Dobbins ARB GA (DOB)-FMP.xlsx
XLSX spreadsheet 107 KB Posted
- Solicitation number
- W912DY26RA017
About this file
This is a comprehensive Facility Maintenance Plan for Dobbins Air Reserve Base (ARB) in Georgia, detailing maintenance requirements for various fuel storage, dispensing, and related infrastructure components. The document includes an extensive inventory of specific facility assets across multiple fuel-related systems, such as bulk storage tanks, diesel tanks, military service stations, fillstands, and offloading areas, with detailed component-level identification including unique identifiers, manufacturers, models, and maintenance specifications.
The maintenance plan covers multiple operational areas with specific maintenance schedules and requirements, including filter separator maintenance, component-specific inspection intervals, and guidelines for replacing/cleaning equipment. Key facilities include a 84K gallon Jet Fuel Tank #1, a 210K gallon Jet Fuel Tank #2, multiple fillstands, diesel tanks, a military service station, and associated infrastructure. The document provides granular details on maintenance procedures, system availability, replacement intervals, and special considerations for each component, with most maintenance tasks requiring lock-out/tag-out procedures and potential service order interventions for repairs beyond routine maintenance.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Installation Name | Dobbins ARB |
| DLA Site Code | DOB | |
| Hours of Operation | 0700-1100 | |
| Address | 1538 Atlantic Ave, Dobbins ARB, GA 30069 | |
| Contract | Contractor | Weston Solutions |
| Contract # | 47QSHA18D0016 / W912DY20f0474 | |
| Local POCs | QAE Phone | 678-655-5322 |
| QAE Email | john.trudeau.1@us.af.mil | |
| Alt QAE Phone | 678-655-2090 | |
| Alt QAE Email | christopher.kaighen@us.af.mil | |
| DLA/SCP POCs | DLA PM Phone | 571-767-8133 |
| DLA PM Email | patricia.beyer@dla.mil | |
| SCP PM Phone | 571-767-0726 | |
| SCP PM Email | david.king@dal.mil | |
| Contractor POCs | Contractor PM Phone | 770-325-7907 |
| Contractor PM Email | john.deahl@westonsolutions.com | |
| Contractor QC Phone | 757-819-5131 | |
| Contractor QC Email | matt.altekruse@westonsolution.com | |
| Contractor SM Phone | 229-415-3445 | |
| Contractor SM Email | brandon.wells@westonsolutions.com | |
| USACE POCs | USACE PM Phone | 256-895-1067 |
| USACE PM Email | richard.a.resler@usace.army.mil | |
| USACE COR Phone | 256-895-1745 | |
| USACE COR Email | moon.h.hemm@usace.army.mil | |
| USACE PE Phone | 256-895-1947 | |
| USACE PE Email | corey.a.asher@usace.army.mil | |
| USACE KO Phone | 256-895-1117 | |
| USACE KO Email | aquiller.e.cole@usace.army.mil |
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
mailto:brandon.wells@westonsolutions.commailto:john.deahl@westonsolutions.commailto:matt.altekruse@westonsolution.commailto:john.trudeau.1@us.af.milmailto:richard.a.resler@usace.army.milmailto:aquiller.e.cole@usace.army.milmailto:corey.a.asher@usace.army.milmailto:moon.h.hemm@usace.army.mil General Facility Description
| FAC 2015 Jet Fuel Tank #1 84K Gallons |
| FAC 2069 Jet Fuel Tank #2 210K Gallons |
| FAC 2019 Jet Fuel Fillstands |
| FAC 2020 Jet Fuel Off-loading |
| FAC Diesel Tank |
| FAC 513 Military Service Station |
| FAC 752 Flightline Diesel Tank |
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Include a general facility description for the installation.
Communication Plan
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, etc.
