This document appears to be Attachment 18 - Replacement Drawing TO-01 TELECOM LEGEND, which provides legend information and general notes for a telecommunications infrastructure project at Joint Base Lewis-McChord (JBLM) in Washington.

The key details include:

  • Telecommunications abbreviations, symbols, and standards references
  • General notes for the project, including requirements for telecommunications manholes, ductbanks, cabling, labeling, testing, and phasing
  • The project involves installing new outside plant (OSP) telecommunications pathways and cables, and transitioning existing cables to the new alignment

The related federal contract opportunity is Solicitation Number W912DW24B0Y1Y for the "Repair Barnes Blvd. Bridge (J84004)" project at JBLM. This is an Invitation for Bid (IFB) set aside for 8(a) small businesses, with a NAICS code of 237310 - Highway, Street, and Bridge Construction. The estimated contract value is between $7,500,000 and $15,000,000.

View the file

Other files

File Type Posted
OF1419 Abstract of Bids for Barnes Blvd. Bridge Repairs (Signed).pdf PDF
Attachment 19 - Replacement Drawing TO-02 TELECOM SITE PLAN in Attachment 2.pdf PDF
W912DW24B0Y1Y - Amendment 0006.pdf PDF
W912DW24B0Y1Y Amendment 0004.pdf PDF
Attachment 14 - Replacement Drawing CU102 NEC Profile Details in Attachment 2 (Rev 1).pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd. - IFB Amendment 0006.pdf PDF
W912DW24B0Y1Y Amendment 0003.pdf PDF
W912DW24B0Y1Y Amendment 0002.pdf PDF
Attachment 20 - Replacement Drawing CU101 UTILITIES PLAN in Attachment 2.pdf PDF
W912DW24B0Y1Y Amendment 0001.pdf PDF
Attachment 7 - Barnes Blvd Temporary Bridge Detour Requirements and Details (Rev 1).pdf PDF
Attachment 1 - SPECIFICATIONS Revised Barnes Blvd Bridge McChord IFC 2024-03-15.pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd. - IFB Amendment 0005.pdf PDF
W912DW24B0Y1Y Amendment 0005.pdf PDF
Attachment 1 - SPECIFICATIONS Revised Barnes Blvd Bridge McChord IFC 2024-03-06.pdf PDF
W912DW24B0Y1Y Amendment 0004.pdf PDF
Attachment 16 - Replacement Drawing S 135 Utility Bridge Typical Section in Attachment 2 (Rev 1).pdf PDF
Attachment 17 - Replacement Drawing S-132 Pedestrian Rail Detail 1 in Attachment 2 (Rev 1).pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd - IFB Amendment 0004.pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd - IFB Amendment 0003.pdf PDF
W912DW24B0Y1Y Amendment 0003.pdf PDF
Attachment 17 - Replacement Drawing S-132 Pedestrian Rail Detail 1 in Attachment 2.pdf PDF
Attachment 16 - Replacement Drawing S-135 Utility Bridge Typical Section in Attachment 2.pdf PDF
W912DW24B0Y1Y Amendment 0002.pdf PDF
Attachment 15 - WADOT Aluminum Pedestrian Rail Details.pdf PDF
Attachment 1 - SPECIFICATIONS Revised Barnes Blvd Bridge McChord IFC 2024-02-21.pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd - IFB Amendment 0002.pdf PDF
Site Visit Sign-In Sheet - Repair Barnes Bridge.pdf PDF
Attachment 14 - Replacement Drawing CU102 NEC ProfileDetails in Attachment 2.pdf PDF
Attachment 10 - Utility Contacts Fees Responsiblities (Rev 01).pdf PDF
W912DW24B0Y1Y Amendment 0001.pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd - IFB Amendment 0001.pdf PDF
Attachment 1 - SPECIFICATIONS Revised Barnes Blvd Bridge McChord IFC 2024-02-09.pdf PDF
Attachment 3 - 2023-11-14 McChord Field Bridges Stormwater Drainage Plan (Rev 1).pdf PDF
Attachment 1 - SPECIFICATIONS Revised Barnes Blvd Bridge McChord IFC.pdf PDF
Attachment 5 - Stream Work to follow Nationwide USACE Permit 2021-NWP14-Enclosure-20220511.pdf PDF
Attachment 2 - 2023-11-17 100 Series - IFC Plans 11x17 (Rev 01).pdf PDF
Attachment 10 - Utility Contacts Fees Responsiblities.pdf PDF
Submittal Register - Barnes Blvd. Bridge Repairs.xlsx XLSX spreadsheet
Attachment 4 - 2021-12-22 McChord Geotech Bridge Foundation Report.pdf PDF
Attachment 13 - Revised PSE Utility Drawings.pdf PDF
Attachment 7 - Barnes Blvd Temporary Bridge Detour Requirements and Details.pdf PDF
Attachment 12 - FAA Form 7460-1 052026.pdf PDF
Attachment 11 - Draft Property Barnes Blvd 2021-10-12 Form DD 1354.pdf PDF
JA Brand Name - Repair Barnes Blvd Redacted.pdf PDF
W912DW24B0Y1Y - Repair Barnes Blvd - IFB.pdf PDF
Attachment 9 - 2021-11-11 McChord H-H Analysis Report.pdf PDF
Attachment 8 - Temp Stockpile Lining Diagram.pdf PDF
Attachment 6 - Standard Operating Procedures for use of Grays Army Airfield Borrow Source Pit.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G

