W9128A-19-B-0001_Am-0004_-_Drawings_(Part_2_of_2).pdf

PDF 9 MB Posted

Attached to
FY19 Repair by Replacement Various Facilities, Blocks A &B, Pohakuloa Training Area, Island of Hawaii, Hawaii
Solicitation number
W9128A-19-B-0001
Issued by

About this file

Amendment 0004 - Drawings (2 of 2)

View the file

Other files

File Type Posted
W9128A-19-B-0001_Abstract_of_Bids.pdf PDF
W9128A-19-B-0001_Am-0008_Drawings.pdf PDF
W9128A-19-B-0001_Am-0008_Specifications.pdf PDF
W9128A-19-B-0001_Am-0008.pdf PDF
W9128A-19-B-0001_Am_0007_Specifications.pdf PDF
W9128A-19-B-0001_Am_0007.pdf PDF
W9128A-19-B-0001_Am_0007_Drawings.pdf PDF
W9128A-19-B-0001_Am-0006_Specifications.pdf PDF
W9128A-19-B-0001_Am-0006_Drawings.pdf PDF
W9128A-19-B-0001_Am-0006.pdf PDF
W9128A-19-B-0001_Am-0005_Drawings.pdf PDF
W9128A-19-B-0001_Am-0005.pdf PDF
W9128A-19-B-0001_Am-0004.pdf PDF
W9128A-19-B-0001_Am-0004_-_Specifications.pdf PDF
W9128A-19-B-0001_Am-0004_-_Drawings_(Part_1_of_2).pdf PDF
W9128A-19-B-0001_Am-0003.pdf PDF
W9128A-19-B-0001_Am-0003_-_Drawings.pdf PDF
W9128A-19-B-0001_Am-0003_-_Specifications.pdf PDF
W9128A-19-B-0001_Am-0002.pdf PDF
W9128A-19-B-0001_Am-0001.pdf PDF
W9128A-19-B-0001_Drawings_(Part_9b_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_8_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_7_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_5_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_9_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_3_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_6_of_9).pdf PDF
W9128A-19-B-0001_IFB.pdf PDF
W9128A-19-B-0001_Specifications.pdf PDF
W9128A-19-B-0001_Drawings_(Part_4_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_2_of_9).pdf PDF
W9128A-19-B-0001_Drawings_(Part_1_of_9).pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B1

A1

SCALE: 1/2" = 1'-0"

TRANSVERSE SECTION

SCALE: 1/2" = 1'-0"

LONGITUDINAL SECTION

GRAPHICS SCALE

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

1'2' 0 2'

= 1'-0"1/2" SCALE:

S E

C T

IO

N S

B

A R

R A

C K

S

L A

R G

E

B U

IL

D

IN

G

R H

J S

B .d g n

S-302

BLDG. TYPE B

B C

/1

/1

A

M E

N D

M E

N T

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

/2 /8

TOP OF PLATE

(E) CONC SLAB

TOP OF PLATE

ARCH DWG, TYP

MTL ROOFING PER

(E) CONC SLAB

FOR EXTERIOR SLABS

SEE CIVIL DRAWINGS

BLKG, TYP

600S162-54 EAVE

CMU WALL BEYOND, TYP

CMU HEADER

FOR SEE

FOOTING PER

FOOTING PER

S-502

B1

S-502

A1

S-503

C5

PER ARCH

PER PLAN

RIDGE BENT PL

A

PER PLAN, TYP

CMU WALL

#10 SCREWS, TYP

MEMBERS W/ (2)

BRACING AT VERT

400S162-54 CONT

PER PLAN UON

TRUSS T-1 AT 4'-0"

PER PLAN

1-1/2" STL DECK

PER PLAN

T-3 HIP

PER PLAN

T-2 GIRDER

PER PLAN UON

TRUSS T-1 AT 4'-0"

PER PLAN

1-1/2" STL DECK

PER

CONNECTOR

, TYPPER

600T200-54 EAVE BLKG

S-505

A1

S-505

A3

A

S-505

A3

PER

SIM, CONNECTOR

, TYPPER

600S162-54 EAVE BLKG

S-505

A1

B

PER

CONNECTOR

S-505

A3

PER

FASCIA

BENT PL

S-506

C5

4'-0" PER PLAN

JACK TRUSSES T-4 AT

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

TOPPING

(N) CONC

TOPPING

(N) CONC

SCALE: 1/2" = 1'-0"

TRANSVERSE SECTION

SCALE: 1/2" = 1'-0"

LONGITUDINAL SECTION

GRAPHICS SCALE

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

1'2' 0 2'

= 1'-0"1/2" SCALE:

S E

C T

IO

N S

B U

IL

D

IN

G

G

P A

D M

IN

S

M A

L L

R H

J S

C .d g n

S-303

BLDG. TYPE C

B C

/1

/1

A

M E

N D

M E

N T

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

/2 /8

TOP OF PLATE

(E) CONC SLAB

TOP OF PLATE

ARCH DWG, TYP

MTL ROOFING PER

(E) CONC SLAB

FOR EXTERIOR SLABS

SEE CIVIL DRAWINGS

BLKG, TYP

600S162-54 EAVE

FOOTING PER

FOOTING PER

S-502

B1

S-502

A1

PER ARCH

PER PLAN

RIDGE BENT PL

CMU WALL BEYOND, TYP

S-503

C5

A

#10 SCREWS, TYP

MEMBERS W/ (2)

BRACING AT VERT

400S162-54 CONT

PER

CONNECTOR

, TYPPER

600T200-54 EAVE BLKG

S-505

A1

S-505

A3

A

S-505

A3

PER

SIM, CONNECTOR

, TYPPER

600S162-54 EAVE BLKG

S-505

A1

B

PER

CONNECTOR

S-505

A3

PER

FASCIA

BENT PL

S-506

C5

PER PLAN

1-1/2" STL DECK

PLAN UON

AT 4'-0" PER

TRUSS T-1

PLAN, TYP

CMU WALL PER

4'-0" PER PLAN

JACK TRUSSES T-4 AT

PER PLAN

1-1/2" STL DECK

PER PLAN

T-3 HIP

PER PLAN

T-2 GIRDER

PER PLAN UON

TRUSS T-1 AT 4'-0"

CMU HEADER

FOR SEE

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

TOPPING

(N) CONC

SCALE: 1/2" = 1'-0"

TRANSVERSE SECTION

SCALE: 1/2" = 1'-0"

LONGITUDINAL SECTION

GRAPHICS SCALE

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

1'2' 0 2'

= 1'-0"1/2" SCALE:

R H

J S

E .d g n

S-304

BLDG. TYPE E

B U

IL

D

IN

G

L

A U

N D

R Y S

E C

T

IO

N S

B C

/1

/1

A

M E

N D

M E

N T

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

/2 /8

TOP OF PLATE

(E) CONC SLAB

TOP OF PLATE

ARCH DWG, TYP

MTL ROOFING PER

(E) CONC SLABFOR EXTERIOR SLABS

SEE CIVIL DRAWINGS

BLKG, TYP

600S162-54 EAVE

CMU HEADER

FOR SEE

FOOTING PER

FOOTING PER

S-502

B1

S-503

C5

S-502

B1

PER ARCH

PER PLAN

RIDGE BENT PL

CMU WALL BEYOND, TYP

A

#10 SCREWS, TYP

MEMBERS W/ (2)

BRACING AT VERT

400S162-54 CONT

PER PLAN

T-3 HIP

PER PLAN

T-2 GIRDER

PER PLAN UON

TRUSS T-1 AT 4'-0"

PER PLAN

1-1/2" STL DECK

PER

CONNECTOR

, TYPPER

600T200-54 EAVE BLKG

S-505

A1

S-505

A3

, TYPPER

600S162-54 EAVE BLKG

S-505

A1

B

PER

CONNECTOR

S-505

A3

PER

FASCIA

BENT PL

S-506

C5

4'-0" PER PLAN

JACK TRUSSES T-4 AT

PER PLAN

1-1/2" STL DECK

PER PLAN, TYP

CMU WALL

PER PLAN UON

TRUSS T-1 AT 4'-0"

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

TOPPING

(N) CONC

SCALE: 1/2" = 1'-0"

TRANSVERSE SECTION

SCALE: 1/2" = 1'-0"

LONGITUDINAL SECTION

GRAPHICS SCALE

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

1'2' 0 2'

= 1'-0"1/2" SCALE:

B U

IL

D

IN

G

L

A T

R

IN

E S

E C

T

IO

N S

R H

J S

F .d g n

S-305

BLDG. TYPE F

B C

/1

/1

A

M E

N D

M E

N T

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

/2 /8

TOP OF PLATE

(E) CONC SLAB

TOP OF PLATE

(E) CONC SLAB

ARCH DWG, TYP

MTL ROOFING PER

MEMBERS, TYP

BRACING AT VERT

400S162-54 CONT

BLKG, TYP

600S162-54 EAVE

PER

LOWERED FTG

FOOTING PER

FOOTING PER PER

LOWERED FTG

T-2-4 AT 4'-0" UON

GIRDER TRUSS

CMU HEADER

FOR SEE

S-502

B1

S-502

B1

S-503

C5

S-502

C3

S-511

C3

PER ARCH

PER PLAN

RIDGE BENT PL

PER

CONNECTOR

, TYPPER

600S162-54 EAVE BLKG

S-505

A1

, TYPPER

600S162-54 EAVE BLKG

S-505

A1

PER

FASCIA

BENT PL

S-506

C5

4'-0" PER PLAN

JACK TRUSSES T-4 AT

C-4

S-512

B3

EXTERIOR SLABS

DRAWINGS FOR

SEE CIVIL

PER PLAN, TYP

CMU WALL

PER PLAN

(N) CONC SOG

PER PLAN

1-1/2" STL DECK

PER PLAN, TYP

CMU WALL

PER PLAN

T-3-4 HIP

PER PLAN

T-2-4 GIRDER

PER PLAN

(N) CONC SOG

PER

CONNECTOR H-4

S-512

B3

PER PLAN

1-1/2" STL DECK

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

SHOWN FOR CLARITY

FRAMING PARTIALLY

(E) FLOOR SLAB

TOPPING

(N) CONC

B4

A1 A2 A3

C5C4

B2

C1 C2

B1

B3

A4

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

NOT TO SCALE

TYPICAL SLAB ON GRADE

NOT TO SCALE

CONCRETE CURBS AND PADS

NOT TO SCALE

GRADE JOINTS

TYPICAL SLAB ON

NOT TO SCALESLAB EDGE

ANDDEPRESSED SLAB

NOT TO SCALENOT TO SCALE

NOT TO SCALE

CONCRETE JOINT

STEPPED FOOTING

TB/WALL FTG

NOT TO SCALE

BAR SPLICE TABLE

NOT TO SCALE

BAR BENDS & HOOKS

TYPICAL SLAB & WALL INTERSECTING WALL FTG

OR TIE BM DETAIL

NOT TO SCALE

EXCAVATIONS PARALLEL

TO FTG

NOT TO SCALE

PIPE PERPENDICULAR TO FOOTING

NOT TO SCALE

INFILL EXISTING SLAB

T Y

P

IC

A L D

E T

A

IL

S

R H

J S -5

.d g n

S-501

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

/2 /8

CURB

CURB

CONTROL JOINT

SLAB EDGE

PAD

10'-0" MIN

MIN

1'-6"

M

IN8

8"

"H

12"

OR 3" MIN

6 BOLT DIA

SEE ARCH DWGS

1" CLR

MIN

10"

IN

"2

M A

X

M A

X

IN3

"T

C L

R

-1 /2

/4

M

IN

M

IN8

MIN

8"

1'-6" (MIN)

6t OR

2ND POUR

1ST POUR

1-1/2"

O R L

E S

S

T B /F

T G D

E P

T H

LAP SPLICE

W/ 90 DEG HOOK

3'-0" OR EXTEND

P L

A N

D E

P T

H P

E R

32 DIA OR

"d

SEE PLANS

3'-0" MIN

3'-0"

3'-0" MIN

C O

N C

L

A

3D MIN

TIE OR STIRRUP

OFFSET BEND

PRINCIPAL REINFORCING

d d

'H d

4d

'H' d

'H d

M A

X

'H

3"

6d O

T

Y P

"d

SLAB

DEPRESSED

24"

SLAB

DEPRESSED

OPENING,

SAW CUT

MAX

4"

M

IN4

CONC SLAB

CHAIRS

CONC BLOCK (1) #4 T&B CONT

DOWELS AT CORNERS TYP

WITH 1'-6" BEND OR 1'-6"x1'-6"

#4 CONT HORIZ BARS AT 8"

ROUGHEN SURFACE TYP

(2) #4 CONT

#4 AT 24" DOWELS

TOP OF SLAB

5" MIN, 9" MAX

CURB WIDTH AS REQ'D

BARRIER

MOISTURE

GRADE, SIZE AND NUMBER

MATCH WALL REINF IN

FOOTING DOWELS SHALL

BARS IN SIZE AND NUMBER

LONGITUDINAL FOOTING

REINF SHALL MATCH

1:3 MIN SLOPE

SPLICE

HORIZ LAP

COVER

3" MIN BAR

EDGE CONDITIONS

SEE ARCH DWGS FOR

"t" (4" MAX)

DEPRESSION

"t" (4" TO 12")

DEPRESSION

#4 CONT

#4 AT 18" 24"

24"

(2) #4 CONT

#4 AT 18"

2'-0"

INTERSECTION

LOWER BARS AT

BOTH SIDES

BARS IF FOOTING

CONTINUOUS INTERSECTION

RAISE BAR AT

1/3

TOP SAME

BARS AT

1/3

PAVING-SEE PLANS

FIN GRADE OR

ON PLAN

SHOWN DASHED

FOOTING STEPS

1-1/2" CLR TYP

H/2 IF H>16"

ADD (2) #4 CONT

#4 AT 12"

PLASTIC RIBBON

OR USE 1" DEEP

12 HOURS AFTER POUR

SAW CUT MAXIMUM OF

CONTRACTOR OPTION:

EXCAVATION

TRENCH

PER SPECS

BACKFILL

EXTEND BELOW THIS LINE

EXCAVATION SHALL NOT

BOTTOM OF TRENCH

FOOTING

COMPLETED PER SPECIFICATIONS.

EXCAVATION FROM CAVE-INS UNTIL ALL BACKFILL IS

OR OTHERWISE MAINTAINING THE SIDE OF THE

THE CONTRACTOR SHALL PROVIDE SHORING, SHEATHING

NOTE:

LINE

GROUND

FILL

COMPACTED

SPLICE

HORIZ LAP

2'-0" MIN

PER PLAN, TYP

REINFORCEMENT

#3 AT 16" EW

TIE BMFTG

ANCHORAGE.

DETAILS FOR

SEE EQUIPMENT 4.

REQUIREMENTS.

FOR #4 HORIZ BAR

SEE CURB DETAIL 3.

DWGS.

ARCH AND MECH

AS REQUIRED BY

PROVIDE INSERTS 2.

CURBS.

LOCATION OF

FOR SIZE AND

SEE ARCH DWGS1.

NOTES:

TYPREQUIREMENTS,

SUBGRADE AND FILL

ON SHT S-001 FOR

SEE FOUNDATION NOTES

NECESSARY

DRAIN WHERE

BTB FOOTING

SOIL EXPOSED

WHEN EXTERIOR

CAP BLOCK

BIOBARRIER

FILL

GRANULAR

SELECT

12" MIN

WALL

PIPE THRU

FOOTING

BOTTOM OF

EQUAL

SLEEVE

'D' OF

THRU WALL

PIPES PASS

LOWER FTG SO

THIS AREA,

FOR PIPES IN

'D'+1'-6"

STEPPED PER

FOOTING SHALL BE 2.

BELOW FOOTING OR

PROVIDE LEAN CONCRETE 1.

BELOW FOOTING

CONTRACTOR OPTION FOR PIPES

#3

#4

#5

#6 f'c

BAR

SIZE

3000 PSI 4000 PSI 5000 PSI

OTHER

BAR

TOP

BAR

OTHER

BAR

OTHER

BAR

TOP

BAR

TOP

BAR

STIRRUP OR

TIE HOOK

STANDARD

HOOKSBAR

SIZE

#3

#4

#5

#6 12

6 4

4-1/2

HOOK HOOK HOOKHOOK

D 2 1D

3-1/2

4-1/2

5-1/2

4-1/2

5-1/2

7-1/2 4-1/2

1-1/2

2-1/2

4-1/2

3-3/4

2-1/4

ALL BENDS SHALL BE MADE COLD.1.

NOTES:

D

1D

FOR #6, #7, #8 BARS

2D

D

HOOK LENGTHS (H, INCHES)

GRADE 60 (INCHES)

SLAB & WALL SPLICE LENGTHS

S-501

B2

SPLICES BASED ON 3/4" MIN COVER2.

CONCRETE IS CAST BELOW THE SPLICE.

SO PLACED THAT MORE THAN 12" OF FRESH

TOP BARS ARE HORIZONTAL REINFORCEMENT 1.

:NOTES

CMU

PIPES, UON

THAN OD OF

2" LARGER

PVC SLEEVES

U O

N

M

X

WALL FOOTING

"d" IS DEPTH OF

NOTE:

LAYER

4" THK CLAY

CONCRETE SLAB ON GRADE.

BTB NOT REQUIRED FOR EXTERIOR

NOTE:

TYP UON

BARRIER,

MOISTURE

10 MIL THK

HOLE (MIN)

4"x5/8" DIA

EA SIDE

32" BARS, ALTERNATE

EPOXY GROUT #4 AT

BARRIER

BASALTIC TERMITE

BARRIER

15 MIL VAPOR

(2 BARS MIN)

#4 AT 12" CONT

LOCATIONS

FOR SIZE AND

SEE MECH DWG

NEW PLUMBLINE

REQUIREMENTS

SYSTEM

CONTROL BARRIER

FOR MESH TERMITE

SEE SPECIFICATION

CONCRETE.