Safety
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
| APPENDIX J - EXISTING MAINTENANCE SCHEDULES | |||||||||||||||||||||
| # | Installation Name | Site Name | DLA Site Code | RPSUID | Location | City | ST | Existing Max Freq | 1st Quarter | ||||||||||||
| Contract PoP 14 Aug 20 -13 Aug 21 | 2nd Quarter | 3rd Quarter | 4th Quarter | ||||||||||||||||||
| Aug-24 | Sep-24 | Oct-24 | Nov-24 | Dec-24 | Jan-25 | Feb-25 | Mar-25 | Apr-25 | May-25 | Jun-25 | Jul-25 | ||||||||||
| 1 | SI CAPE CANAVERAL | Cape Canaveral AFS Site #1 | DBE | 1555 | Cape Canaveral AFS | Cape Canaveral | FL | 1 | Annual |
2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21
| 3 | JACKSONVILLE IAP | Jacksonville IAP Site #1 | JVL | 2390 | Jacksonville ANG | Jacksonville | FL | 1 | SA1/Q1 | |
| 10/16-10/18 | Q2 | |||||||||
| 1/21-1/22 | A/SA2/Q3 | |||||||||
| 4/22-4/25 | Q4 |
7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10
| 5 | ROBINS AFB | Robins Air Force Base Site 1 | ROB | 3219 | Robins ANG, GA | Warner Robins | GA | 4 | SA1/Q1 | |
| 8/28-8/30 | Q2 | |||||||||
| 11/21-11/22 | A/SA2/Q3 | |||||||||
| 3/3-3/6 | Q4 |
6/3-6/4
| 6 | SI MOODY | Moody AFB | MDY | 3020 | Moody AFB, GA | Valdosta | GA | 4 | Q1 | |
| 9/16-9/18 | A-SA1-Q2 | |||||||||
| 12/02-12/11 | Q3 | |||||||||
| 3/24-3/26 | SA2-Q4 |
6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16
| 8 | SAVANNAH HILTON HEAD IAP | Savannah ANG (IAP ID 107) | SAG | 17105 | Savannah ANG, GA (IAP ID 107) | Savannah | GA | 1 | Annual | |
| 12/17-12/19 | MC | |||||||||
| 9 | SAVANNAH HILTON HEAD IAP | Savannah/Hilton Head IAP Site #3 | SHH | 3358 | SAVANNAH/HILTON HEAD IAP SITE #5 | Savannah | GA | 4 | Annual |
12/20
| 10 | JB CHARLESTON | DFSP Charleston | CHS | 1580 | DFSP Charleston | Charleston | SC | 1 | SA1/Q1 | |
| 8/19-8/23 | Q2 | |||||||||
| 11/13-11/15 | A/SA2/Q3 | |||||||||
| 2/3-2/21 | Q4 |
5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22
| 12 | JB CHARLESTON | Joint Base Charleston NWS | JBC | 213 | JOINT BASE CHARLESTON NAVAL WEAPONS STATION | Charleston | SC | 4 | Q1 | |
| 9/10 | SA1-Q2 | |||||||||
| 12/10-12/11 | Q3 | |||||||||
| 3/11-3/12 | A-SA2-Q4 |
6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24
| 15 | CHARLOTTE IAP | Douglas MAP ANG (ID 146) | DGL | 1661 | Douglas MAP ANG, NC (ID 146) | Charlotte | NC | 1 | Annual | |
| 11/04-11/06 | MC | |||||||||
| 16 | CHARLOTTE IAP | Stanly County Airport | WEF | 3312 | Stanly County Airport | New London | NC | 1 | Annual |
11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17
Task Matrix
| Special Considerations | ||||||||||||||||||||
| EBS Facility # | iNFADS Facility # | ACES/ NEXGEN Facility # | Real Property Unique Identifier | Facility Name | Operational Area | Component Type | CUID | Make | Model | Serial | Capacity/Size | Q | S | A | UFC Section Reference | Manufacturer Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments |
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Cabinet | DOB-513-DSCB-0001 | Wayne | G6202D/27AGJKD4/AW1 | 23737C | x | 7-7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Meter | DOB-513-DSMTR-0001 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Meter | DOB-513-DSMTR-0002 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Filter | DOB-513-DSFLR-0001 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Filter | DOB-513-DSFLR-0002 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Sump | DOB-513-DSSMP-0001 | x | 7-13 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Emergency Shutoff Valve (Shear) | DOB-513-ESHVL-0001 | x | 7-12 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Hose 1 | DOB-513-DSHS-0001 | 3/4" x 10' | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Hose Retriever | DOB-513-HSRTV-0001 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Breakaway 1 | DOB-513-DSBW-0001 | Catlow | 3/4" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Swivel 1 | DOB-513-DSSW-0001 | Catlow | 3/4" | 7-5 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Nozzle 1 | DOB-513-DSNZ-0001 | Catlow | 3/4" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Hose 2 | DOB-513-DSHS-0002 | 3/4" x 10' | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Hose Retriever | DOB-513-HSRTV-0002 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Breakaway 2 | DOB-513-DSBW-0002 | Catlow | 3/4" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Swivel 2 | DOB-513-DSSW-0002 | Catlow | 3/4" | 7-5 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Dispenser Nozzle 2 | DOB-513-DSNZ-0002 | OPW | 3/4" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Cabinet | DOB-513-DSCB-0002 | Wayne | G6202D/27ACJK/AW1 | 23736C | x | 7-7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Meter | DOB-513-DSMTR-0003 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Meter | DOB-513-DSMTR-0004 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Filter | DOB-513-DSFLR-0003 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Filter | DOB-513-DSFLR-0004 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Sump | DOB-513-DSSMP-0002 | x | 7-13 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Emergency Shutoff Valve (Shear) | DOB-513-ESHVL-0002 | x | 7-12 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Hose 3 | DOB-513-DSHS-0003 | 1" x 12' | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Hose Retriever | DOB-513-HSRTV-0003 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Breakaway 3 | DOB-513-DSBW-0003 | OPW | 66V | 1" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Swivel 3 | DOB-513-DSSW-0003 | Husky | 1" | 7-5 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Nozzle 3 | DOB-513-DSNZ-0003 | OPW | 1" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Hose 4 | DOB-513-DSHS-0004 | 1" x 12' | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Hose Retriever | DOB-513-HSRTV-0004 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Breakaway 4 | DOB-513-DSBW-0004 | OPW | 66V | 1" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Swivel 4 | DOB-513-DSSW-0004 | Husky | 1" | 7-5 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Nozzle 4 | DOB-513-DSNZ-0004 | OPW | 1" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Cabinet | DOB-513-DSCB-0003 | Gasboy | 9153AX-CCSSA | 464360 | x | 7-7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Meter | DOB-513-DSMTR-0005 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Filter | DOB-513-DSFLR-0005 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Sump | DOB-513-DSSMP-0003 | x | 7-13 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Mogas Dispenser | Emergency Shutoff Valve (Shear) | DOB-513-ESHVL-0003 | x | 7-12 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Hose 5 | DOB-513-DSHS-0005 | 1" x 12' | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Hose Retriever | DOB-513-HSRTV-0004 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Breakaway 5 | DOB-513-DSBW-0005 | OPW | 1" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Diesel Dispenser | Dispenser Nozzle 5 | DOB-513-DSNZ-0005 | OPW | 1" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | VIL Reader | Fuel Management Unit | DOB-513-ELTREQ-0001 | Syntech | FMU2500 | 3748 | X | 9-1.9 | See Mfr. O&M | Replacement will be performed through a service order and should be executed in conjunction with recurring maintenance to avoid additional mobilization costs. | Requires LOTO ans System placed Out-of-Service | ||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | VIL Reader | Fuel Management Unit | DOB-513-ELTREQ-0002 | Syntech | FMU2500 | 3749 | X | 9-1.9 | See Mfr. O&M | Replacement will be performed through a service order and should be executed in conjunction with recurring maintenance to avoid additional mobilization costs. | Requires LOTO ans System placed Out-of-Service | ||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Canopy | DOB-513-CNPY-0001 | x | 11-2.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | EFSO System | DOB-513-EFSO-0001 | x | 7-16 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | EFSO System | DOB-513-EFSO-0002 | x | 7-16 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | EFSO System | DOB-513-EFSO-0003 | x | 7-16 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | EFSO Signs & Markings | DOB-513-SIGN-0001 | x | 2-7 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | EFSO Signs & Markings | DOB-513-SIGN-0002 | x | 2-7 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | EFSO Signs & Markings | DOB-513-SIGN-0003 | x | 2-7 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Panelboard | DOB-513-PNLB-0001 | x | x | 9-1.5 | See Mfr. O&M | Breaker schedules shall be developed by SO. | Requires LOTO ans System placed Out-of-Service | ||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Electronic Equipment | DOB-513-ELTREQ-0001 | Veeder-Root | TLS-350 | x | 9-1.9 | See Mfr. O&M | Replacement will be performed through a service order and should be executed in conjunction with recurring maintenance to avoid additional mobilization costs. | Requires LOTO ans System placed Out-of-Service | |||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Signs and Markings | DOB-513-SIGN-0004 | x | 2-7 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Bollards | DOB-513-BLRD-0001 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Bollards | DOB-513-BLRD-0002 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Bollards | DOB-513-BLRD-0003 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Bollards | DOB-513-BLRD-0004 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Bollards | DOB-513-BLRD-0005 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Fence | DOB-513-FENC-0001 | X | 11-1.1 | See Mfr. O&M | Repairs shall be performed through a service order. | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Gate | DOB-513-GATE-0001 | x | 11-1.1 | See Mfr. O&M | Repairs shall be performed through a service order. | ||||||||||
| FOS1.1.40 | 513 | 407667 | Military Service Station | Military Service Station | Gate | DOB-513-GATE-0002 | x | 11-1.1 | See Mfr. O&M | Repairs shall be performed through a service order. | ||||||||||
