2025-09-09-083263-ELEC ADDENDUM 4 (Signed).pdf
PDF 1 MB Posted
- Attached to
- Bartlett Hall - USMA
- Solicitation number
- W912DS25RA007
About this file
These documents are electrical engineering drawings for a renovation project at the United States Military Academy at West Point, specifically the Bartlett Hall 4th Floor Conversion and Courtyard Repair. The project involves detailed electrical power plans and one-line electrical diagrams for multiple building floors, including the fourth floor, fifth floor, sub-basement, and third floor. The drawings, prepared by the US Army Corps of Engineers New York District, show electrical infrastructure modifications such as power distribution, panel replacements, circuit breaker configurations, and electrical equipment positioning. Key technical specifications include new electrical panels (RP4C, RP5A), transformer replacements, emergency generator configurations, and comprehensive power routing for mechanical and building systems across different floors.
The electrical drawings include precise technical details like voltage specifications (480/277V, 208/120V), circuit breaker ratings, transformer capacities, and specific electrical equipment locations. The project documents are dated May 20, 2025, with a solicitation number W912DS25RA0007 and contract number W912DS19D0009. The drawings provide extensive coded notes about electrical installation requirements, emphasizing coordination between trades, adherence to National Electrical Code (NEC) standards, and specific installation instructions for various electrical components and systems.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
J
A.1
A.2
A.3
B.1
B.2
C.1
C.2
D.1
D.2
D.3
D.4
E.1
E.2
E.3
F.1
H.1
H.2
H.4
F.2
11 1012.112.212.513.113.2
ELEV 2
LARGE
CONFERENCE
ROOM
400D
COMM
AV
400E
STORAGE
430A
COMM
ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
DIR/ AP/
ADMIN
OFFICER
INST
ASSOC /
FULL
ADMIN
OFFICER
CONF
400C
SMALL
CONF
400B
ASSIST
PROF
ASSIST
PROF
ASSOC /
FULL
425A
ASSOC /
FULL
ASSOC /
FULL
TOILET
424A
TOILET
424B
STORAGE
424D
COLLAB
A-4C3B
COLLABORATION
A-4C6A
ADMIN
COLLAB
A-4C6B
INST
INST
ASSOC /
FULL
PRINT/COPY
424C
PROF/
DEPUTY
PROF/
HEAD
404ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
ASSOC /
FULL
425B
BREAK
AREA
400A
PRINT /
COPY
405A
CIRCULATION
A-4C1
PRINT/COPY
A-4C3A
ELEV 1
STAIR 3
A-4S3
STAIR 1
A-4S1
SERVICE
430 TOILET
430B
TOILET
430C
JAN
A-483
CORRIDOR
A-4C3
COLLABORATION
CORRIDOR
A-4C5
CORRIDOR
A-4C4
WAITING
A-4C2
TOILET
481A
TOILET
481B
CORRIDOR
A-4C6
RP4B
PP4A
RP4A
H.134 H.135
REF.
REF.
MONITOR
+48" +48"
+72"
MONITOR
TV
TV
+72"
+72"
RP4C
+50" +50" +50"
+65"
TV
TV TV TV
INST
LAB
TECH
HUDDLE
428A
HUDDLE
428B HUDDLE
428C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C11
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C13
RP4C
RP4C
RP4C15
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C35
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C47
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
(ETR)
(ETR) (ETR) (ETR)
2 2
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
TV
RP4C37
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
RP4C
(TYP.)
RP4B
RP4B
RP4B
RP4B
RP4B
RP4B
RP4B 8
RP4B
RP4B
RP4B
RP4B
RP4B
RP4B
RP4B
RP4B
3'-0" NEC
DEDICATED
WORKSPACE
(ETR)
(N)
RP4C
MONITOR 46
RP4C
+48"
MONITOR +74"
RP4C
RP4C
RP4C
RP4C
3'-0" NEC
DEDICATED
WORKSPACE
(ETR)
(ETR)
RP4C
RP4C
+44" +44"
DW +44" +44" +44"
A V
A V
A V
AV RACK
5(TYP.)