UNDERMINED BACKFILL WITH

IF EXISTING SLAB BECOMES

NOTE:

C1 C2

B4

C3 C5

A1 A2 A4

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

NOT TO SCALE

FLOOR EDGE DEMOLITION

NOT TO SCALE

TYPICAL SLAB FOOTING

NOT TO SCALE

NOT TO SCALE

TYPICAL PERIMETER

THICKENED SLAB FOOTING

NOT TO SCALE

LOWERED INTERIOR WALL FOOTING

NOT TO SCALE

DEMOLITION DETAIL

PIPES AND CONDUITS PERPENDICULAR

TO FOOTING

NOT TO SCALE

COMBINED INTERIOR -

EXTERIOR FOOTING

NOT TO SCALE

WALL FOOTING

LOWERED PERIMETER

NOT TO SCALE

DEMOLITION DETAIL

T Y

P

IC

A L D

E T

A

IL

S

R H

J S -5

.d g n

S-502

B C

/1

/1

A

M E

N D

M E

N T

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

/2 /8

2' 0"

FLR EDGE

12" MIN REMOVED

A

X

10" MAX

3" MIN

M

IN

MIN

12"

C L

R

F T

G T

H K

FLR EDGE

1'-6" MIN REMOVED

2'-0"

REMOVE 3'-8" MIN

REMOVE 4'-6" MIN

M

IN6

M

IN6

12" MIN

(3) #5

(1) #5

#4 AT 8" OC

(E) SLAB, TYP

EPOXY EMBED 6" INTO

(N) #4 x16" LONG AT 18", 12" REMOVED (E) SLAB

S-502

C1

TYP AT FTG PERIMETER

INTO EXISTING SLAB.

DOWELS. EPOXIED 6"

#4 AT 18" x 16" LONG

(2) #5

#4 AT 8"

S-501

A3

ANDSEE

SLAB ON GRADE,

1'-6" MIN REPLACED

S-501

B4

(2) #5

#4 AT 8"

EMBED, TYP

6" EPOXY

OC, EW

#4 AT 16"

TYPSEE

WHERE OCCURS,

(N) PIPE THRU WALL

S-501

B3

S-502

C5

DEMO DETAIL

FOR SEE

NOTE:

(E) CONC SLAB

(E) CONC SLAB

ON GRADE

(E) CONC SLAB

S-502

B4

(N) CMU WALL PER PLAN

TOP OF FTG

REINF

BOT LONGITUDINAL FTG

ADDED REINF TO MATCH

CONDUIT, TYP

THAN PIPE OR

BE 3" LARGER

PIPE SLEEVE TO

6'-0" LONG

ADD (3) #4 x

FTG REINF

LONGITUDINAL

BEND 2'-0"

ABOVE FTG

CONDUIT

S-501

C1 FOR REBAR SPLICE EMBEDMENT AND DETAILS.SEE3.

PIPES.

CONTRACTOR TO DETERMINE EXACT DEPTH AND LOCATION OF

GENERAL CONTRACTOR SHALL CONSULT WITH MECHANICAL

DEPTH OF FOOTING MAY BE AFFECTED BY LOCATION OF PIPES. 2.

WITH COMPACTED FILL PER SHEET S-001, FOUNDATION NOTES.

BELOW BOTTOM OF FOOTING TRENCH MAY BE BACKFILLED

FOR PIPES PERPENDICULAR TO FOOTING, MORE THAN 3'-0" 1.

NOTES:

ABV FTG

CONDUIT

S-502

B1

BALANCE OF INFO

FOR SEE

BARS MIN)

#4 AT 16" ((2)

#4 AT 8"

(2) #5

(E) CONC SLAB

INTO (E) SLAB6"

EPOXIED DOWELS

#4 AT 12"

OD OF PIPE UON

LARGER THAN

PVC SLEEVES 2"

SEC

SECTION

PER PLAN

TOF ELEV

TOF ELEV PER PLAN

WITHIN FTG

BELOW OR

CONDUIT

S-501

A3

S-501

B4

#4 AT 8"

S-501

B3

S-502

C1

DEMO DETAIL

FOR SEE

NOTE:

TYPSEE

WHERE OCCURS,

(N) PIPE THRU WALL

EMBED, TYP

6" EPOXY

(3) #5

GRADE, SEE AND

1'-6" MIN REPLACED SLAB ON

#4 AT 16" OC, EW

(N) CONC WALL

(2) #5

WALL FOOTING

AT TYPICAL PERIMETER

WALL FOOTING

AT LOWERED PERIMETER

S-502

B1

FTG PER

OUTLINE OF (N)

S-502

A2

FTG PER

OUTLINE OF (N)

S-502

A4

S-502

A1

FTG PER

OUTLINE OF (N)

S-502

C3

FTG PER

OUTLINE OF (N)

(E) CONC SLAB

#5 DOWELS

GRADE

SLAB ON

(E) CONC

(E) CONC SLAB

FOR PIPE OPENING DETAIL.SEE2.

FOR SLAB DEMO DETAIL.SEE1.

NOTES:

1"

PER PLAN

(N) CMU WALL

PER PLAN

(N) CMU WALL

PER PLAN

(N) CMU WALL

PER PLAN

(N) CMU WALL

SLAB DEMO DETAIL.

FOR SEE1.

NOTE:

PER CIVIL

FINISH GRADE ELEV

PER CIVIL

GRADE ELEV

FINISH

ELEV PER CIVIL

FINISH GRADE

ELEV PER CIVIL

FINISH GRADE

VAPOR BARRIER

BARRIER

VAPOR

BARRIER

VAPOR

BARRIER

VAPOR PER PLAN

TOF ELEV

FLR JOIST

(E) STL

FLR SILL

(E) STL

FLR SILL

(E) STL

FLR JOIST

(E) STL

FLR SILL

(E) STL

JOIST

FLR

(E) STL

JOIST/SILL

(E) STEEL FLR

(N) CONC TOPPING

(N) CONC TOPPING

(N) CONC TOPPING

(N) CONC TOPPING

TOPPING

(N) CONC TOPPING

C3C1

A3A1

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

SCALE: 1" = 1'-0"SCALE: 1" = 1'-0"

DEMOLITION FOR MIDDLE FOOTING

SCALE: 1" = 1'-0"SCALE: 1" = 1'-0"

DEMOLITION FOR COMBINED FOOTING

GRAPHICS SCALE

SCALE: 1'' = 1'-0''

01' 1' 2'

R H

J S

A .d g n

S-508

BLDG. TYPE A

S H

O W

E R /L

A T

R

IN

E D

U P

L E

X D

E T

A

IL

S B

U

IL

D

IN

G

A /1

A /1

DETAIL - BUILDING 131A/131 AND 142A/142

DETAIL - BUILDING 131A/131 AND 142A/142

B C

A M

E N

D M

E N

T

/3 /1

4 4

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

5'-0" MIN

TYP

5"

DWGS

SEE ARCH

EMBED, TYP

6" EPOXY

ABOVE

MATCH CMU

EMBED, TYP

6" EPOXY

S-501

A3

ANDSEE

SLAB-ON-GRADE,

3'-4" MIN REPLACED

S-501

B4

TYPSEE

WHERE OCCURS,

(N) PIPE THRU WALL

S-501

B3

#5 AT 12" T&B(6) #5 T&B CONT

DETAIL FOR DEMO SEE

GRADE

SLAB-ON-

(E) CONC

S-508

C1

S-501

A3

ANDSEE

SLAB-ON-GRADE,

1'-6" MIN REPLACED

S-501

B4

#4 AT 12" T&B

TYPSEE

WHERE OCCURS,

(N) PIPE THRU WALL

S-501

B3

DETAIL FOR DEMO SEE

S-508

A1

OC, EW

#4 AT 16"

GRADE

SLAB-ON-

(E) CONC

SEE MEP DWGS, TYP

WHERE OCCURS,

PIPE IN CHASE

#5 AT 12" HORIZ

EXTERIOR

GRADE

(E) FINISHED

CONT

(4) #5 T&B

(N) CONC WALL

S-508

C3

S-508

A3

AND FTG, SEE

OUTLINE OF (N) CMU WALL

AND FTG, SEE

OUTLINE OF (N) CMU WALL

SLAB EDGE

REMOVE

(2) #4

#4 AT 16"

#4 AT 16" OC, EW

SIDE OF (N) FTG

SLAB-ON-GRADE EA

REMOVE 4'-0" MIN OF

PER PLAN

(N) CMU WALL

PER PLAN

(N) CMU WALL

ELEV PER CIVIL

FINISH GRADE

BARRIER

VAPOR

BARRIER

VAPOR

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

GRAPHICS SCALE

DEMOLITION DETAIL

B U

IL

D

IN

G

L

A U

N D

R Y D

E T

A

IL

S

R H

J S

E .d g n

S-510

BLDG. TYPE E

DETAIL - BUILDING 121

SCALE: 1-1/2" = 1'-0"SCALE: 1-1/2" = 1'-0"

