This file is a comprehensive Facility Maintenance Plan (Appendix K) for the Jacksonville Air National Guard Installation (IAP) in Florida, detailing maintenance requirements for multiple fuel storage and distribution facilities. The document provides an exhaustive inventory of fuel infrastructure, including two 100K-gallon jet fuel tanks (Facilities 1711 and 1712), a pump station, offloading stations, fillstands, diesel tanks, a mogas tank, and associated equipment such as pumps, valves, sensors, and grounding systems.

The maintenance plan specifies detailed maintenance protocols for each component, with most tasks requiring touch-up coating repair, periodic inspection, and specific manufacturer-recommended maintenance procedures. Many components require service order interventions for complex repairs, and several systems necessitate lock-out/tag-out procedures during maintenance. The document includes maintenance schedules, component tracking information, and references to specific UFC (Unified Facilities Criteria) sections governing maintenance requirements, providing a comprehensive framework for maintaining the fuel handling infrastructure at the Jacksonville IAP facility.

View the file

Other files

File Type Posted
Shaw AFB SC (SHW)-FMP.xlsx XLSX spreadsheet
Moody AFB GA (MDY)-FMP.xlsx XLSX spreadsheet
Attachment 6 Draft QASP.pdf PDF
Attachment 4 - PPQ Sample (3).pdf PDF
DFSP Charleston SC (CHS)-FMP.xlsx XLSX spreadsheet
CDRL Set 16 60-64.pdf PDF
Attachment 3 Technical Evaluation Form.pdf PDF
Savannah ANG GA (SAG)-FMP.xlsx XLSX spreadsheet
Savannah-Hilton Head GA (SHH)-FMP.xlsx XLSX spreadsheet
Robins AFB GA (ROB-TBD)-FMP.xlsx XLSX spreadsheet
CDRL Set 15 57-60.pdf PDF
CDRL Set 2 5-8.pdf PDF
CDRL Set 3 9-12.pdf PDF
CDRL Set 9 33-36.pdf PDF
CDRL Set 6 21-24.pdf PDF
Douglas MAP ANG NC (DGL)-FMP.xlsx XLSX spreadsheet
Dobbins ARB GA (DOB)-FMP.xlsx XLSX spreadsheet
McEntire ANG SC (MNT)-FMP.xlsx XLSX spreadsheet
Attachment 2 Sample Service Order (Appendix A - Attachment 1 Service Order Form).xlsx XLSX spreadsheet
Attachment 7 Pricing Worksheet SAD-AF2.xlsx XLSX spreadsheet
Charleston AFB SC (CAF)-FMP.xlsx XLSX spreadsheet
CDRL Set 13 49-52.pdf PDF
CDRL Set 4 13-16.pdf PDF
CDRL Set 7 25-28.pdf PDF
CDRL Set 8 29-32.pdf PDF
CDRL Set 14 53-56.pdf PDF
12.0 PWS Appendix K SAD-AF2 Real Property Data SAD-AF2 Final 20250225.xlsx XLSX spreadsheet
Patrick AFB FL (PAT)-FMP.xlsx XLSX spreadsheet
Attachment 1 Performance Work Statement SAD-AF2.pdf PDF
Fuels SAD-AF2 Draft Solicitation W912DY26RA017.pdf PDF
Attachment 5 Instructions and Evaluation Factors.pdf PDF
CDRL Set 1 1-4.pdf PDF
CDRL Set 12 45-48.pdf PDF
CDRL Set 5 17-20.pdf PDF
CDRL Set 10 37-40.pdf PDF
CDRL Set 17 65-67.pdf PDF
CDRL Set 11 41-44.pdf PDF
Seymour Johnson AFB NC (SMJ)-FMP.xlsx XLSX spreadsheet
Joint Base Charleston SC (JBC)-FMP.xlsx XLSX spreadsheet
2.1 Appendix A - Attachment 1 Service Order Form-v11.5_20251027.xlsx XLSX spreadsheet
Attachment 8 Small Business Participation Plan Template.pdf PDF
Stanly County Airport NC (WEF)-FMP.xlsx XLSX spreadsheet
Glynco ANG Station GA (JAS)-FMP.xlsx XLSX spreadsheet
Cape Canaveral AFS FL (DBE)-FMP.xlsx XLSX spreadsheet
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationInstallation Name
DLA Site Code
Hours of Operation
Address
ContractContractor
Contract #
Local POCsQAE Phone904-741-7480
QAE Emaildaryl.zoller.1@us.af.mil
Alt QAE PhoneN/A
Alt QAE EmailN/A
DLA/SCP POCsDLA PM Phone
DLA PM Email
SCP PM Phone
SCP PM Email
Contractor POCsContractor PM Phone
Contractor PM Email
Contractor QC Phone
Contractor QC Email
Contractor SM Phone229-415-3445
Contractor SM Emailbrandon.wells@westonsolutions.com
USACE POCsUSACE PM/COR Phone
USACE PM/COR Email
USACE PE Phone
USACE PE Email
USACE KO Phone
USACE KO Email