RP4C
RP4C
RP4C
RP4C
5 (TYP.)
5 (TYP.)
W
W
W
W
5 (TYP.)
DATA OUTLETS SERVED
FROM RM. COMM 427
DATA OUTLETS SERVED
FROM RM. COMM 428
RP4C
RP4C
EWC-1
RP4C
RP4C
EWC-2
RP4C
RP4C
RP4B
CM
PL
PL
PL
PL PL PL PL PL PL PL PL PL PL
PL
PL
PL
PL
PL PL
PL PL
PL PL
PL PL
PL
PL
PL
PL
PLCM PL CM PL CM PL CM PL CM PL CM PL CM PL CM PL
CM PL
PL
CM PL
PL PL PL PL PL PL
PL PL PL PL PL PL
CM PL CM PL CM PL CM PL CM PL
CM PL CM PL PL
PL
PL
PL
CM PL
PL
PL
CM PL33
RP4C
PL
PL
PL
CM PL PL
PL
PL
PL
CM PL
PL
PL
PL
PL
PLPL
CM PL
PL
PL PL
PL
PL
CM
PL
PL PL
PL
PL
PL
PL
CM PL
PL
PL
CM PL
PL PL
CM PL
PL
PL
PLPL
PL
CM PL
PL
PL
PL
PL
PL
CM PL
CM PL
PL
PL PL
PL
PL
CM PL
CM PL
+40"+40"
+40" +40"
+40" +40"
(ETR)
EP4A
EXST
STORAGE
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S N
E W
Y O
R K
D
IS
T R
IC
T
N E
W Y
O R
K N
Y D
R A
W N
B Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
P R
O J E
C T
N O
E-140
F O
U R
T H
F L O
O R
P O
W E
R P
L A
N
U n it e d S ta te s M ili ta ry A c a d e m y a t W e s t P o in t A
G
M P
E W
A G
M
A Y
W D
S R
A
W D
S D
100% RTA SUBMISSION
B a rt le tt H a ll th
F lo o r
C o n v e rs io n a n d C o u rt y a rd
R e p a ir
0' 4' 8' 16'1/8" = 1'-0" A1
FOURTH FLOOR POWER PLAN
1. PROTECT EXISTING RECEPTACLES LOCATED INSIDE OF CASEWORK.
2. E.C. SHALL MAINTAIN EXISTING 120V CIRCUITRY (WIRING & EXISTING PANEL/CIRCUIT) FOR REFERENCED
RECEPTACLES.
3. ALL CIRCUIT #'S INDICATED TO BE CONNECTED TO EXISTING PANELBOARD 'RP4B' ARE CIRCUITING ARRANGEMENTS AND FOR REFERENCE ONLY. ACTUAL CIRCUIT #'S TO BE CONNECTED TO PANELBOARD 'RP4B' WILL BE MADE AVAILABLE AFTER DEMOLITION, AND FINAL CONNECTIONS SHALL BE MADE BY ELECTRICAL CONTRACTOR.
4. E.C. SHALL PROVIDE JUNCTION BOX WITH CIRCUIT NUMBER SHOWN FOR CONFERENCE ROOM SCHEDULING PANEL.
5. E.C. SHALL PROVIDE 1" EMPTY CONDUIT STUB-UP TO HUNG CEILING FOR EACH DATA DEVICE LOCATED IN ALL STANDARD OFFICES, HUDDLE ROOMS, CONFERENCE ROOMS AND COMBINATION INSTRUCTION ROOMS. FOR THE EXACT QUANITY OF DATA DEVICES AND LOCATIONS, REFER TO TELECOM CONSULTANT DRAWINGS.
6. E.C. SHALL PROVIDE (1) 1"C. FOR (2) WIRELESS ACCESS POINT DEVICES, AS INDICATED. FOR PRICING PURPOSES, EACH 1" C. SHALL RUN TO COMM RM. 428.
7. E.C. SHALL PROVIDE (2) EMPTY 4"C. IN LOCATIONS REFERENCED, FOR PATHWAYS FOR DATA CABLING BACK TO
RESPECTIVE COMM CLOSETS.
