RTA Submittal Design Specifications - Vol. 02 Binder.pdf
PDF 3 MB Posted
- Solicitation number
- W912DS22B0021
About this file
This document provides details on an upcoming federal contract opportunity for construction services. The U.S. Army Corps of Engineers, New York District intends to issue a solicitation by mid-July 2022 seeking a firm-fixed price contract to construct an 8-bed, single story Level 1 confinement facility at McGuire Air Force Base in New Jersey. The 4,607 square foot facility will house pre-trial detainees and include 8 cells, administrative areas, a visitation room, training room, waiting room, day room, and full building systems. The performance period is 540 calendar days from notice to proceed. The procurement will be conducted as a small business set-aside and NAICS code 236220 applies with a size standard of $39.5 million. The estimate for the construction is between $5-10 million. Questions must be submitted in writing and bids will be accepted until approximately 30 days after issuance at the specified New York address.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Construct 8 Bed Level 1 Confinement Facility
Joint Base McGuire-Dix-Lakehurst, New Jersey
U
Specifications – Vol. 02
Project Number: 2795/PTFL186000
24 June 2022
W912DS-19-D-0011
TO: W912DS21F0109
BMcD PN 138107
US Army Corps Of Engineers® New York District
138107 USCOE – JB MDL Construct 8 Bed Level 1 Confinement Facility
PROJECT TABLE OF CONTENTS
DI VI SI ON 00 - PROCUREMENT AND CONTRACTI NG REQUI REMENTS
00 00 01 05/22 COVER SHEET
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 08/15 SUMMARY OF WORK
01 14 00 11/11, CHG 14: 02/22 WORK RESTRICTIONS
01 22 00.00 10 08/15 PRICE AND PAYMENT PROCEDURES
01 30 00 08/15 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 02/15 PROJECT SCHEDULE
01 33 00 08/18 SUBMITTAL PROCEDURES
01 33 29 02/21 SUSTAINABILITY REQUIREMENTS AND
REPORTING
01 35 26 11/15 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 02/19 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 11/16 QUALITY CONTROL
01 45 00.15 10 11/16 RESIDENT MANAGEMENT SYSTEM CONTRACTOR
MODE (RMS CM)
01 45 20.00 18 NY Dist. July 2018 TESTING FOR MECHANICAL AND ELECTRICAL
SYSTEMS
01 45 35 11/20 SPECIAL INSPECTIONS
01 50 00 05/18 TEMPORARY CONSTRUCTION FACILITIES AND
CONTROLS
01 57 19 11/15, CHG 5: 08/21 TEMPORARY ENVIRONMENTAL CONTROLS
01 58 00 08/19 PROJECT IDENTIFICATION
01 74 19 02/19 CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL
01 78 00 05/19 CLOSEOUT SUBMITTALS
01 78 23 08/15 OPERATION AND MAINTENANCE DATA
01 91 00.15 10 05/19, CHG 2: 08/20 TOTAL BUILDING COMMISSIONING
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 05/10, CHG 2: 02/19 DEMOLITION AND DECONSTRUCTION
DI VI SI ON 03 - CONCRETE
03 30 00 02/19, CHG 3: 11/21 CAST-IN-PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 11/15, CHG 2: 05/19 UNIT MASONRY
DI VI SI ON 05 - METALS
05 12 00 08/18, CHG 2: 05/21 STRUCTURAL STEEL
05 30 00 05/15, CHG 2: 08/18 STEEL DECKS
05 40 00 05/15, CHG 1: 08/18 COLD-FORMED METAL FRAMING
05 50 13 05/17, CHG 1: 08/18 MISCELLANEOUS METAL FABRICATIONS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 08/16, CHG 2: 11/18 ROUGH CARPENTRY
06 41 16.00 10 08/10, CHG 1: 11/18 PLASTIC-LAMINATE-CLAD ARCHITECTURAL
CABINETS
06 61 16 08/20 SOLID SURFACING FABRICATIONS
PROJECT TABLE OF CONTENTS Page 1
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 08/19 PRESSURE TESTING AN AIR BARRIER SYSTEM
FOR AIR TIGHTNESS
07 11 13 08/11, CHG 1: 05/17 BITUMINOUS DAMPPROOFING
07 21 13 02/16, CHG 2: 08/20 BOARD AND BLOCK INSULATION
07 22 00 02/16, CHG 3: 11/18 ROOF AND DECK INSULATION
07 27 10.00 10 08/19, CHG 1: 02/20 BUILDING AIR BARRIER SYSTEM
07 27 19.01 05/17, CHG 2: 08/20 SELF-ADHERING AIR BARRIERS
07 27 26 05/17, CHG 2: 08/20 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 27 36 05/17, CHG 2: 08/20 SPRAY FOAM AIR BARRIERS
07 42 13 05/11, CHG 2: 02/18 METAL PANELS
07 60 00 05/17, CHG 2: 11/18 FLASHING AND SHEET METAL
07 61 14.00 20 08/16, CHG 1: 08/18 STEEL STANDING SEAM ROOFING
07 84 00 05/10, CHG 1: 08/13 FIRESTOPPING
07 92 00 08/16, CHG 3: 11/18 JOINT SEALANTS
DI VI SI ON 08 - OPENI NGS
08 11 13 08/20 STEEL DOORS AND FRAMES
08 13 73 02/11 SLIDING METAL DOORS
08 31 00 05/17, CHG 1: 08/18 ACCESS DOORS AND PANELS
08 34 63 05/11 DETENTION HOLLOW METAL FRAMES, DOORS,
AND DOOR FRAMES
08 56 63 04/06 DETENTION AND SECURITY WINDOWS
08 71 00 02/16, CHG 3: 08/20 DOOR HARDWARE
08 71 63 04/06 DETENTION HARDWARE
08 71 63.10 02/21 ELECTRICAL LOCKING CONTROL FOR BRIGS
08 88 53 05/11 DETENTION AND SECURITY GLAZING
08 91 00 08/20 METAL WALL LOUVERS
DI VI SI ON 09 - FI NI SHES
09 06 00 05/09, CHG 1: 11/13 SCHEDULES FOR FINISHES
09 29 00 08/16, CHG 4: 02/20 GYPSUM BOARD
09 51 00 08/20 ACOUSTICAL CEILINGS
09 65 00 08/10, CHG 3: 08/18 RESILIENT FLOORING
09 67 23.13 11/19 STANDARD RESINOUS SYSTEMS
09 90 00 02/21 PAINTS AND COATINGS