| 2141 | 2141 | 407609 | Military Service Station | MOGAS Tank | Underground Double-walled Shop-Fabricated Tank | DOB-2141-UGDSFT-0001 | 8-5.4.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 2141 | 2141 | 407609 | Military Service Station | MOGAS Tank | Remote Dispenser Pump | DOB-2141-RDSP-0001 | 7-15.1 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| 2141 | 2141 | 407609 | Military Service Station | MOGAS Tank | Ball Valve | DOB-2141-BLVL-0001 | 2" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2141 | 2141 | 407609 | Military Service Station | MOGAS Tank | Stilling Well | DOB-2141-STGW-0001 | 8-9.17 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 2141 | 2141 | 407609 | Military Service Station | MOGAS Tank | Stilling Well | DOB-2141-STGW-0002 | 8-9.17 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 2141 | 2141 | 407609 | Military Service Station | Diesel Tank | Underground Double-walled Shop-Fabricated Tank | DOB-2141-UGDSFT-0002 | 8-5.4.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 2141 | 2141 | 407609 | Military Service Station | Diesel Tank | Remote Dispenser Pump | DOB-2141-RDSP-0002 | 7-15.1 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| 2141 | 2141 | 407609 | Military Service Station | Diesel Tank | Ball Valve | DOB-2141-BLVL-0002 | 2" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2141 | 2141 | 407609 | Military Service Station | Diesel Tank | Stilling Well | DOB-2141-STGW-0003 | 8-9.17 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 2141 | 2141 | 407609 | Military Service Station | Diesel Tank | Stilling Well | DOB-2141-STGW-0004 | 8-9.17 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Self-Diking or Vaulted Tank | DOB-512-SDVT-0001 | 3k gl | x | 8-5.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Remote Dispenser Pump | DOB-512-RDSP-0001 | Franklin | STPA075-VL1-12 | 13081799 | 7-15.1 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Emergency Vent | DOB-512-EMGVT-0001 | Morrison Bros | x | 8-9.4 | See Mfr. O&M | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Emergency Vent | DOB-512-EMGVT-0002 | Morrison Bros | x | 8-9.4 | See Mfr. O&M | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Mechanical Tape Gauge (Clock) | DOB-512-MTGA-0001 | Morrison Bros | x | 8-9.7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Magnetostrictive Probe | DOB-512-MRPRB-0001 | Veeder-Root | x | x | 8-9.8.2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Ball Valve | DOB-512-BLVL-0001 | 1" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Ball Valve | DOB-512-BLVL-0002 | 1 1/2" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Ball Valve | DOB-512-BLVL-0003 | 2" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Check Valve | DOB-512-CKVL-0001 | 2" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Dispenser Cabinet | DOB-512-DSCB-0001 | Wayne | E3/G7207D/2GHJRX/JS2 | 48843C | x | 7-7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Dispenser Meter | DOB-512-DSMTR-0001 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Dispenser Filter | DOB-512-DSFLR-0001 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Dispenser Sump | DOB-512-DSSMP-0001 | x | 7-13 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Emergency Shutoff Valve (Shear) | DOB-512-ESHVL-0001 | x | 7-12 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Dispenser Hose | DOB-512-DSHS-0001 | Continental | 3/4" | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Hose Retriever | DOB-512-HSRTV-0001 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Breakaway | DOB-512-DSBW-0001 | OPW | 66V | 3/4" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Dispenser Nozzle | DOB-512-DSNZ-0001 | OPW | 3/4" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Swivel | DOB-512-DSSW-0001 | OPW | 3/4" | 7-5 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 512 | 512 | 1276060 | Military Service Station | VIL Reader | Fuel Management Unit | DOB-512-ELTREQ-0001 | Syntech | FMU2500 | 13090 | X | 9-1.9 | See Mfr. O&M | Replacement will be performed through a service order and should be executed in conjunction with recurring maintenance to avoid additional mobilization costs. | Requires LOTO ans System placed Out-of-Service | ||||||
