Jacksonville IAP FL (JVL)-FMP.xlsx
XLSX spreadsheet 104 KB Posted
- Solicitation number
- W912DY26RA017
About this file
This file is a comprehensive Facility Maintenance Plan (Appendix K) for the Jacksonville Air National Guard Installation (IAP) in Florida, detailing maintenance requirements for multiple fuel storage and distribution facilities. The document provides an exhaustive inventory of fuel infrastructure, including two 100K-gallon jet fuel tanks (Facilities 1711 and 1712), a pump station, offloading stations, fillstands, diesel tanks, a mogas tank, and associated equipment such as pumps, valves, sensors, and grounding systems.
The maintenance plan specifies detailed maintenance protocols for each component, with most tasks requiring touch-up coating repair, periodic inspection, and specific manufacturer-recommended maintenance procedures. Many components require service order interventions for complex repairs, and several systems necessitate lock-out/tag-out procedures during maintenance. The document includes maintenance schedules, component tracking information, and references to specific UFC (Unified Facilities Criteria) sections governing maintenance requirements, providing a comprehensive framework for maintaining the fuel handling infrastructure at the Jacksonville IAP facility.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Installation Name | |
| DLA Site Code | ||
| Hours of Operation | ||
| Address | ||
| Contract | Contractor | |
| Contract # | ||
| Local POCs | QAE Phone | 904-741-7480 |
| QAE Email | daryl.zoller.1@us.af.mil | |
| Alt QAE Phone | N/A | |
| Alt QAE Email | N/A | |
| DLA/SCP POCs | DLA PM Phone | |
| DLA PM Email | ||
| SCP PM Phone | ||
| SCP PM Email | ||
| Contractor POCs | Contractor PM Phone | |
| Contractor PM Email | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SM Phone | 229-415-3445 | |
| Contractor SM Email | brandon.wells@westonsolutions.com | |
| USACE POCs | USACE PM/COR Phone | |
| USACE PM/COR Email | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO Phone | ||
| USACE KO Email |
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
mailto:daryl.zoller.1@us.af.milmailto:brandon.wells@westonsolutions.com General Facility Description
| FAC 1711 Jet Fuel Tank #1 100K Gallons |
| FAC 1712 Jet Fuel Tank #2 100K Gallons |
| FAC 1061 Jet Fuel Pumphouse |
| FAC 1720 Jet Fuel Fillstands |
| FAC 1730 Jet Fuel Offload Stands |
| FAC 1508 Refueling Unit Parking |
| FAC 1315 Remote Containment Basin For Refueling Unit Parking |
| FAC 1060 POL Ops BLDG (Lab) |
| FAC 1701 Diesel Tank 2K Gallons |
| FAC 1771 Diesel Tank 2K Gallons |
| FAC 1772 Mogas Tank 2K Gallons |
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Include a general facility description for the installation.
Communication Plan
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, etc.
Safety
Appendix K - Facility Maintenance Plan
&P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
| APPENDIX J - EXISTING MAINTENANCE SCHEDULES | |||||||||||||||||||||
| # | Installation Name | Site Name | DLA Site Code | RPSUID | Location | City | ST | Existing Max Freq | 1st Quarter | ||||||||||||
| Contract PoP 14 Aug 20 -13 Aug 21 | 2nd Quarter | 3rd Quarter | 4th Quarter | ||||||||||||||||||
| Aug-24 | Sep-24 | Oct-24 | Nov-24 | Dec-24 | Jan-25 | Feb-25 | Mar-25 | Apr-25 | May-25 | Jun-25 | Jul-25 | ||||||||||
| 1 | SI CAPE CANAVERAL | Cape Canaveral AFS Site #1 | DBE | 1555 | Cape Canaveral AFS | Cape Canaveral | FL | 1 | Annual |
2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21
| 3 | JACKSONVILLE IAP | Jacksonville IAP Site #1 | JVL | 2390 | Jacksonville ANG | Jacksonville | FL | 1 | SA1/Q1 | |
| 10/16-10/18 | Q2 | |||||||||
| 1/21-1/22 | A/SA2/Q3 | |||||||||
| 4/22-4/25 | Q4 |
7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10
| 5 | ROBINS AFB | Robins Air Force Base Site 1 | ROB | 3219 | Robins ANG, GA | Warner Robins | GA | 4 | SA1/Q1 | |
| 8/28-8/30 | Q2 | |||||||||
| 11/21-11/22 | A/SA2/Q3 | |||||||||
| 3/3-3/6 | Q4 |
6/3-6/4
| 6 | SI MOODY | Moody AFB | MDY | 3020 | Moody AFB, GA | Valdosta | GA | 4 | Q1 | |
| 9/16-9/18 | A-SA1-Q2 | |||||||||
| 12/02-12/11 | Q3 | |||||||||
| 3/24-3/26 | SA2-Q4 |
6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16
| 8 | SAVANNAH HILTON HEAD IAP | Savannah ANG (IAP ID 107) | SAG | 17105 | Savannah ANG, GA (IAP ID 107) | Savannah | GA | 1 | Annual | |
| 12/17-12/19 | MC | |||||||||
| 9 | SAVANNAH HILTON HEAD IAP | Savannah/Hilton Head IAP Site #3 | SHH | 3358 | SAVANNAH/HILTON HEAD IAP SITE #5 | Savannah | GA | 4 | Annual |
12/20
| 10 | JB CHARLESTON | DFSP Charleston | CHS | 1580 | DFSP Charleston | Charleston | SC | 1 | SA1/Q1 | |
| 8/19-8/23 | Q2 | |||||||||
| 11/13-11/15 | A/SA2/Q3 | |||||||||
| 2/3-2/21 | Q4 |
5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22
| 12 | JB CHARLESTON | Joint Base Charleston NWS | JBC | 213 | JOINT BASE CHARLESTON NAVAL WEAPONS STATION | Charleston | SC | 4 | Q1 | |