DI VI SI ON 10 - SPECI ALTI ES
10 14 00.10 08/17, CHG 1: 11/18 EXTERIOR SIGNAGE
10 14 00.20 08/20 INTERIOR SIGNAGE
10 28 13 08/20 TOILET ACCESSORIES
10 44 16 11/19 FIRE EXTINGUISHERS
DI VI SI ON 12 - FURNI SHI NGS
12 55 00 04/06 DETENTION FURNITURE AND ACCESSORIES
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 13 13 08/20 WET PIPE SPRINKLER SYSTEMS, FIRE
PROTECTION
DI VI SI ON 22 - PLUMBI NG
PROJECT TABLE OF CONTENTS Page 2
22 00 00 11/15, CHG 4: 05/21 PLUMBING, GENERAL PURPOSE
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 03 00.00 20 08/10, CHG 3: 08/18 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93 11/15 TESTING, ADJUSTING, AND BALANCING FOR
HVAC
23 07 00 02/13, CHG 7: 05/20 THERMAL INSULATION FOR MECHANICAL
SYSTEMS
23 09 00 02/19, CHG 3: 05/21 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 11/15, CHG 2: 05/21 INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC
23 09 23.02 02/19, CHG 1: 02/20 BACNET DIRECT DIGITAL CONTROL FOR HVAC
AND OTHER BUILDING CONTROL SYSTEMS
23 11 20 05/20 FACILITY GAS PIPING
23 21 23 08/17 HYDRONIC PUMPS
23 23 00 08/21 REFRIGERANT PIPING
23 30 00 05/20 HVAC AIR DISTRIBUTION
23 52 00 04/08, CHG 5: 11/19 HEATING BOILERS
23 74 33.00 40 05/17 PACKAGED, OUTDOOR, HEATING AND COOLING
MAKEUP AIR-CONDITIONERS
23 81 00 05/18, CHG 1: 02/21 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 82 00.00 20 02/16, CHG 1: 08/18 TERMINAL HEATING UNITS
DI VI SI ON 25 - I NTEGRATED AUTOMATI ON
25 05 11.01 05/21 CYBERSECURITY FOR FACILITY-RELATED
CONTROL SYSTEMS LOW IMPACT HVAC
CONTROL SYSTEMS
25 05 11.02 05/21 CYBERSECURITY FOR FIRE ALARM/MASS
NOTIFICATION SYSTEM
DI VI SI ON 26 - ELECTRI CAL
26 08 00 11/21 APPARATUS INSPECTION AND TESTING
26 12 19.10 05/19, CHG 1: 11/19 THREE-PHASE, LIQUID-FILLED PAD-MOUNTED
TRANSFORMERS
26 20 00 08/19, CHG 3: 11/21 INTERIOR DISTRIBUTION SYSTEM
26 28 01.00 10 08/21 COORDINATED POWER SYSTEM PROTECTION
AND ARC FLASH RISK ASSESSMENT
26 29 23 02/20, CHG 1: 05/21 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS
UNDER 600 VOLTS
26 32 15.00 05/20 ENGINE-GENERATOR SET STATIONARY
15-2500 KW, WITH AUXILIARIES
26 36 23 05/20, CHG 1: 08/21 AUTOMATIC TRANSFER SWITCHES AND
BY-PASS/ISOLATION SWITCH
26 41 00 11/13 LIGHTNING PROTECTION SYSTEM
26 51 00 05/20, CHG 2: 11/21 INTERIOR LIGHTING
26 56 00 08/21 EXTERIOR LIGHTING
DI VI SI ON 27 - COMMUNI CATI ONS
27 05 13.43 05/20 TELEVISION DISTRIBUTION SYSTEM
27 10 00 08/11 BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
27 51 23 11/21 INTERCOMMUNICATION SYSTEM
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
PROJECT TABLE OF CONTENTS Page 3
28 31 76 08/20 INTERIOR FIRE ALARM AND MASS
NOTIFICATION SYSTEM, ADDRESSABLE
DI VI SI ON 31 - EARTHWORK
31 00 00 08/08 EARTHWORK
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 11 23 08/17 GRADED-CRUSHED AGGREGATE BASE COURSE
32 12 16.16 11/20 ROAD-MIX ASPHALT PAVING
32 16 19 05/18 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 08/16, CHG 5: 11/18 PAVEMENT MARKINGS
32 31 13.53 11/21 HIGH-SECURITY FENCES AND GATES
32 92 19 10/06 SEEDING
DI VI SI ON 33 - UTI LI TI ES
33 11 00 02/18 WATER UTILITY DISTRIBUTION PIPING
33 30 00 04/08 SANITARY SEWERS
33 40 00 11/21 STORMWATER UTILITIES
33 71 02 08/21 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 04/06 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
SECTION 10 14 00.10
EXTERIOR SIGNAGE
08/ 17, CHG 1: 11/ 18
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test
AMERICAN WELDING SOCIETY (AWS)
AWS C1.1M/C1.1 (2012) Recommended Practices for Resistance Welding
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A653/A653M (2020) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A924/A924M (2020) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B26/B26M (2018; E 2018) Standard Specification for Aluminum-Alloy Sand Castings
ASTM B108/B108M (2019) Standard Specification for Aluminum-Alloy Permanent Mold Castings
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2021) Standard Specification for Aluminum
SECTION 10 14 00.10 Page 1 and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
1.2 GENERAL REQUIREMENTS
All exterior signage must be provided by a single manufacturer. Exterior signage must be of the design, detail, sizes, types, and message content shown on the drawings, must conform to the requirements specified, and must be provided at the locations indicated. Submit exterior signage schedule in electronic media with spread sheet format. Spread sheet must include sign location, sign type, and message. Signs must be complete with lettering, framing as detailed, and related components for a complete installation. Each sample must consist of a complete sign panel with letters and symbols. Samples may be installed in the work, provided each sample is identified and location recorded. Submit three color samples for each material requiring color and 12 inch square sample of sign face color sample.