1' 6" 1'

SCALE: 1-1/2'' = 1'-0"

B C

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

"SLAB-ON-GRADE

MIN 1'-6" REMOVED

PER PLAN

CONC CURB

AT 12"

#4 VERT DOWEL

SLAB-ON-GRADE

(E) CONC

CONT

(2) #4 T&B

#4 AT 12" BOT

EMBEDDED, TYP

#4 AT 16" EPOXY

DETAIL FOR DEMO SEE

S-510

C1

S-510

C3

PER

CURB AND FTG

OUTLINE OF (N)

(2) #4 CONT

(N) CONC TOPPING

G

G U

T

IE

R R

E Z

B

C E

Z A

R

K S

H

IM

O K

A W

A

G E

O R

G E G

U T

IE

R R

E Z J

R

SCALE: 1" = 1'-0"SCALE: 1" = 1'-0"

DEMOLITION DETAIL

GRAPHICS SCALE

SCALE: 1'' = 1'-0''

01' 1' 2'

B U

IL

D

IN

G

L

A T

R

IN

E D

E T

A

IL

S

R H

J S

F .d g n

S-511

BLDG. TYPE F

DETAIL - BUILDING 133

B C

A M

E N

D M

E N

T

/3 /1

4 4

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

A N

S I

D

IS

S

U E D

A T

E

A S N

O T

E D

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

/2 /8

W

A -1

-D -0

W

A -1

-D -0

S-501

A3

ANDSEE

SLAB-ON-GRADE,

1'-6" MIN REPLACED

S-501

B4

OC, EW

#4 AT 16"

#4 AT 12" T&B

DETAIL FOR DEMO SEE

GRADE

SLAB-ON-

(E) CONC

S-511

C1

MATCH ADJACENT FFE

FINISH GRADE TO

REMOVED SLAB

MIN 5'-0"

CONT

(4) #5 T&B

WALL AND FTG PER

OUTLINE OF (N) CMU

S-511

C3

PER PLAN

(N) CMU WALL

BARRIER

VAPOR

C H

A N

IC

A

L G

E N

E R

A L

N O

TE

S

A N

D L

E G

E N

D

GENERAL NOTES THIS SHEET ONLY

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

MECHANICAL GENERAL NOTES:

1. THE ENTIRE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF THE MILITARY HANDBOOKS, MILITARY ENGINEERING TECHNICAL LETTERS, INTERNATIONAL BUILDING CODE, INTERNATIONAL PLUMBING CODE, INTERNATIONAL FIRE CODE, NATIONAL FIRE PROTECTION ASSOCIATION CODE, NATIONAL ELECTRICAL CODE, ASME BOILER AND PRESSURE VESSEL CODE, ASME PRESSURE PIPING CODE, UFC 1-200-02, UFC 3-401-01, UFC

3-410-01, AND ALL OTHER AGENCIES HAVING JURISDICTION.

2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO COVER THE COMPLETE INSTALLATION OF SYSTEMS TO FUNCTION AS DESCRIBED AND SPECIFIED. THE OMISSION OF REFERENCE TO ANY NECESSARY ITEM OF LABOR OR MATERIAL SHALL NOT RELIEVE THE CONTRACTOR FROM PROVIDING SUCH LABOR AND MATERIAL.

3. ALL EQUIPMENT SHALL BE CAPABLE OF FITTING INTO THE SPACES ALLOCATED WHILE MEETING THE MANUFACTURER'S RECOMMENDED ACCESS REQUIREMENTS. REVIEW ALL SPACES WHERE EQUIPMENT IS TO BE INSTALLED PRIOR TO ORDERING OF EQUIPMENT AND NOTIFY THE ENGINEER OF ANY INADEQUATE CLEARANCES OR CONDITIONS THAT WILL PREVENT THE PROPER INSTALLATION, MAINTENANCE, AND OPERATION OF THE

EQUIPMENT.

4. PROVIDE SHOP DRAWINGS FOR THE LAYOUT OF EQUIPMENT, PIPING, AND DUCTWORK SHOWING COORDINATION OF ALL WORK WITH ALL OTHER TRADES, INCLUDING PLUMBING, FIRE SPRINKLER, FIRE ALARM, CONTROLS, ELECTRICAL, AND COMMUNICATION SYSTEMS. COORDINATION DRAWINGS SHALL OVERLAY HVAC, PLUMBING, FIRE SPRINKLER, ELECTRICAL, AND FIRE ALARM SYSTEMS, AND ALL CONFLICTS BETWEEN TRADES SHALL BE

NOTED AND RESOLVED.

5. VERIFY AND COORDINATE ALL ROOF, WALL, AND FLOOR PENETRATIONS WITH THE STRUCTURAL AND

ARCHITECTURAL DRAWINGS PRIOR TO THE START OF CONSTRUCTION.

6. OBTAIN APPROVAL FROM THE CONTRACTING OFFICER BEFORE MAKING ANY PENETRATIONS THROUGH

STRUCTURAL MEMBERS, WALLS, AND SLABS.

7. VERIFY THE EXACT LOCATION , SIZE, AND INVERT OF ALL EXISTING SEWER, STORM DRAIN, AND WATER LINES AT

THE NEW POINT OF CONNECTION PRIOR TO THE START OF CONSTRUCTION.

8. TONE AND LOCATE ALL UTILITY LINES OR OTHER INTERFERENCES IN AREAS OF PROPOSED TRENCH WORK PRIOR

TO START OF EXCAVATION. REPAIR OR PAY FOR ALL DAMAGES TO EXISTING UTILITIES.

9. DRAWINGS DO NOT ATTEMPT TO SHOW EXACT DETAILS OF PIPING AND DUCTWORK. PROVIDE OFFSETS AS NECESSARY TO AVOID LOCAL OBSTRUCTIONS OR INTERFERENCE WITH OTHER TRADES. REVIEW ALL PIPING AND DUCT RUNS PRIOR TO FABRICATION AND IMMEDIATELY NOTIFY THE CONTRACTING OFFICER OF ANY

INTERFERENCE AND/OR LACK OF ADEQUATE CLEARANCES.

10. SHOULD PROJECT CONDITIONS REQUIRE REARRANGEMENT OF WORK, MARK SUCH CHANGES ON THE AS-BUILT DRAWINGS. IF THESE CHANGES REQUIRE ALTERNATE METHODS TO THOSE APPROVED BY THE CONTRACT DOCUMENTS, SUBMIT SHOP DRAWINGS SHOWING THE PROPOSED ALTERNATE METHODS TO THE CONTRACTING

OFFICER FOR REVIEW. DO NOT PROCEED UNTIL REVIEWED.

11. PATCH AND PAINT ALL EXPOSED MATERIAL, TO MATCH ADJACENT SURFACES OR AS INDICATED.

12. REPAIR ANY DAMAGE TO EXISTING CONSTRUCTION RESULTING FROM THE INSTALLATION OF MECHANICAL ITEMS.

THE AREAS REPAIRED SHALL MATCH THE ADJACENT SURFACES IN TEXTURE AND COLOR.

13. PROPERLY FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED WALLS, FLOORS, OR PARTITIONS WITH A UL APPROVED SYSTEM APPROPRIATE FOR THE PENETRATION TYPE AND FIRE RATING. FIRESTOP ALL

PENETRATIONS BETWEEN FLOORS.

14. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PANELS SHALL BE MILCOR OR EQUAL. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE THAT THE EQUIPMENT CAN BE

MAINTAINED ADEQUATELY.

15. PROVIDE ISOLATION VALVES ON PIPING BRANCH LINES AND VOLUME DAMPERS ON DUCTWORK BRANCH LINES

WHETHER SHOWN ON THE DRAWINGS OR NOT.

16. SEISMICALLY BRACE ALL EQUIPMENT AND PIPING IN ACCORDANCE WITH THE IBC .

17. ROUTE ALL CONTROL AND MOTOR STARTER WIRING IN CONDUIT.

18. MOUNT ALL ROOM THERMOSTATS AT 4'-0” ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED.

DESCRIPTIONABBRV.SYMBOL

T THERMOSTATT-STAT

NOT TO SCALENTS

SF SUPPLY FAN

EXISTINGEXST

EXHAUST FANEF

S SW SWITCH

DIAMETERDIAØ

CUBIC FEET PER MINUTECFM

EXHAUST AIR EA

AFG ABOVE FINISHED GRADE

EMERGENCY HVAC SHUTDOWN SWITCHESS

M-001

R H

JG

-M -0

.d gn

D T

IS

E

D J

B

JO

A M

E N

D M

E N

T

2 4

7/ 3/

AutoCAD SHX Text

MECHANICAL LEGEND

C H

A N

IC

A

L D

E

TA

IL

S

GENERAL NOTES THIS SHEET ONLY

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

TYPICAL DUCT PENETRATION THROUGH WALL

NOT TO SCALEC1

DUCT

20 GAGE GALVANIZED

STEEL COLLAR (EXPOSED

ONLY). SECURE TO WALL

ON 6" CENTERS

(MINIMUM 4 FASTENERS

PER SIDE).

