNT-1161-FSCVL-0001Watts Valve124-9R3"XX4-4.2.2See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2Watts ValMNT-1161-FSCVL-0002Watts Valve124-9R3"XX4-4.2.2See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #1VISI FLOWMNT-1161-SFND-0001VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #2VISI FLOWMNT-1161-SFND-0002VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 1VISI FLOWMNT-1161-SFND-0003VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2VISI FLOWMNT-1161-SFND-0004VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec F/S Discharge HeaderVISI FLOWMNT-1161-SFND-0005VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPressure Bypass LineVISI FLOWMNT-1161-SFND-0006VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump Suction HeaderVISI FLOWMNT-1161-SFND-0007VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #1Ball ValMNT-1161-BLVL-00012"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #1Flanged Ball ValMNT-1161-BLVL-0002FlotiteSF1503"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #2Ball ValMNT-1161-BLVL-00032"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #2Flanged Ball ValMNT-1161-BLVL-0004FlotiteSF1503"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec F/S By-Pass LineFlanged Ball ValMNT-1161-BLVL-0005NIBCO4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec F/S By-Pass LineFlanged Ball ValMNT-1161-BLVL-0006NIBCO4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec F/S By-Pass LineFlanged Ball ValMNT-1161-BLVL-0007NIBCO3"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 1Flanged Ball ValMNT-1161-BLVL-0008FlotiteSF1503"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 1Flanged Ball Val - DrainMNT-1161-BLVL-00093/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2Flanged Ball ValMNT-1161-BLVL-0010FlotiteSF1503"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2Flanged Ball Val - DrainMNT-1161-BLVL-00113/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec F/S Discharge HeaderFlanged Ball ValMNT-1161-BLVL-0012NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-ServiceValve is very hard to open / Takes 2 people
11611161488905PMP STN, LFRec F/S Discharge HeaderFlanged Ball ValMNT-1161-BLVL-0013NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-ServiceValve is very hard to open / Takes 2 people
11611161488905PMP STN, LFRec F/S Discharge HeaderFlanged Ball ValMNT-1161-BLVL-0014NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-ServiceValve is very hard to open / Takes 2 people
11611161488905PMP STN, LFRec F/S Discharge HeaderFlanged Ball ValMNT-1161-BLVL-0015NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-ServiceValve is very hard to open / Takes 2 people
11611161488905PMP STN, LFIssue Pump #1 SuctionFlanged Ball ValMNT-1161-BLVL-0016NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #1 SuctionBall Vall - Basket Straner DrainMNT-1161-BLVL-0017NIBCO3/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #1 SuctionBall ValMNT-1161-BLVL-00181/2"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #2 SuctionFlanged Ball ValMNT-1161-BLVL-0019NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #2 SuctionBall Vall - Basket Straner DrainMNT-1161-BLVL-0020NIBCO3/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #2 SuctionBall ValMNT-1161-BLVL-00211/2"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump #1 Pressure Bypass LineFlanged Ball ValMNT-1161-BLVL-0022NIBCO3"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump #2 Pressure Bypass LineFlanged Ball ValMNT-1161-BLVL-0023NIBCO3"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #1PRVMNT-1161-PRVL-0001Taylor Tools82-75151-00-10-03/4" R 60-175XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec Line #2PRVMNT-1161-PRVL-0002Taylor Tools82-75151-00-10-03/4" R 60-175XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 1PRVMNT-1161-PRVL-0003Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2PRVMNT-1161-PRVL-0004Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFRec F/S Discharge HeaderPRVMNT-1161-PRVL-0005Taylor Tools82-75151-00-10-03/4" R 60-175XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPressure Bypass LinePRVMNT-1161-PRVL-0006Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump Suction HeaderPRVMNT-1161-PRVL-0007Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 1Pressure GaugeMNT-1161-PVGA-0001Palmer1/4" 0-300XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFREC F/S # 2Pressure GaugeMNT-1161-PVGA-0002Palmer1/4" 0-300XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFIssue Pump #1 SuctionVac Pressure GaugeMNT-1161-PVGA-00031/4" -30 - 30XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFIssue Pump #2 SuctionVac Pressure GaugeMNT-1161-PVGA-00041/4" -30 - 30XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFREC F/S # 1DP GuageMNT-1161-DPGA-0001GammonGTP-690-10-30XX6-7.2See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFREC F/S # 2DP GuageMNT-1161-DPGA-0002GammonGTP-690-10-30XX6-7.2See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #1MotorMNT-1161-ELEMT-0001Reliance Electric1MF7869750 HP / 60 Hz / 3555 RPMXXX9-1.7See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Pump #2MotorMNT-1161-ELEMT-0002Reliance Electric1MF7869750 HP / 60 Hz / 3555 RPMXXX9-1.7See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #1 DischargePRVMNT-1161-PRVL-0008Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #1 DischargeVISI FLOWMNT-1161-SFND-0008VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #1 DischargePressure GaugeMNT-1161-PVGA-0005Weston0 - 160XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFIssue #1 DischargeWatts ValMNT-1161-GSCVL-0003Watts Val6"X4-3.2.