1.2.1 Character Proportions and Heights
Letters and numbers on indicated signs for handicapped-accessible buildings must have a width-to-height ratio between 3:5 and 1:1 and a stroke-width-to-height ratio between 1:5 and 1:10. Characters and numbers on indicated signs must be sized according to the viewing distance from which they are to be read. The minimum height is measured using an upper case letter "X". Lower case characters are permitted.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Approved Detail Drawings; G
SD-03 Product Data
Installation
Exterior Signage; G
SD-04 Samples
Exterior Signage; G
SD-10 Operation and Maintenance Data
SECTION 10 14 00.10 Page 2
Protection and Cleaning; G
1.4 QUALIFICATIONS
Signs, must be the standard product of a manufacturer regularly engaged in the manufacture of the products. Items of equipment must essentially duplicate equipment that has been in satisfactory use at least 2 years prior to bid opening.
1.5 DELIVERY AND STORAGE
Materials must be wrapped for shipment and storage, delivered to the job site in manufacturer's original packaging, and stored in a clean, dry area in accordance with manufacturer's instructions.
1.6 WARRANTY
Manufacturer's standard performance guarantees or warranties that extend beyond a one-year period must be provided.
PART 2 PRODUCTS
2.1 GRAPHICS FOR EXTERIOR SIGNAGE SYSTEMS
2.1.1 Graphics
Signage graphics must conform to the following:
a. Pressure sensitive precision cut vinyl letters with reflecting surface must be provided.
b. Message must be applied using the frisket method. Photomechanically reproduced graphic masks must be applied to the sign face which has been coated with the graphics color. A background must then be applied to the exposed surfaces. Handcut masks will not be accepted.
Edges that are nicked, cut, or ragged will not be acceptable. A protective overcoat containing UV-resistant additives must be applied.
2.1.2 Messages
See drawings and schedule for message content. Typeface: Helvetica medium.
Type size as indicated.
2.2 ALUMINUM ALLOY PRODUCTS
Aluminum alloy products must conform to ASTM B209 for sheet or plate, ASTM B221 for extrusions and ASTM B26/B26M or ASTM B108/B108M for castings. Aluminum extrusions must be provided at least 1/8 inch thick and aluminum plate or sheet at least 16 gauge thick. Welding for aluminum products must conform to AWS C1.1M/C1.1 .
2.3 ANODIC COATING
Anodized finish must conform to AA DAF45 as follows:
Electrolytically deposited color - anodized designation AA-M10-C22-A34, Architectural Class II 0.4 to 0.7 mil.
SECTION 10 14 00.10 Page 3
2.4 ORGANIC COATING
Clean, prime and give surfaces a semi-gloss baked enamel or two-component acrylic polyurethane finish in accordance with NAAMM AMP 500, AMP 505, with total dry film thickness not less than 1.2 mils.
2.5 ACRYLIC SHEET
Acrylic sheet must be in accordance with the flammability requirements of ASTM E84 and must conform to ANSI Z97.1 .
2.6 ANCHORS AND FASTENERS
Exposed anchor and fastener materials must be compatible with metal to which applied and must match in color and finish and must be non-rusting, non-corroding, and non-staining. Exposed fasteners must be tamper-proof.
2.7 SHOP FABRICATION AND MANUFACTURE
2.7.1 Factory Workmanship
Work must be assembled in the shop, as far as practical, ready for installation at the site. Work that cannot be shop assembled must be given a trial fit in the shop to ensure proper field assembly. Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Welding to or on structural steel must be in accordance with AWS D1.1/D1.1M . Welding must be continuous along the entire area of contact. Exposed welds must be ground smooth.
Exposed surfaces of work must have a smooth finish and exposed riveting must be flush. Fastenings must be concealed where practical. Items specified to be galvanized must be by hot-dip process after fabrication if practical. Galvanization must be in accordance with ASTM A123/A123M and ASTM A653/A653M , as applicable. Other metallic coatings of steel sheet must be in accordance with ASTM A924/A924M . Joints exposed to the weather must be formed to exclude water. Drainage and weep holes must be included as required to prevent condensation buildup.
2.7.2 Dissimilar Materials
Where dissimilar metals are in contact, or where aluminum is in contact with concrete, mortar, masonry, wet or pressure-treated wood, or absorptive materials subject to wetting, the surfaces must be protected with a coat of asphalt varnish or a coat of zinc-molybdate primer to prevent galvanic or corrosive action.
2.7.3 Shop Painting
Surfaces of miscellaneous metal work, except nonferrous metal, corrosion resisting steel, and zinc-coated work, must be given one coat of zinc-molybdate primer or an approved rust-resisting treatment and metallic primer in accordance with manufacturer's standard practice. Surfaces of items to be embedded in concrete must not be painted. Upon completion of work, damaged surfaces must be recoated.
2.8 COLOR, FINISH, AND CONTRAST
Color must be as indicated on the drawings. Color listed is not intended to limit the selection of equal colors from other manufacturers. For buildings required to be handicapped-accessible, the characters and
SECTION 10 14 00.10 Page 4 background of signs must be eggshell, matte, or other non-glare finish.