CMU WALL

GROUT

20 GAGE GALVANIZED

STEEL SLEEVE

INSULATION

NOTES:

SEE STRUCT SHTS FOR DETAIL

OF WALL OPENING.

1/2" CLEARANCE BETWEEN

2" X 2" X 1/4" ∠

TACKWELDED OR

RIVETED TO SLEEVE

SUPPLY FAN DETAIL

NOT TO SCALEC4

WALL EXHAUST FAN SUPPORT DETAIL

NOT TO SCALEB2

NOTE:

INSTALLATION SHALL BE PER

MANUFACTURERS

RECOMMENDATIONS

NOTE:

INSTALLATION SHALL BE

PER MANUFACTURERS

RECOMMENDATIONS

SEALANT AND

BACKER ROD

HVAC

EMERGENCY SHUTDOWN

RESET

FRANGIBLE

ENCLOSURE

PUSH BUTTONS

NOTE: SWITCHES SHALL

BE OF DIFFERENT COLOR

THAN FIRE ALARM PULL

STATION.

A2 NOT TO SCALE

HVAC EMERGENCY

SHUTDOWN SWITCH DETAIL

MOUNTING COLLAR

(SUPPLIED BY FAN

MFR.) SET IN SEALANT

CMU WALL

EXHAUST REGISTER

DAMPER

BACKDRAFT

TREATED

WOOD

BLOCK

SIDEWALL

EXHAUST FAN

EXTERIOR

SS EXPANSION SHIELDS

& BOLTS AS

RECOMMENDED BY FAN

MFR. (1/2" MIN.)

INTERIOR

ANGLE SUPPORT, TYP.

MOTOR GUARD

1/4" EXPANDED METAL

(GALV. STEEL)

FAN

INTERIOR EXTERIOR

CMU WALL

AIR

INTAKE

LOUVER

BACKDRAFT

DAMPER

ANCHOR BOLT, TYP

M-501

R H

JG

-M -5

.d gn

D T

IS

E

D J

B

JO

A M

E N

D M

E N

T

2 4

7/ 3/

GENERAL NOTES THIS SHEET ONLY

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

B A

R R

A C

K S

L A

R G

E

M E

C H

A N

IC

A

L S

C H

E M

A

TI

C D

IA

G

R A

M S

A N

D E

Q U

IP

M

E N

T S

C H

E D

U

LE

S

REFER TO GENERAL INFORMATION

AND DETAILS FOR ADDITIONAL

INFORMATION AND DETAILS

1.

HVAC SYSTEM SEQUENCE OF OPERATION:

THE EFS SHALL BE PROVIDED WITH A HAND-OFF-AUTO SWITCH. IN THE HAND MODE,

THE UNIT SHALL BE MANUALLY OPERATED. IN THE AUTO POSITION, THE UNIT SHALL

OPERATE AS FOLLOWS:

1. THE EXHAUST FANS SHALL BE CONTROLLED VIA A T-STAT MOUNTED ON THE

WALL WHERE INDICATED ON THE DRAWINGS.

2. THE T-STAT SHALL MODULATE THE EXHAUST FAN VOLUME TO MAINTAIN A SPACE

TEMPERATURE SET BY THE ROOM CONTROLLER. THE SPACE SHALL BE

MAINTAINED AT A DEFAULT TEMPERATURE OF 75F, BUT SHALL BE FULLY

ADJUSTABLE BY THE USER.

120 V

A

H

OFF

T-STAT

OL

EF

EF STARTER

CONTROL DIAGRAM AND SEQUENCE OF OPERATIONS

NOT TO SCALEC1

POWER

BLDG SERVED EXT SP

(INCH WG)

FAN

RPMTYPE (CFM)

EXHAUST FAN (EF) SCHEDULE

ELECTRICAL

V PH HZ

EF

NO.

(HP)

(LBS)

WEIGHTAIRFLOW

EF-B-1 1,405 0.2DIRECT DRIVE

CENTRIFUGAL SIDEWALL

898 1/2 115 1 60 86BARRACKS

(DBA)

SOUND

LEVEL REMARKS

EM

120 V

EMERGENCY

SHUTDOWN

RELAY

EM EMERGENCY

SHUTDOWN

BUTTON (WHERE

INDICATED ON

PLANS)

RESET

BUTTON

EMERGENCY HVAC SHUTDOWN SWITCH

SEQUENCE OF OPERATION:

1. ACTIVATION OF THE EMERGENCY

SHUTDOWN SWITCH SHALL SHUTDOWN

THE AFFECTED EF EQUIPMENT.

EM

EMERGENCY

SHUTDOWN SWITCH

EF CONTROL DIAGRAM EMERGENCY HVAC SHUTDOWN SWITCH CONTROL DIAGRAM

M-602

BLDG. TYPE B

R H

JG

-M -6

.d gn

D T

IS

E

D J

B

JO

A M

E N

D M

E N

T

2 4

7/ 3/

GENERAL NOTES THIS SHEET ONLY

O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

G P

A D

M

IN

S M

A

LL

M

E C

H A

N

IC

A L

S C

H E

M A

TI

C

D

IA

G R

A M

S A

N D

E Q

U

IP

M E

N T

S C

H E

D U

LE

S

REFER TO GENERAL INFORMATION

AND DETAILS FOR ADDITIONAL

INFORMATION AND DETAILS

1.

POWER

BLDG

SERVED

EXT SP

(INCH WG)

FAN

RPMTYPE (CFM)

EXHAUST FAN (EF) SCHEDULE

ELECTRICAL

V PH HZ

EF

NO.

(HP)

(LBS)

WEIGHTAIRFLOW

EF-C-1

(DBA)

LEVEL REMARKS

735 0.20DIRECT DRIVE

SIDEWALL CENTRIFUGAL

1000 1/4 115 1 60 72GP ADMIN SMALL 42

SOUND

HVAC SYSTEM SEQUENCE OF OPERATION:

THE EFS SHALL BE PROVIDED WITH A HAND-OFF-AUTO SWITCH. IN THE HAND MODE,

THE UNIT SHALL BE MANUALLY OPERATED. IN THE AUTO POSITION, THE UNIT SHALL

OPERATE AS FOLLOWS:

1. THE EXHAUST FANS SHALL BE CONTROLLED VIA A T-STAT MOUNTED ON THE

WALL WHERE INDICATED ON THE DRAWINGS.

2. THE T-STAT SHALL MODULATE THE EXHAUST FAN VOLUME TO MAINTAIN A SPACE

TEMPERATURE SET BY THE ROOM CONTROLLER. THE SPACE SHALL BE

MAINTAINED AT A DEFAULT TEMPERATURE OF 75F, BUT SHALL BE FULLY

ADJUSTABLE BY THE USER.

120 V

A

H

OFF

T-STAT

OL

EF

EF STARTER

CONTROL DIAGRAM AND SEQUENCE OF OPERATIONS

NOT TO SCALEC1

EM

120 V

EMERGENCY

SHUTDOWN

RELAY

EM EMERGENCY

SHUTDOWN

BUTTON (WHERE

INDICATED ON

PLANS)

RESET

BUTTON

EMERGENCY HVAC SHUTDOWN SWITCH

SEQUENCE OF OPERATION:

1. ACTIVATION OF THE EMERGENCY

SHUTDOWN SWITCH SHALL SHUTDOWN

THE AFFECTED EF EQUIPMENT.

EM

EMERGENCY

SHUTDOWN SWITCH

EF CONTROL DIAGRAM EMERGENCY HVAC SHUTDOWN SWITCH CONTROL DIAGRAM

M-603

BLDG. TYPE C

R H

JG

-M -6

.d gn

D T

IS

E

D J

B

JO

A M

E N

D M

E N

T

2 4

7/ 3/

W

DD

W W W W W

D D D

4" VTR

LI

5-1

GWH

5-1

WMB

G

CONN. TO EXIST.

LPG PIPING

WATER METER

RPBP

WMB WMB WMB WMB

HB

FD

GWH

5-1

GWH

5-1

ET

CONN. 4" S. TO 6" S

STUBOUT BY OTHERS

1 1/2" CW POC TO

EXIST. WATER LINE

COTG

COTG

HB HB HB HB

ROUTE WATER PIPING

HIGH AT CLN'G

FD

COTG

FCO

FCO

G SHUTOFF VALVE,

REGULATOR, & METER

TRAP PRIMER

TO FD'S. PROVIDE W/

ACCESS PANEL, TYP.

PROVIDE ACCESS

PANEL FOR WHA'S

CW & HW SUPPLY

TO WMB'S. ROUTE

LOW ON WALL

ROUTE V PIPE

BELOW WINDOW SILL

WMB

POTABLE CW SERVICE

TO LATRINE BLDG. FOR

CONT. SEE VOL4 PLUMBING COTG

G

PROVIDE POTABLE 3/4" CW U/G

SERVICE FOR LATRINE BLDG.

ROUTE CW U/G

HEATER CONTROLLER.