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

mailto:daryl.zoller.1@us.af.milmailto:brandon.wells@westonsolutions.com General Facility Description

FAC 1711 Jet Fuel Tank #1 100K Gallons
FAC 1712 Jet Fuel Tank #2 100K Gallons
FAC 1061 Jet Fuel Pumphouse
FAC 1720 Jet Fuel Fillstands
FAC 1730 Jet Fuel Offload Stands
FAC 1508 Refueling Unit Parking
FAC 1315 Remote Containment Basin For Refueling Unit Parking
FAC 1060 POL Ops BLDG (Lab)
FAC 1701 Diesel Tank 2K Gallons
FAC 1771 Diesel Tank 2K Gallons
FAC 1772 Mogas Tank 2K Gallons

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Include a general facility description for the installation.

Communication Plan

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, etc.

Safety

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

APPENDIX J - EXISTING MAINTENANCE SCHEDULES
#Installation NameSite NameDLA Site CodeRPSUIDLocationCitySTExisting Max Freq1st Quarter
Contract PoP 14 Aug 20 -13 Aug 212nd Quarter3rd Quarter4th Quarter
Aug-24Sep-24Oct-24Nov-24Dec-24Jan-25Feb-25Mar-25Apr-25May-25Jun-25Jul-25
1SI CAPE CANAVERALCape Canaveral AFS Site #1DBE1555Cape Canaveral AFSCape CanaveralFL1Annual

2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21

3JACKSONVILLE IAPJacksonville IAP Site #1JVL2390Jacksonville ANGJacksonvilleFL1SA1/Q1
10/16-10/18Q2
1/21-1/22A/SA2/Q3
4/22-4/25Q4

7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10

5ROBINS AFBRobins Air Force Base Site 1ROB3219Robins ANG, GAWarner RobinsGA4SA1/Q1
8/28-8/30Q2
11/21-11/22A/SA2/Q3
3/3-3/6Q4

6/3-6/4

6SI MOODYMoody AFBMDY3020Moody AFB, GAValdostaGA4Q1
9/16-9/18A-SA1-Q2
12/02-12/11Q3
3/24-3/26SA2-Q4

6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16

8SAVANNAH HILTON HEAD IAPSavannah ANG (IAP ID 107)SAG17105Savannah ANG, GA (IAP ID 107)SavannahGA1Annual
12/17-12/19MC
9SAVANNAH HILTON HEAD IAPSavannah/Hilton Head IAP Site #3SHH3358SAVANNAH/HILTON HEAD IAP SITE #5SavannahGA4Annual

12/20

10JB CHARLESTONDFSP CharlestonCHS1580DFSP CharlestonCharlestonSC1SA1/Q1
8/19-8/23Q2
11/13-11/15A/SA2/Q3
2/3-2/21Q4

5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22

12JB CHARLESTONJoint Base Charleston NWSJBC213JOINT BASE CHARLESTON NAVAL WEAPONS STATIONCharlestonSC4Q1
9/10SA1-Q2
12/10-12/11Q3
3/11-3/12A-SA2-Q4

6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24

15CHARLOTTE IAPDouglas MAP ANG (ID 146)DGL1661Douglas MAP ANG, NC (ID 146)CharlotteNC1Annual
11/04-11/06MC
16CHARLOTTE IAPStanly County AirportWEF3312Stanly County AirportNew LondonNC1Annual