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #1 DischargeFlanged Ball ValMNT-1161-BLVL-0024NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #1 DischargeFlanged Ball ValMNT-1161-BLVL-0025NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #2 DischargePRVMNT-1161-PRVL-0009Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #2 DischargeVISI FLOWMNT-1161-SFND-0009VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #2 DischargePressure GaugeMNT-1161-PVGA-0006Weston0 - 160XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFIssue #2 DischargeCla ValMNT-1161-GSCVL-0004Cla Val6"X4-3.2.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #2 DischargeFlanged Ball ValMNT-1161-BLVL-0026NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue #2 DischargeFlanged Ball ValMNT-1161-BLVL-0027NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Discharge By PassFlanged Ball ValMNT-1161-BLVL-0028NIBCOF510-S6-R-66 FS6"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Discharge By PassPRVMNT-1161-PRVL-0010Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Discharge By PassVISI FLOWMNT-1161-SFND-0010VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1F/SMNT-1161-FLSP-0003Facet InternationalCFCS-D-7K38SB-1263T2M300 GPM; 7 Filters, 1 CoalescerX3-6.2See Mfr. O&MRoutine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order.
Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1DP GuageMNT-1161-DPGA-0003GammonGTP-690-10-30XX6-7.2See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1Pressure GaugeMNT-1161-PVGA-0007Palmer1/4" 0-300XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFIssue F/S # 1PRVMNT-1161-PRVL-0011Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1Air ElimanatorMNT-1161-AAVT-00033/4"X3-10.2See Mfr. O&M
11611161488905PMP STN, LFIssue F/S # 1Watts ValMNT-1161-FSCVL-0003Watts Valve124-9R6"XX4-4.2.2See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1Flanged Ball ValMNT-1161-BLVL-0029FlotiteSF1506"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1Flanged Ball Val - DrainMNT-1161-BLVL-00303/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 1VISI FLOWMNT-1161-SFND-0011VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2F/SMNT-1161-FLSP-0004Facet InternationalCFCS-D-7K38SB-1263T2M300 GPM; 7 Filters, 1 CoalescerX3-6.2See Mfr. O&MRoutine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order.
Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2DP GuageMNT-1161-DPGA-0004GammonGTP-690-10-30XX6-7.2See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2Pressure GaugeMNT-1161-PVGA-0008Palmer1/4" 0-300XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFIssue F/S # 2PRVMNT-1161-PRVL-0012Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2Air ElimanatorMNT-1161-AAVT-00043/4"X3-10.2See Mfr. O&M
11611161488905PMP STN, LFIssue F/S # 2Watts ValMNT-1161-FSCVL-0004Watts Valve124-9R6"XX4-4.2.2See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2Flanged Ball ValMNT-1161-BLVL-0031FlotiteSF1506"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2Flanged Ball Val - DrainMNT-1161-BLVL-00323/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue F/S # 2VISI FLOWMNT-1161-SFND-0012VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue HeaderPRVMNT-1161-PRVL-0013Taylor82E4751311-00-00-03/4"XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue HeaderVISI FLOWMNT-1161-SFND-0013VISI Flow1471-F 13/4"6-12.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFIssue Header BypassFlanged Ball ValMNT-1161-BLVL-0033FlotiteSF1506"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPump HouseEye wash / ShowerMNT-1161-EMEWSH-0001XXX11-3See Mfr. O&M
11611161488905PMP STN, LFPRTPRTMNT-1161-PRDST-0001Highland1200 GallonsX8-9.10See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRTPumpMNT-1161-CENP-0003BlackmerHRO-GX3.3 HPXX3-8.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRTMotorMNT-1161-ELEMT-0003MarathonNH143TTGN6526AAPXXX9-1.7See Mfr. O&MRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRTFlanged Ball ValMNT-1161-BLVL-0034Flow TiteF1502"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump DischargeFlanged Ball ValMNT-1161-BLVL-0035Flow TiteF1501/2"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump DischargePressure Gauge w StubberMNT-1161-PVGA-0009Palmer1/2" 0-300XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFPRT Pump DischargeInline Check ValveMNT-1161-CKVL-0001TitanCV4041424344462"X6-6.2.8See Mfr. O&MRepairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump DischargeFlanged Ball ValMNT-1161-BLVL-0036Flow TiteF1502"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump DischargePRVMNT-1161-PRVL-0014Taylor82E3751311-10-10-01" R 51 - 100XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump SuctionFlanged Ball ValMNT-1161-BLVL-0037Flow TiteF1501/2"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump SuctionPressure GaugeMNT-1161-PVGA-0010Palmer1/2" 0-300XXX6-7.1See Mfr. O&M