Characters and symbols must contrast with their background - either light characters on a dark background or dark characters on a light background.
PART 3 EXECUTION
3.1 INSTALLATION
Signs must be installed in accordance with approved manufacturer's instructions at locations shown on the approved detail drawings; submit drawings showing elevations of each type of sign; dimensions, details, and methods of mounting or anchoring; shape and thickness of materials; and details of construction. A schedule showing the location, each sign type, and message must be included. Signs must be installed plumb and true at mounting heights indicated, and by method shown or specified. Signs mounted on other surfaces must not be installed until finishes on such surfaces have been completed. Submit manufacturer's installation instructions and cleaning instructions.
3.1.1 Anchorage
Anchorage and fastener materials must be in accordance with approved manufacturer's instructions for the indicated substrate. Anchorage not otherwise specified or indicated must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. 2 sided adhesive approved by manufacturer for application on door face.
3.1.2 Protection and Cleaning
The work must be protected against damage during construction. Hardware must be adjusted for proper operation. Glass, frames, and other sign surfaces must be cleaned in accordance with manufacturer's instructions.
After signs are completed and inspected, cover all project identification, directional, and other signs which may mislead the public. Covering must be maintained until instructed to be removed by the Contracting Officer or until the facility is to be opened for business. Submit six copies of maintenance instructions listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guides. The instructions must include simplified diagrams for the equipment as installed. Signs must be cleaned, as required, at time of cover removal.
3.2 FIELD PAINTED FINISH
Miscellaneous metals and frames must be field painted in accordance with Section 09 90 00 PAINTS AND COATINGS. Anodized metals, masonry, and glass must be protected from paint. Finish must be free of scratches or other blemishes.
-- End of Section --
SECTION 10 14 00.10 Page 5
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 10 14 00.10 Page 6
SECTION 10 14 00.20
INTERIOR SIGNAGE
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2604 (2017a) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST SP 800-82 (2015; Rev 2) Guide to Industrial Control Systems (ICS) Security
U.S. DEPARTMENT OF DEFENSE (DOD)
DOD 8510.01 (2020; Change 1-2020) Risk Management Framework (RMF) for DoD Information Technology (IT)
DODI 8500.01 (2014) Cybersecurity
UFC 4-010-06 (2016; with Change 1, 2017) Cybersecurity of Facility-Related Control Systems
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SECTION 10 14 00.20 Page 1
SD-02 Shop Drawings
Detail Drawings; G
SD-03 Product Data
Room Identification And Directional Signage System; G
SD-04 Samples
Interior Signage; G
Room Identification and Directional Signage System
SD-10 Operation and Maintenance Data
Approved Manufacturer's Instructions
Protection and Cleaning
1.3 QUALITY ASSURANCE
1.3.1 Samples
Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: Room Identification.
Approved samples may be installed in the work, provided each sample is identified and location recorded.
1.3.2 Detail Drawings
Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.
1.3.3 Sign Fabricator
Sign Fabricator to follow room number strategies created by designer. The room numbering system to be reviewed and approved by the Contracting Officer and command end users during the shop drawing phase, and prior to fabrication.
1.3.4 Cybersecurity
a. The Risk Management Framework (RMF) is the process by which information systems are accredited for operation by a designated official from the Using Military Department. It is the standard process under which all DoD information systems achieve and maintain their Authority To Operate. The cybersecurity process is documented in DOD 8510.01 and NIST SP 800-82 . Refer to UFC 4-010-06 and DODI 8500.01 for additional requirements.
b. All systems that are IP addressable or interface with the Assured Network required certification to operate. Coordinate with the Government to initiate and complete the accreditation process.
c. Cybersecurity requires input from the system vendor or provider and
SECTION 10 14 00.20 Page 2 support from the local IMD. The local IMD-IA office is the point of contact for all Cyber Security requirements. The local CMIO is the point of contact for all clinical and functional system requirements.
1.4 DELIVERY, STORAGE, AND HANDLING
Package materials to prevent damage and deterioration during shipment, handling, storage and installation. Deliver products to the job site in manufacturer's original packaging and store in a clean, dry area in accordance with manufacturer's instructions.
1.5 WARRANTY
Provide manufacturer's warranty to repair or replace defective interior signage materials and workmanship for a period of 2 years from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 ROOM IDENTIFICATION AND DIRECTIONAL SIGNAGE SYSTEM
Provide signs that are standard products of manufacturers regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letter forms and graphics true and clean.
2.1.1 Panel Sign Systems
Provide direct print acrylic with applied tactile graphics, sign is fabricated of 0.375 inch acrylic in two layers with smooth edge conforming to ANSI Z97.1 . Provide signs that can accept raised copy and Braille with printable message inserts.
Corners of signs must be rounded to 1/2 inch radius.
2.1.2 Standard Room Signs
Provide signs that include tactile letters, symbols and Braille for interior rooms or spaces where the sign is not likely to change over time. Tactile text descriptions are required for pictograms that are provided to identify a permanent room. Examples include interior signs that label restrooms, stairs, room numbers or letters, and room names.
These permanent room signs can include paper inserts for updatable information.
2.1.2.1 Tactile Letters, Symbols and Braille
Provide ADA compliant material per 36 CFR 1191 which is raised 1/32 inch from the first surface, has a minimum 5/8 inch in height and is an ADA acceptable font. The color of the tactile letters is required to contrast with the sign face color per ADA standards. The ADA required Braille has a minimum durometer reading of 90. All raised letters, numbers and symbols are to comply.
2.1.3 Type of Mounting for Signs
Provide surface mounted signs mounted with concealed mechanical fastening through the holders.
SECTION 10 14 00.20 Page 3
2.1.4 Character Proportions and Heights
Letters and numbers on signs conform to 36 CFR 1191 .