| 9/10 | SA1-Q2 | |||||||||
| 12/10-12/11 | Q3 | |||||||||
| 3/11-3/12 | A-SA2-Q4 |
6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24
| 15 | CHARLOTTE IAP | Douglas MAP ANG (ID 146) | DGL | 1661 | Douglas MAP ANG, NC (ID 146) | Charlotte | NC | 1 | Annual | |
| 11/04-11/06 | MC | |||||||||
| 16 | CHARLOTTE IAP | Stanly County Airport | WEF | 3312 | Stanly County Airport | New London | NC | 1 | Annual |
11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17
Task Matrix
| Special Considerations | |||||||||||||||||||||
| EBS Facility # | iNFADS Facility # | ACES/ NEXGEN Facility # | Real Property Unique Identifier | Facility Name | Operational Area | Component Type | CUID | Make | Model | Serial | Capacity/Size | Q | S | A | UFC Section Reference | Manufacturer Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments | |
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Above Ground Field Erected Tank | JVS-1711-AGVET-0001 | 100k gl | x | 8-4 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0001 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0002 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0003 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0004 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0005 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0006 | Velan | CF8M | 3/4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Ball Valve | JVS-1711-BLVL-0007 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Thermal Pressure Relief Valve | JVS-1711-PRVL-0001 | Taylor | 8200 | 065679-2 | 150 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Sight Flow Indicator | JVS-1711-SFND-0001 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Check Valve | JVS-1711-CKVL-0001 | 1 in. | x | 6-6.2.8 | See Mfr. Req. | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | External High Level Shutoff Valve | JVS-1711-EHLSVL-0001 | Claval | 6 in. | x | 8-9.6.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Receiving | Double Block and Bleed Valve | JVS-1711-DBBVL-0001 | General | 211RF | 111757296001 | 6 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Double Block and Bleed Valve | JVS-1711-DBBVL-0002 | General | 8811RF | 111757294002 | 10 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Ball Valve | JVS-1711-BLVL-0008 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Ball Valve | JVS-1711-BLVL-0009 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Ball Valve | JVS-1711-BLVL-0010 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Ball Valve | JVS-1711-BLVL-0011 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Ball Valve | JVS-1711-BLVL-0012 | Velan | CF8M | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Sight Flow Indicator | JVS-1711-SFND-0002 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Check Valve | JVS-1711-CKVL-0002 | 1 in. | x | 6-6.2.8 | See Mfr. Req. | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Thermal Pressure Relief Valve | JVS-1711-PRVL-0002 | Taylor | 8200 | 004420-16 | 50 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 Issue | Double Block and Bleed Valve | JVS-1711-DBBVL-0003 | General | 211RF | 111737480001 | 4 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Product Saver Tank | JVS-1711-PRDST-0001 | 55 gl | x | 8-9.10 | See Mfr. Req. | |||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Centrifugal Pump | JVS-1711-CENP-0001 | x | x | 3-8.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Electric Motor | JVS-1711-ELEMT-0001 | Corcoran | D10126848 | F1812052361 | 1 HP | x | x | x | 9-1.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Ball Valve | JVS-1711-BLVL-0013 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Ball Valve | JVS-1711-BLVL-0014 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Ball Valve | JVS-1711-BLVL-0015 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Ball Valve | JVS-1711-BLVL-0016 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Check Valve | JVS-1711-CKVL-0003 | 1 in. | x | 6-6.2.8 | See Mfr. Req. | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Pressure Control Valve (CRL) | JVL-1711-PCVL-0001 | Claval | (20 - 200 psi) | x | 4-4.2.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Product Saver Tank | Ball Valve | JVS-1711-BLVL-0017 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | Externally Mounted Alarm (High Level) | JVS-1711-EMLA-0001 | Scully | 07436 | x | 8-9.9.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | Ball Valve | JVS-1711-BLVL-0018 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | Ball Valve | JVS-1711-BLVL-0019 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | Ball Valve | JVS-1711-BLVL-0020 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | High Level Shutoff Valve (Controller) | JVS-1711-EHLSVL-0001 | Claval | 04-109 | x | 8-9.6.