ABBREVIATION

AFC

AFF

AHJ

ANSI

APPROX

ARCH

AWG

BB

BC

BET

BLDG

C

CAT

CFCI

CFGI

CLG

- CMP

CMR

co

COL

COMM

CONN

cu

F

E

DB

DED

DET

DIA

DIM

DN

DPW

DWG

EA

EF

EIA

ELEC

EMT

ENCL

ER

EXIST OR (E)

EXT

FLR

FT

FUT

GorGND

GC

GFCI

GFGI

GFI

HH

HT

HVAC

13A

IDS

- IN

D

C

JB orJBOX

LAN

M

MATL

MAX

MBPS

MCC

MECH

MFR

MH

MHZ

MIN

MISC

MM

MTD

N.E.C.

NEC

NEMA

NIC

NO.

oc

OPNG

PDS

PNL

PR

PVC

PWR

QTY

RCDD

REG

REQD

REV

RG

RGB

RM

RTU

- SCHED

SECT

SIPRNET

SM

B

SP

SPECS

SQ

ss

STD

STL

STRUCT

SVC

SYS

TBB

TEBC

TEL

TEMP

TGB

TIA

TMGB

TR

TTB

TTC

TV

TVSS

TYP

A UF

UG

UL

UON

UTP

WAN

WM

WP

I

TELECOMMUNICATIONS ABBREVIATIONS

DESCRIPTION

ABOVE FINISHED COUNTER

ABOVE FINISHED FLOOR

AUTHORITIES HAVING JURISDICTION

AMERICAN NATIONAL STANDARDS INSTITUTE

APPROXIMATELY

ARCHITECTURAL

AMERICAN WIRE GAUGE

BACKBONE

BONDING CONDUCTOR

BUILDING ENTRANCE PROTECTOR

BUILDING

CONDUIT

CATALOG

CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

CONTRACTOR FURNISHED, GOVERNMENT INSTALLED

CEILING

COMMUNICATIONS PLENUM

COMMUNICATIONS RISER

CONDUIT ONLY WITH PULL STRING

COLUMN

COMMUNICATIONS

CONNECT or CONNECTION

COPPER

DECIBEL

DEDICATED

DETAIL

DIAMETER

DIMENSION

DOWN

DIRECTORATE OF PUBLIC WORKS

DRAWING

EACH

ENTRANCE FACILITY

ELECTRONIC INDUSTRY ALLIANCE

ELECTRICAL

ELECTRICAL METALLIC TUBING

ENCLOSURE

EQUIPMENT ROOM

EXISTING

EXTERIOR

FLOOR

FOOT or FEET

FUTURE

GROUND

GENERAL CONTRACTOR

GOVERNMENT FURNISHED, CONTRACTOR INSTALLED

GOVERNMENT FURNISHED, GOVERNMENT INSTALLED

GROUND FAULT CIRCUIT INTERRUPTER

HANDHOLE

HEIGHT

HEATING, VENTILATION AND AIR CONDITIONING

INSTALLATION INFORMATION INFRASTRUCTURE ARCHITECTl RE

INTRUSION DETECTION SYSTEM

INCH or INCHES

JUNCTION BOX

LOCAL AREA NETWORK

METER

MATERIAL

MAXIMUM

MEGABITS PER SECOND

MAIN CROSS CONNECT

MECHANICAL

MANUFACTURER

MANHOLE

MEGAHERTZ

MINIMUM

MISCELLANEOUS

MULTI-MODE

MOUNTED

NATIONAL ELECTRICAL CODE

NETWORK ENTERPRISE CENTER

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NOT IN CONTRACT