2.2 MATERIALS
2.2.1 Organic Coating
Organic coating conforms to AAMA 2604, with total dry film thickness not less than 1.2 mils.
2.2.2 Fabrication and Manufacture
2.2.2.1 Factory Workmanship
Holes for bolts and screws are drilled or punched. Drilling and punching produces clean, true lines and surfaces. Exposed surfaces of work have a smooth finish; exposed riveting is flush. Conceal fastenings where practicable.
2.2.2.2 Dissimilar Materials
Where dissimilar metals are in contact, protect surfaces prevent galvanic or corrosive action.
2.2.3 Typeface
ADA-ABA compliant font for Room Signs.
2.3 COLOR, FINISH, AND CONTRAST
Provide color as specified in Section 09 06 00 SCHEDULES FOR FINISHES;
colors listed are not intended to limit the selection of equal colors from other manufacturers. Finish of eggshell, matte, or other non-glare finish for all signs as required in handicapped-accessible buildings.
PART 3 EXECUTION
3.1 INSTALLATION
Install signs plumb and true and in accordance with approved manufacturer's instructions at locations shown on the detail drawings.
Submit operating instructions outlining the step-by-step procedures required for system operation. The instructions include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Provide each set permanently bound with a hard cover. The following identification must be inscribed on the covers: "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Submit in accordance with Section 01 78 23 OPERATING AND MAINTENANCE DATA. Mounting height and mounting location complies with 36 CFR 1191 . Install required blocking. Do not install signs on doors or other surfaces until finishes on such surfaces have been installed. Signs installed on glass surfaces are installed with matching blank back-up plates in accordance with manufacturer's instructions.
Do not install items that show visual evidence of biological growth.
SECTION 10 14 00.20 Page 4
3.1.1 Anchorage
Provide anchorage in accordance with approved manufacturer's instructions. Anchorage not otherwise specified or shown includes slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Provide exposed anchor and fastener materials compatible with metal to which applied with matching color and finish.
a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.
3.1.2 Protection and Cleaning
Protect the work against damage during construction. Adjust hardware and electrical equipment for proper operation. Clean glass, frames, and other sign surfaces at completion of signage installation in accordance with the manufacturer's written instructions.
SECTION 10 14 00.20 Page 5
SECTION 10 14 00.20 Page 6
SECTION 10 28 13
TOILET ACCESSORIES
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-1691 (1994; Rev F) Construction and Material Schedule for Military Medical and Dental Facilities
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Product Schedule; G
Submit product Schedule indicating types, quantities, sizes, and installation locations by room for each toilet accessory item required. Identify locations using room designations indicated on the drawings.
SD-03 Product Data
Recycled content for stainless steel toilet accessories; S
Detention Mirror; G
Surface Mounted Soap Dispenser; G
Jail-type Breakaway Curtain System; G
Safety Clothes Hook; G
Dispenser, Paper Towel, SS, Surface Mounted; G
Disposal, Sanitary Napkin, SS, Surface Mounted; G
Grab Bar, 1-1/4 inch Dia., SS, 2 Wall, W/C Accessible; G
Shelf, Utility W/ Mop/Broom Holders, SS, Surf Mntd; G
SECTION 10 28 13 Page 1
Hook, Garment, Security; G
Rod, Shower Curtain, 1 inch Diameter, W/Curtain & Hooks; G
Item A5195 Dispenser, Toilet Tissue, SS, 1-Roll, Surface Mntd; G
Submit catalog numbers, literature, data sheets, construction details, profiles, anchoring and mounting requirements, including cutouts in other work and substrate preparation, and other pertinent data for each toilet accessory item to evaluate function, materials, dimensions and appearance.
SD-10 Operation and Maintenance Data
Detention Mirror; G
Surface Mounted Soap Dispenser; G
Jail-type Breakaway Curtain System; G
Safety Clothes Hook; G
Dispenser, Paper Towel, SS, Surface Mounted; G
Disposal, Sanitary Napkin, SS, Surface Mounted; G
Grab Bar, 1-1/4 inch Dia., SS, 2 Wall, W/C Accessible; G
Shelf, Utility W/ Mop/Broom Holders, SS, Surf Mntd; G
Hook, Garment, Security; G
Rod, Shower Curtain, 1 inch Diameter, W/Curtain & Hooks; G
Dispenser, Toilet Tissue, SS, 1-Roll, Surface Mntd; G
Mirror, 14 inch by 16 inch, SS, surface mounted; G
Submit Data Package 1 for each toilet accessory item in accordance with Section 01 78 23 OPERATIONS AND MAINTENANCE DATA.
1.3 DELIVERY, STORAGE, AND HANDLING
Wrap toilet accessories for shipment and storage, then deliver to the job site in manufacturer's original packaging, and store in a clean, dry area protected from construction damage and vandalism.
1.4 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for a period of one year from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 ACCESSORY ITEMS
Provide toilet accessories where indicated in accordance with Contractor-provided product schedule. Conform to the requirements for
SECTION 10 28 13 Page 2 accessory items specified herein which are based on MIL-STD-1691 Joint Schedule Numbers (JSN). Provide each accessory item complete with the necessary mounting plates of sturdy construction with corrosion resistant surface.
Provide stainless steel products listed herein manufactured from materials containing a minimum of 50 percent recycled content. Provide data identifying percentage of recycled content for stainless steel toilet accessories.
2.1.1 Anchors and Fasteners
Provide corrosion-resistant anchors and fasteners capable of developing a restraining force commensurate with the strength of the accessory to be mounted and suited for use with the supporting construction. Provide tamperproof design exposed fasteners with finish to match the accessory.
Provide fasteners proposed for use for each type of wall construction and mounting.