11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17

Task Matrix

Special Considerations
EBS Facility #iNFADS Facility #ACES/ NEXGEN Facility #Real Property Unique IdentifierFacility NameOperational AreaComponent TypeCUIDMakeModelSerialCapacity/SizeQSAUFC Section ReferenceManufacturer RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
171117111169315Jet Tank 1Jet Tank 1Above Ground Field Erected TankJVS-1711-AGVET-0001100k glx8-4See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0001VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0002VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0003VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0004VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0005VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0006VelanCF8M3/4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingBall ValveJVS-1711-BLVL-0007VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingThermal Pressure Relief ValveJVS-1711-PRVL-0001Taylor8200065679-2150 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1 ReceivingSight Flow IndicatorJVS-1711-SFND-0001Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingCheck ValveJVS-1711-CKVL-00011 in.x6-6.2.8See Mfr. Req.Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1 ReceivingExternal High Level Shutoff ValveJVS-1711-EHLSVL-0001Claval6 in.x8-9.6.1See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 ReceivingDouble Block and Bleed ValveJVS-1711-DBBVL-0001General211RF1117572960016 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueDouble Block and Bleed ValveJVS-1711-DBBVL-0002General8811RF11175729400210 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueBall ValveJVS-1711-BLVL-0008VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueBall ValveJVS-1711-BLVL-0009VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueBall ValveJVS-1711-BLVL-0010VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueBall ValveJVS-1711-BLVL-0011VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueBall ValveJVS-1711-BLVL-0012VelanCF8M4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueSight Flow IndicatorJVS-1711-SFND-0002Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1 IssueCheck ValveJVS-1711-CKVL-00021 in.x6-6.2.8See Mfr. Req.Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1 IssueThermal Pressure Relief ValveJVS-1711-PRVL-0002Taylor8200004420-1650 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1 IssueDouble Block and Bleed ValveJVS-1711-DBBVL-0003General211RF1117374800014 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankProduct Saver TankJVS-1711-PRDST-000155 glx8-9.10See Mfr. Req.
171117111169315Jet Tank 1Product Saver TankCentrifugal PumpJVS-1711-CENP-0001xx3-8.1See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankElectric MotorJVS-1711-ELEMT-0001CorcoranD10126848F18120523611 HPxxx9-1.7See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankBall ValveJVS-1711-BLVL-0013VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankBall ValveJVS-1711-BLVL-0014VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankBall ValveJVS-1711-BLVL-0015VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankBall ValveJVS-1711-BLVL-0016VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankCheck ValveJVS-1711-CKVL-00031 in.x6-6.2.8See Mfr. Req.Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171117111169315Jet Tank 1Product Saver TankPressure Control Valve (CRL)JVL-1711-PCVL-0001Claval(20 - 200 psi)x4-4.2.7See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Product Saver TankBall ValveJVS-1711-BLVL-0017VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberExternally Mounted Alarm (High Level)JVS-1711-EMLA-0001Scully07436x8-9.9.1See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberBall ValveJVS-1711-BLVL-0018VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberBall ValveJVS-1711-BLVL-0019VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberBall ValveJVS-1711-BLVL-0020VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberHigh Level Shutoff Valve (Controller)JVS-1711-EHLSVL-0001Claval04-109x8-9.6.1See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberBall ValveJVS-1711-BLVL-0021VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1High Level ChamberBall ValveJVS-1711-BLVL-0022VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Low Level ChamberExternally Mounted Alarm (Low Level)JVS-1711-EMLA-0001Scully07436x8-9.9.1See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Low Level ChamberBall ValveJVS-1711-BLVL-0023VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Low Level ChamberBall ValveJVS-1711-BLVL-0024VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Low Level ChamberBall ValveJVS-1711-BLVL-0025VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Low Level ChamberBall ValveJVS-1711-BLVL-0026VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Tank TopStilling WellJVS-1711-STGW-00018-9.17See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Tank TopStilling WellJVS-1711-STGW-00028-9.17See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Tank TopStilling WellJVS-1711-STGW-00038-9.17See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Tank TopAutomatic Tank Gauging (Servo Gauge)JVS-1711-SRVGA-0001Honeywell/Enraf854ATG854051759xxx8-9.8.3See Mfr. Req.Per PWS Touch-up Coating Repairx
171117111169315Jet Tank 1Jet Tank 1Cathodic ProtectionJVS-1711-CP-0001ADALETCE-1011006-N4x9-2.1See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1Mechanical Tape GaugeJVS-1711-MTGA-0001VarecBM13661-1112006665x8-9.7See Mfr. Req.Per PWS Touch-up Coating Repair