NUMBER

ON-CENTER

OPENING

PROTECTIVE DISTRIBUTION SYSTEM

PANEL

PAIR

POLYVINYL CHLORIDE

POWER

QUANTITY

REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER

RECEPTACLE

REQUIRED

REVISION

RADIO GUIDE (COAXIAL CABLE)

RED, GREEN, BLUE

ROOM

REMOTE TERMINAL UNIT

SCHEDULE

SECTION

SECURE INTERNET PROTOCOL ROUTER NETWORK

SINGLE-MODE

SERVICE PROVIDER

SPECIFICATIONS

SQUARE

STAINLESS STEEL

STANDARD

STEEL

STRUCTURAL

SERVICE

SYSTEM

TELECOMMUNICATIONS BONDING BACKBONE

TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR

TELEPHONE

TEMPERATURE or TEMPORARY

TELECOMMUNICATIONS GROUNDING BUS BAR

TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

TELECOMMUNICATIONS ROOM

TELEPHONE TERMINAL BOARD

TELEPHONE TERMINAL CABINET

TELEVISION

TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYPICAL

UNDER-FLOOR

UNDERGROUND

UNDERWRITER LABO RA TORIES

UNLESS OTHERWISE NOTED

UNSHIELDED TWISTED PAIR

WIDE AREA NETWORK

WALL-MOUNTED

WEATHERPROOF

I

I

I

I

I

I

I r-o_s_ P _ S_Y _M _B _OL_ L_E _G _EN_ D ________________ ___, TELECOMMUNICATIONS STANDARDS REFERENCE r-_

_ s

Y_ M� B�O�L���

-----------D_ E_S_ C _R_IP _T_IO _N ______________ ----i JBLM NEC - SPECIFICATION 33 82 00 "TELECOMMUNICATIONS OUTSIDE PLANT (OSP)"

EXISTING CABLE (AERIAL OR IN DUCT) - LIGHT LINEWEIGHT

·ssHSSSSHSHSSSSS

--UG/T-

--OH/T-

I I I I I I I I

D [iiB] t:t

I�

I� t:lQ-�1RAND§:

NEW WORK - HEAVY LINEWEIGHT

EXISTING TO BE REMOVED (CROSSHATCHED)

PROPOSED UNDERGROUND TELECOMMUNICATIONS CONDUIT OR DUCT BANK

PROPOSED OVERHEAD CABLE

EXISTING CONDUIT

PROPOSED CONDUIT

EXISTING TELECOM MAINTENANCE HOLE

PROPOSED TELECOM MAINTENANCE HOLE

EXISTING HAND HOLE

PROPOSED SPLICE SYMBOL (ONE SYMBOL= ALL SPLICE CASES)

ROAD CROSSING WITH CUT

EXISTING POLE

EXISTING JOINT USE POLE

RISER POLE

NEW POLE

WORK LOCATION NUMBER

EXISTING ISP UNPROTECTED TERMINAL

ISP PROTECTED ENTRANCE TERMINAL

OSP PROTECTED ENTRANCE TERMINAL

OSP UNPROTECTED ENTRANCE TERMINAL

PEDESTAL PROTECTED ENTRANCE TERMINAL

PROPOSED FIBER DISTRIBUTION PANEL (LIU)