2.1.2 Finishes
Except where noted otherwise, provide the following finishes on metal:
Metal Finish
Stainless steel No. 4 satin finish
Carbon steel, copper alloy, and brass Chromium plated, bright
2.1.3 Dispenser, Paper Towel, Sensor, Hands Free (TA-04)
Surface mounted paper towel dispenser with hands free operation. Unit made of high impact plastic in a dark translucent color. Unit has the capacity of one standard 8 inch wide by 8 inch diameter 800 ft roll with optional paper length settings. Unit is battery operated by four "D" size alkaline batteries, and have low battery indicator light, or optional AC power adapter. Unit has keyed lock.
Approximate size: 12 inches wide by 15 inches high by 10 inches deep.
2.1.4 Disposal, Sanitary Napkin, SS, Surface Mounted (TA-06)
Surface mounted sanitary napkin receptacle. Unit made of stainless steel with satin finish and all welded construction. Unit has piano hinge attached at the top and an integral finger depression for opening. For use with disposable paper liners, available separately. Unit may be attached to wall or toilet partition.
Approximate size: 7 inches wide by 4 inches deep by 10 inches high.
2.1.5 Item A5109 Grab Bar, 1-1/4 Inch Diameter, SS, 2 Wall, W/C Accessible
(TA-01)
Grab bar of 1-1/4 inch diameter satin finish stainless steel with peened gripping surface for use in toilet stall/room. Snap-on flange covers for concealed mounting are stainless steel and equipped with two screw holes for attachment to wall. Grab bars designed to meet and exceed ADA requirements for structural strength. Grab bars designed to withstand
SECTION 10 28 13 Page 3 loads of 900 pounds when properly installed. Clearance from wall to grab bar is 1-1/2 inches to meet ADA and ANSI codes.
2.1.6 Item A5135 Shelf, Utility W/ Mop/Broom Holders, SS, Surf Mounted
Surface mounted mop/broom holder with shelf made of 18 gauge stainless steel with all exposed surfaces in satin finish. Unit has shelf 8 inches deep with shelf support brackets of satin finish stainless steel welded to mounting base, and a minimum of 3 hooks/3 holders. Mop holders have spring-loaded rubber cams and hold mop or broom handle with a diameter between 5/8 inch and 1 inch.
Approximate size: 36 inches wide by 8 inches deep.
2.1.7 Safety Clothes Hook
Provide 1/4 inch steel hook and a 10 gauge steel bracket safety clothes hook designed to collapse under a heavy load. Provide an adjustable friction device that permits variation of factory setting with use of a simple spanner tool. Finish shall be cadmium plate. Provide 1/4 inch, 20 by 1 inch flat head spanner machine screws to fit widely spaced holes designed to resist abuse.
2.1.8 Jail-type Breakaway Curtain System
Provide ceiling hung tracksets made of extruded 6063-T5 aluminum with satin anodized finish. Provide flat head spanner machine screws to fit widely spaced holes designed to resist abuse. Supply 2 inch long x 3/4 inch wide velcro safety tabs, three velcro safety tabs per foot. Provide curtain stitched with a header of 1-1/2 inch continuous velcro loop tape sewn to the top hem, constructed of flame resistant vinyl fabric with filament reinforcement, stain resistant, odor resistant and antimicrobial. Provide clear vinyl panels for the top and bottom.
2.1.9 Toilet Tissue, SS, 1-Roll, Surface Mounted (TA-02)
Concealed surface mounted single roll toilet tissue dispenser of satin finish stainless steel. Spindle to be free-spinning for non-controlled delivery, chrome-plated high impact resistant plastic and equipped with heavy-duty internal spring. Unit accommodates standard core toilet paper roll up to 5-1/2 inches diameter. Mounting hardware included.
Approximate size: 7-3/4 inches wide by 2 inches high by 4 inches deep.
2.1.10 Mirror, 36 inch by 24 inch, SS, Surface Mounted (TA-03)
Surface mounted mirror, 14 ga stainless steel frame with seamless construction, with satin finish on exposed surfaces. All mounting hardware included. Mirror held to frame by fiberboard backing. Mirror is 20 ga stainless steel, bright annealed. Stretcher leveled. Surface is bright and smooth, with mirror-like finish.
2.1.11 Surface Mounted Soap Dispenser (TA-05)
Provide soap dispenser surface mounted, liquid type consisting of a vertical Type 304 stainless steel tank with holding capacity of 40 fluid ounces with a corrosion-resistant all-purpose valve that dispenses liquid soaps, lotions, detergents and antiseptic soaps.
SECTION 10 28 13 Page 4
2.1.12 Detention Mirror - 11" W X 17" H
Mirror shall be 0.031 inches thick sheet steel, highly polished and bright chrome plated. Frame shall be 16 gauge cold-finished steel with 5/16 inch inner and outer flanges. Mirror size shall be as indicated.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install items that show visual evidence of biological growth.
Provide the same finish for the surfaces of fastening devices exposed after installation as the attached accessory. Provide oval exposed screw heads. Install accessories at the location and height indicated. Protect exposed surfaces of accessories with strippable plastic or by other means until the installation is accepted. After acceptance of accessories, remove and dispose of strippable plastic protection. Coordinate accessory manufacturer's mounting details with other trades as their work progresses. Use sealants for brackets, plates, anchoring devices and similar items in showers (a silicone sealant specified in Section 07 92 00 JOINT SEALANTS) as they are set to provide a watertight installation.
After installation, thoroughly clean exposed surfaces and restore damaged work to its original condition or replace with new work.
3.1.1 Recessed Accessories
Fasten accessories with wood screws to studs, blocking or rough frame in wood construction. Set anchors in mortar in masonry construction. Fasten to metal studs or framing with sheet metal screws in metal construction.