171117111169315Jet Tank 1Jet Tank 1Aluminum Honeycomb Floating PanJVS-1711-AHFP-0001x8-9.1.1See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1Pan LegsJVS-1711-FRPLG-00018-9.1.6See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1Fire Protection System (wet pipe)JVS-1711-FPRS-0001x8-9.15See Mfr. Req.
171117111169315Jet Tank 1Jet Tank 1Static Grounding SystemJVS-1711-STGS-0001x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1Static Grounding SystemJVS-1711-STGS-0002x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1Static Grounding SystemJVS-1711-STGS-0003x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1Jet Tank 1Static Grounding SystemJVS-1711-STGS-0004x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171117111169315Jet Tank 1ContainmentDikeJVS-1711-CCBWS-0001x8-10.2See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2Above Ground Field Erected TankJVS-1712-AGVET-0001100k glx8-4See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0001VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0002VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0003VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0004VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0005VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0006VelanCF8M3/4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingBall ValveJVS-1712-BLVL-0007VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingThermal Pressure Relief ValveJVS-1712-PRVL-0001Taylor8200065679-1150 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2 ReceivingSight Flow IndicatorJVS-1712-SFND-0001Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingCheck ValveJVS-1712-CKVL-00011 in.x6-6.2.8See Mfr. Req.Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2 ReceivingExternal High Level Shutoff ValveJVS-1712-EHLSVL-0001Claval6 in.x8-9.6.1See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 ReceivingDouble Block and Bleed ValveJVS-1712-DBBVL-0001General211RF1117572960026 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueDouble Block and Bleed ValveJVS-1712-DBBVL-0002General8811RF11175729400110 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueBall ValveJVS-1712-BLVL-0008VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueBall ValveJVS-1712-BLVL-0009VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueBall ValveJVS-1712-BLVL-0010VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueBall ValveJVS-1712-BLVL-0011VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueBall ValveJVS-1712-BLVL-0012VelanCF8M4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueSight Flow IndicatorJVS-1712-SFND-0002Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2 IssueCheck ValveJVS-1712-CKVL-00021 in.x6-6.2.8See Mfr. Req.Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2 IssueThermal Pressure Relief ValveJVS-1712-PRVL-0002Taylor8200004420-2050 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2 IssueDouble Block and Bleed ValveJVS-1712-DBBVL-0003General211RF1117374800024 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankProduct Saver TankJVS-1712-PRDST-000155 glx8-9.10See Mfr. Req.
171217121169316Jet Tank 2Product Saver TankCentrifugal PumpJVS-1712-CENP-0001xx3-8.1See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankElectric MotorJVS-1712-ELEMT-0001LeesonA6C4XK4C1 HPxxx9-1.7See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankBall ValveJVS-1712-BLVL-0013VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankBall ValveJVS-1712-BLVL-0014VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankBall ValveJVS-1712-BLVL-0015VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankBall ValveJVS-1712-BLVL-0016VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankCheck ValveJVS-1712-CKVL-00031 in.x6-6.2.8See Mfr. Req.Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
171217121169316Jet Tank 2Product Saver TankPressure Control Valve (CRL)JVL-1712-PCVL-0001Claval(20 - 200 psi)x4-4.2.7See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Product Saver TankBall ValveJVS-1712-BLVL-0017VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberExternally Mounted Alarm (High Level)JVS-1712-EMLA-0001Scully07436x8-9.9.1See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberBall ValveJVS-1712-BLVL-0018VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberBall ValveJVS-1712-BLVL-0019VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberBall ValveJVS-1712-BLVL-0020VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberHigh Level Shutoff Valve (Controller)JVS-1712-EHLSVL-0001Claval04-109x8-9.6.1See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberBall ValveJVS-1712-BLVL-0021VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2High Level ChamberBall ValveJVS-1712-BLVL-0022VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Low Level ChamberExternally Mounted Alarm (Low Level)JVS-1712-EMLA-0001Scully07436x8-9.9.1See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Low Level ChamberBall ValveJVS-1712-BLVL-0023VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Low Level ChamberBall ValveJVS-1712-BLVL-0024VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Low Level ChamberBall ValveJVS-1712-BLVL-0025VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Low Level ChamberBall ValveJVS-1712-BLVL-0026VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Tank TopStilling WellJVS-1712-STGW-00018-9.17See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Tank TopStilling WellJVS-1712-STGW-00028-9.17See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Tank TopStilling WellJVS-1712-STGW-00038-9.17See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Tank TopAutomatic Tank Gauging (Servo Gauge)JVS-1712-SRVGA-0001Honeywell/Enraf854ATG854051758xxx8-9.8.3See Mfr. Req.Per PWS Touch-up Coating Repairx