11611161488905PMP STN, LFPRT Pump SuctionFlanged Ball ValMNT-1161-BLVL-0038Flow TiteF1502"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump SuctionFlanged Ball ValMNT-1161-BLVL-0039Flow TiteF1502"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump SuctionInline Check ValveMNT-1161-CKVL-0002TitanCV4041424344462"X6-6.2.8See Mfr. O&MRepairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFPRT Pump SuctionFlanged Ball ValMNT-1161-BLVL-0040Flow TiteF1502"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
11611161488905PMP STN, LFCanopyCanopyMNT-1161-CNPY-000111-2.2See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0001XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0002XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0003XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0004XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0005XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0006XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0007XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0008XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFCanopyExplosion Proof LightsMNT-1161-LIGHT-0009XX9-1.8See Mfr. O&MRepairs shall be performed through a service order.
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00016" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00026" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00036" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00046" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00056" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00066" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00076" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00086" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00096" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00106" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00116" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00126" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00136" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00146" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00156" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00166" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00176" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00186" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00196" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00206" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00216" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00226" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00236" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00246" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00256" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00266" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00276" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00286" coversX11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00294"X11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
11611161488905PMP STN, LFBollardsBollardMNT-1161-BLRD-00304"X11-2.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
30583058489201OPG STOR, DIESELDS-2 TankTankMNT-3058-AGSFP-000120K8-5.1See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
30583058489201OPG STOR, DIESELDS-2 TankBall ValMNT-3058-BLVL-00014"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
30583058489201OPG STOR, DIESELDS-2 TankPumpMNT-3058-VTSP-0001Red JacketXXX3-8.1.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
30593059489202OPG STOR, MOGASGUR TankTankMNT-3059-AGSFP-000120K8-5.1See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
30593059489202OPG STOR, MOGASGUR TankBall ValMNT-3059-BLVL-00014"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
30593059489202OPG STOR, MOGASGUR TankPumpMNT-3059-VTSP-0001Red JacketXXX3-8.1.3See Mfr. O&MRequires LOTO and System placed Out-of-Service
30603060486213VEHICLE FUEL STATIONDS-2MeterMNT-3060-PDMT-0001Total Control700-15SPA2AT2X3-7.1See Mfr. O&MCalibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation.Requires LOTO and System placed Out-of-Service
30603060486213VEHICLE FUEL STATIONDS-2SwivelMNT-3060-DSSW-0001OPW1"7-5See Mfr. O&MRequires LOTO and System placed Out-of-ServiceRemove by 09/20
30603060486213VEHICLE FUEL STATIONDS-2BreakawayMNT-3060-DSBW-0001OPW66V-13001"7-4See Mfr. O&MRequires LOTO and System placed Out-of-ServiceRemove by 04/22
30603060486213VEHICLE FUEL STATIONDS-2HoseMNT-3060-DSHS-00011' x 10'7-3See Mfr. O&MRequires LOTO and System placed Out-of-Service