PROVIDE CONDUIT FOR ALL

WIRING TO HEATERS

WMB WMB

B

LD

G

LA

U

N D

R Y

P

LU

M B

IN

G

F

LO

O R

P

LA

N

GENERAL NOTES THIS SHEET ONLY

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

SCALE: 1/4" = 1'-0"

BLDG 121 - LAUNDRY - PLUMBING FLOOR PLANA1

P-102

BLDG. TYPE E

2" DIA. DRAIN PIPE

12" DIA. CONC. PIPE

20 CRUSHED ROCK FILL

A

FIN. FLR.

50"

38"

A

4"

4"

FOR CORNER

DETAIL, SEE

LIFTING RUNG SEE

DETAIL, FOR DETAIL SEE

SEDIMENT TRAP

6"

FROM BOOTWASH WASTE TO

SEWER

VENT PIPE,

TYP.DRAIN PIPE

C1

A1

1" THK. CHECKERED

COVER METAL PLATE

H40 RATING

DRAIN PIPE

NOT TO SCALE

LINT TRAP INTERCEPTOR DETAILA3

D T

IS

E

D J

B

JO

R H

JG

-P -1

.d gn

10"

A M

E N

D M

E N

T

1 4

7/ 3/

AutoCAD SHX Text M

AutoCAD SHX Text

SECTION A-A

PLAN VIEW

P

LU

M B

IN

G

D E

TA

IL

S

GENERAL NOTES THIS SHEET ONLY

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

IN SLEEVE

CENTER PIPE

ESCUTCHEON AT

FINISHED WALLS

CMU WALL OR

CONC. WALL

FIRESTOP W/ UL

APPROVED SYSTEM

C1 P-501

PIPE THRU WALL DETAIL

NOT TO SCALE C2

P-501

ADA CLEANOUT TO GRADE DETAIL

NOT TO SCALE

PLUG IF END

CONDITION

8" MIN.

WASTE LINE

SANITARY WYE

CONCRETE COLLAR

CONCRETE WALK

BRASS PLUG AT PAVING OR

CLEANOUT PLUG USE COUNTERSUNK

1/4" BEND

6" MIN.

FINISHED GRADE

MAIN UP TO MAXIMUM OF 6"

CLEANOUT SAME SIZE AS

NICKEL BRONZE

ADJUSTABLE STRAINER

STRUCTURAL SLABFLASHING CLAMP

W/ WEEP HOLES

THREADED, CAULKED OR

NO-HUB CONNECTION

NOTE: SEE PLUMBING SCHEDULE FOR FLOOR DRAIN TYPE.

CAST IRON CLEANOUT WITH ROUND

ADJUSTABLE SECURED NICKEL

BRONZE TOP, SLOTTED CLOSURE PLUG

INTO HUB & SEAL WITH

INDICATED). TURN DOWN

VAPOR BARRIER (WHERE

FIN. FLR.

1/4" BEND, LONG SWEEP

WASTE LINE

CONC. FLOOR

1"

3/4"

SQUARE HEAD VALVE

VACUUM BREAKER

FINISHED WALL

MIN.

4"

6"

12"

FINISHED FLOOR

INTERIOR/EXTERIOR WALL

PIPE WALL SUPPORT

HB W/ REMOVABLE

TEE HANDLE

18" ABV. FIN.

FLR./GRADE

VACUUM BREAKER

HB W/ REMOVABLE

TEE HANDLE

INTERIOR/EXTERIOR WALL

3/4"

SQUARE HEAD VALVE

PIPE WALL SUPPORT

1/2" POLISHED CHROME

W/LOOSE KEY W/

NON-REMOVABLE

VACUUM BREAKER &

19mm HOSE HOSE

OUTLET

CHROME PLATED, HEX.

HD. LOOSE KEY VALVE

W/ WALL PLATE

C4 P-501

FLOOR CLEAN OUT

NOT TO SCALE

B1 P-501

FLOOR DRAIN DETAIL

NOT TO SCALE

B3 P-501

HOSE BIBB DETAIL

NOT TO SCALE

B4 P-501

INTERIOR HOSE BIBB DETAIL

NOT TO SCALE

24" MIN.

12"

6"

6"

GAS PIPE

SELECT MATERIAL

I.D. PIPE SLEEVE 1/2"

LARGER THAN PIPE OR

INSULATION O.D.

A1 P-501

GAS PIPE TRENCH DETAIL

NOT TO SCALE

AC PAVEMENT/FIN. GRADE

FIN. GRADE

RPBP WATTS MDL 909

OR BWS APPROVED

EQUAL

30" MAX.

12" MIN.

A2 P-501

REDUCED PRESSURE BACKFLOW PREVENTER (RPBP)

NOT TO SCALE

FINISHED FLOOR FINISHED GRADE

COPPER CW

SUPPLY. SIZE

SHOWN ON DWGS.

A4 P-501

WATER METER DETAIL

NOT TO SCALE

MUELLER MODEL MVR 2" OR

3" OR APPROVED EQUAL

NOTE: OPTIONALAL REMOTE AMR READING SYSTEM BY MUELLER.

CW PIPE. SIZES

SHOWN ON DWGS.

BALL VALVE, TYP.

UNION

CHECK VALVE

#10 COPPER

TRACING WIRE

GAS PIPE

WARNING TAPE

STRAINER

P-501

D T

IS

E

D J

B

JO

R H

JG

-P -5

.d gn

A M

E N

D M

E N

T

1 4

7/ 3/

1/4" MIN

ESx ESx

D

D

D

D

BLD

G 14

2A

BLD

G 14

BLD

G 14

BLD

G 14

BLD

G 14

BLD

G 14

BLD

G 14

BLD

G 14

BLD

G 14

BLD

G 13

BLD

G 13

BLD

G 13

BLD

G 13

BLD

G 13

BLD

G 13

BLD

G 13

1A

BLD

G 12

BLDG 133

CONCRETE PAD

FOR GAS TANK.

SEE STRUCTURAL

FOR DETAILS

NEW GAS PIPING

PROVIDED BY HAWAII

GAS

TRENCHING

PROVIDED BY THE

CONTRACTOR.

NEW 1150 GALLON

LPG TANK PROVIDED

BY HAWAII GAS

25'-0"

CLEARANCE FOR

THE GAS TANK

EXISTING 2000

GALLON LPG TANK TO

REMAIN TO SERVE

LAUNDRY BLDG.

4" POTABLE WATER

CONNECTION BY

BASE WATER SUPPLY

CONTRACTOR

6" S. CONNECTION

BY OTHERS.

4" POTABLE WATER

CONNECTION BY

BASE WATER

SUPPLY

CONTRACTOR

6" S. CONNECTION

BY OTHERS

1 1/2" CW PROVIDE BY

BASE WATER SUPPLY

CONTRACTOR.

6" S. CONNECTION

BY OTHERS

ROUTE GAS PIPING IN

EXIST. SLEEVE UNDER

EXIST. PAVEMENT.

P

LU

M B

IN

G

S

IT

E P

LA

N

GENERAL NOTES THIS SHEET ONLY

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

D A

TE

M

A R

K D

E S

C R

IP

TI

O N

C O

N

TR

A C

T N

O

D A

TE

A

P P

R

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

A N

S I D

IS

S

U E

D A

TE

P A

C

IF

IC

O

C E

A N

H O

N O

LU

LU

, H A

W A

II

B O

W E

R S

A N

D K

U B

O

TA

M A

N A

G E

M E

N T

-4

A

K O

K I S

TR

E

E T

W A

IP

A

H U

, H I 9

W

A

-1 5-

D -0

A S

N O

TE

D

W

A

-1 5-

D -0

D

C

A

B

1 2 3 4 5

SHEET ID

FY

M C

A P

N

O P

E R

A

TI

O N

A L

R E

A D

IN

E

S S

TR

A

IN

IN

G C

O M

P

LE

X (B

A R

R A

C K

S

P H

P

O H

A K

U

LO

A T

R A

IN

IN

G A

R E

A

IS

LA

N

D O

F H

A W

A

II,

H A

W A

II

/2 /8

/2 /8

BUILDING 135, 137, 138, 139, 144, 145,

146, 147, 148 - BARRACKS - LARGE

NO PLUMBING WORK IN THIS AREA

BUILDING 140, 149, - GP ADMIN - SMALL

NO PLUMBING WORK IN THIS AREA

BUILDING 131/131A, 142/142A -

SHOWER/LATRINES DUPLEX

FOR PLUMBING WORK, SEE PA101

BUILDING 133 - LATRINE ONLY

FOR PLUMBING WORK, SEE PF101

BUILDING 121 - LAUNDRY

FOR PLUMBING WORK, SEE PE101

SCALE: 1" = 40'-0"

PLUMBING SITE PLANA1 00 40' 80'

SCALE: 1" = 40'

120'