171217121169316Jet Tank 2Jet Tank 2Cathodic ProtectionJVS-1712-CP-0001ADALETCE-1011006-N4x9-2.1See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2Mechanical Tape GaugeJVS-1712-MTGA-0001VarecBM13661-1112006686x8-9.7See Mfr. Req.Per PWS Touch-up Coating Repair
171217121169316Jet Tank 2Jet Tank 2Aluminum Honeycomb Floating PanJVS-1712-AHFP-0001x8-9.1.1See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2Pan LegsJVS-1712-FRPLG-00018-9.1.6See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2Fire Protection System (wet pipe)JVS-1712-FPRS-0001x8-9.15See Mfr. Req.
171217121169316Jet Tank 2Jet Tank 2Static Grounding SystemJVS-1712-STGS-0001x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2Static Grounding SystemJVS-1712-STGS-0002x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2Static Grounding SystemJVS-1712-STGS-0003x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2Jet Tank 2Static Grounding SystemJVS-1712-STGS-0004x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
171217121169316Jet Tank 2ContainmentDikeJVS-1712-CCBWS-0001x8-10.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingOffloading Fuel HoseJVS-1730-OLHS-00014 in. x 10 ft.xx3-9.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingOffloading Fuel HoseJVS-1730-OLHS-00024 in. x 10 ft.xx3-9.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0001Velan996-0104 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0002Velan996-0104 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingSight Flow IndicatorJVS-1730-SFND-00014 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingSight Flow IndicatorJVS-1730-SFND-00024 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0003VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0004VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0001Taylor8200004420-2540 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingSight Flow IndicatorJVS-1730-SFND-0003Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0005VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0006VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0007VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBasket StrainerJVS-1730-BSTR-0001Titan6 in.x3-6.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingDifferential Pressure GuageJVS-1730-DPGA-0001Gammon534-30xxx6-7.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0008VelanCF8M6 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingAir Eliminator TankJVS-1730-AELT-0001ME IndustriesAEV366300S150RH10234250 glx3-10.1See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingPressure Vacuum VentJVS-1730-TPVVT-0001Groth1202B-02-115-V021006231-01-16x8-9.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingPoint Sensor (wet)JVS-1730-PSWET-0001SOR701K1-U-P7-C-FM100604481x8-9.13.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingPoint Sensor (wet)JVS-1730-PSWET-0002SOR701K1-U-P7-C-FM100604482x8-9.13.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0002Taylor8200.00005029-250 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingSight Flow IndicatorJVS-1730-SFND-0004Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0009VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0010VelanCF8M6 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingFlow SwitchJVS-1730-PRTR-0001SOR902C-F7C-C-A4-N7-WV100604477xx6-7.3See Mfr. Req.Repairs shall be performed by SO.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0003Taylor8200004420-2240 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingSight Flow IndicatorJVS-1730-SFND-0005Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0011VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0012VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0013VelanCF8M1/2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingPressure GaugeJVS-1730-PVGA-0001USG(-30 - 60 psi) / 1/2 in. NPTxxx6-7.1See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingVertical Inline PumpJVS-1730-VILP-0001Clyde UnionCM100115B-1300 gpmxx3-8.1.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingElectric MotorJVS-1730-ELEMT-0001Baldor RelianceB551905-010001KN25 HPxxx9-1.7See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0014VelanCF8M1/2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingPressure GaugeJVS-1730-PVGA-0002Palmer(0 -160 psi) / 1/2 in. NPTxxx6-7.1See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0015VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingControl ValveJVS-1730-GSCVL-0001Claval4 in.x4-3.2.1See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingControl ValveJVS-1730-GSCVL-0002Claval2 in.x4-3.2.1See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0016VelanCF8M4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingPlug ValveJVS-1730-NPLVL-0001Velan2 in.xx6-6.2.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0017VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0018VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0019VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0004Taylor8200004420-14125 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingSight Flow IndicatorJVS-1730-SFND-0006Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0020VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingBall ValveJVS-1730-BLVL-0021VelanCF8M4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingDouble Block and Bleed ValveJVS-1730-DBBVL-0001General211RF1117374800034 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 1ReceivingGround Verfication SystemJVS-1730-GRVS-0001ScullyST47ELKx9-5See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingGround ReelJVS-1730-STGS-0001Anetekxx9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 1ReceivingStatic Grounding SystemJVS-1730-STGS-0001x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingOffloading Fuel HoseJVS-1730-OLHS-00034 in. x 10 ft.xx3-9.