3.1.2 Surface Mounted Accessories
Mount on concealed backplates, unless specified otherwise. Conceal fasteners on accessories without backplates. Install accessories with corrosion-resistant fasteners as required by the construction. Install backplates in the same manner, or provide with lugs or anchors set in mortar, as required by the construction. Fasten accessories mounted on gypsum board and plaster walls without solid backing into the metal or wood studs, or to backplates secured to metal studs.
3.2 CLEANING
Clean material in accordance with manufacturer's recommendations. Do not use alkaline or abrasive agents. Take precautions to avoid scratching or marring exposed surfaces.
SECTION 10 28 13 Page 5
SECTION 10 28 13 Page 6
SECTION 10 44 16
FIRE EXTINGUISHERS
11/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 1 (2021) Fire Code
NFPA 10 (2018; ERTA 1-2 2018) Standard for Portable Fire Extinguishers
NFPA 101 (2021) Life Safety Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.157 (2003) Portable Fire Extinguishers
UNDERWRITERS LABORATORIES (UL)
UL 299 (2012; May 2021) Dry Chemical Fire Extinguishers
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Fire Extinguishers; G
Accessories; G
Cabinets; G
Schedule; G
SD-03 Product Data
Fire Extinguishers; G
Accessories; G
Cabinets; G
SECTION 10 44 16 Page 1
Replacement Parts List; G
SD-04 Samples
Equipment Samples; G
SD-07 Certificates
Fire Extinguishers Certifications; G
Manufacturer's Warranty with Inspection Tag; G
1.3 DELIVERY, STORAGE, AND HANDLING
Protect materials from weather, soil, and damage during delivery, storage, and construction.
Deliver materials in their original packages, containers, or bundles bearing the brand name and the name and type of the material.
1.3.1 Samples
Provide the following equipment samples: One of each type of fire extinguisher being installed; one full-sized sample of each type of cabinet being installed; three samples of wall brackets and accessories of each type being used.
Use approved samples for installation, with proper identification and storage.
1.4 WARRANTY
Guarantee that Fire Extinguishers are free of defects in materials, fabrication, finish, and installation and that they will remain so for a period of not less than 5 years after completion.
Submit the manufacturer's warranty with inspection tag.
1.5 PROJECT SCHEDULE
For fire extinguishers. Coordinate final fire extinguisher schedule with fire protection cabinet schedule to ensure proper fit and function. Use same designations indicated on Drawings.
PART 2 PRODUCTS
Submit fabrication drawings consisting of fabrication and assembly details performed in the factory and product data for the following items: Fire Extinguishers; Accessories, cabinets.
2.1 SYSTEM DESCRIPTION
2.1.1 Types
Submit fire extinguishers certifications showing compliance with local codes and regulations.
Provide fire extinguishers conforming to NFPA 10 . Provide quantity and placement in compliance with the applicable sections of NFPA 1, NFPA 101 , SECTION 10 44 16 Page 2 and 29 CFR 1910.157 .
Provide dry chemical type fire extinguishers compliant with UL 299 .
2.1.2 Material
Provide enameled steel extinguisher shell.
2.1.3 Size
10 pounds extinguishers.
2.1.4 Accessories
Forged brass valve
Fusible plug
Safety release
Antifreeze
Pressure gauge
2.2 EQUIPMENT
2.2.1 Interior Cabinets
2.2.1.1 Material
Provide enameled steel cabinets.
2.2.1.2 Type
Provide semi-recessed type cabinets.
2.2.1.3 Size
Dimension cabinets to accommodate the specified fire extinguishers.
2.2.2 Exterior Cabinets
2.2.2.1 Material
Provide enameled steel or anodized aluminum cabinets.
2.2.2.2 Type
Provide weather proof semi-recessed type cabinets.
2.2.2.3 Size
Dimension cabinets to accommodate the specified fire extinguishers.
2.2.3 Wall Brackets
2.2.3.1 Identification
Provide lettering complying with authorities having jurisdiction for
SECTION 10 44 16 Page 3 letter style, size, spacing, and location. Locate as indicated by the drawings.
Identify bracket-mounted fire extinguishers with the words "FIRE EXTINGUISHER" in red letter decals applied to mounting surface.
Orientation: Vertical.
PART 3 EXECUTION
3.1 INSTALLATION
Install Fire Extinguishers where indicated on the drawings. Verify exact locations prior to installation.
Provide extinguishers which are fully charged and ready for operation upon installation. Provide extinguishers complete with Manufacturer's Warranty with Inspection Tag attached.
Install fire extinguishers in locations indicated and in compliance with requirements of authorities having jurisdiction.
Comply with the manufacturer's recommendations for all installations.
3.2 PROTECTION
3.2.1 Repairing
Remove and replace damaged and unacceptable portions of completed work with new work at no additional cost to the Government.
Submit replacement parts list indicating specified items replacement part, replacement cost, and name, address and contact for replacement parts distributor.
3.2.2 Cleaning
Clean all surfaces of the work, and adjacent surfaces which are soiled as a result of the work. Remove from the site all construction equipment, tools, surplus materials and rubbish resulting from the work.
SECTION 10 44 16 Page 4
SECTION 12 55 00
DETENTION FURNITURE AND ACCESSORIES
04/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Bed
Desk
Shelf
Include details of frames, conditions of openings, details of construction, location and installation requirements of hardware and reinforcements, and details of joints and connections showing sizes and locations of welds. Indicate fabrication, erection, anchorage, and accessories.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver furniture and accessories in packaging to provide protection during transit and job storage. Leave in unopened original containers, clearly labeled for location of installation.
PART 2 PRODUCTS
2.1 MATERIAL
Steel plate, ASTM A36/A36M.
2.2 BED
Provide wall mounted bed. One piece, rotationally molded design constructed of high impact polyethylene. Not steel or wood components.
With Molded air flow troughs. Stain resistant. Bolt to the wall with
SECTION 12 55 00 Page 1 concealed pilot holes. Passes 2,000 lb. static load test. Bed measuring 81 inches long by 35 inches wide. Bed height of 18 inches. Accommodates 30 by 75 inch mattress.