PLAN

NORTHTRUE

NORTH

PS101

D T

IS

E

D J

B

JO

R H

JG

-P -1

.d gn

A M

E N

D M

E N

T

1 4

AutoCAD SHX Text S

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

EHH

AutoCAD SHX Text S

AutoCAD SHX Text

EHH

AutoCAD SHX Text S

AutoCAD SHX Text

EHH

AutoCAD SHX Text

EHH

AutoCAD SHX Text S

AutoCAD SHX Text

EHH

AutoCAD SHX Text

EHH

AutoCAD SHX Text

EHH

AutoCAD SHX Text

EHH

AutoCAD SHX Text W3/4

AutoCAD SHX Text W 1/2

AutoCAD SHX Text W3

AutoCAD SHX Text W3

AutoCAD SHX Text W3

AutoCAD SHX Text W3

AutoCAD SHX Text W2

AutoCAD SHX Text W1 1/2

AutoCAD SHX Text W2

AutoCAD SHX Text W2

AutoCAD SHX Text W2

AutoCAD SHX Text W4

AutoCAD SHX Text W12

AutoCAD SHX Text W1 1/2

AutoCAD SHX Text W12

AutoCAD SHX Text W4

AutoCAD SHX Text W4

AutoCAD SHX Text

SEEPAGE PIT #28

AutoCAD SHX Text

SEPTIC TANK

AutoCAD SHX Text

SEEPAGE PIT #27

AutoCAD SHX Text

SEEPAGE PIT #26

AutoCAD SHX Text

SEPTIC TANK

AutoCAD SHX Text

SEPTIC TANK

AutoCAD SHX Text

CESSPOOL #25

AutoCAD SHX Text

CESSPOOL #24

AutoCAD SHX Text

CESSPOOL #23

AutoCAD SHX Text

SEPTIC TANK

AutoCAD SHX Text

LEACHING WELL #3

AutoCAD SHX Text

LEACHING WELL #4

AutoCAD SHX Text

SEPTIC TANK

AutoCAD SHX Text

SEEPAGE PIT #18

AutoCAD SHX Text

CESSPOOL #19

AutoCAD SHX Text

MISSING CESSPOOL #16

AutoCAD SHX Text

MISSING CESSPOOL #21

AutoCAD SHX Text

MISSING CESSPOOL #20

AutoCAD SHX Text

CESSPOOL #22

AutoCAD SHX Text

CESSPOOL #12

AutoCAD SHX Text

CESSPOOL #11

AutoCAD SHX Text

CESSPOOL #13

AutoCAD SHX Text

MISSING CESSPOOL #32

AutoCAD SHX Text

MISSING CESSPOOL #31

AutoCAD SHX Text

GREASE TRAP

AutoCAD SHX Text

GREASE TRAP

AutoCAD SHX Text

SMH TOP=6383.6 INV.=6381.43

AutoCAD SHX Text

SEPTIC TANK SMH TOP=6383.5 PIPE INV.=6381.79

AutoCAD SHX Text

SEPTIC TANK SMH TOP=6382.76 PIPE INV.=6378.68

AutoCAD SHX Text

SEPTIC TANK SMH TOP=6375.10 PIPE INV.=6371.16

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text H

AutoCAD SHX Text Y

AutoCAD SHX Text D

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text H

AutoCAD SHX Text Y

AutoCAD SHX Text D

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text T-131A

AutoCAD SHX Text T-122A

AutoCAD SHX Text T-113A

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text Y

AutoCAD SHX Text H

AutoCAD SHX Text D

AutoCAD SHX Text Y

AutoCAD SHX Text H

AutoCAD SHX Text D

AutoCAD SHX Text Y

AutoCAD SHX Text H

AutoCAD SHX Text D

AutoCAD SHX Text Y

SCALE: 1/4" = 1'-0"

C1

GRAPHIC SCALE

E-107

SCALE: 1/4" = 1'-0"

A1

KEY NOTES THIS SHEET ONLY

N O

R T

H

P L A N

N O

R T

H

P L A N

ED103

A S N

O T

E D

A N

S I

D

0 4' 8'

SCALE: 1/4"=1'-0"

A C

H

M K

E

A C

H

A C

H

CONFIGURATION "A"

R H

J E -1

.d g n

DETAILS AND ADDITIONAL INFORMATION.

INFORMATION AND DETAILS, FOR

1. REFER TO GENERAL

W

A -1

-D -0

W

A -1

-D -0

C O

N F

IG

U R

A T

IO

N

A

E L E

C T

R

IC

A L A

N D L

IG

H T

IN

G P

L A

B U

IL

D

IN

G

G

P A

D M

IN

S

M A

L

BUILDING 149 - GP ADMIN SMALL - LIGHTING PLAN CONFIGURATION "A"

BUILDING 149 - GP ADMIN SMALL - ELECTRICAL PLAN CONFIGURATION "A"

E-503

GENERAL NOTES THIS SHEET ONLY

BLDG. TYPE C

E-610

/2 /8

/2 /8

IN LIEU OF STUBBING OUT.

UNDERGROUND INFRASTRUCTURE

CONNECT NEW DUCTS TO

INFRASTRUCTURE IS IN PLACE,

IF UNDERGROUND TELECOM

REINFORCING STEEL AND TMGB.

END. BOND SLEEVE TO

PLASTIC THREADED CAPS ON EACH

BLOCK. PROVIDE PVC OR ABS

CORNER) TO FIT IN ONE MASONRY

+24" AFF 6" (AT LEAST 8" FROM

ASSOCIATED EQUIPMENT CABLING,

TEMPORARY ANTENNA AND

1 x 4"C GRC SLEEVE FOR

MOUNTED IN TELECOM CABINET.

CONDUCTORS.

INSTALL NEW ELECTRICAL SERVICE

AND .

CONDUIT/DUCT. SEE SHEET

ELECTRICAL SERVICE

CONDUIT/DUCT TO EXISTING

INSTALL NEW ELECTRICAL SERVICE

BACKBOARD.

FROM METER TO TELECOM

PROVIDE 1"C WITH PULLSTRING

SECTION INFORMATION.

SEE SHEET FOR DUCT

A

M E

N D

M E

N T

/1

/1

A

M E

N D

M E

N T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

IS

S

U E D

A T

E

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

D

C

A

B

1 2 3 4 5

SHEET ID

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

AE

AEA

AAE

A

AE

A

3 3

A A

A

3b3,3b

J b a1

3b3b3,3b3b3b

1,1a

1a1a1,1a a b

PANEL "A"

A-1,3

J

A 3bAE 3,3b

B

+7'-6"

B+7'-6"

AE

3,3b

C

C C

CCCC

C

PANEL "A"

J

J

8 10 10 12 12

A-14

C

C

C

C C C C

G

SEE

SERVICE DISCONNECT,

C3

E-203

C C

C

1 S 2 A

E

J 42

GG G

G G

C

FACP

C

C C

2 T 4 B

C

C

B1

E-203

DUCT MARKER. SEE

AND CAP. PROVIDE

STUB 10 FT FROM BLDG

(4'W x 8'H). SEE

TELECOM BACKBOARD

D1

E-507

FOR CONTINUATION

SEE SHEET

ED103

F

M

WPI

J

M

WPI

21F

1/4 HP, 120V, 1PH, 60Hz

EF 2-1

EF 2-1

1/4 HP, 120V, 1PH, 60Hz

A-42

C

C

JJ

J

J

A-8,10,12

A-2,4,6

A-21,23

A-13,15

J

NEMA 4X CABINET

KWHR METER IN

SCALE: 1/4" = 1'-0"

C1

GRAPHIC SCALE

E-108SCALE: 1/4" = 1'-0"

A1

KEY NOTES THIS SHEET ONLY

N O

R T

H

P L A N

N O

R T

H

P L A N

ED103

A S N

O T

E D

A N

S I

D

0 4' 8'

SCALE: 1/4"=1'-0"

A C

H

M K

E

A C

H

A C

H

CONFIGURATION "B"

DETAILS AND ADDITIONAL INFORMATION.

INFORMATION AND DETAILS, FOR

1. REFER TO GENERAL

W

A -1

-D -0

W

A -1

-D -0

C O

N F

IG

U R

A T

IO

N

B

E L E

C T

R

IC

A L A

N D L

IG

H T

IN

G P

L A

IL

D

IN

G

G

P A

D M

IN

S

M A

L

BUILDING 140 - GP ADMIN SMALL - LIGHTING PLAN - CONFIGURATION "B"

BUILDING 140 - GP ADMIN SMALL - ELECTRICAL PLAN - CONFIGURATION "B"

R H

J E -1

.d g n

E503

GENERAL NOTES THIS SHEET ONLY

BLDG. TYPE C

E-611

/2 /8

/2 /8

IN LIEU OF STUBBING OUT.

UNDERGROUND INFRASTRUCTURE

CONNECT NEW DUCTS TO

INFRASTRUCTURE IS IN PLACE,

IF UNDERGROUND TELECOM

REINFORCING STEEL AND TMGB.

END. BOND SLEEVE TO

PLASTIC THREADED CAPS ON EACH

BLOCK. PROVIDE PVC OR ABS

CORNER) TO FIT IN ONE MASONRY

+24" AFF 6" (AT LEAST 8" FROM

ASSOCATED EQUIPMENT CABLING,

TEMPORARY ANTENNA &

1 x 4"C GRC SLEEVE FOR

MOUNTED IN TELECOM CABINET.