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingOffloading Fuel HoseJVS-1730-OLHS-00044 in. x 10 ft.xx3-9.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0022Velan996-0104 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0023Velan996-0104 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingSight Flow IndicatorJVS-1730-SFND-00074 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingSight Flow IndicatorJVS-1730-SFND-00084 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0024VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0025VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0005Taylor8200004420-2840 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingSight Flow IndicatorJVS-1730-SFND-0009Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0026VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0027VelanCF8M3/8 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0028VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBasket StrainerJVS-1730-BSTR-0002Titan6 in.x3-6.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingDifferential Pressure GuageJVS-1730-DPGA-0002Gammon534-30xxx6-7.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0029VelanCF8M6 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingAir Eliminator TankJVS-1730-AELT-0002ME IndustriesAEV366300S150RH10235250 glx3-10.1See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingPressure Vacuum VentJVS-1730-TPVVT-0002Groth1202B-02-115-V021006231-01-6x8-9.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingPoint Sensor (wet)JVS-1730-PSWET-0003SOR701K1-U-P7-C-FM100604484x8-9.13.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingPoint Sensor (wet)JVS-1730-PSWET-0004SOR701K1-U-P7-C-FM100604483x8-9.13.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0006Taylor8200005029-150 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingSight Flow IndicatorJVS-1730-SFND-0010Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0030VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0031VelanCF8M6 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingFlow SwitchJVS-1730-PRTR-0002SOR902C-F7C-C-A4-N7-WV100604479xx6-7.3See Mfr. Req.Repairs shall be performed by SO.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0007Taylor8200004420-2340 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingSight Flow IndicatorJVS-1730-SFND-0011Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0032VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0033VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0034VelanCF8M1/2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingPressure GaugeJVS-1730-PVGA-0003Palmer(-30 - 60 psi) / 1/2 in. NPTxxx6-7.1See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingVertical Inline PumpJVS-1730-VILP-0002Clyde UnionCM100115B-2300 gpmxx3-8.1.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingElectric MotorJVS-1730-ELEMT-0002Baldor RelianceB551905-010002KN25 HPxxx9-1.7See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0035VelanCF8M1/2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingPressure GaugeJVS-1730-PVGA-0004Palmer(0 -160 psi) / 1/2 in. NPTxxx6-7.1See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0036VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingControl ValveJVS-1730-GSCVL-0003Claval4 in.x4-3.2.1See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingControl ValveJVS-1730-GSCVL-0004Claval2 in.x4-3.2.1See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0037VelanCF8M4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingPlug ValveJVS-1730-NPLVL-0002Velan2 in.xx6-6.2.2See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0038VelanCF8M2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0039VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0040VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingThermal Pressure Relief ValveJVS-1730-PRVL-0008Taylor8200004420-13125 psig.xx6-6.3See Mfr. Req.Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating RepairRequires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingSight Flow IndicatorJVS-1730-SFND-0012Visi-Flo1 in.6-12.3See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0041VelanCF8M1 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingBall ValveJVS-1730-BLVL-0042VelanCF8M4 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingDouble Block and Bleed ValveJVS-1730-DBBVL-0002General211RF1117374800044 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
173017301175848Offloading Station 2ReceivingGround Verfication SystemJVS-1730-GRVS-0002ScullyST47ELKx9-5See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingGround ReelJVS-1730-STGS-0002Anetekxx9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
173017301175848Offloading Station 2ReceivingStatic Grounding SystemJVS-1730-STGS-0002x9-1.6.2See Mfr. Req.This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System placed out-of-service
172017201175847Fillstand 1Fillstand 1Double Block and Bleed ValveJVS-1720-DBBVL-0001General211RF1117374800064 in.xx6-6.2.5See Mfr. Req.Per PWS Touch-up Coating Repair
172017201175847Fillstand 1Fillstand 1Ball ValveJVS-1720-BLVL-0001VelanCF8M1/2 in.x6-6.2.4See Mfr. Req.Per PWS Touch-up Coating Repair