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | Ball Valve | JVS-1711-BLVL-0021 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | High Level Chamber | Ball Valve | JVS-1711-BLVL-0022 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Low Level Chamber | Externally Mounted Alarm (Low Level) | JVS-1711-EMLA-0001 | Scully | 07436 | x | 8-9.9.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Low Level Chamber | Ball Valve | JVS-1711-BLVL-0023 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Low Level Chamber | Ball Valve | JVS-1711-BLVL-0024 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Low Level Chamber | Ball Valve | JVS-1711-BLVL-0025 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Low Level Chamber | Ball Valve | JVS-1711-BLVL-0026 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Tank Top | Stilling Well | JVS-1711-STGW-0001 | 8-9.17 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Tank Top | Stilling Well | JVS-1711-STGW-0002 | 8-9.17 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Tank Top | Stilling Well | JVS-1711-STGW-0003 | 8-9.17 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Tank Top | Automatic Tank Gauging (Servo Gauge) | JVS-1711-SRVGA-0001 | Honeywell/Enraf | 854ATG | 854051759 | x | x | x | 8-9.8.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | x | |||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Cathodic Protection | JVS-1711-CP-0001 | ADALET | CE-1011006-N4 | x | 9-2.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Mechanical Tape Gauge | JVS-1711-MTGA-0001 | Varec | BM13661-111 | 2006665 | x | 8-9.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Aluminum Honeycomb Floating Pan | JVS-1711-AHFP-0001 | x | 8-9.1.1 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Pan Legs | JVS-1711-FRPLG-0001 | 8-9.1.6 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Fire Protection System (wet pipe) | JVS-1711-FPRS-0001 | x | 8-9.15 | See Mfr. Req. | ||||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Static Grounding System | JVS-1711-STGS-0001 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Static Grounding System | JVS-1711-STGS-0002 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Static Grounding System | JVS-1711-STGS-0003 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Jet Tank 1 | Static Grounding System | JVS-1711-STGS-0004 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1711 | 1711 | 1169315 | Jet Tank 1 | Containment | Dike | JVS-1711-CCBWS-0001 | x | 8-10.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Above Ground Field Erected Tank | JVS-1712-AGVET-0001 | 100k gl | x | 8-4 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0001 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0002 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0003 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0004 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0005 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0006 | Velan | CF8M | 3/4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Ball Valve | JVS-1712-BLVL-0007 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Thermal Pressure Relief Valve | JVS-1712-PRVL-0001 | Taylor | 8200 | 065679-1 | 150 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Sight Flow Indicator | JVS-1712-SFND-0001 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Check Valve | JVS-1712-CKVL-0001 | 1 in. | x | 6-6.2.8 | See Mfr. Req. | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | External High Level Shutoff Valve | JVS-1712-EHLSVL-0001 | Claval | 6 in. | x | 8-9.6.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Receiving | Double Block and Bleed Valve | JVS-1712-DBBVL-0001 | General | 211RF | 111757296002 | 6 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Double Block and Bleed Valve | JVS-1712-DBBVL-0002 | General | 8811RF | 111757294001 | 10 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Ball Valve | JVS-1712-BLVL-0008 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Ball Valve | JVS-1712-BLVL-0009 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Ball Valve | JVS-1712-BLVL-0010 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Ball Valve | JVS-1712-BLVL-0011 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Ball Valve | JVS-1712-BLVL-0012 | Velan | CF8M | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Sight Flow Indicator | JVS-1712-SFND-0002 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Check Valve | JVS-1712-CKVL-0002 | 1 in. | x | 6-6.2.8 | See Mfr. Req. | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Thermal Pressure Relief Valve | JVS-1712-PRVL-0002 | Taylor | 8200 | 004420-20 | 50 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 Issue | Double Block and Bleed Valve | JVS-1712-DBBVL-0003 | General | 211RF | 111737480002 | 4 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Product Saver Tank | JVS-1712-PRDST-0001 | 55 gl | x | 8-9.10 | See Mfr. Req. | |||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Centrifugal Pump | JVS-1712-CENP-0001 | x | x | 3-8.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Electric Motor | JVS-1712-ELEMT-0001 | Leeson | A6C4XK4C | 1 HP | x | x | x | 9-1.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Ball Valve | JVS-1712-BLVL-0013 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Ball Valve | JVS-1712-BLVL-0014 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Ball Valve | JVS-1712-BLVL-0015 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Ball Valve | JVS-1712-BLVL-0016 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Check Valve | JVS-1712-CKVL-0003 | 1 in. | x | 6-6.2.8 | See Mfr. Req. | Repairs that require servicing the valve in a shop should be performed through a service order. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Pressure Control Valve (CRL) | JVL-1712-PCVL-0001 | Claval | (20 - 200 psi) | x | 4-4.2.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Product Saver Tank | Ball Valve | JVS-1712-BLVL-0017 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | Externally Mounted Alarm (High Level) | JVS-1712-EMLA-0001 | Scully | 07436 | x | 8-9.9.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | Ball Valve | JVS-1712-BLVL-0018 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | Ball Valve | JVS-1712-BLVL-0019 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | Ball Valve | JVS-1712-BLVL-0020 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | High Level Shutoff Valve (Controller) | JVS-1712-EHLSVL-0001 | Claval | 04-109 | x | 8-9.6.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | Ball Valve | JVS-1712-BLVL-0021 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | High Level Chamber | Ball Valve | JVS-1712-BLVL-0022 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Low Level Chamber | Externally Mounted Alarm (Low Level) | JVS-1712-EMLA-0001 | Scully | 07436 | x | 8-9.9.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Low Level Chamber | Ball Valve | JVS-1712-BLVL-0023 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Low Level Chamber | Ball Valve | JVS-1712-BLVL-0024 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Low Level Chamber | Ball Valve | JVS-1712-BLVL-0025 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Low Level Chamber | Ball Valve | JVS-1712-BLVL-0026 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Tank Top | Stilling Well | JVS-1712-STGW-0001 | 8-9.17 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Tank Top | Stilling Well | JVS-1712-STGW-0002 | 8-9.17 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Tank Top | Stilling Well | JVS-1712-STGW-0003 | 8-9.17 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Tank Top | Automatic Tank Gauging (Servo Gauge) | JVS-1712-SRVGA-0001 | Honeywell/Enraf | 854ATG | 854051758 | x | x | x | 8-9.8.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | x | |||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Cathodic Protection | JVS-1712-CP-0001 | ADALET | CE-1011006-N4 | x | 9-2.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Mechanical Tape Gauge | JVS-1712-MTGA-0001 | Varec | BM13661-111 | 2006686 | x | 8-9.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Aluminum Honeycomb Floating Pan | JVS-1712-AHFP-0001 | x | 8-9.1.1 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Pan Legs | JVS-1712-FRPLG-0001 | 8-9.1.6 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | |||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Fire Protection System (wet pipe) | JVS-1712-FPRS-0001 | x | 8-9.15 | See Mfr. Req. | ||||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Static Grounding System | JVS-1712-STGS-0001 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Static Grounding System | JVS-1712-STGS-0002 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Static Grounding System | JVS-1712-STGS-0003 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Jet Tank 2 | Static Grounding System | JVS-1712-STGS-0004 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1712 | 1712 | 1169316 | Jet Tank 2 | Containment | Dike | JVS-1712-CCBWS-0001 | x | 8-10.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Offloading Fuel Hose | JVS-1730-OLHS-0001 | 4 in. x 10 ft. | x | x | 3-9.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Offloading Fuel Hose | JVS-1730-OLHS-0002 | 4 in. x 10 ft. | x | x | 3-9.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0001 | Velan | 996-010 | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0002 | Velan | 996-010 | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0001 | 4 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0002 | 4 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0003 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0004 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0001 | Taylor | 8200 | 004420-25 | 40 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0003 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0005 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0006 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0007 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Basket Strainer | JVS-1730-BSTR-0001 | Titan | 6 in. | x | 3-6.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Differential Pressure Guage | JVS-1730-DPGA-0001 | Gammon | 534-30 | x | x | x | 6-7.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0008 | Velan | CF8M | 6 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Air Eliminator Tank | JVS-1730-AELT-0001 | ME Industries | AEV366300S150RH | 10234 | 250 gl | x | 3-10.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Pressure Vacuum Vent | JVS-1730-TPVVT-0001 | Groth | 1202B-02-115-V02 | 1006231-01-16 | x | 8-9.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Point Sensor (wet) | JVS-1730-PSWET-0001 | SOR | 701K1-U-P7-C-FM | 100604481 | x | 8-9.13.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Point Sensor (wet) | JVS-1730-PSWET-0002 | SOR | 701K1-U-P7-C-FM | 100604482 | x | 8-9.13.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0002 | Taylor | 8200.00 | 005029-2 | 50 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0004 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0009 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0010 | Velan | CF8M | 6 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Flow Switch | JVS-1730-PRTR-0001 | SOR | 902C-F7C-C-A4-N7-WV | 100604477 | x | x | 6-7.3 | See Mfr. Req. | Repairs shall be performed by SO. | Requires LOTO and System placed out-of-service | ||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0003 | Taylor | 8200 | 004420-22 | 40 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0005 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0011 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0012 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0013 | Velan | CF8M | 1/2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Pressure Gauge | JVS-1730-PVGA-0001 | USG | (-30 - 60 psi) / 1/2 in. NPT | x | x | x | 6-7.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Vertical Inline Pump | JVS-1730-VILP-0001 | Clyde Union | CM100115B-1 | 300 gpm | x | x | 3-8.1.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Electric Motor | JVS-1730-ELEMT-0001 | Baldor Reliance | B551905-010001KN | 25 HP | x | x | x | 9-1.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0014 | Velan | CF8M | 1/2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Pressure Gauge | JVS-1730-PVGA-0002 | Palmer | (0 -160 psi) / 1/2 in. NPT | x | x | x | 6-7.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0015 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Control Valve | JVS-1730-GSCVL-0001 | Claval | 4 in. | x | 4-3.2.1 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Control Valve | JVS-1730-GSCVL-0002 | Claval | 2 in. | x | 4-3.2.1 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0016 | Velan | CF8M | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Plug Valve | JVS-1730-NPLVL-0001 | Velan | 2 in. | x | x | 6-6.2.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0017 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0018 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0019 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0004 | Taylor | 8200 | 004420-14 | 125 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0006 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0020 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ball Valve | JVS-1730-BLVL-0021 | Velan | CF8M | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Double Block and Bleed Valve | JVS-1730-DBBVL-0001 | General | 211RF | 111737480003 | 4 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ground Verfication System | JVS-1730-GRVS-0001 | Scully | ST47ELK | x | 9-5 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Ground Reel | JVS-1730-STGS-0001 | Anetek | x | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 1 | Receiving | Static Grounding System | JVS-1730-STGS-0001 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Offloading Fuel Hose | JVS-1730-OLHS-0003 | 4 in. x 10 ft. | x | x | 3-9.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Offloading Fuel Hose | JVS-1730-OLHS-0004 | 4 in. x 10 ft. | x | x | 3-9.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0022 | Velan | 996-010 | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0023 | Velan | 996-010 | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0007 | 4 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0008 | 4 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0024 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0025 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0005 | Taylor | 8200 | 004420-28 | 40 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0009 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0026 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0027 | Velan | CF8M | 3/8 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0028 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Basket Strainer | JVS-1730-BSTR-0002 | Titan | 6 in. | x | 3-6.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Differential Pressure Guage | JVS-1730-DPGA-0002 | Gammon | 534-30 | x | x | x | 6-7.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0029 | Velan | CF8M | 6 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Air Eliminator Tank | JVS-1730-AELT-0002 | ME Industries | AEV366300S150RH | 10235 | 250 gl | x | 3-10.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Pressure Vacuum Vent | JVS-1730-TPVVT-0002 | Groth | 1202B-02-115-V02 | 1006231-01-6 | x | 8-9.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Point Sensor (wet) | JVS-1730-PSWET-0003 | SOR | 701K1-U-P7-C-FM | 100604484 | x | 8-9.13.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Point Sensor (wet) | JVS-1730-PSWET-0004 | SOR | 701K1-U-P7-C-FM | 100604483 | x | 8-9.13.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0006 | Taylor | 8200 | 005029-1 | 50 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0010 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0030 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0031 | Velan | CF8M | 6 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Flow Switch | JVS-1730-PRTR-0002 | SOR | 902C-F7C-C-A4-N7-WV | 100604479 | x | x | 6-7.3 | See Mfr. Req. | Repairs shall be performed by SO. | Requires LOTO and System placed out-of-service | ||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0007 | Taylor | 8200 | 004420-23 | 40 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0011 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0032 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0033 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0034 | Velan | CF8M | 1/2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Pressure Gauge | JVS-1730-PVGA-0003 | Palmer | (-30 - 60 psi) / 1/2 in. NPT | x | x | x | 6-7.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Vertical Inline Pump | JVS-1730-VILP-0002 | Clyde Union | CM100115B-2 | 300 gpm | x | x | 3-8.1.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Electric Motor | JVS-1730-ELEMT-0002 | Baldor Reliance | B551905-010002KN | 25 HP | x | x | x | 9-1.7 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0035 | Velan | CF8M | 1/2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Pressure Gauge | JVS-1730-PVGA-0004 | Palmer | (0 -160 psi) / 1/2 in. NPT | x | x | x | 6-7.1 | See Mfr. Req. | Per PWS Touch-up Coating Repair | |||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0036 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Control Valve | JVS-1730-GSCVL-0003 | Claval | 4 in. | x | 4-3.2.1 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Control Valve | JVS-1730-GSCVL-0004 | Claval | 2 in. | x | 4-3.2.1 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0037 | Velan | CF8M | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Plug Valve | JVS-1730-NPLVL-0002 | Velan | 2 in. | x | x | 6-6.2.2 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0038 | Velan | CF8M | 2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0039 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0040 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Thermal Pressure Relief Valve | JVS-1730-PRVL-0008 | Taylor | 8200 | 004420-13 | 125 psig. | x | x | 6-6.3 | See Mfr. Req. | Maintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves. Per PWS Touch-up Coating Repair | Requires LOTO and System placed out-of-service | |||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Sight Flow Indicator | JVS-1730-SFND-0012 | Visi-Flo | 1 in. | 6-12.3 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0041 | Velan | CF8M | 1 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ball Valve | JVS-1730-BLVL-0042 | Velan | CF8M | 4 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Double Block and Bleed Valve | JVS-1730-DBBVL-0002 | General | 211RF | 111737480004 | 4 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ground Verfication System | JVS-1730-GRVS-0002 | Scully | ST47ELK | x | 9-5 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Ground Reel | JVS-1730-STGS-0002 | Anetek | x | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||
| 1730 | 1730 | 1175848 | Offloading Station 2 | Receiving | Static Grounding System | JVS-1730-STGS-0002 | x | 9-1.6.2 | See Mfr. Req. | This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan. | Requires LOTO and System placed out-of-service | ||||||||||
| 1720 | 1720 | 1175847 | Fillstand 1 | Fillstand 1 | Double Block and Bleed Valve | JVS-1720-DBBVL-0001 | General | 211RF | 111737480006 | 4 in. | x | x | 6-6.2.5 | See Mfr. Req. | Per PWS Touch-up Coating Repair | ||||||
| 1720 | 1720 | 1175847 | Fillstand 1 | Fillstand 1 | Ball Valve | JVS-1720-BLVL-0001 | Velan | CF8M | 1/2 in. | x | 6-6.2.4 | See Mfr. Req. | Per PWS Touch-up Coating Repair |