CONDUCTORS.

INSTALL NEW ELECTRICAL SERVICE

AND .

HANDHOLE (EHH-1-SB3). SEE SHEET

CONDUIT/DUCT TO EXISTING

INSTALL NEW ELECTRICAL SERVICE

BACKBOARD.

FROM METER TO TELECOM

PROVIDE 1"C WITH PULLSTRING

SECTION INFORMATION.

SEE SHEET FOR DUCT

A M

E N

D M

E N

T

/1

/1

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

IS

S

U E D

A T

E

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

D

C

A

B

1 2 3 4 5

SHEET ID

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

AE

AEA

AAE

A

AE

A

3 3

A A

A

3b3,3b

J b a1

3b3b3,3b3b3b

1,1a

1a1a1,1a a b

PANEL "A"

A-1,3

J

A 3bAE 3,3b

B

+7'-6"

B+7'-6"

AE

3,3b

C

C C

CCCCC

C

C

PANEL "A"

J

A-2,4,6

J

8 10 10 12 12

A-8,10,12

A-14

C

C

C

C

B1

E-203

C C C

C

G

SEE

SERVICE DISCONNECT,

C3

E-203

C C

C

1 S 2 A

E

2 T 4 B

A-13,15

J

G GG

G G

C

FACP

C

C

D1

E-507

MARKER. SEE

CAP. PROVIDE DUCT

STUB 10 FT FROM BLDG AND

FOR CONTINUATION

SEE SHEET

ED103

G

J

A-42

EF 2-1

1/4 HP, 120V, 1PH, 60Hz

F 23

M

WPI

J

SEE

TELECOM BACKBOARD (4'W x 8'H).

J

C

J 2

C

A-21,23

F 21

CABINET

IN NEMA 4X

KWHR METER

E-203

0 1' 2' 3'

SCALE: 3/4"=1'-0"

GRAPHIC SCALE

A N

S I

D

A S N

O T

E D

0 1' 2'

SCALE: 1"=1'-0"

A C

H

A C

H

M K

E

A C

H

W

A -1

-D -0

W

A -1

-D -0

A N

D S

E R

V

IC

E E

Q U

IP

M E

N T E

L E

V A

T

IO

N T

E L E

C O

M S

E R

V

IC

E E

N T

R A

N C

E E

L E

V A

T

IO

IL

D

IN

G

G

P A

D M

IN

S

M A

L

J E -2

.d g n

BLDG. TYPE C

/2 /8

/2 /8

A M

E N

D M

E N

T

/1

/1

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

IS

S

U E D

A T

E

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

D

C

A

B

1 2 3 4 5

SHEET ID

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

FINISHED GRADE

STEEL

NEMA 4X, STAINLESS

CIRCUIT BREAKER,

DISCONNECT/

MAIN SERVICE

SCALE: 3/4" = 1'-0"

C3

(SEALABLE)

STAINLESS STEEL

CONSTRUCTED OF

NEMA 3R

30"SQ x 11"D

CT ENCLOSURE

NEMA 4X

ENCLOSURE, HINGED,

KWHR METER IN METER

SEE SITE PLAN

DUCTLINE.

TO EXISTING

STEEL (SEALABLE)

NEMA 4X, STAINLESS

SERVICE PULLBOX,

TO GROUND WELL

SERVICE EQUIPMENT ELEVATION

BUILDING 140, 149 - GP ADMIN SMALL -

SPD

STAINLESS STEEL

BREAKER, NEMA 4X

ENCLOSED CIRCUIT

ENCLOSURE

DEVICE. NEMA 4X

SURGE PROTECTION

FINISHED FLOOR

DUCTS

TELECOM SERVICE

2 x 4"C INCOMING

TERMINAL (GFGI)

PROTECED ENTRANCE

NOTES:

1.

110 BLOCK

B1

A4

E-801

SCALE: 1" = 1'-0"

A1

E-803

110 BLOCK

FIRE RATED (4'W x 8'H)

TELECOM BACKBOARD,

TELECOM SERVICE ENTRANCE ELEVATION

BUILDING 140, 149 - GP ADMIN SMALL -

FOR ADDITIONAL INFORMATION

CABINET, SEE

WALL MOUNTED TELECOM

FOR ADDITIONAL INFORMATION

TMGB. SEE

CONDUITS SHOWN)

OUTLETS (NOT ALL

1"C (EMT) TO TELECOM

CONVENIENCE RECEPTACLE

CORNER

6"

2.

5"

OPENED (I.E. MAIN CABINET AND FRONT DOOR).

BLOCKS AND PROTECTED ENTRANCE TERMINAL AND CAN BE COMPLETELY

OF THE CABINET IS OPENED UP, IT DOES NOT COME IN CONTACT WITH 110

PLACEMENT OF TELECOM CABINET SHALL BE SUCH THAT WHEN THE MAIN BODY

WITH NEC VIA THE CONTRACTING OFFICER.

COORDINATE INSTALLATION ARRANGEMENT AND REQUIREMENTS

E-501

S N

O T

E D

A N

S I

D

A C

H

A C

H

M K

E

A C

H

W

A -1

-D -0

W

A -1

-D -0

R H

J E -5

.d g n

D E

T A

IL

S L

IG

H T F

IX

T U

R E A

N D M

IS

C

E L L

A N

E O

/2 /8

/2 /8

A M

E N

D M

E N

T

/3 /1

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

D A

T E

A P

P R

®of Engineers

US Army Corps

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

IS

S

U E D

A T

E

P A

C

IF

IC

O

C E

A N

H O

N O

L U

L U

H A

W A

II

B O

W E

R S A

N D K

U B

O T

A

M A

N A

G E

M E

N T

-4

A

K O

K I S

T R

E E

T

W A

IP

A H

U

H I

D

C

A

B

1 2 3 4 5

SHEET ID

IS

L

A N

D O

F H

A W

A

II

H A

W A

II

P O

H A

K U

L O

A T

R A

IN

IN

G A

R E

A

T R

A

IN

IN

G C

O M

P L E

X

B A

R R

A C

K S P

H

F Y M

C A P

N O

P E

R A

T

IO

N A

L R

E A

D

IN

E S

S

LAMP

LENS

CHASSIS

MOUNT

TYPE

INTERNAL HOUSING

AFTER FABRICATION

POWDER COAT, PAINT

w/ WHITE POLYESTER

COLD ROLLED STEEL

22-GAUGE DIE-FORMED

A

OUTER HOUSING CONSISTS OF POLYESTER REINFORCED FIBERGLASS w/ INTERNAL BRASS STUDS

FEATURES 1

FEATURES 2

ACRYLIC DIFFUSER

IMPACT RESISTANT

EMERGENCY BATTERY PACK, 90 MINUTE OPERATION

7"

48" ±

FRONT VIEW SIDE VIEW

5.40"

.6

LAMP

LENS

CHASSIS

MOUNT

TYPE B

DRIVER

FEATURES

POLYESTER POWDER COAT FINISH, BRONZE

MARINE GRADE HEAT TREATED EXTRUDED ALUMINUM WITH

120V CONSTANT CURRENT LED DRIVER @ 350mA

WALL

EXTRUDED UV STABILIZED CLEAR PRISMATIC POLYCARBONATE

WALL / CEILING / PENDANT

AE

5. FULL CUTOFF

4. INTEGRAL PHOTOELECTRIC SWITCH.

3. UL LISTED FOR WET LOCATIONS.

DAMAGED DUE TO VANDALISM.

b. VANDALISM - LIFETIME REPAIR OR REPLACEMENT OF FIXTURE IF

a. LED BOARDS - TEN YEARS FOR OPERATIONAL DEFECTS.

2. WARRANTY

1. RATED LIFE: 130,000 HOURS @ 50° C.

(LESS THAN 2% BLUE LIGHT)

LED, 292 LUMENS, 10 WATTS, AMBER, OBSERVATORY FRIENDLY

20.79"

NO SCALE

A1

FOR INTERIOR LOCATIONS

WEATHERPROOF SWITCH PLATE

FROSTED, RIBBED, IMPACT ACRYLIC, FULLY GASKETED

DRIVER

LED, 48W, 5,800 NOMINAL LUMENS, 120 LUMENS PER WATT MINIMUM EFFICACY. 3985K+/-275K, 80 MIN CRI

277V/120V OPERATION

7. 5 YEAR MINIMUM WARRANTY.

PRODUCTS BELOW 70% OF THEIR INITIAL LUMEN VALUE.

6. 50,000 HRS MINIMUM B10/L70 LIFETIME WHERE L70 IS 70% LUMEN MAINTENANCE AND B10 IS NO MORE THAN 10% OF

5. RE-LAMPABLE LIGHT ENGINES

4. THERMAL MANAGEMENT.

3. LEDs IN COMPLIANCE WITH IESNA LM80 AND ANSI C78.377.

2. PHOTOMETRICS TESTED IN ACCORDANCE WITH IESNA LM-79.

1. UL LISTED FOR DAMP LOCATIONS.