| 512 | 512 | 1276060 | Military Service Station | E-85 Tank | Static Grounding System | DOB-512-STGS-0001 | x | 9-1.6.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Signs and Markings | DOB-512-SIGN-0001 | x | 2-7 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0001 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0002 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0003 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0004 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0005 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0006 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0007 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0008 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0009 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 512 | 512 | 1276060 | Military Service Station | Military Service Station | Bollards | DOB-512-BLRD-0010 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Self-Diking or Vaulted Tank | DOB-752-SDVT-0001 | Highland | 34902 | 6k gl | x | 8-5.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Remote Dispenser Pump | DOB-752-RDSP-0001 | Franklin | STP75-VL1-00 | 16D502000013S | 0.75 HP | 7-15.1 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Emergency Vent | DOB-752-EMGVT-0001 | Morrison Bros | x | 8-9.4 | See Mfr. O&M | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Emergency Vent | DOB-752-EMGVT-0002 | Morrison Bros | x | 8-9.4 | See Mfr. O&M | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Mechanical Tape Gauge (Clock) | DOB-752-MTGA-0001 | Morrison Bros | x | 8-9.7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Magnetostrictive Probe | DOB-752-MRPRB-0001 | Ronan | x | x | 8-9.8.2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Ball Valve | DOB-752-BLVL-0001 | 1" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Ball Valve | DOB-752-BLVL-0003 | 3" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Check Valve | DOB-752-CKVL-0001 | 3" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Dispenser Cabinet | DOB-752-DSCB-0001 | Gasboy | 9153KX | DEAT041626 | x | 7-7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Dispenser Meter | DOB-752-DSMTR-0001 | x | 7-8 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Dispenser Filter | DOB-752-DSFLR-0001 | x | 7-9 | See Mfr. O&M | Routine filter changes shall be performed as part of the maintenance activities. Filter changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Dispenser Sump | DOB-752-DSSMP-0001 | x | 7-13 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Emergency Shutoff Valve (Shear) | DOB-752-ESHVL-0001 | x | 7-12 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Dispenser Hose | DOB-752-DSHS-0001 | 1" | 7-3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Hose Retriever | DOB-752-HSRTV-0001 | 7-6 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Breakaway | DOB-752-DSBW-0001 | Catlow | 1" | 7-4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Dispenser Nozzle | DOB-752-DSNZ-0001 | OPW | 1" | x | 7-2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Swivel | DOB-752-DSSW-0001 | OPW | 1" | 7-5 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | VIL Reader | Fuel Management Unit | DOB-752-ELTREQ-0001 | Syntech | FMU2500 | 15132 | X | 9-1.9 | See Mfr. O&M | Replacement will be performed through a service order and should be executed in conjunction with recurring maintenance to avoid additional mobilization costs. | Requires LOTO ans System placed Out-of-Service | ||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Static Grounding System | DOB-752-STGS-0001 | x | 9-1.6.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0001 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0002 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0003 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0004 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0005 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0006 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Bollards | DOB-752-BLRD-0007 | x | 11-2.1 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | EFSO System | DOB-752-EFSO-0001 | x | 7-16 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | EFSO Signs & Markings | DOB-752-SIGN-0001 | x | 2-7 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Electronic Equipment | DOB-752-ELTREQ-0001 | Ronan | x | 9-1.9 | See Mfr. O&M | Replacement will be performed through a service order and should be executed in conjunction with recurring maintenance to avoid additional mobilization costs. | Requires LOTO ans System placed Out-of-Service | ||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Signs and Markings | DOB-752-SIGN-0002 | x | 2-7 | See Mfr. O&M | |||||||||||
| 752 | 752 | 1300897 | Flightline Diesel Tank | Flightline Diesel Tank | Remote Spill Containment | DOB-752-RSCS-0001 | x | x | 11-1.2 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Offloading Fuel Hose | DOB-2020-OLHS-0001 | 4" x 15' | x | x | 3-9.2 | See Mfr. O&M | Repairs should be performed by service order unless otherwise covered in the PWS. | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Offloading Fuel Hose | DOB-2020-OLHS-0002 | 4" x 15' | x | x | 3-9.2 | See Mfr. O&M | Repairs should be performed by service order unless otherwise covered in the PWS. | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0001 | N-J | 4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0002 | N-J | 4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0001 | Technocorp | 8755 | 4" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0002 | Technocorp | 8755 | 4" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Sight Flow Indicator | DOB-2020-SFND-0001 | Visi-Flow | 4" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Automatic