2.3 DESK
Provide a detention desk with swivel stool. Detention grade. Desk with built-in swiveling stool with 360 degree rotation around the table leg.
Constructed of heavy duty 12 gauge stainless steel table top with brushed finish. 12 gauge stainless steel stool top. Provide solid stainless steel frame with gas tungsten arc welding. With 1/8 inch thick foot flanges on each leg with two pre-drilled mounting holes for floor mounting. All corners fully seam-welded and ground smooth for safety.
Desk dimensions of 32 inches wide by 19 inches deep by 32 inches high.
Stool dimensions of 12 inch diameter. Provide tamper-resistant mounting hardware.
2.4 SHELF
Stainless-steel shelf measuring 12 inches deep by 24 inches wide. Mounted 18 inches above the desk. Detention grade.
PART 3 EXECUTION
3.1 ADJUSTMENT
Adjust items and components of items specified in this section to ensure proper operation.
SECTION 12 55 00 Page 2
SECTION 21 13 13
WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B16.1 (2020) Gray Iron Pipe Flanges and Flanged Fittings Classes 25, 125, and 250
ASME B16.3 (2016) Malleable Iron Threaded Fittings, Classes 150 and 300
ASME B16.4 (2016) Standard for Gray Iron Threaded Fittings; Classes 125 and 250
ASME B16.21 (2016) Nonmetallic Flat Gaskets for Pipe Flanges
AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)
ASSE 1015 (2021) Performance Requirements for Double Check Backflow Prevention Assemblies
AMERICAN WATER WORKS ASSOCIATION (AWWA)
AWWA C104/A21.4 (2016) Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water
AWWA C110/A21.10 (2012) Ductile-Iron and Gray-Iron Fittings for Water
AWWA C111/A21.11 (2017) Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
AWWA C203 (2020) Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enamel and Tape - Hot-Applied
AWWA M14 (2015) Manual: Recommended Practice for Backflow Prevention and Cross-Connection Control
ASTM INTERNATIONAL (ASTM)
ASTM A47/A47M (1999; R 2018; E 2018) Standard Specification for Ferritic Malleable Iron Castings
SECTION 21 13 13 Page 1
ASTM A53/A53M (2020) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A135/A135M (2021) Standard Specification for Electric-Resistance-Welded Steel Pipe
ASTM A153/A153M (2016a) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A183 (2014; R 2020) Standard Specification for Carbon Steel Track Bolts and Nuts
ASTM A536 (1984; R 2019; E 2019) Standard Specification for Ductile Iron Castings
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-71 (2018) Gray Iron Swing Check Valves, Flanged and Threaded Ends
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 13 (2019; Errata 19-1; Errata 19-2; TIA 19-1;
TIA 19-2; TIA 19-3; TIA 19-4; Errata 19-3;
Errata 20-4; TIA 19-5; TIA 19-6) Standard for the Installation of Sprinkler Systems
NFPA 24 (2022) Standard for the Installation of Private Fire Service Mains and Their Appurtenances
NFPA 291 (2016) Recommended Practice for Fire Flow Testing and Marking of Hydrants
NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES
(NICET)
NICET 1014-7 (2012) Program Detail Manual for Certification in the Field of Fire Protection Engineering Technology (Field Code 003) Subfield of Automatic Sprinkler System Layout
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-600-01 (2016; with Change 6, 2021) Fire Protection Engineering for Facilities
UNDERWRITERS LABORATORIES (UL)
UL 199 (2020) UL Standard for Safety Automatic
SECTION 21 13 13 Page 2
Sprinklers for Fire-Protection Service
UL 312 (2010; Reprint Mar 2018) UL Standard for Safety Check Valves for Fire-Protection Service
UL 668 (2004; Reprint Jul 2016) UL Standard for Safety Hose Valves for Fire-Protection Service
UL Fire Prot Dir (2012) Fire Protection Equipment Directory
1.2 SYSTEM DESCRIPTION
Provide wet pipe sprinkler system(s) in all areas of the building. Except as modified herein, the system must meet the requirements of NFPA 13 and UFC 3-600-01 . Pipe sizes which are not indicated on the Contract drawings must be determined by hydraulic calculations.
1.2.1 Hydraulic Design
1.2.1.1 Basis for Calculations
Perform a fire hydrant flow test prior to shop drawing submittal in accordance with NFPA 291 . Results must include hydrant elevations relative to the building and hydrant number/identifiers for the tested hydrants, including which were flowed, which had a gauge. This information must be presented in a tabular form if multiple hydrants were flowed. The results must be included with the hydraulic calculations.
Hydraulic calculations must be based on flow test noted in this paragraph, unless approved by Contracting Officer. Hydraulic calculations must be based upon the Hazen-Williams formula with a "C" value noted in NFPA 13 for piping.
1.2.1.2 Hydraulic Calculations
a. Water supply curves and system requirements must be plotted on semi-logarithmic graph (N^1.85) paper so as to present a summary of the complete hydraulic calculation.
b. Provide a summary sheet listing sprinklers in the design area and their respective hydraulic reference points, elevations, minimum discharge pressures and minimum flows. Elevations of hydraulic reference points (nodes) must be indicated.
c. Documentation must identify each pipe individually and the nodes connected thereto. Indicate the diameter, length, flow, velocity, friction loss, number and type fittings, total friction loss in the pipe, equivalent pipe length and Hazen-Williams coefficient for each pipe.
d. Where the sprinkler system is supplied by interconnected risers, the sprinkler system must be hydraulically calculated using the hydraulically most demanding single riser. The calculations must not assume the simultaneous use of more than one riser.
e. All calculations must include the backflow preventer manufacturer's stated friction loss at the design flow or 8 psi for double check backflow preventer, whichever is greater.
SECTIO…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .