This file is a detailed Facility Maintenance Plan for Patrick Air Force Base in Florida, specifically Appendix K, which provides comprehensive maintenance requirements for multiple fuel storage and distribution facilities. The document covers 25 facilities including various aboveground storage tanks (ASTs) for Jet A, Diesel, and Mogas fuels, with facility numbers ranging from 611-656, detailing specific maintenance needs for components like ball valves, thermal pressure relief valves, pumps, electric motors, filter separators, and associated equipment.

The maintenance plan includes intricate details for each facility, specifying unique identifiers, manufacturer requirements, system availability considerations, and maintenance procedures. Key facilities include the Central Storage area (Facilities 626-634), North Storage area (Facilities 612-623), South Storage area (Facilities 643-645), a Military Service Station (Facility 656), and an E-85 Tank area (Facility 649). Each facility section provides extensive information on specific components, their technical specifications, maintenance requirements, and special considerations such as lock-out/tag-out procedures, system out-of-service protocols, and recommended maintenance intervals. The document appears to be part of a broader maintenance contract supporting fuel infrastructure at Patrick Air Force Base.

View the file

Other files

File Type Posted
Moody AFB GA (MDY)-FMP.xlsx XLSX spreadsheet
Shaw AFB SC (SHW)-FMP.xlsx XLSX spreadsheet
Attachment 6 Draft QASP.pdf PDF
Attachment 4 - PPQ Sample (3).pdf PDF
DFSP Charleston SC (CHS)-FMP.xlsx XLSX spreadsheet
CDRL Set 16 60-64.pdf PDF
Attachment 3 Technical Evaluation Form.pdf PDF
Savannah ANG GA (SAG)-FMP.xlsx XLSX spreadsheet
Savannah-Hilton Head GA (SHH)-FMP.xlsx XLSX spreadsheet
Attachment 1 Performance Work Statement SAD-AF2.pdf PDF
Fuels SAD-AF2 Draft Solicitation W912DY26RA017.pdf PDF
Attachment 5 Instructions and Evaluation Factors.pdf PDF
CDRL Set 1 1-4.pdf PDF
CDRL Set 12 45-48.pdf PDF
CDRL Set 5 17-20.pdf PDF
CDRL Set 10 37-40.pdf PDF
CDRL Set 17 65-67.pdf PDF
CDRL Set 11 41-44.pdf PDF
Seymour Johnson AFB NC (SMJ)-FMP.xlsx XLSX spreadsheet
Joint Base Charleston SC (JBC)-FMP.xlsx XLSX spreadsheet
2.1 Appendix A - Attachment 1 Service Order Form-v11.5_20251027.xlsx XLSX spreadsheet
Attachment 8 Small Business Participation Plan Template.pdf PDF
Stanly County Airport NC (WEF)-FMP.xlsx XLSX spreadsheet
Glynco ANG Station GA (JAS)-FMP.xlsx XLSX spreadsheet
Cape Canaveral AFS FL (DBE)-FMP.xlsx XLSX spreadsheet
Attachment 7 Pricing Worksheet SAD-AF2.xlsx XLSX spreadsheet
Charleston AFB SC (CAF)-FMP.xlsx XLSX spreadsheet
CDRL Set 13 49-52.pdf PDF
CDRL Set 4 13-16.pdf PDF
CDRL Set 7 25-28.pdf PDF
CDRL Set 8 29-32.pdf PDF
CDRL Set 14 53-56.pdf PDF
12.0 PWS Appendix K SAD-AF2 Real Property Data SAD-AF2 Final 20250225.xlsx XLSX spreadsheet
Jacksonville IAP FL (JVL)-FMP.xlsx XLSX spreadsheet
Robins AFB GA (ROB-TBD)-FMP.xlsx XLSX spreadsheet
CDRL Set 15 57-60.pdf PDF
CDRL Set 2 5-8.pdf PDF
CDRL Set 3 9-12.pdf PDF
CDRL Set 9 33-36.pdf PDF
CDRL Set 6 21-24.pdf PDF
Douglas MAP ANG NC (DGL)-FMP.xlsx XLSX spreadsheet
Dobbins ARB GA (DOB)-FMP.xlsx XLSX spreadsheet
McEntire ANG SC (MNT)-FMP.xlsx XLSX spreadsheet
Attachment 2 Sample Service Order (Appendix A - Attachment 1 Service Order Form).xlsx XLSX spreadsheet
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationInstallation NamePatrick AFB
DLA Site CodePAT
Hours of Operation0700-2300
Address1224 S Patrick Dr, Patrick AFB, FL 32925
ContractContractorWeston Solutions
Contract #47QSHA18D0016 / W912DY20F0474
Local POCsQAE Phone321-494-7890
QAE Emailjames.kelley.13@us.af.mil
Alt QAE Phone321-494-5942
Alt QAE Emailcharlie.roy@us.af.mil
DLA/SCP POCsDLA PM Phone571-767-8133
DLA PM Emailpatricia.beyer@dla.mil
SCP PM Phone571-767-0726
SCP PM Emaildavid.king@dal.mil
Contractor POCsContractor PM Phone770-325-7907
Contractor PM Emailjohn.deahl@westonsolutions.com
Contractor QC Phone757-819-5131
Contractor QC Emailmatt.altekruse@westonsolution.com
Contractor SM Phone229-415-3445
Contractor SM Emailbrandon.wells@westonsolutions.com
USACE POCsUSACE PM Phone256-895-1067
USACE PM Emailrichard.a.resler@usace.army.mil
USACE COR Phone256-895-1745
USACE COR Emailmoon.h.hemm@usace.army.mil
USACE PE Phone256-895-1947
USACE PE Emailcorey.a.asher@usace.army.mil
USACE KO Phone256-895-1117
USACE KO Emailaquiller.e.cole@usace.army.mil

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

mailto:brandon.wells@westonsolutions.commailto:john.deahl@westonsolutions.commailto:matt.altekruse@westonsolution.commailto:james.kelley.13@us.af.milmailto:charlie.roy@us.af.milmailto:richard.a.resler@usace.army.milmailto:aquiller.e.cole@usace.army.milmailto:corey.a.asher@usace.army.milmailto:moon.h.hemm@usace.army.mil General Facility Description

FAC 611-622 25K Gallon AST
FAC 627 Jet A Pumphouse
FAC 626 16K Gallon AST
FAC 633 16K Gallon AST
FAC 634 30K Gallon AST
FAC 623 Pumphouse Servicing 611-622 ASTs
FAC 656 Military Service Station

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Include a general facility description for the installation.

Communication Plan

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, etc.

Safety

Appendix K - Facility Maintenance Plan

&P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

APPENDIX J - EXISTING MAINTENANCE SCHEDULES
#Installation NameSite NameDLA Site CodeRPSUIDLocationCitySTExisting Max Freq1st Quarter
Contract PoP 14 Aug 20 -13 Aug 212nd Quarter3rd Quarter4th Quarter
Aug-24Sep-24Oct-24Nov-24Dec-24Jan-25Feb-25Mar-25Apr-25May-25Jun-25Jul-25
1SI CAPE CANAVERALCape Canaveral AFS Site #1DBE1555Cape Canaveral AFSCape CanaveralFL1Annual

2/24-2/25 2 SI PATRICK Patrick AFB PAT 3143 Patrick AFB Cocoa Beach FL 4 Annual 2/17-2/21

3JACKSONVILLE IAPJacksonville IAP Site #1JVL2390Jacksonville ANGJacksonvilleFL1SA1/Q1
10/16-10/18Q2
1/21-1/22A/SA2/Q3
4/22-4/25Q4

7/23-7/24 4 DOBBINS ARB Dobbins ARB (ID 192) DOB 1660 Dobbins ARB, GA (ID 192) Marietta GA 1 MC Annual 4/7-4/10

5ROBINS AFBRobins Air Force Base Site 1ROB3219Robins ANG, GAWarner RobinsGA4SA1/Q1
8/28-8/30Q2
11/21-11/22A/SA2/Q3
3/3-3/6Q4

6/3-6/4

6SI MOODYMoody AFBMDY3020Moody AFB, GAValdostaGA4Q1
9/16-9/18A-SA1-Q2
12/02-12/11Q3
3/24-3/26SA2-Q4

6/17-6/20 7 SAVANNAH HILTON HEAD IAP Glynco ANG Station JAS 2124 Glynco Air National Guard Station Brunswick GA 1 Annual 12/16

8SAVANNAH HILTON HEAD IAPSavannah ANG (IAP ID 107)SAG17105Savannah ANG, GA (IAP ID 107)SavannahGA1Annual
12/17-12/19MC
9SAVANNAH HILTON HEAD IAPSavannah/Hilton Head IAP Site #3SHH3358SAVANNAH/HILTON HEAD IAP SITE #5SavannahGA4Annual

12/20

10JB CHARLESTONDFSP CharlestonCHS1580DFSP CharlestonCharlestonSC1SA1/Q1
8/19-8/23Q2
11/13-11/15A/SA2/Q3
2/3-2/21Q4

5/06-5/08 11 JB CHARLESTON Charleston AFB (ID 26) - Joint Base CAF 1579 Charleston AFB, SC (ID 26) - Joint Base Charleston SC 1 Annual 11/18-11/22

12JB CHARLESTONJoint Base Charleston NWSJBC213JOINT BASE CHARLESTON NAVAL WEAPONS STATIONCharlestonSC4Q1
9/10SA1-Q2
12/10-12/11Q3
3/11-3/12A-SA2-Q4

6/18-6/20 13 MCENTIRE JOINT NATIONAL GUARD BASE McEntire ANG (ID 158) MNT 2793 McEntire ANG, SC (ID 158) Eastover SC 1 MC Annual 4/14-4/16 14 SHAW AFB Shaw AFB (ID 55) SHW 3269 Shaw AFB, SC (ID 55) Sumter SC 1 Annual 4/17-4/24

15CHARLOTTE IAPDouglas MAP ANG (ID 146)DGL1661Douglas MAP ANG, NC (ID 146)CharlotteNC1Annual
11/04-11/06MC
16CHARLOTTE IAPStanly County AirportWEF3312Stanly County AirportNew LondonNC1Annual

11/7 17 SEYMOUR JOHNSON AFB Seymour Johnson AFB (ID 56) SMJ 3268 NC Goldsboro NC 1 MC Annual 6/09-6/17

Task Matrix

Special Considerations
EBS Facility #iNFADS Facility #ACES/ NEXGEN Facility #Real Property Unique IdentifierFacility NameOperational AreaComponent TypeCUIDMakeModelSerialCapacity/SizeQSAUFC Section ReferenceManufacturer RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
627627530146Central StorageOffloading SkidSight Flow IndicatorPAT-627-SFND-00014"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidSight Flow IndicatorPAT-627-SFND-00024"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidSight Flow IndicatorPAT-627-SFND-00034"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidSight Flow IndicatorPAT-627-SFND-00044"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidSight Flow IndicatorPAT-627-SFND-00054"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0001Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0002Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0003Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0004Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0005Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidThermal Pressure Relief ValvePAT-627-PRVL-0001Kunckle3/4" to 1"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBasket StrainerPAT-627-BSTR-0001Titan6"x3-6.4See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidDifferential Pressure GuagePAT-627-DPGA-00010-15 psidxxx6-7.4See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0006Flo-Tite6"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidAir Eliminator TankPAT-627-AELT-0001x3-10.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0007Flo-Tite6"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidPressure/Vaccum GaugePAT-627-PVGA-00010-300 PSIxxx6-7.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidCentrifugal PumpPAT-627-CENP-0001RUHR Pumping600 gpmxx3-8.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidElectric MotorPAT-627-ELEMT-0001Crown-TritonHLS2B6SR135Bxxx9-1.7See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidPressure/Vaccum GaugePAT-627-PVGA-00020-300 PSIxxx6-7.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidPositive Displacement MeterPAT-627-PDMT-0001Liquid ControlsM-60-1657202600 gpmx3-7.1See Mfr. O&MCalibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation.Requires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidThermal Pressure Relief ValvePAT-627-PRVL-0002Kunklexx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0008Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-0009Flo-Tite4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidDouble Block and Bleed ValvePAT-627-DBBVL-0001Franklin4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidGeneral System Control ValvePAT-627-GSCVL-0001OCV1517E100934"xx4-3.2.1See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidGeneral System Control ValvePAT-627-GSCVL-0002OCV108-24653311V4"xx4-3.2.1See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidBall ValvePAT-627-BLVL-00104"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading SkidStatic Grounding SystemPAT-627-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-00114"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-00123"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandFilter SeparatorPAT-627-FLSP-0001FacetVCS64323614447600 gpmx3-6.2See Mfr. O&MRoutine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order.
Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
627627530146Central StorageFillstandDifferential Pressure GuagePAT-627-DPGA-0002Gammon534-300-300 psixxx6-7.4See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandThermal Pressure Relief ValvePAT-627-PRVL-0003Taylor8200034047-2275 psigxx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageFillstandAutomatic Air VentPAT-627-AAVT-0001Armstrong3/4"x3-10.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandFilter Separator Control ValvePAT-627-FSCVL-0001Cla-Val6"xx4-4.2.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandThermal Pressure Relief ValvePAT-627-PRVL-0004Taylor7700030350-2150 psigxx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-00013Flo-Tek1"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-00014Flo-Tek1"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-00015Flo-Tek4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandPositive Displacement MeterPAT-627-PDMT-0002Total Control Systems700-45SPA2AG820129600 gpmx3-7.1See Mfr. O&MCalibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation.Requires LOTO and System Out-of-Service
627627530146Central StorageFillstandThermal Pressure Relief ValvePAT-627-PRVL-0005Taylor7700030350-5150 psigxx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-0016Flo-Tek1"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandBall ValvePAT-627-BLVL-0017Flo-Tek1"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandFixed PantographPAT-627-FXPNT-0001Cla-Val3"x4-7.1.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandFueling NozzlePAT-627-FLNZ-0001Cla-CalD-24-7.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandStatic Grounding SystemPAT-627-STGS-0002x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageFillstandElectronic Overfill Protection SystemPAT-627-EOPS-0001ScullyOGVx9-6See Mfr. O&M