EXISTING PULLBOX

-T - EXISTING DIRECT BURY TELEPHONE CABLE (TO DRAWINGS ONLY)

�W- WATER UTILITIES (TO DRAWINGS ONLY)

---E --- ELECTRICAL UTILITIES (TO DRAWINGS ONLY)

--$$-- SEWER (TO DRAWINGS ONLY)

-SD--- STORM DRAIN (TO DRAWINGS ONLY)

---ST-- STEAM LINE (TO DRAWINGS ONLY)

USAISEC - TECHNICAL CRITERIA FOR THE INSTALLATION INFORMATION INFRASTRUCTURE ARCHITECTURE, NOV. 2017 (I3A) USAISEC - REFER TO THE CURRENT VERSION OF EACH PUBLICATION CITED IN APPENDIX D OF THE I3A

GENERAL NOTES

1. SYMBOLS SHOWN IN THE LEGEND ARE TYPICAL. NOT ALL SYMBOLS MAY APPLY TO THIS PROJECT.

2. CONDITIONS SHOWN ON DOCUMENTS WERE TAKEN FROM AVAILABLE RECORD DOCUMENT INFORMATION AND FIELD INVESTIGATION. THE CONTRACTOR

SHALL LOCATE AND VERIFY ALL TELECOM SYSTEMS WITHIN THE IDENTIFIED AREAS PRIOR TO STARTING ANY WORK. ANY DISCREPANCIES BETWEEN INFORMATION SHOWN AND ACTUAL CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER.

3. PROVIDE ALL MATERIALS, LABOR AND EQUIPMENT REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION. MATERIALS AND WORKMANSHIP SHALL FULLY COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE ARMY TECHNICAL CRITERIA FOR INSTALLATION INFORMATION INFRASTRUCTURE ARCHITECTURE (I3A), JOINT BASE LEWIS-MCCHORD NETWORK ENTERPRISE CENTER (NEC) STANDARDS, AND TIA STANDARDS.

4. ALL TELECOMMUNICATIONS WORK SHALL BE COORDINATED WITH NEC, MR. CHRIS SMITH AT 253-967-3870.

5. POINT OF CONTACT FOR COMCAST COMMERCIAL CABLE TELEVISION SERVICE IS MR. ANDREW MARTIN AT 253-999-0187.

6. POINT OF CONTACT FOR CENTURYLINK COMMERCIAL TELEPHONE SERVICE IS ROB BAIR AT 253-393-5384.

7. SPLICE CASES SHALL BE PRE-FORMED STAINLESS STEEL. STRETCH TYPE CASES ARE NOT ALLOWED. ENCAPSULATING COMPOUNDS SHALL NOT BE USED.

FLASH TEST SPLICE CASES USING DRY NITROGEN GAS TO ENSURE DRY AND AIRTIGHT SEAL.

8. ALL AREAS IN THIS PROJECT ARE WITHIN THE CANTONMENT AREA OF JBLM.

9. TELECOM MANHOLES SHALL BE UTILITY VAULT OR APPROVED EQUAL AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

INSTRUCTIONS AND IN ACCORDANCE WITH THE I3A AND TIA STANDARDS. MANHOLES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 7000 PSI AT 28-DAYS, MEET AASHTO H-20 LOADING, INCLUDE GALVANIZED EMBEDDED PULLING IRONS IN EACH CORNER, TOP AND BOTTOM, INCLUDE FOUR GALVANIZED C-CHANNELS ON EACH LONGITUDINAL SIDE, AND SHALL BE EQUIPPED WITH PVC DUCT TERMINATIONS AT ALL POINTS OF ENTRY. PROVIDE GROUNDING AND BONDING PER I3A CRITERIA. NOTIFY NEC 48-HOURS PRIOR TD INSTALLATION OF MANHOLES TO OBTAIN APPROVAL ON ORIENTATION.

10. INSTALL DUCTS IN MANHOLES AT THE LOWEST AVAILABLE DUCT POSITIONS TO ALLOW DUCTS TO BE PLACED ON TOP IF REQUIRED IN THE FUTURE.