8. E.C. SHALL PROVIDE (1) EMPTY 3"C. IN LOCATION REFERENCED, FOR PATHWAYS FOR DATA CABLING BACK TO
RESPECTIVE COMM CLOSET.
9. DENOTES APPROXIMATE LOCATION OF (4)#4/0 & (1)#4G. IN 2 1/2"C. RUNNING INTO STORAGE RM. 489 FROM ELEC. RM A-300 (THIRD FLOOR) VIA EXISTING PANEL RDP3, FOR FEED TO NEW PANEL RP4C. FOR FURTHER INFORMATION, REFER TO ELECTRICAL ONE-LINE DIAGRAM ON DWG. E-600.
CODED NOTES: #
1. FURNISH AND INSTALL ALL ELECTRICAL ROUGH IN EQUIPMENT AND APPURTENANCES PER THE NEC
(MINIMUM).
2. COORDINATE ALL WORK WITH ALL INVOLVED TRADES, EQUIPMENT VENDORS, UTILITIES, AND THE
PROJECT COORDINATOR AS REQUIRED. BASE BID ACCORDINGLY.
3. FINAL CONDUIT/CABLE ROUTING SHALL BE DETERMINED IN FIELD, AND PRIOR TO THE COMMENCEMENT OF
WORK, COORDINATED WITH OTHER TRADES AND THE PROJECT COORDINATOR.
4. REFER TO NEC TABLE 310.15(B)(16) FOR AMPACITIES OF CONDUCTORS, 60°C TERMINALS FOR UP TO 100A
AND 75°C TERMINALS FOR 101A AND LARGER, 30°C AMBIENT TEMPERATURE.
5. ALL WIRING SHALL BE PROPERLY IDENTIFIED PER NEC 310.110 & 310.120 AS REQUIRED.
6. REFER TO MECHANICAL DRAWINGS FOR FINAL RATINGS AND/OR CHARACTERISTICS OF MECHANICAL
EQUIPMENT DEVICES THAT REQUIRE POWER WIRING, AND BASE BID ACCORDINGLY.
7. ALL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
8. HOMERUNS ARE SHOWN IN LOCATIONS FOR DRAWING CLARITY. POWER MAY BE FED FROM OTHER CIRCUIT BREAKERS WITHIN PANELBOARDS DESIGNATED, AS LONG AS FUNCTIONAL INTENT IS MAINTAINED, AND FIELD DRAWINGS MARKED ACCORDINGLY.
9. BRANCH CIRCUITS ARE DESIGNATED BY THE NUMBER(S) ADJACENT TO AND/OR HOMERUNS SHOWN FROM ALL MECHANICAL EQUIPMENT INDICATES CIRCUIT NUMBERS IN PANELBOARD, U.O.N.. PROVIDE ALL
WIRING, CONDUIT AND BOXES AS REQUIRED TO ENERGIZE THE EQUIPMENT AS INDICATED.
10. PROVIDE INSULATED GROUNDING CONDUCTORS AS REQUIRED FOR ALL EQUIPMENT, ETC. GROUND
CONDUCTORS MAY NOT BE EXPLICITLY SHOWN IN ALL ILLUSTRATED WIRING DESIGNATIONS.
POWER DRAWING NOTES:
11. WHERE MORE THAN THREE CURRENT CARRYING CONDUCTORS PER RACEWAY IS USED, NEC TABLE 310.15(B)(2)(A) DERATING FACTORS SHALL BE APPLIED. IN ADDITION, CONDUIT FILL SHALL COMPLY WITH
NEC 344.22 AND 352.22 RESPECTIVELY.
12. CONDUCTORS OR CABLES INSTALLED IN CONDUIT EXPOSED TO DIRECT SUNLIGHT ON OR ABOVE ROOFTOPS SHALL BE DERATED AND SIZE-ADJUSTED IN ORDER TO COMPLY WITH NEC 310.15(B)(2)(b).