30603060486213VEHICLE FUEL STATIONDS-2SwivelMNT-3060-DSSW-0002OPW1"7-5See Mfr. O&MRequires LOTO and System placed Out-of-ServiceRemove by 09/20
30603060486213VEHICLE FUEL STATIONDS-2NozzleMNT-3060-DSNZ-0001Harco1"7-2See Mfr. O&MRequires LOTO and System placed Out-of-ServiceNo stamped dates
30603060486213VEHICLE FUEL STATIONMURMeterMNT-3060-PDMT-0002Total Control700-15SPA2AT2X3-7.1See Mfr. O&MCalibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation.Requires LOTO and System placed Out-of-Service
30603060486213VEHICLE FUEL STATIONMURSwivelMNT-3060-DSSW-0003OPW3/4"7-5See Mfr. O&MRequires LOTO and System placed Out-of-ServiceRemove by 9/20
30603060486213VEHICLE FUEL STATIONMURBreakawayMNT-3060-DSBW-0002OPW66V-13003/4"7-4See Mfr. O&MRequires LOTO and System placed Out-of-ServiceNo stamped dates
30603060486213VEHICLE FUEL STATIONMURHoseMNT-3060-DSHS-00023/4" x 10'7-3See Mfr. O&MRequires LOTO and System placed Out-of-Service
30603060486213VEHICLE FUEL STATIONMURSwivelMNT-3060-DSSW-0004OPW3/4"7-5See Mfr. O&MRequires LOTO and System placed Out-of-ServiceNo stamped dates
30603060486213VEHICLE FUEL STATIONMURNozzleMNT-3060-DSNZ-0002Harco3/4"7-2See Mfr. O&MRequires LOTO and System placed Out-of-ServiceNo stamped dates
315731571140728OPG STOR, JET FLTank # 1API 653 TankMNT-3157-AGFET-0001105K Gal8-4See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLTank # 1Tank groundMNT-3157-STGS-0001# 1XX9-1.6.2See Mfr. O&M
315731571140728OPG STOR, JET FLTank # 1Tank groundMNT-3157-STGS-0002# 2XX9-1.6.2See Mfr. O&M
315731571140728OPG STOR, JET FLTank # 1Tank groundMNT-3157-STGS-0003# 3XX9-1.6.2See Mfr. O&M
315731571140728OPG STOR, JET FLTank # 1Tank groundMNT-3157-STGS-0004# 4XX9-1.6.2See Mfr. O&M
315731571140728OPG STOR, JET FLTank # 1Varec GaugeMNT-3157-MOTGA-0001VarecBM13661-111XX8-9.8.1See Mfr. O&M
315731571140728OPG STOR, JET FLTank # 1Low Level CanisterMNT-3157-EMLA-0001X8-9.9.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLTank # 1High Level CanisterMNT-3157-EMLA-0002ScullyX8-9.9.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLLow Level CanisterWelded Ball ValveMNT-3157-BLVL-00011"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLLow Level CanisterWelded Ball ValveMNT-3157-BLVL-00021"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLLow Level CanisterWelded Ball ValveMNT-3157-BLVL-00031"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLLow Level CanisterWelded Ball ValveMNT-3157-BLVL-00041"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLLow Level CanisterWelded Ball ValveMNT-3157-BLVL-00051"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLHigh Level CanisterWelded Ball ValveMNT-3157-BLVL-00061"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLHigh Level CanisterWelded Ball ValveMNT-3157-BLVL-00071"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLHigh Level CanisterWelded Ball ValveMNT-3157-BLVL-00081"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLHigh Level CanisterWelded Ball ValveMNT-3157-BLVL-00091"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLHigh Level CanisterWelded Ball ValveMNT-3157-BLVL-00101"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLIssue LineFlanged Ball ValMNT-3157-BLVL-0011Flow TiteF1503/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLIssue LinePRVMNT-3157-PRVL-0001Taylor Valve82E3751311-10-10-03/4" to 1" R 101 - 225XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLIssue LineFlanged Ball ValMNT-3157-BLVL-0012Flow TiteF1501"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLIssue LineDB&B ValMNT-3157-DBBVL-0001Twin Seal881110"XX6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLStripper LineFlanged Ball ValMNT-3157-BLVL-0013NIBCOF510-S6-R-66 FS4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLStripper LineDB&B ValMNT-3157-DBBVL-0002Trus Seal4"XX6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLStripper LineFlanged Ball ValMNT-3157-BLVL-0014Flow TiteF1501"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LineFlanged Ball ValMNT-3157-BLVL-0015Flow TiteF1503/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LinePRVMNT-3157-PRVL-0002Taylor Valve82E3751311-10-10-03/4" to 1" R 101 - 225XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LineHLCVMNT-3157-EHLSVL-0001Cla Val413-05AGS6"XX8-9.6.1See Mfr. O&MRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LineFlanged Ball ValMNT-3157-BLVL-0016Flow TiteF1503/4"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LinePRVMNT-3157-PRVL-0003Taylor Valve82E3751311-10-10-03/4" to 1" R 101 - 225XX6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair.Requires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LineDB&B ValMNT-3157-DBBVL-0003Trus Seal211RF6"XX6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLRec LineFlanged Ball ValMNT-3157-BLVL-0017Flow TiteF1501"X6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System placed Out-of-Service
315731571140728OPG STOR, JET FLPRTPRTMNT-3157-PRDST-0001Schultz100 GallonX8-9.10See Mfr. O&MRequires LOTO and System placed Out-of-Service