COORDINATE WITH POWER DUCT BANK INSTALLATION AND AVOID PLACEMENT OF DUCTS THAT WOULD PREVENT THE ABILITY TO INSTALL FUTURE DUCTS. TRANSITION DUCT BANKS FROM TRENCH DEPTH TO LOWER DUCT WINDOWS IN NO LESS THAN 30-LINEAR FEET TO MAINTAIN MINIMUM BEND RADIUS. COORDINATE WITH NEC FOR INSPECTION OF DUCT BANK INSTALLATION PRIOR TO ENCASING IN 3000 PSI REINFORCED CONCRETE. CONCRETE ENCASEMENT SHALL SURROUND DUCTS WITH NO VOIDS. DUCTS SHALL BE TESTED WITH A 12-INCH NON-FLEXIBLE MANDREL WITH A DIAMETER THAT IS 1/2" LESS THAN THE DUCT INSIDE DIAMETER IN ALL MAIN RUNS. ALL DUCTS. SUB-DUCTS AND INNERDUCTS SHALL BE PLUGGED USING UNIVERSAL

SCREW-TYPE DUCT PLUGS IN MANHOLES.

11. PROVIDE NYLON MULE-TAPE AND THREE CELL MAXCELL MULTICELL INNERDUCTS IN ALL DUCTBANK CONDUIT THAT WILL BE UTILIZED FOR FIBER CABLING.

12. LABELING SHALL BE IN ACCORDANCE WITH THE MOST CURRENT I3A, TIA-606 AND NEC STANDARDS. LABELS ON ISP HORIZONTAL CABLING SHALL BE

MACHINE PRINTED; 1/8" FONT MINIMUM HEIGHT WITH BLACK LETTERS ON A WHITE BACKGROUND AND SHALL BE LOCATED WITHIN 4" OF CABLE

TERMINATIONS. HANDWRITTEN LABELS ARE NOT ACCEPTABLE.

13. CABLE QUANTITIES AND TYPES ARE TAKEN FROM RECORD DOCUMENTS. CONTRACTOR TO FIELD VERIFY CONDITIONS PRIOR TO BID. REFLECT VERIFIED

CONDITIONS IN SUBMITTALS AND SHOP DRAWINGS.

14. PROVIDE 20' SERVICE LOOP IN EACH FIBER OPTIC CABLE WITHIN MANHOLE 206A AND 206B.

15. PROVIDE 50' SERVICE LOOP IN EACH EXISTING AND NEW FIBER OPTIC CABLE ON EACH SIDE OF SPLICE CLOSURES IN MH205 AND MH207.

16. SERVICE LOOPS NOT REQUIRED FOR OSP COPPER.

17. EMPTY CONDUITS WILL BE SUPPLIED WITH METERED PULL CORD.

18. NEW DUCTBANKS WILL CONSIST OF FOUR 4" CONDUITS. TWO CONDUITS WILL BE SUPPLIED WITH THREE EACH 3-CELL FABRIC INNERDUCTS, TOTAL OF

NINE CELLS. PROVIDE METERED PULL TAPE IN CONDUIT AND WITHIN EACH EMPTY INNERDUCT CELL. TWO CONDUITS WILL BE EMPTY AND SUPPLIED WITH

METERED PULL TAPE.

19. CONDUITS WILL BE MANDRELED PRIOR TO USE, REFER TO I3A FOR REQUIREMENTS.

20. INNERDUCTS WILL BE FABRIC-MESH 3-CELL 3". INNERDUCT WILL BE CUT OFF IN EACH MANHOLE AND EXTEND AT LEAST 2' INTO THE MANHOLE.

21. PULL TAPE WILL BE RATED NOT LESS THAN 200LB TENSILE STRENGTH. LEAVE MINIMUM 5' OF PULL TAPE EXPOSED IN MANHOLES. COIL AND SECURE IN

EACH MANHOLE TO PREVENT PULL TAPE FROM BEING PULLED BACK INTO CONDUIT/INNERDUCT.