13. ALL WIRING AND EQUIPMENT WITHIN DROP CEILING SPACES, AND/OR WITHIN DUCTS, PLENUMS, AND OTHER AIR-HANDLING SPACES SHALL BE LISTED FOR PLENUM USE, AND SHALL CONFORM WITH NEC 300.22.
14. MEASURE PHASE LOADS (TRUE RMS) OF ALL PANELBOARDS UTILIZED TO COMPLETE THE CONTRACT
WORK, AND BALANCE LOADS AS REQUIRED.
15. REFER TO ELECTRICAL ONE LINE DIAGRAMS AND PANELBOARD SCHEDULES FOR ADDITIONAL
REQUIREMENTS THAT MAY APPLY.
16. UTILIZE SPARE CIRCUITS MADE AVAILABLE FROM DEMOLITION FOR NEW WORK.
17. FOR EQUIPMENT THAT ARE EXISTING TO REMAIN, E.C. SHALL RETAIN THE BRANCH CIRCUIT SERVING THE
EXISTING EQUIPMENT. REFER TO PANEL SCHEDULES FOR FURTHER INFORMATION.
A
D D
E N
D U
M
/0
/2
Giordano_Anthony_NY_PE_Seal_Sig
T
VFD VFD
T
T
D.1
D.2
D.3
D.4
E.1
E.2
E.3
F.1
H.1
H.2
H.4
F.2
AHU-4
VAV-4-19
H.134 H.135
UH
CUH
(ETR)
200A/3P/600V U.F.D.S.
75 KVA XFMR (ETR)
RP5A
DP5A
37,39,41
DP5A
(3)#2 & (1)#8G.-1 1/4"C.
RP5A
(ETR)
3'-0" NEC
DEDICATED
WORKSPACE
(ETR)
(ETR)
3'-0" NEC DEDICATED
WORKSPACE
MS
MS
UH-8
(RE)
SF-1
MS
VAV-4-5
MS
(ETR)
RP5A
DDC CONTROL
PANEL
HEAT TRACE
CONTROL
PANEL (RE)
C.1
C.2
D.1
D.2
D.3
D.4
E.1
E.2
E.3
F.1
F.2
EEDP (ETR)
ATS-1 (ETR)
ATS-2 (ETR)
GENDP
(ETR)
ELS4
(ETR) (ETR)
ELSDP (ETR)
EMERG.
ELEC.
RM.
M401B
7.57.5
3'-0" NEC DEDICATED
WORKSPACE
1,3,5
DPSBA
P-1
P-2
7,9,11
DPSBA
DPSBA
(ETR)
VFDVFD
A.1
A.2
A.3
B.1
B.2
1112.112.212.513.113.2
RDP3
EP3A (SUB. PANEL)
EP3A
EPDP
PP3A
ELS3
RP-3A
DP3A
112.5 kVA XFMR.
225 kVA XFMR.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S N
E W
Y O
R K
D
IS
T R
IC
T
N E
W Y
O R
K N
Y D
R A
W N
B Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
P R
O J E
C T
N O
E-151
E L E
C T
R
IC
A L P
A R
T
IA
L P
O W
E R
P L A
N S
U n it e d S ta te s M ili ta ry A c a d e m y a t W e s t P o in t A
G
M P
E W
A G
M
A Y
W D
S R
A
W D
S D
100% RTA SUBMISSION
B a rt le tt H a ll th
F lo o r
C o n v e rs io n a n d C o u rt y a rd
R e p a ir
0' 4' 8' 16'1/8" = 1'-0" A7
ELECTRICAL FIFTH FLOOR MECHANICAL POWER PLAN
0' 4' 8' 16'1/8" = 1'-0" D1
ELECTRICAL FOURTH FLOOR MEZZANINE MECHANICAL POWER PLAN
0' 4' 8' 16'1/8" = 1'-0" A1
ELECTRICAL SUB-BASEMENT MECHANICAL POWER PLAN
1. E.C. SHALL MAINTAIN EXISTING 120V CIRCUITRY (WIRING & EXISTING PANEL/CIRCUIT) FOR REFERENCED
RECEPTACLES.