627627530146Central StorageOffloading HeaderBall ValvePAT-627-BLVL-00184"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading HeaderBall ValvePAT-627-BLVL-00194"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading HeaderSight Flow IndicatorPAT-627-SFND-00064"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageOffloading HeaderSight Flow IndicatorPAT-627-SFND-00074"6-12.3See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageRTB HeaderDouble Block and Bleed ValvePAT-627-DBBVL-0002General4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageOff/RTB HeaderStatic Grounding SystemPAT-627-STGS-0003x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageRTB HeaderFuel Truck Containment AreaPAT-627-FTRKCS-0001xx11-1.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00204"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00214"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00224"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00234"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00244"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00254"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00264"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00283"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseBall ValvePAT-627-BLVL-00293"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StoragePump HousePressure Vacuum GaugePAT-627-PVGA-0003(-30)-150 psixxx6-7.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HousePressure Vacuum GaugePAT-627-PVGA-0004(-30)-150 psixxx6-7.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HousePressure Vacuum GaugePAT-627-PVGA-0005(-30)-150 psixxx6-7.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HousePressure Vacuum GaugePAT-627-PVGA-0006(-30)-150 psixxx6-7.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00071"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00081"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00091"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00101"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00111"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00121"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseThermal Pressure Relief ValvePAT-627-PRVL-00131"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StoragePump HouseCentrifugal PumpPAT-627-CENP-0002xx3-8.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseElectric MotorPAT-627-ELEMT-0002Baldor RelianceB85293922171006034715 HPxxx9-1.7See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseCentrifugal PumpPAT-627-CENP-0003xx3-8.1See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseElectric MotorPAT-627-ELEMT-0003xxx9-1.7See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseMotor ControlPAT-627-MTRCT-0001xx9-1.4See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseEFSO SystemPAT-627-EFSO-0001x7-16See Mfr. O&M
627627530146Central StoragePump HouseEFSO SystemPAT-627-EFSO-0002x7-16See Mfr. O&M
627627530146Central StoragePump HouseEFSO Signs & MarkingsPAT-627-SIGN-0001x2-7See Mfr. O&M
627627530146Central StoragePump HouseEFSO Signs & MarkingsPAT-627-SIGN-0002x2-7See Mfr. O&M
627627530146Central StoragePump HouseMotor ControlPAT-627-MTRCT-0002xx9-1.4See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StoragePump HouseEmergency Eyewash/ShowersPAT-627-EMEWSH-0001xxx11-3See Mfr. O&M
627627530146Central StorageReceipt Filter AreaStatic Grounding SystemPAT-627-STGS-0004x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaBall ValvePAT-627-BLVL-00304"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaDouble Block and Bleed ValvePAT-627-DBBVL-00034"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaThermal Pressure Relief ValvePAT-627-PRVL-00141"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaThermal Pressure Relief ValvePAT-627-PRVL-00151"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaBall ValvePAT-627-BLVL-0031FLO-Tek4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaBall ValvePAT-627-BLVL-0032FLO-Tek4"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaFilter SeparatorPAT-627-FLSP-0002600 GPMx3-6.2See Mfr. O&MRoutine coalescer changes shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Coalescer cartridge changes required due to a repair, out of sequence, or other circumstance beyond normal system operation shall be performed by service order.
Coalescer cartridges will be provided by the Government. Routine separator cartridge replacement shall be performed as part of the FFP maintenance activities and priced under CLIN 0006 for Base Year and OY3. Separator cartridges will be provided by the Government. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaDifferential Pressure GuagePAT-627-DPGA-0003Gammon534-300-30 psixxx6-7.4See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaThermal Pressure Relief ValvePAT-627-PRVL-0016xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaAutomatic Air VentPAT-627-AAVT-0002Armstrong3/4"x3-10.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaFilter Separator Control ValvePAT-627-FSCVL-0002Cla-Val6"xx4-4.2.2See Mfr. O&MRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaThermal Pressure Relief ValvePAT-627-PRVL-00171"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaDouble Block and Bleed ValvePAT-627-DBBVL-00044"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageReceipt Filter AreaBall ValvePAT-627-BLVL-00334"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
627627530146Central StorageCentral StorageSigns and MarkingsPAT-627-SIGN-0003x2-7See Mfr. O&M
627627530146Central StorageCentral StorageConcrete Berm Walls and FloorsPAT-627-CCBWF-0001x8-10.2See Mfr. O&M
627627530146Central StorageCentral StorageFencePAT-627-FENC-0001X11-1.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
627627530146Central StorageCentral StorageGatePAT-627-GATE-0001x11-1.1See Mfr. O&MPer PWS Joint Sealant and Crack Repair
626626530145Central StorageJet A TankExternal High Level Shutoff ValvePAT-626-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankBall ValvePAT-626-BLVL-00011"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankBall ValvePAT-626-BLVL-00021"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankThermal Pressure Relief ValvePAT-626-PRVL-0001Taylor8200070996-175 psixx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
626626530145Central StorageJet A TankDouble Block and Bleed ValvePAT-626-DBBVL-00014"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankMagnetostrictive Probe (ATG)PAT-626-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankTank Pressure/Vacuum VentPAT-626-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankAboveground Shop Fab TanksPAT-626-AGSFP-000116K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankProduct Saver TankPAT-626-PRDST-0002x8-9.10See Mfr. O&MRequires LOTO and System Out-of-Service
626626530145Central StorageJet A TankSigns and MarkingsPAT-626-SIGN-0001x2-7See Mfr. O&M
626626530145Central StorageJet A TankStatic Grounding SystemPAT-626-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankBall ValvePAT-633-BLVL-00014"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankBall ValvePAT-633-BLVL-00024"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankExternal High Level Shutoff ValvePAT-633-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankThermal Pressure Relief ValvePAT-633-PRVL-00011"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
633633530152Central StorageJet A TankDouble Block and Bleed ValvePAT-633-DBBVL-00013"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankThermal Pressure Relief ValvePAT-633-PRVL-00021"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
633633530152Central StorageJet A TankMagnetostrictive Probe (ATG)PAT-633-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankTank Pressure/Vacuum VentPAT-633-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankAboveground Shop Fab TanksPAT-633-AGSFP-000116 K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
633633530152Central StorageJet A TankSigns and MarkingsPAT-633-SIGN-0001x2-7See Mfr. O&M
633633530152Central StorageJet A TankStatic Grounding SystemPAT-633-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankBall ValvePAT-634-BLVL-00014"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankExternal High Level Shutoff ValvePAT-634-EHLSVL-0001OCV4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankDouble Block and Bleed ValvePAT-634-DBBVL-0001xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankDouble Block and Bleed ValvePAT-634-DBBVL-00023"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankAboveground Shop Fab TanksPAT-634-AGSFP-000130K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankTank Pressure/Vacuum VentPAT-634-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankSigns and MarkingsPAT-634-SIGN-0001x2-7See Mfr. O&M
634634530153Central StorageJet A TankStatic Grounding SystemPAT-634-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
634634530153Central StorageJet A TankMagnetostrictive Probe (ATG)PAT-634-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankAboveground Shop Fab TanksPAT-612-AGSFP-000125.9K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankBall ValvePAT-612-BLVL-00011"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankBall ValvePAT-612-BLVL-00021"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankThermal Pressure Relief ValvePAT-612-PRVL-0001Taylor8200065769-175 psixx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
612612503130North StorageDiesel TankExternal High Level Shutoff ValvePAT-612-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankDouble Block and Bleed ValvePAT-612-DBBVL-0001Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankBall ValvePAT-612-BLVL-0003x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankDouble Block and Bleed ValvePAT-612-DBBVL-0002Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankBall ValvePAT-612-BLVL-00041"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankBall ValvePAT-612-BLVL-00053"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankBall ValvePAT-612-BLVL-00062"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankThermal Pressure Relief ValvePAT-612-PRVL-0002Taylor8200065301-275 psixx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
612612503130North StorageDiesel TankTank Pressure/Vacuum VentPAT-612-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankMagnetostrictive Probe (ATG)PAT-612-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
612612503130North StorageDiesel TankStilling WellPAT-612-STGW-00018-9.17See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
612612503130North StorageDiesel TankSigns and MarkingsPAT-612-SIGN-0001x2-7See Mfr. O&M
612612503130North StorageDiesel TankStatic Grounding SystemPAT-612-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankAboveground Shop Fab TanksPAT-614-AGSFP-000125.9K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankBall ValvePAT-614-BLVL-00011"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankBall ValvePAT-614-BLVL-00021"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankThermal Pressure Relief ValvePAT-614-PRVL-0001Taylor8200065769-275 psixx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
614614503132North StorageDiesel TankExternal High Level Shutoff ValvePAT-614-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankDouble Block and Bleed ValvePAT-614-DBBVL-0001Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankBall ValvePAT-614-BLVL-0003x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankDouble Block and Bleed ValvePAT-614-DBBVL-0002Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankBall ValvePAT-614-BLVL-00041"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankBall ValvePAT-614-BLVL-00053"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankBall ValvePAT-614-BLVL-00062"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankThermal Pressure Relief ValvePAT-614-PRVL-0002Taylor8200065301-175 psixx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
614614503132North StorageDiesel TankTank Pressure/Vacuum VentPAT-614-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankMagnetostrictive Probe (ATG)PAT-614-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
614614503132North StorageDiesel TankStilling WellPAT-614-STGW-00018-9.17See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
614614503132North StorageDiesel TankSigns and MarkingsPAT-614-SIGN-0001x2-7See Mfr. O&M
614614503132North StorageDiesel TankStatic Grounding SystemPAT-614-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankAboveground Shop Fab TanksPAT-618-AGSFP-000125.9K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankExternal High Level Shutoff ValvePAT-618-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankDouble Block and Bleed ValvePAT-618-DBBVL-0001Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankDouble Block and Bleed ValvePAT-618-DBBVL-0002Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankTank Pressure/Vacuum VentPAT-618-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankMagnetostrictive Probe (ATG)PAT-618-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
618618503136North StorageJet A TankStilling WellPAT-618-STGW-00018-9.17See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
618618503136North StorageJet A TankSigns and MarkingsPAT-618-SIGN-0001x2-7See Mfr. O&M
618618503136North StorageJet A TankStatic Grounding SystemPAT-618-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankAboveground Shop Fab TanksPAT-622-AGSFP-000125.9K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankExternal High Level Shutoff ValvePAT-622-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankDouble Block and Bleed ValvePAT-622-DBBVL-0001Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankDouble Block and Bleed ValvePAT-622-DBBVL-0002Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankBall ValvePAT-622-BLVL-00011"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankThermal Pressure Relief ValvePAT-622-PRVL-0011"xx6-6.3See Mfr. O&MMaintenance procedure shall include process to verify that the valve has properly reseated after all maintenance activities are performed on pressure relief valves or thermal and pressure relief valves.Requires LOTO and System Out-of-Service
622622503141North StorageJet A TankTank Pressure/Vacuum VentPAT-622-TPVVT-0001x8-9.3See Mfr. O&MRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankMagnetostrictive Probe (ATG)PAT-622-MRPRB-0001Veeder-Rootxx8-9.8.2See Mfr. O&MRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankStilling WellPAT-622-STGW-00018-9.17See Mfr. O&MThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Requires LOTO and System Out-of-Service
622622503141North StorageJet A TankSigns and MarkingsPAT-622-SIGN-0001x2-7See Mfr. O&M
622622503141North StorageJet A TankStatic Grounding SystemPAT-622-STGS-0001x9-1.6.2See Mfr. O&MRequires LOTO and System Out-of-Service
622622503141North StorageJet A TankProduct Saver TankPAT-622-PRDST-0001x8-9.10See Mfr. O&MRequires LOTO and System Out-of-Service
616616503134North StorageNorth StorageAboveground Shop Fab TanksPAT-616-MDEAC-000125.9K Gallonx12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageExternal High Level Shutoff ValvePAT-616-MDEAC-0002Cla-Val4"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageDouble Block and Bleed ValvePAT-616-MDEAC-0003Tru-Seal4"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageDouble Block and Bleed ValvePAT-616-MDEAC-0004Tru-Seal4"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageBall ValvePAT-616-MDEAC-00011"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageTank Pressure/Vacuum VentPAT-616-MDEAC-0006x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageMagnetostrictive Probe (ATG)PAT-616-MDEAC-0007Veeder-Rootx12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageStilling WellPAT-616-MDEAC-0008x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
616616503134North StorageNorth StorageSigns and MarkingsPAT-616-MDEAC-0009x12-5See Mfr. O&MRepairs shall be performed by SO.
616616503134North StorageNorth StorageStatic Grounding SystemPAT-616-MDEAC-0010x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageAboveground Shop Fab TanksPAT-616-MDEAC-000125.9K Gallonx12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageExternal High Level Shutoff ValvePAT-616-MDEAC-0002Cla-Val4"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageDouble Block and Bleed ValvePAT-616-MDEAC-0003Tru-Seal4"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageDouble Block and Bleed ValvePAT-616-MDEAC-0004Tru-Seal4"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageBall ValvePAT-620-MDEAC-00011"x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageTank Pressure/Vacuum VentPAT-616-MDEAC-0006x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageMagnetostrictive Probe (ATG)PAT-616-MDEAC-0007Veeder-Rootx12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageStilling WellPAT-616-MDEAC-0008x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
620620503139North StorageNorth StorageSigns and MarkingsPAT-616-MDEAC-0009x12-5See Mfr. O&MRepairs shall be performed by SO.
620620503139North StorageNorth StorageStatic Grounding SystemPAT-616-MDEAC-0010x12-5See Mfr. O&MRepairs shall be performed by SO.Requires LOTO and System Out-of-Service
621621503140North StorageJet A TankAboveground Shop Fab TanksPAT-621-AGSFP-000125.9K Gallonx8-5.1See Mfr. O&MRequires LOTO and System Out-of-Service
621621503140North StorageJet A TankExternal High Level Shutoff ValvePAT-621-EHLSVL-0001Cla-Val4"x8-9.6.1See Mfr. O&MRequires LOTO and System Out-of-Service
621621503140North StorageJet A TankDouble Block and Bleed ValvePAT-621-DBBVL-0001Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
621621503140North StorageJet A TankBall ValvePAT-621-BLVL-0001x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
621621503140North StorageJet A TankDouble Block and Bleed ValvePAT-621-DBBVL-0002Tru-Seal4"xx6-6.2.5See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service
621621503140North StorageJet A TankBall ValvePAT-621-BLVL-00024"x6-6.2.4See Mfr. O&MPer PWS Touch-up Coating RepairRequires LOTO and System Out-of-Service

This is the start of the file's text. The full file is on GovTribe.