�------�-----------------------------� 22. OUTAGES WILL BE LIMITED TO OFF-DUTY HOURS. COORDINATE WITH CO AND NEC PRIOR SCHEDULING ANY OUTAGES.

REFERENCE SYMBOL LEGEND

SYMBOL DESCRIPTION

---0

DETAIL SYMBOL

A-IDENTIFYING NUMBER

NORTH

SECTION OR ELEVATION SYMBOL

A-IDENTIFYING NUMBER

B-SHEET WHERE SECTION IS SHOWN OR TAKEN

NORTH ARROW

PROJECT NORTH

SHEET REFERENCE NOTE SYMBOL

A-NOTE NUMBER

REVISION SYMBOL

OSP DUCT BANK SYMBOLS LEGEND

EXISTING DUCT WITH

PROPOSED FABRIC MESH

EXISTING DUCT

INNERDUCT WITH 1 CABLE

WITH THREE

EACH THREE

CELL FABRIC �--.

MESH INNERDUCT

� �1-----EXISTING VACANT

DUCT

VACANT DUCT DUCT WITH EXISTING--------------

1 ...___EXISTING

W/ PULLSTRING Q Q :��R���T

KNOCKOUT \_

EXISTING DUCT WITH

COPPER CABLE

EXISTING DUCT WITH ONE EXISTING

AND ONE PROPOSED COPPER CABLE

23. PHASING:

a. NEW OSP PATHWAY, AND NEW OSP CABLES, WILL BE INSTALLED, SPLICED, AND TESTED, PRIOR TO ANY DUCTBANK DEMOLITION.

b. EXISTING CABLES WILL BE CUT AND SPLICED TO NEW CABLES ONE AT A TIME TO LIMIT DOWNTIME AND RISK. ALL FIBER SPLICES WILL BE FUSION TYPE.

OSP CABLE WILL BE TESTED RIGHT AFTER SPLICING.

c. ALL OUTAGES WILL BE SCHEDULED AT LEAST TWO WEEKS IN ADVANCE WITH THE COMM SQUADRON AND CONTRACTING OFFICER. OUT AGES WILL

OCCUR AFTER DUTY HOURS UNLESS APPROVED IN ADVANCE.

d. AFTER ALL CABLES ARE TRANSITIONED TO THE NEW ALIGNMENT THE DUCTBANK BETWEEN MH206 AND MH207 MAY BE DISCONNECTED AND REMOVED.

24. TESTING

a. CONTRACTOR WILL TEST OSP CABLING TO BE MODIFIED BEFORE WORK COMMENCES AND SUBMIT TEST REPORTS TO THE CONTRACTING OFFICER.

FAILED CABLING MAY BE REQUESTED TO BE REPLACED, AT AN ADDITIONAL COST, OR ACCEPTED AT GOVERNMENTS DISCRETION.

b. CONTRACTOR WILL RETEST MODIFIED OSP CABLING AT THE COMPLETION OF CONSTRUCTION. ALL CABLES WHICH FAIL FINAL TESTING, UNLESS

PREVIOUSLY ACCEPTED BY THE GOVERNMENT, WILL BE REPLACED/REPAIRED AT NO ADDITIONAL COST TO THE GOVERNMENT.

25. LABELING

a. CONTRACTOR TO FIELD VERIFY ACCURACY OF EXISTING CSP CABLE TAGS PRIOR TO COMMENCING WORK.

b. CONTRACTOR TO BRING ANY LABELING DISCREPANCIES TO THE ATTENTION OF NEC, PRIOR TO WORK, FOR CLARIFICATION / DIRECTION.

c. CONTRACTOR TO LABEL ALL NEW CABLING USING THE SAME MATERIALS, METHODS, AND NAMES, AS EXISTING CABLES BEING SPLICED, UNLESS

OTHERWISE DIRECTED BY NEC.

I w :, "' !!l m US Army Corps of Engineers•

Cl LU zf LU Cl (!)Z

LU _J

_J �

� LU

Oz

(.) LU

LU Cl f- z

SHEET ID

T0-01

SHEET 31 OF 76

ISSUED FOR CONSTRUCTION