2. ALL DEDICATED WORKSPACE CLEARANCES PER NEC 110.26 FOR EXISTING PANELBOARDS IN THIS ROOM HAVE BEEN
INVESTIGATED AND SHALL BE MAINTAINED.
3. E.C. SHALL PROVIDE NEW (2) #12 & (1) #12G. - 3/4"C. FOR EACH PIECE OF MECHANICAL EQUIPMENT REFERENCED FROM EXISTING SALVAGED C/B IN PANEL RP5A TO NEW LOCATION OF REINSTALLED SALVAGED EQUIPMENT INDICATED.
4. E.C. SHALL PROVIDE COMBINATION 30A/3P/600V D.S./VFD IN LOCATION SHOWN.
5. E.C. SHALL PROVIDE (3) #12 & (1) #12G. - 3/4"C.
6. E.C. SHALL CONNECT NEW DUPLEX RECEPTACLE THAT IS PROVIDED WITH UNIT TO EXISTING RECEPTACLE CIRCUIT
SERVING AREA.
7. E.C. SHALL PROVIDE DUPLEX RECEPTACLE FOR CORD & PLUG STYLE FLOW METER. CONNECT TO NEAREST EXISTING
RECEPTACLE CIRCUIT SERVING AREA.
8. E.C. SHALL RELOCATE EXISTING HEAT TRACE CONTROL PANEL TO NEW LOCATION SHOWN, 4'-0" TO THE RIGHT ON EXISTING WALL. ONCE CONTROL PANEL IS INSTALLED IN PLACE, REINSTALL & RECONNECT ALL EXISTING WIRING AND CONDUIT AS REQUIRED FOR A COMPLETE INSTALLATION. COORDINATE ALL WORK WITH MECHANICAL CONTRACTOR.
9. FOR FURTHER DETAIL REGARDING FEEDER TO NEW PANEL RP4C, REFER TO FOURTH FLOOR POWER PLAN DWG.
E-140 AND ELECTRICAL ONE-LINE DIAGRAM ON DWG. E-600.
CODED NOTES: #
A
D D
E N
D U
M
/0
/2
NOT TO SCALED6
ELECTRICAL THIRD FLOOR RM. A300 PARTIAL PLAN
G
1600AF
1600AT
OUTDOOR
EMERGENCY
GENERATOR,
GEN-1 (ETR)
1000kW 480/277V, 3Ø, 4W
15kV LOAD
BREAKER
SWITCH
600A
250E FUSE
UTILITY
CKT. A-4
K kVA
13.8kV
480/277V
5000AF
5000AT
N.C.
K
K
1600AF
1200AT
800AF
250AT
1600AF
1000AT
250AF
225AT
250AF
225AT
1200AF
1200AT
GENDP (ETR)
1600A MLO
480/277V, 3Ø, 4W 22 kAIC
E
L
N ATS-1(ETR)
260A
E
L
N ATS-2(ETR)
1200A 100A
3P 80A 3P
25A 3P
100A 3P
600A 3P
600A 3P
DP2A (ETR)
10000A MCB
480/277V, 3Ø, 4W 65 kAIC
100A 3P
70A 3P
100A 3P
100A 3P
350A 3P
DP3A (ETR)
600A MCB
480/277V, 3Ø, 4W 65 kAIC
20A 3P
20A 3P
150A 3P
150A 3P
150A 3P
60A 3P
110A 3P
450A 3P
DP5A (ETR)
1600A MCB
480/277V, 3Ø, 4W 65 kAIC
60A 3P
60A 3P
60A 3P
110A 3P
60A 3P
480V
208/120V kVA
5000AF
5000AT
K
N.O.