Air Vent | DOB-2020-AAVT-0001 | x | 3-10.2 | See Mfr. O&M | |||||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0003 | Jamos Bury | 3/4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Thermal Pressure Relief Valve | DOB-2020-PRVL-0001 | Taylor | 3/4" | x | x | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. | Requires LOTO ans System placed Out-of-Service | 3/4" Inlet - 1" Outlet | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Sight Flow Indicator | DOB-2020-SFND-0002 | Visi-Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0003 | 1" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Basket Strainer | DOB-2020-BSTR-0001 | SF Equipment | 4" | x | 3-6.4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0001 | (-30 - 30 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0002 | (-30 - 30 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Centrifugal Pump | DOB-2020-CENP-0001 | Blackmer | 300 GPM | x | x | 3-8.1 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Electric Motor | DOB-2020-ELEMT-0001 | Corro-Duty | x | x | x | 9-1.7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0003 | (0 - 300 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Automatic Air Vent | DOB-2020-AAVT-0002 | Liquid Controls | A8170 | x | 3-10.2 | See Mfr. O&M | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | General System Control Valve | DOB-2020-GSCVL-0001 | x | x | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0004 | (0 - 300 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Positive Displacement Meter | DOB-2020-PDMT-0001 | Liquid Controls | M-60-2 | 624830 | 600 GPM | x | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO ans System placed Out-of-Service | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0004 | N-J | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Pressure Transmitter (Flow Switch) | DOB-2020-PRTR-0001 | Flowtect | V4SS2DU | S29761001 | x | x | x | 6-7.3 | See Mfr. O&M | Repairs shall be performed by SO. | Requires LOTO ans System placed Out-of-Service | ||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0005 | Flow-Tek | 3" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0006 | Flow-Tek | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0007 | Flow-Tek | 3" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0008 | N-J | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Filter Separator | DOB-2020-FLSP-0001 | Velcon | HV2838285 | 87606-2 | 300 GPM | x | 3-6.2 | See Mfr. O&M | Routine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order. | Requires LOTO ans System placed Out-of-Service | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Differential Pressure Guage | DOB-2020-DPGA-0001 | Gammon | x | x | x | 6-7.4 | See Mfr. O&M | Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Automatic Air Vent | DOB-2020-AAVT-0003 | x | 3-10.2 | See Mfr. O&M | |||||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0009 | Jamos Bury | 3/4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Thermal Pressure Relief Valve | DOB-2020-PRVL-0002 | Taylor | 3/4" | x | x | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. | Requires LOTO ans System placed Out-of-Service | 3/4" Inlet - 1" Outlet | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Sight Flow Indicator | DOB-2020-SFND-0003 | Visi-Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0004 | 1" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Filter Separator Control Valve | DOB-2020-FSCVL-0001 | OCV | 6" | x | x | 4-4.2.2 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0010 | Jamos Bury | 3/4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Thermal Pressure Relief Valve | DOB-2020-PRVL-0003 | Taylor | 3/4" | x | x | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. | Requires LOTO ans System placed Out-of-Service | 3/4" Inlet - 1" Outlet | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0005 | 1" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0011 | Sharpe | 3" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Basket Strainer | DOB-2020-BSTR-0002 | SF Equipment | 4" | x | 3-6.4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0006 | Technocorp | 8755 | 4" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0012 | N-J | 4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Ball Valve | DOB-2020-BLVL-0013 | Jamos Bury | 3/4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Thermal Pressure Relief Valve | DOB-2020-PRVL-0004 | Taylor | 3/4" | x | x | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. | Requires LOTO ans System placed Out-of-Service | 3/4" Inlet - 1" Outlet | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Sight Flow Indicator | DOB-2020-SFND-0004 | Visi-Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Check Valve | DOB-2020-CKVL-0007 | 1" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Motor Control | DOB-2020-MTRCT-0001 | x | x | 9-1.4 | See Mfr. O&M | Repairs shall be performed by SO. | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 1 | Static Grounding System | DOB-2020-STGS-0001 | x | 9-1.6.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Offloading Fuel Hose | DOB-2020-OLHS-0003 | 4" x 15' | x | x | 3-9.2 | See Mfr. O&M | Repairs should be performed by service order unless otherwise covered in the PWS. | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Offloading Fuel Hose | DOB-2020-OLHS-0004 | 4" x 15' | x | x | 3-9.2 | See Mfr. O&M | Repairs should be performed by service order unless otherwise covered in the PWS. | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0014 | N-J | 4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0015 | N-J | 4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Check Valve | DOB-2020-CKVL-0008 | Technocorp | 8755 | 4" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Check Valve | DOB-2020-CKVL-0009 | Technocorp | 8755 | 4" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Sight Flow Indicator | DOB-2020-SFND-0005 | Visi-Flow | 4" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Automatic Air Vent | DOB-2020-AAVT-0004 | x | 3-10.2 | See Mfr. O&M | |||||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0016 | Jamos Bury | 3/4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Thermal Pressure Relief Valve | DOB-2020-PRVL-0005 | Taylor | 3/4" | x | x | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. | Requires LOTO ans System placed Out-of-Service | ||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Sight Flow Indicator | DOB-2020-SFND-0006 | Visi-Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Check Valve | DOB-2020-CKVL-0010 | 1" | x | 6-6.2.8 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Basket Strainer | DOB-2020-BSTR-0003 | SF Equipment | 4" | x | 3-6.4 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0005 | (-30 - 30 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0006 | (-30 - 30 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Centrifugal Pump | DOB-2020-CENP-0002 | Blackmer | 300 GPM | x | x | 3-8.1 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Electric Motor | DOB-2020-ELEMT-0002 | Corro-Duty | x | x | x | 9-1.7 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0007 | (0 - 300 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Automatic Air Vent | DOB-2020-AAVT-0005 | Liquid Controls | A8170 | x | 3-10.2 | See Mfr. O&M | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | General System Control Valve | DOB-2020-GSCVL-0002 | x | x | 4-3.2.1 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Pressure/Vaccum Gauge | DOB-2020-PVGA-0008 | (0 - 300 psi) / 1/4" NPT | x | x | x | 6-7.1 | See Mfr. O&M | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Positive Displacement Meter | DOB-2020-PDMT-0002 | Liquid Controls | M-60-2 | 624830 | 600 GPM | x | 3-7.1 | See Mfr. O&M | Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation. | Requires LOTO ans System placed Out-of-Service | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0017 | N-J | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Pressure Transmitter (Flow Switch) | DOB-2020-PRTR-0002 | Flowtect | V4SS2DU | S29761001 | x | x | x | 6-7.3 | See Mfr. O&M | Repairs shall be performed by SO. | Requires LOTO ans System placed Out-of-Service | ||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0018 | Flow-Tek | 3" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0019 | Flow-Tek | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Ball Valve | DOB-2020-BLVL-0020 | Flow-Tek | 3" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Motor Control | DOB-2020-MTRCT-0002 | x | x | 9-1.4 | See Mfr. O&M | Repairs shall be performed by SO. | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offload 2 | Static Grounding System | DOB-2020-STGS-0002 | x | 9-1.6.2 | See Mfr. O&M | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | ||||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offloading Area | Ball Valve | DOB-2020-BLVL-0021 | N-J | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offloading Area | Ball Valve | DOB-2020-BLVL-0022 | N-J | 6" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | |||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offloading Area | Ball Valve | DOB-2020-BLVL-0023 | 3/4" | x | 6-6.2.4 | See Mfr. O&M | Per PWS Touch-up Coating Repair | Requires LOTO ans System placed Out-of-Service | ||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offloading Area | Thermal Pressure Relief Valve | DOB-2020-PRVL-0006 | Taylor | 3/4" | x | x | 6-6.3 | See Mfr. O&M | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. | Requires LOTO ans System placed Out-of-Service | 3/4" Inlet - 1" Outlet | |||||
| 2020 | 2020 | 411291 | Bulk Storage | Offloading Area | Sight Flow Indicator | DOB-2020-SFND-0007 | Visi-Flow | 1" | 6-12.3 | See Mfr. O&M | Requires LOTO ans System placed Out-of-Service | |||||||||
| 2020 | 2020 | 411291 | Bulk Storage | Offloading Area | Fuel Truck Containment Area | DOB-2020-FTRKCS-0001 | x | x | 11-1.1 | See Mfr. O&M | Per PWS Joint Sealant and Crack Repair |