1600AF
1600AT
UTILITY
CKT. A-8
15kV LOAD
BREAKER
SWITCH
600A
250E FUSE
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
1600AF
1600AT
TO
AHU-4
(N)
600AF
600AT
225AF
225AT
PP4A (E)
480/277V 3Ø, 4W
100A MCB
60A 3P
20A 3P
20A 3P
60A 3P
60A 3P
60A 3P
60A 3P
60A 3P
ELS4 (ETR)
480/277V 3Ø, 4W
60A MCB
ELSDP (ETR)
225A MCB
480/277V,3Ø,4W 22 kAIC
150A 3P
150A 3P
150A 3P
150A 3P
150A 3P
600A 3P
400A 3P
175A 3P
800A 3P
EEDP (ETR)
1200A MCB
480/277V,3Ø, 4W 65 kAIC
480V
208/120V
100A 3P
100A 3P
100A 3P
100A 3P
225A 3P
100A 3P
EP4A (ETR)
208/120V 3Ø, 4W
100A MCB
EPDP (ETR)
400A MCB
208/120V, 3Ø, 4W 10 kAIC
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
225A 3P
RDP3 (ETR)
600A MCB
208/120V, 3Ø, 4W 22 kAIC
225A 3P
225A 3P
225A 3P
112.5 kVA
600AF
600AT
RP4B (ETR)
208/120V 3Ø, 4W
225A MCB
RP4A (ETR)
208/120V 3Ø, 4W
225A MCB
RP4C (N)
208/120V 3Ø, 4W
225A MCB
400AF
400AT
1200AF
1200AT
225AF
225AT
K
K
13.8V
480/277V
5000AF
5000AT
N.C.
kVA
480V
208/120V kVA
RP5A (ETR)
208/120V 3Ø, 4W
225A MCB
DPSBA (ETR)
400A MCB
480/277V, 3Ø, 4W 65 kAIC
20A 3P
25A 3P
20A 3P
40A 3P
40A 3P
100A 3P
110A 3P
20A 3P
40A 3P
40A 3P
40A 3P
40A 3P
25A 3P
TO
P-1 (N)
TO
P-2 (N)
800AF
400AT
800AF
400AT
15A 3P
15A 3P
MS1 (ETR), 5000A, 480/277V, 3Ø, 4W, 100 kAIC
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S N
E W
Y O
R K
D
IS
T R
IC
T
N E
W Y
O R
K N
Y D
R A
W N
B Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
P R
O J E
C T
N O
E-600
E L E
C T
R
IC
A L O
N E
-L
IN
E D
IA
G
R A
M
U n it e d S ta te s M ili ta ry A c a d e m y a t W e s t P o in t A
G
M P
E W
A G
M
A Y
W D
S R
A
W D
S D
100% RTA SUBMISSION
B a rt le tt H a ll th
F lo o r
C o n v e rs io n a n d C o u rt y a rd
R e p a ir
NOT TO SCALE
ELECTRICAL ONE-LINE DIAGRAM
B1
1. PROVIDE NEW MATCHING TYPE 110A/3P CIRCUIT BREAKER TO REPLACE
EXISTING 3P SPACE CORRESPONDING TO C/B'S (37,39,41).
2. PROVIDE (3) #2 & (1) #8G.-1 1/4"C. REFER TO DWG. E-151 FOR ADDITIONAL
INFORMATION.
3. PROVIDE (4) #4/0 & (1) #4G.-2 1/2"C. FEEDER SHALL BE CONNECTED TO
SPARE 225A/3P C/B IN PANELBOARD 'RDP3' IN ELEC. RM. A-300 UP TO 4TH
FLOOR TO NEW PANELBOARD RP4C (REFER TO DWG. E-140 FOR
LOCATION). FOR LOCATION OF EXISTING PANEL RDP3, REFER TO THIRD
FLOOR PARTIAL PLAN ON DWG. E-151.
4. PROVIDE NEW MATCHING TYPE 15A/3P CIRCUIT BREAKER TO REPLACE
EXISTING 3P SPACES CORESPONDING TO C/B'S (1,3,5) & (7,9,11).
CODED NOTES: #
A
D D
E N
D U
M
/0
/2
| Sheets |
| E-140 - FOURTH FLOOR POWER PLAN |
| E-151 - ELECTRICAL PARTIAL POWER PLANS |
| E-600 - ELECTRICAL ONE-LINE DIAGRAM |
File details come from the government source that posted it. Updated .